DP/PA coupler, active field distributors, ___________________ Preface DP/PA Link and Y Link SIMATIC Bus links DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions 1 ___________________ Product Overview Description of the 2 ___________________ components Active field distributor AFDiS 3 ___________________ in hazardous areas 4 ___________________ Application planning 5 ___________________ Mounting 6 ___________________ Connecting Commissioning: DP/PA 7 ___________________ coupler 8 ___________________ Commissioning: DP/PA link 9 ___________________ Commissioning: Y link Operation of the DP/PA-Link 10 ___________________ and Y-Link 11 ___________________ Maintenance and service 12 ___________________ Functions Interrupt, error and system 13 ___________________ messages 14 ___________________ Technical specifications A ___________________ Appendix 07/2011 A5E00193841-17 Legal information Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger. DANGER indicates that death or severe personal injury will result if proper precautions are not taken. WARNING indicates that death or severe personal injury may result if proper precautions are not taken. CAUTION with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken. CAUTION without a safety alert symbol, indicates that property damage can result if proper precautions are not taken. NOTICE indicates that an unintended result or situation can occur if the relevant information is not taken into account. If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage. Qualified Personnel The product/system described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems. Proper use of Siemens products Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be complied with. The information in the relevant documentation must be observed. Trademarks All names identified by (R) are registered trademarks of Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner. Disclaimer of Liability We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions. Siemens AG Industry Sector Postfach 48 48 90026 NURNBERG GERMANY A5E00193841-17 06/2011 Copyright (c) Siemens AG 2011. Technical data subject to change Preface Purpose of the operating instructions These operating instructions provide important information to configure, mount, wire, and commission the DP/PA coupler, the active field distributors AFD, AFS and AFDiS and the DP/PA link and Y link bus links. Basic knowledge required To understand these operating instructions you should have general experience in the field of automation engineering. When using the AFDiS you should be familiar with the fundamentals of explosion protection, the identification of explosion-protected equipment and the regulations regarding explosion protection. Range of validity of these operating instructions These operating instructions apply for the following products: IM 153-2: 6ES7153-2BA02-0XB0 IM 153-2 (Outdoor): 6ES7153-2BA82-0XB0 DP/PA coupler FDC 157-0: 6ES7157-0AC83-0XA0 DP/PA coupler Ex [i]: 6ES7157-0AD82-0XA0 Y coupler: 6ES7197-1LB00-0XA0 Bus modules - BM PS/IM: 6ES7195-7HA00-0XA0 - BM PS/IM SIPLUS extreme: 6AG1195-7HA00-2XA0 - BM IM/IM: 6ES7195-7HD10-0XA0 - BM IM/IM (Outdoor): 6ES7195-7HD80-0XA0 - BM FDC: 6ES7195-7HF80-0XA0 - BM FDC/FDC (redundant): 6ES7195-7HG80-0XA0 - BM Y coupler: 6ES7654-7HY00-0XA0 DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 3 Preface Active field distributors - AFD (Active Field Distributors) product version 02: 6ES7157-0AF81-0XA0 - AFS (Active Field Splitters), product version 02: 6ES7157-0AF82-0XA0 - AFDiS (Active Field Distributor intrinsic safety): 6ES7157-0AG83-0XA0 These operating instructions contain a description of the components that was valid at the time the operating instructions were published. We reserve the right to include product information with information updates with new components and components with a new product status. Changes compared to the previous version The following changes have been made to these operating instructions compared to the previous version (10/2006 edition): New: Active field distributor AFDiS for use in hazardous areas Integration of the product information 09/2008 and 11/2009 Configuring with STEP 7 The DP/PA coupler FDC 157-0 can be configured with STEP 7 from V5.3 SP3 and HSP0095 or optionally with SIMATIC PCS 7 V7.0 or higher for diagnostic purposes. Position in the overall information structure Depending on the hardware used you require the following manuals in addition to these operating instructions: The manual for the implemented DP master, including the following special information: - Configuring and commissioning of a DP master system - Description of the DP master The manual SIMATIC NET, PROFIBUS network manual (http://support.automation.siemens.com/WW/view/en/35222591) The operating instructionsSIMATIC S7-300 CPU 31xC and CPU 31x: Installation (http://support.automation.siemens.com/WW/view/en/36305386) The manual Automation Systems S7-300, ET 200M Ex I/O modules (http://support.automation.siemens.com/WW/view/en/1096709), including in particular information on the topics intrinsic safety and explosion protection. System manual Principles of Explosion Protection (http://support.automation.siemens.com/WW/view/en/12521844) More information on explosion protection can be found in the corresponding directives and standards. DP/PA coupler, active field distributors, DP/PA Link and Y Link 4 Operating Instructions, 07/2011, A5E00193841-17 Preface Sign posts These operating instructions are subdivided into the following subjects: Product overview and description of the components Install, connect and commission Operation and diagnostics Technical specifications Appendices Important terms are explained in the glossary. The index helps you to quickly find all texts relevant to your keyword. Recycling and disposal The described components are ecologically compatible, and thus suitable for recycling. For environmentally sound recycling and disposal of your old devices please contact a certified disposal service company for electronic scrap. Additional support If you have any questions relating to the products described in these operating instructions and do not find the answers in this document, please contact your local Siemens representative (http://www.siemens.com/automation/partners). A guide to the technical documentation for the various SIMATIC products and systems is available on the Internet. (http://www.siemens.com/simatic-docu). The online catalog and order system is available on the Internet (http://www.siemens.com/automation/mall). Training center Siemens offers a series of courses that will help you getting started with the components and the SIMATIC S7 automation system. Please contact your regional training center or the central training center in D-90327, Nuremberg, Germany (http://www.siemens.com/sitrain). Technical support You can contact Technical Support for all Industry Automation products by means of the Internet Web form for the Support Request. (http://www.siemens.com/automation/csi_en_WW/support_request) Additional information on our technical support is available on the Internet (http://www.siemens.com/automation/csi_en_WW/service). DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 5 Preface Service & Support on the Internet In addition to our documentation, we offer a comprehensive knowledge base on the Internet (http://www.siemens.com/automation/csi_en_WW/support). There you will find: Our Newsletter, which constantly provides you with the latest information about your products. The documents you require, via our service & support search facility. Worldwide forum in which users and experts exchange ideas. Your local contact for Automation & Drives from our contact database. Information about on-site service, repairs, spare parts, and much more. DP/PA coupler, active field distributors, DP/PA Link and Y Link 6 Operating Instructions, 07/2011, A5E00193841-17 Table of contents Preface ...................................................................................................................................................... 3 1 2 3 Product Overview .................................................................................................................................... 13 1.1 Bus links.......................................................................................................................................13 1.2 1.2.1 1.2.2 1.2.3 1.2.4 1.2.5 Integration in the automation environment ..................................................................................14 What are distributed I/O devices?................................................................................................14 DP/PA coupler FDC 157-0 with active field distributors ..............................................................16 DP/PA coupler / DP/PA Ex [i] coupler..........................................................................................18 DP/PA link ....................................................................................................................................19 Y link ............................................................................................................................................20 Description of the components ................................................................................................................ 21 2.1 DP/PA coupler FDC 157-0...........................................................................................................21 2.2 DP/PA coupler / DP/PA Ex [i] coupler..........................................................................................23 2.3 Y coupler ......................................................................................................................................24 2.4 2.4.1 2.4.2 2.4.3 IM 153-2 .......................................................................................................................................25 Routing of frames of the slave initiative .......................................................................................25 Improved link behavior during commissioning.............................................................................26 Which devices can be operated behind the Y Link?....................................................................26 2.5 DP/PA link ....................................................................................................................................27 2.6 Y link ............................................................................................................................................30 2.7 Active field splitter (AFS)..............................................................................................................32 2.8 Active field distributor (AFD) ........................................................................................................33 2.9 Active field distributor AFDiS .......................................................................................................34 2.10 Compatibility with predecessor modules .....................................................................................37 Active field distributor AFDiS in hazardous areas .................................................................................... 39 3.1 Fundamentals of hazardous areas and intrinsic safety ...............................................................39 3.2 Configuration with AFDiS.............................................................................................................42 3.3 Mounting AFDiS...........................................................................................................................43 3.4 Grounding ....................................................................................................................................44 3.5 Safety instructions for connection................................................................................................46 3.6 Connecting PROFIBUS PA to the AFDiS ....................................................................................50 3.7 Grounding AFDiS.........................................................................................................................53 3.8 AFDiS maintenance and cleaning................................................................................................54 3.9 Replacing/supplementing the AFDiS ...........................................................................................56 DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 7 Table of contents 4 5 6 Application planning................................................................................................................................. 57 4.1 4.1.1 4.1.2 4.1.3 4.1.3.1 4.1.3.2 4.1.3.3 4.1.3.4 4.1.3.5 Installation variants with the DP/PA coupler FDC 157-0 ............................................................ 57 Configuration variants ................................................................................................................. 57 DP/PA coupler in non-redundancy mode.................................................................................... 58 DP/PA coupler in redundancy mode........................................................................................... 59 Ring redundancy with active field distributor (AFD).................................................................... 59 Coupler redundancy with active field splitter (AFS) .................................................................... 62 Redundancy mode of the DP/PA coupler in the DP/PA link ....................................................... 64 Redundancy mode of the DP/PA coupler in the redundant DP/PA link...................................... 66 Combination of non-redundant and redundant DP/PA couplers................................................. 68 4.2 4.2.1 4.2.2 Installation variants with the IM 153-2......................................................................................... 70 Configuration variants ................................................................................................................. 70 Detecting the configuration variant by means of the IM 153-2 ................................................... 71 Mounting.................................................................................................................................................. 73 5.1 Mounting rules............................................................................................................................. 73 5.2 5.2.1 5.2.2 5.2.3 Mounting the DP/PA coupler....................................................................................................... 75 Mounting DP/PA coupler for non-redundant mode..................................................................... 75 Mounting the DP/PA coupler for redundancy mode ................................................................... 76 Swapping DP/PA couplers FDC 157-0 ....................................................................................... 77 5.3 5.3.1 Installing the active field distributor AFD and active field splitter AFS........................................ 78 Screwing down the active field distributor AFD and active field splitter AFS on substrate......... 78 5.4 5.4.1 5.4.2 Mounting the DP/PA link ............................................................................................................. 79 Mounting the DP/PA link for non-redundant mode ..................................................................... 79 Mounting the DP/PA link for redundant operation ...................................................................... 81 5.5 Mounting the Y link...................................................................................................................... 83 5.6 Setting the PROFIBUS address of the IM 153-2 ........................................................................ 85 Connecting .............................................................................................................................................. 87 6.1 6.1.1 6.1.2 6.1.3 6.1.4 Electrical isolation and grounding ............................................................................................... 87 General Rules and Regulations for Operation ............................................................................ 88 Grounding the active field distributor AFD / AFS ........................................................................ 90 Operating with grounded supply ................................................................................................. 90 Operation with ungrounded reference potential.......................................................................... 92 6.2 6.2.1 6.2.2 6.2.2.1 6.2.2.2 6.2.3 6.2.3.1 6.2.3.2 Connecting DP/PA couplers........................................................................................................ 93 Wiring the DP/PA coupler for stand-alone mode ........................................................................ 93 Connecting DP/PA couplers for ring redundancy ....................................................................... 94 Connections for ring redundancy ................................................................................................ 94 Connecting the PROFIBUS PA to the active field distributor (AFD) ........................................... 95 Connecting DP/PA couplers for coupler redundancy ................................................................. 98 Connections for coupler redundancy .......................................................................................... 98 Connecting the PROFIBUS PA to the active field splitter (AFS) ................................................ 99 6.3 6.3.1 6.3.2 Connecting the DP/PA link........................................................................................................ 102 Wiring the DP/PA link for non-redundant mode ........................................................................ 102 Wiring the DP/PA link for redundant operation ......................................................................... 103 6.4 Connecting Y link ...................................................................................................................... 104 6.5 Connecting the power supply.................................................................................................... 105 DP/PA coupler, active field distributors, DP/PA Link and Y Link 8 Operating Instructions, 07/2011, A5E00193841-17 Table of contents 7 8 9 10 6.6 Connecting PROFIBUS DP .......................................................................................................106 6.7 Connecting PROFIBUS PA on the DP/PA coupler....................................................................107 Commissioning: DP/PA coupler............................................................................................................. 111 7.1 Commissioning the DP/PA coupler for stand-alone mode ........................................................111 7.2 Commissioning the DP/PA coupler FDC 157-0 .........................................................................111 7.3 Configuration with a GSD file.....................................................................................................114 7.4 Configuring with STEP 7............................................................................................................115 7.5 DP/PA coupler FDC 157-0 in the redundant DP/PA link ...........................................................117 7.6 Parameters for diagnostic selection of the DP/PA coupler FDC 157-0 .....................................118 7.7 Setting the PROFIBUS address and redundancy mode ...........................................................119 Commissioning: DP/PA link ................................................................................................................... 121 8.1 Commissioning DP/PA link ........................................................................................................121 8.2 8.2.1 8.2.2 Configuring for S7 standard or redundant mode .......................................................................122 Configuring DP/PA link ..............................................................................................................122 Configuring the PROFIBUS PA master system.........................................................................124 8.3 8.3.1 8.3.2 8.3.3 Configuring for DP standard master mode ................................................................................125 GSD files ....................................................................................................................................125 Configuring DP/PA link ..............................................................................................................126 How to configure PROFIBUS PA field devices..........................................................................127 Commissioning: Y link ........................................................................................................................... 129 9.1 Commissioning Y link.................................................................................................................129 9.2 9.2.1 9.2.2 Configuring for the redundancy mode .......................................................................................130 How to configure Y link ..............................................................................................................130 Configuring underlying DP slaves..............................................................................................133 9.3 9.3.1 9.3.2 9.3.3 Configuring for DP standard master mode ................................................................................134 GSD files ....................................................................................................................................134 How to configure Y link ..............................................................................................................135 Configuring underlying DP slaves..............................................................................................136 Operation of the DP/PA-Link and Y-Link................................................................................................ 139 10.1 Start-up delay.............................................................................................................................139 10.2 Behavior after certain events in the redundancy mode .............................................................140 10.3 10.3.1 10.3.2 Startup characteristics ...............................................................................................................141 Startup characteristics of the DP/PA link in non-redundant mode.............................................141 Startup characteristics in redundancy mode..............................................................................142 10.4 CP 342-5 behind a Y link in a redundant DP master system ....................................................143 DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 9 Table of contents 11 12 13 Maintenance and service ....................................................................................................................... 145 11.1 Replacing IM 153-2 or Y couplers............................................................................................. 145 11.2 Replacing DP/PA couplers........................................................................................................ 146 11.3 Replacing the active field distributor AFD / AFS ....................................................................... 147 11.4 11.4.1 11.4.2 Firmware update ....................................................................................................................... 148 When should you update the IM 153-2? ................................................................................... 148 Update of the IM 153-2 ............................................................................................................. 148 11.5 Maintenance.............................................................................................................................. 151 Functions ............................................................................................................................................... 153 12.1 12.1.1 12.1.2 12.1.3 12.1.4 12.1.5 12.1.5.1 12.1.5.2 IM 153-2 .................................................................................................................................... 153 Time synchronization on the underlying master system........................................................... 153 Redundancy with IM 153-2 ....................................................................................................... 154 Reading and writing data records ............................................................................................. 156 Identification and maintenance data (I&M data) ....................................................................... 158 System modification during operation....................................................................................... 161 System modification in S7 standard mode................................................................................ 161 System modification in redundancy mode ................................................................................ 162 12.2 12.2.1 12.2.2 12.2.3 12.2.3.1 12.2.3.2 12.2.4 12.2.5 12.2.6 DP/PA coupler FDC 157-0 ........................................................................................................ 163 Reading and writing the identification and maintenance data (I&M data) ................................ 163 Reading the local LifeList .......................................................................................................... 164 Read out of the current value and voltage value ...................................................................... 165 User data of the DP/PA coupler................................................................................................ 165 Structure of the current value and voltage value ...................................................................... 167 Data records.............................................................................................................................. 169 Diagnostic record 62 ................................................................................................................. 171 Address space of the inputs...................................................................................................... 172 Interrupt, error and system messages ................................................................................................... 173 13.1 13.1.1 13.1.2 13.1.3 13.1.4 13.1.5 13.1.6 13.1.7 Diagnostics by means of LED displays..................................................................................... 173 The LED displays of the IM 153-2............................................................................................. 173 LED displays of the DP/PA coupler FDC 157-0........................................................................ 176 LED displays of the DP/PA coupler .......................................................................................... 178 LED displays of the Y coupler ................................................................................................... 179 LED displays of the AFD ........................................................................................................... 180 LED displays of the active field splitter (AFS) ........................................................................... 180 LED displays of the active field distributor AFDiS..................................................................... 181 13.2 13.2.1 13.2.2 13.2.3 13.2.3.1 13.2.3.2 13.2.3.3 13.2.3.4 13.2.3.5 13.2.3.6 Diagnostics with STEP 7: IM 153-2 .......................................................................................... 182 Structure of slave diagnostics ................................................................................................... 183 Reading out the diagnostics of underlying slaves..................................................................... 184 Structure of the diagnostic blocks ............................................................................................. 185 Default diagnosis....................................................................................................................... 185 Identifier-related diagnostics ..................................................................................................... 187 Module status............................................................................................................................ 189 Status message ........................................................................................................................ 191 H status ..................................................................................................................................... 194 Interrupts ................................................................................................................................... 196 DP/PA coupler, active field distributors, DP/PA Link and Y Link 10 Operating Instructions, 07/2011, A5E00193841-17 Table of contents 13.2.4 13.2.4.1 13.2.4.2 13.2.4.3 Example of a diagnosis in redundant mode...............................................................................199 Task specification ......................................................................................................................199 Solution with STEP 7 .................................................................................................................200 Evaluating the diagnostics data .................................................................................................201 13.3 Diagnostics with STEP 7: DP/PA coupler FDC 157-0 ...............................................................204 13.3.1 Structure of slave diagnostics ....................................................................................................204 13.3.2 Structure of the diagnostic blocks ..............................................................................................205 13.3.2.1 Station statuses 1 to 3 ...............................................................................................................205 13.3.2.2 Master PROFIBUS address.......................................................................................................207 13.3.2.3 Manufacturer ID .........................................................................................................................207 13.3.2.4 PA status....................................................................................................................................208 13.3.2.5 Identifier-related diagnostics ......................................................................................................209 13.3.2.6 Module status.............................................................................................................................210 13.3.2.7 Local LifeList ..............................................................................................................................211 13.3.2.8 PA redundancy status................................................................................................................212 13.3.2.9 Channel-related diagnostics ......................................................................................................213 13.3.2.10 H status.................................................................................................................................214 14 Technical specifications......................................................................................................................... 215 14.1 14.1.1 14.1.2 14.1.3 General technical data ...............................................................................................................215 Standards and Approvals...........................................................................................................215 Standards and approvals of DP/PA Ex [i] coupler(6ES7157-0AD82-0XA0) .............................219 Standards and approvals of the active field distributors (AFD) and active field splitters (AFS)..........................................................................................................................................221 14.1.4 Standards and approvals of active field distributor AFDiS ........................................................223 14.1.5 Use in zone 2 potentially explosive areas..................................................................................224 14.1.6 Electromagnetic compatibility ....................................................................................................224 14.1.7 Shipping and storage conditions................................................................................................226 14.1.8 Mechanical and climatic ambient conditions for operation ........................................................227 14.1.9 Specifications for insulation tests, protection class and degree of protection ...........................230 14.1.10 Rated voltage .............................................................................................................................230 A 14.2 Technical specifications of the IM 153-2 (6ES7153-2BAx2-0XB0) ...........................................231 14.3 Technical data DP/PA coupler FDC 157-0 (6ES7157-0AC83-0XA0)........................................232 14.4 Technical specifications of DP/PA coupler Ex [i] (6ES7157-0AD82-0XA0) ..............................234 14.5 Technical specifications Y coupler (6ES7197-1LB00-0XA0).....................................................235 14.6 Technical data - active field splitter (AFS) (6ES7157-0AF82-0XA0) .........................................236 14.7 Technical data - active field distributor (AFD) (6ES7157-0AF81-0XA0)....................................237 14.8 Technical specifications of active field distributor AFDiS (6ES7157-0AG83-0XA0)..................238 Appendix................................................................................................................................................ 241 A.1 A.1.1 A.1.2 Dimension drawings...................................................................................................................241 Active field distributor AFD/AFS.................................................................................................241 Active field distributor AFDiS .....................................................................................................243 A.2 A.2.1 A.2.2 A.2.3 Order numbers ...........................................................................................................................245 Components of the bus links......................................................................................................245 Accessories for PROFIBUS DP .................................................................................................246 Accessories for PROFIBUS PA .................................................................................................247 DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 11 Table of contents A.3 A.3.1 A.3.2 A.3.3 A.3.4 Basics about PROFIBUS PA .................................................................................................... 248 Intrinsic safety ........................................................................................................................... 249 Field device supply via PROFIBUS PA..................................................................................... 250 Configuration of PROFIBUS PA with the DP/PA link bus coupler ............................................ 251 Line and star-type topology....................................................................................................... 252 Glossary ................................................................................................................................................ 255 Index...................................................................................................................................................... 263 DP/PA coupler, active field distributors, DP/PA Link and Y Link 12 Operating Instructions, 07/2011, A5E00193841-17 Product Overview 1.1 1 Bus links DP/PA coupler The DP/PA coupler is the physical link between PROFIBUS DP and PROFIBUS PA. In stand-alone operation it offers the possibility of addressing PA field devices via PROFIBUS DP. No other components are required for this. The DP/PA coupler is also used for more advanced coupling tasks in the DP/PA link. The DP/PA coupler Ex [i] is available for connecting PA field devices in explosion protected environments. DP/PA coupler FDC 157-0 The DP/PA coupler FDC 157-0, FDC stands for "Field Device Coupler" has PROFIBUS-DP diagnostic functions as DP slave. Using a DP/PA coupler pair and field distributors enables redundant operation on an equipotential bonding line in 2 variants: Coupler redundancy with the active field splitter AFS Ring redundancy with active field distributors AFD and AFDiS. The DP/PA coupler FDC 157-0 can be used stand-alone or in the DP/PA link in this regard Active field distributors Active field distributors distribute the PROFIBUS PA via spur lines to the PA field devices. You can connect up to 31 PA field devices to the active field distributors depending on the version, e.g. measuring instruments, sensors and actuators. AFS (Active Field Splitter): Connection of up to 31 PA field devices AFD (Active Field Distributor): Connection of up to 4 PA field devices AFDiS (Active Field Distributor): Connection of up to 6 PA field devices, use in hazardous areas is possible. The active field distributors are suitable for the extended temperature range. DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 13 Product Overview 1.2 Integration in the automation environment DP/PA link The DP/PA link consists of one or two IM 153-2 interface modules, and one to five DP/PA couplers that are either connected with one another via passive bus couplers or via bus modules. The DP/PA link creates a network transition from a PROFIBUS DP master system to PROFIBUS PA. In this case the two bus systems are non-interacting through the IM 153-2 both physically (galvanically) and in terms of protocols and time. By using two IM 153-2 interface modules, the entire lower-level PROFIBUS PA master system can be connected to a redundant DP master system of an S7-400H as switched peripherals. For this purpose installation is always executed with bus modules. Y link The Y link comprises two IM 153-2 interface modules and a Y coupler that are connected to one another via bus modules. The Y link creates a network transition from the redundant DP master system of an S7-400H to a non-redundant DP master system. This means that devices with only one PROFIBUS DP interface can be connected to a S7-400H as switched peripherals. 1.2 Integration in the automation environment 1.2.1 What are distributed I/O devices? Distributed I/O Devices - Field of Application When a system is configured, the I/Os from and/or to the process are often integrated centrally in the automation system. In the case of greater distances of the inputs and outputs from the automation system the wiring may be very extensive and confusing. Electromagnetic interference may be impair reliability. Distributed I/O is suitable for use with systems of this kind. The PROFIBUS DP master is located in a central position. The distributed I/O devices (inputs and outputs) work at their decentral locations. With its high transmission speeds the high power PROFIBUS DP ensures that the control system CPU and the distributed I/O devices communicate smoothly. DP/PA coupler, active field distributors, DP/PA Link and Y Link 14 Operating Instructions, 07/2011, A5E00193841-17 Product Overview 1.2 Integration in the automation environment What is PROFIBUS DP? PROFIBUS DP is an open bus system conforming to IEC 61784-1:2002 Ed1 CP 3/1 with the "DP" transmission protocol (DP stands for distributed I/O). Physically PROFIBUSDP is implemented either as an electrical network based on shielded twisted-pair cables, or as an optical network based on fiber optic cable. The "DP" transmission protocol facilitates very fast cyclical data exchange between the control system CPU and the distributed I/O devices. What is PROFIBUS PA? PROFIBUS PA is the communication-compatible extension of PROFIBUS DP to include a transmission technology that also permits applications in potentially explosive areas. Transmission from PROFIBUS PA conforms to the international IEC 617841:2002 Ed1 CP 3/2 standard. PROFIBUS PA enables transducers and control devices in potentially explosive areas to communicate with the automation system over long distances. With the PROFIBUS PA the field devices can be fed via the data lead at the same time. The following components are available for the transition of the transmission technology of PROFIBUS DP (IEC 61784-1:2002 Ed1 CP 3/1) to PROFIBUS PA (IEC 617841:2002 Ed1 CP 3/2): DP/PA coupler in stand-alone mode DP/PA link DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 15 Product Overview 1.2 Integration in the automation environment 1.2.2 DP/PA coupler FDC 157-0 with active field distributors DP/PA coupler FDC 157-0 with active field distributors The DP/PA coupler FDC 157-0 with diagnostics function is a transition between PROFIBUS DP and PROFIBUS PA. Active field distributors combine the field devices with the main line and ensure a rugged field distribution. Using a DP/PA coupler pair and field distributors also enables redundant operation on an equipotential bonding line in the following variants: Coupler redundancy with the active field splitter AFS Ring redundancy with a maximum 8 active field distributors (AFD) Ring redundancy with a maximum of 5 active field distributors with mixed use of AFD and AFDiS +LJKHUOHYHOOD\HU ,QGXVWULDO(WKHUQHW '30DVWHU 352),%86'3 '36ODYH '33$FRXSOHU )'& $)' /RZHVWOHYHOILHOG GHYLFHV '33$FRXSOHU )'& $)6 $)' 352),%863$ Figure 1-1 Integration of the DP/PA coupler FDC 157-0 in the system environment DP/PA coupler, active field distributors, DP/PA Link and Y Link 16 Operating Instructions, 07/2011, A5E00193841-17 Product Overview 1.2 Integration in the automation environment DP/PA coupler FDC 157-0 with AFDiS Up to 5 active field distributors AFDiS can be mounted in the hazardous area zone 1/21. You can connect intrinsically safe PA field devices, which may be located in Zone 0/20, to the AFDiS. +LJKHUOHYHOOD\HU ,QGXVWULDO(WKHUQHW '30DVWHU 352),%86'3 '36ODYH '33$FRXSOHU )'& '33$FRXSOHU )'& $)6 352),%863$ $)'L6 $)'L6 $)'L6 $)'L6 3RWHQWLDOO\H[SORVLYH DWPRVSKHUH=RQH /RZHVWOHYHOILHOG GHYLFHV 3RWHQWLDOO\H[SORVLYH DWPRVSKHUH=RQH Figure 1-2 DP/PA coupler FDC 157-0 with AFDiS DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 17 Product Overview 1.2 Integration in the automation environment 1.2.3 DP/PA coupler / DP/PA Ex [i] coupler DP/PA coupler The DP/PA coupler is a transition between PROFIBUS DP and PROFIBUS PA to which the PA field devices are connected. The following figure shows how the DP/PA coupler is integrated into the system. 2SHUDWRUVWDWLRQRUHQJLQHHULQJ VWDWLRQZLWKSDUDPHWHUL]DWLRQ WRRO +LJKHUOHYHOOD\HU ,QGXVWULDO(WKHUQHW /RFDOSDUDPHWHUL]DWLRQWRRO '3PDVWHU 352),%86'3 '33$FRXSOHU([>L@ '33$FRXSOHU '3VODYH 352),%863$ /RZHVWOD\HUILHOG GHYLFHV 3RWHQWLDOO\H[SORVLYHDUHD Figure 1-3 Integration of the DP/PA coupler within the system environment DP/PA coupler, active field distributors, DP/PA Link and Y Link 18 Operating Instructions, 07/2011, A5E00193841-17 Product Overview 1.2 Integration in the automation environment 1.2.4 DP/PA link DP/PA link In relation to higher level systems (towards the automation device) the DP/PA link is a DP slave and it is a DP master in relation to lower level systems. The following figure shows how the DP/PA link is integrated into the system. 2SHUDWRUVWDWLRQRU HQJLQHHULQJVWDWLRQZLWK FRQILJXUDWLRQWRRO +LJKHUOHYHO ,QGXVWULDO(WKHUQHW /RFDOFRQILJXUDWLRQWRRO '3PDVWHU 352),%86'3 '33$OLQN '3 VODYH '33$FRXSOHU /RZHVWOHYHOILHOG GHYLFHV ,0 352),%863$ )LHOGGHYLFHVRI352),%863$ Figure 1-4 Integration of the DP/PA coupler within the system environment DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 19 Product Overview 1.2 Integration in the automation environment 1.2.5 Y link Y link In relation to higher level systems (towards the automation device) the Y link is a DP slave and it is a DP master in relation to lower level systems. The following figure shows how the Y link is integrated into the system. 2SHUDWRUVWDWLRQRU HQJLQHHULQJVWDWLRQZLWK FRQILJXUDWLRQWRRO +LJKHUOHYHO ,QGXVWULDO(WKHUQHW /RFDOFRQILJXUDWLRQWRRO 6+ 5HGXQGDQW'3PDVWHU V\VWHP 1 m). Length of the PROFIBUS PA main line up to 1900 m, without taking into account the sum of the spur lines, because these are to be considered separately from the main line via the repeater. This enables significantly greater network spans than in the case of devices without a repeater function. Electrical isolation and bi-directional signal reproduction ensure reaction-free transmission between PA main lines and spur lines. This will significantly increase the segment's resistance to faults. DP/PA coupler, active field distributors, DP/PA Link and Y Link 36 Operating Instructions, 07/2011, A5E00193841-17 Description of the components 2.10 Compatibility with predecessor modules 2.10 Compatibility with predecessor modules Compatibility DP/PA coupler FDC 157-0: The DP/PA coupler FDC 157-0 with order number 6E7157-0AC83-0XA0 replaces the DP/PA coupler with order number 6E7157-0AC82-0XA0. The bus module does not need to be replaced. On the DP/PA coupler FDC 157-0 the PROFIBUS address is factory set to 0. Thus the diagnostic function is deactivated, the DP/PA coupler is transparent. This means that it is compatible to the predecessor module as a replacement part. Configuration is not required. Note Diagnostics function If you would like to use the diagnostic function of the DP/PA coupler FDC 157-0 in existing systems as well, then set the PROFIBUS address on the DP/PA coupler and in the configuration > 0. Note Redundancy mode If you would like to use the DP/PA coupler FDC 157-0 with ring redundancy or coupler redundancy, then you must use the BM FDC/FDC (redundant) bus module. Bus module BM FDC/FDC (redundant) The bus module BM FDC (redundant) with order number 6ES7195-7HG80-0XA0 can only be used together with the DP/PA coupler FDC 157-0 with order number 6ES7157-0AC83-0XA0. Compatibility of the IM 153-2 and the IM 157 You can find information on compatible versions of interface modules IM 153-2 and IM 157 on the Internet (http://support.automation.siemens.com/WW/view/en/23372259). Compatibility of the Y coupler Der Y coupler 6ES7197-1LB00-0XA0 cannot be used as a spare part for Y coupler 6ES7654-0YK00-0AB0. Compatibility of the bus modules The bus module BM IM/IM 6ES7195-7HD80-0XA0 can only be used together with the following interface modules: IM 153-2BAx1-0XB0 IM 153-2BAx2-0XB0 IM 157-0AA82-0XA0 It can not be used as a spare part for 6ES7195-7HE80-0XA0. DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 37 Description of the components 2.10 Compatibility with predecessor modules DP/PA coupler, active field distributors, DP/PA Link and Y Link 38 Operating Instructions, 07/2011, A5E00193841-17 Active field distributor AFDiS in hazardous areas 3.1 3 Fundamentals of hazardous areas and intrinsic safety Properties of zones Hazardous areas are classified into zones. The zones are distinguished according to the probability of the existence of an explosive atmosphere. The active field distributor AFDiS can be used in hazardous areas up to Zone 1/ 21. You can connect intrinsically safe PA field devices, which may be located in Zone 0/20, to the AFDiS. The PA field devices must be certified for operation in the corresponding hazardous areas. You will find an overview of the zone divisions in the following table: Table 3- 1 Classification of zones Hazardous areas Explosion hazard Example Zone 0/ 20 Long-term, frequent or permanent presence of explosive gas or dust atmosphere Within containers. Zone 1/ 21 Infrequent presence of potentially explosive gas or dust atmosphere In the area of openings for filling and emptying. Zone 2/ 22 Rare or short-term presence of potentially explosive gas or dust atmosphere Areas bordering on zone 1/ 21 For additional information, refer to the Principles of Explosion Protection (http://support.automation.siemens.com/WW/view/en/12521844) system manual. DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 39 Active field distributor AFDiS in hazardous areas 3.1 Fundamentals of hazardous areas and intrinsic safety Design types of protection on AFDiS The types of protection include design and electrical measures relating to the equipment to achieve explosion protection in the hazardous areas. The following types of protection can be used for AFDiS: Table 3- 2 Types of protection Type of protection Meaning Intrinsic safety i All voltages, currents, inductance and capacitance occurring are limited by electrical measures (intrinsically safe) sparks or thermal effects capable of causing ignition cannot occur. Representation The spur line connections of AFDiS are designed to be intrinsically safe [ia]. Increased-safety enclosure e The enclosure and the main line terminals of the AFDiS have the increased safety Ex e type of protection. This type of protection has additional features that provide an increased degree of safety against the occurrence of high temperatures, sparks and arcover. Encapsulation "m" The internal electronics of the AFDiS are embedded in a casting compound. This means that an explosive atmosphere surrounding the equipment can be ignited neither by sparks nor by unacceptable heating. Marking of the AFDiS Equipment for operation in hazardous areas is marked with an identifier indicating the hazardous environments in which the equipment can be used. The AFDiS has the following safety measures: (QFORVXUHDQG3$PDLQOLQHWHUPLQDOVSURWHFWHG E\PHDQVRILQFUHDVHGVDIHW\ (OHFWURQLFVSURWHFWHGE\HQFDSVXODWLRQ 6SXUOLQHVLJQDOVSURWHFWHGE\LQWULQVLFVDIHW\ DP/PA coupler, active field distributors, DP/PA Link and Y Link 40 Operating Instructions, 07/2011, A5E00193841-17 Active field distributor AFDiS in hazardous areas 3.1 Fundamentals of hazardous areas and intrinsic safety Certifications of the active field distributor AFDiS The EC type-examination certificate and EC certificates of conformity for the active field distributor AFDiS can be found on the Internet (http://www.siemens.com/automation/csi_en_WW/support) at Service & Support. Verification of intrinsic safety The active field distributor limits the energy in hazardous areas on the spur line to the intrinsically safe PA field devices and electrically isolates them from the PA main line. All spur lines have Ex [ia] type of protection and can therefore be installed in Zone 0/20. In addition to the following requirements, no further verification of the intrinsic safety in accordance with the FISCO model is required: PROFIBUS PA bus cable (6XV1830-5AH10) for the PA main lines and for the spur lines to the intrinsically-safe PA field devices Maximum spur line length 60 m or subsegment line length of 500 m at connection S1 DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 41 Active field distributor AFDiS in hazardous areas 3.2 Configuration with AFDiS 3.2 Configuration with AFDiS Introduction The active field distributor AFDiS is designed for hazardous areas. It supplies up to six spur lines or five spur lines and a subsegment with a length of up to 500 meters. The subsegment is supplied with 60 mA for max. 6 devices. To achieve the maximum availability for each port, connect only one device to each port. Active field distributor AFDiS with subsegment in hazardous areas The following graphic shows an example of the configuration of a DP/PA system with several field distributors. The subsegment of an AFDiS with its connected devices extends into Zone 0. To prevent signal reflections, the subsegment must be terminated with a bus terminating resistor. 352),%86'3 '33$FRXSOHU )'& $)'L6 $)'L6 $)'L6 3RWHQWLDOO\H[SORVLYH DWPRVSKHUH=RQH 6XEVHJPHQW PD[P %XVWHUPLQDWRU UHVLVWRU 2KP 3RWHQWLDOO\H[SORVLYH DWPRVSKHUH=RQH Figure 3-1 AFDiS with subsegment in hazardous areas DP/PA coupler, active field distributors, DP/PA Link and Y Link 42 Operating Instructions, 07/2011, A5E00193841-17 Active field distributor AFDiS in hazardous areas 3.3 Mounting AFDiS 3.3 Mounting AFDiS Safety information DANGER Explosion hazard in Zone 21 / 22 During mounting, observe the guidelines according to EN 60079-14. When you mount the AFDiS in areas with dust (Zone 21, Zone 22), you must also observe EN 61241-14. DANGER Explosion hazard Under some circumstances, sparks capable of ignition or unacceptable surface temperatures can occur during installation. Never install when an explosive atmosphere is present! CAUTION Risk of injury due to high weight of the AFDiS The weight of the AFDiS is 4.5 kg. During mounting, hold the device firmly in your hand. Mounting position Mount the active field distributor AFDiS preferably with the connections facing downward. CAUTION Damage to property A tensile load on the screws is not permitted. Implement a fixed installation for the cable inlet. Requirement The substrate must be level, with load-bearing capacity, and it must be vibration free. Select appropriate fixing accessories for the substrate. Space of at least 60 mm below the modules for the connections of the PA main lines and spur lines. DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 43 Active field distributor AFDiS in hazardous areas 3.4 Grounding Tools required 2 fixing screws M8; dowels depending on the substrate Screwdriver suitable for the screws used Mounting AFDiS Screw the lower part of the enclosure tightly to the substrate with two fixing screws. The torque depends on the fixing screws used. You can find the drill hole spacing on the back of the enclosure base. Additional information Important information can be found in the chapter Mounting work in hazardous areas in the System Manual Principles of Explosion Protection (http://support.automation.siemens.com/WW/view/en/12521844). See also Screwing down the active field distributor AFD and active field splitter AFS on substrate (Page 78) 3.4 Grounding Equipotential bonding EB You must set up an equipotential bonding EB in hazardous areas. This should be in accordance with IEC 60079-14. Shields of the PROFIBUS PA bus lines must be connected to the equipotential bonding EB. The best EMC protection is achieved with direct grounding for the AFDiS active field distributor. Direct grounding The shield of the PROFIBUS PA bus cables is grounded directly in both the hazardous area and in the safe area. This is possible if the equipotential bonding EB ranges from the DP/PA couplers (in the safe area) to the field devices (in hazardous areas), i.e. if a corresponding equipotential bonding conductor was installed. Note Direct grounding on the field distributor AFDiS The braided shield of the PROFIBUS PA cable must be lead through under the shield clamps. DP/PA coupler, active field distributors, DP/PA Link and Y Link 44 Operating Instructions, 07/2011, A5E00193841-17 Active field distributor AFDiS in hazardous areas 3.4 Grounding Example of direct grounding 6DIH]RQH 3RWHQWLDOO\H[SORVLYHDWPRVSKHUH '33$FRXSOHU $)'L6 $)'L6 7V 7V 6V 6V 6V 6V 6V 6V 7V 7V 6V 6V 6V 6V 6V 6V *URXQG LQJEDU *URXQG LQJEDU )LHOGGHYLFH )LHOGGHYLFH (TXLSRWHQWLDOERQGLQJ3$ Figure 3-2 Example: Direct grounding See also Principles of Explosion Protection (http://support.automation.siemens.com/WW/view/en/12521844) profibus.com (http://www.profibus.com) DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 45 Active field distributor AFDiS in hazardous areas 3.5 Safety instructions for connection 3.5 Safety instructions for connection Safety information DANGER When laying cables and wiring, make sure that you adhere to the installation regulations in accordance with EN 60079-14 and any regulations specific to your country. Information on how to install the PROFIBUS PA can be found in the "Technical Guideline PROFIBUS PA, User and Installation Guideline". Available from PROFIBUS Nutzerorganisation e. V. DANGER Explosion hazard Ignitable sparks may be generated during connection. Therefore use a non-magnetic screwdriver when connecting the cables! DANGER Explosion hazard A tensile load on the screws of AFDiS can impair the degree of protection and is not permitted. Implement a fixed Installation for inlet of the cable! DANGER Explosion hazard In mixed operation with AFD, always disconnect the DP/PA couplers from the power supply before you replace active field distributors AFDiS. WARNING Risk for intrinsic safety If the wrong connection is made on the AFDiS (PA main line <--> spur lines) or the cables are incorrectly connected to the PA field devices, the intrinsic safety is put at risk: Only connect Ex i circuits (intrinsically-safe PA field devices) to the spur lines! Check the wiring to the PA field devices. DP/PA coupler, active field distributors, DP/PA Link and Y Link 46 Operating Instructions, 07/2011, A5E00193841-17 Active field distributor AFDiS in hazardous areas 3.5 Safety instructions for connection IP30 cover The connections of the PA main cables inside the enclosure of the AFDiS are sealed with an IP30 cover. Opening the IP30 cover switches off the voltage supply to the terminals and the feed lines. Depending on the zone in which the AFDiS is located, you are permitted to open the IP30 cover during operation for a visual inspection. 6 7 Figure 3-3 7 6 6 6 6 6 6 6 6 6 6 6 AFDiS with IP30 covers DANGER Explosion hazard In the potentially explosive area Zone 1 you are not permitted to open the IP30 cover during operation. Before opening the IP30 cover, disconnect the voltage supply to the relevant DP/PA couplers. In the potentially explosive area Zone 2, you are permitted to open the IP30 cover during operation. Zone 1: Disconnecting the main line / connecting the main line to AFDiS DANGER Explosion hazard In the potentially explosive area Zone 1 it is not permitted to disconnect the main line to an AFDiS during operation. Prior to starting work, disconnect the voltage supply to the DP/PA coupler(s). DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 47 Active field distributor AFDiS in hazardous areas 3.5 Safety instructions for connection Zone 2: Disconnecting the main line / connecting the main line to AFDiS DANGER Explosion hazard In the potentially explosive area Zone 2, you are not permitted to disconnect the main line to an AFDiS during operation if it is directly connected to a DP/PA coupler or an AFS. Prior to starting work, disconnect the voltage supply to the DP/PA coupler(s). In hazardous area Zone 2, it is permissible to disconnect a main line to a AFDiS during operation if you have connected 2 AFDiS. Note Labelling the AFDiS In your plant, label the field distributors AFDiS which are directly connected to the DP/PA coupler or AFS. DP/PA coupler, active field distributors, DP/PA Link and Y Link 48 Operating Instructions, 07/2011, A5E00193841-17 Active field distributor AFDiS in hazardous areas 3.5 Safety instructions for connection Rules for connecting the cables The following examples illustrate the rules which you must observe when connecting main lines: )'& =RQH $OZD\VGLVFRQQHFW)'&IURPWKHSRZHUVXSSO\ =RQH 'LVFRQQHFW)'&IURPWKHSRZHUVXSSO\ZKHQGLVFRQQHFWLQJWKHFDEOH WRWKH$)'L6 $)'L6 =RQH )'& 'LVFRQQHFWERWK)'&VIURPWKHSRZHUVXSSO\ =RQH 'LVFRQQHFW)'&IURPWKHSRZHUVXSSO\ZKHQGLVFRQQHFWLQJWKHFDEOH WRWKH$)'L6 'LVFRQQHFW)'&IURPWKHSRZHUVXSSO\ZKHQGLVFRQQHFWLQJWKHFDEOH WRWKH$)'L6 )'& =RQH 'LVFRQQHFWERWK)'&VIURPWKHSRZHUVXSSO\ =RQH 'LVFRQQHFWERWK)'&VIURPWKHSRZHUVXSSO\ZKHQGLVFRQQHFWLQJWKHFDEOH $)6 7KHIROORZLQJDSSOLHVWRDOOFRQILJXUDWLRQV =RQH&RQQHFWLRQRIWKHFDEOHV LVSRVVLEOHGXULQJRSHUDWLRQ )RUPL[HGRSHUDWLRQZLWK$)''LVFRQQHFW)'&IURPWKHSRZHUVXSSO\ The spur lines S1 to S6 can always be connected during operation. DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 49 Active field distributor AFDiS in hazardous areas 3.6 Connecting PROFIBUS PA to the AFDiS 3.6 Connecting PROFIBUS PA to the AFDiS Introduction The PROFIBUS PA cables are introduced into the enclosure by means of cable glands. The PA main line via T1 and T2. The spur lines to the field devices via S1 to S6 6 7 Figure 3-4 7 6 6 6 6 6 6 6 6 6 6 6 Internal view of AFDiS Pin assignment Connect the wiring of the PROFIBUS PA cable to the terminal block in the active field distributor via the screw-type terminals. Table 3- 3 77 Pin assignment on the active field distributor AFDiS 77 Connection T1, T2 S11 to S6 Shield / bar 66 66 Terminal Main line Spur line to the field devices 66 66 66 66 Assignment + Data cable (red) - Data cable (green) + Data cable (red) - Data cable (green) Direct grounding for T1/T2; S1 to S6 S1 optionally for a subsegment with a length of up to 500 m or for a spur line; line termination with bus terminating resistor 1 DP/PA coupler, active field distributors, DP/PA Link and Y Link 50 Operating Instructions, 07/2011, A5E00193841-17 Active field distributor AFDiS in hazardous areas 3.6 Connecting PROFIBUS PA to the AFDiS Basic procedure 1. Prepare PROFIBUS PA cable. 2. Connect the PROFIBUS PA cable: - Open the field distributor. - Connect the spur lines and PA main lines to the terminal block. 3. Close field distributor Requirement Active field distributor is mounted. Note Before connecting the PROFIBUS PA, read the chapter "Safety instructions for connection"! Tools required Phillips screwdriver, size 4 Open ring spanner 19 mm Screwdriver 3 mm Small knife, end-cutting nipper or FC stripping tool Required accessories PROFIBUS PA cable (cable type A) Sealing plugs for unused connections Stripping dimensions for PROFIBUS PA cable For secure connection of the wires in the screw-type terminals, observe the following stripping dimensions of the PA cables for the main lines and spur lines. Table 3- 4 Stripping dimensions for PA cable Type of grounding Direct grounding Length of stripping a Main line T1, T2 Spur lines S1 to S3 Spur lines S4 to S6 105 mm 120 mm 105 mm DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 51 Active field distributor AFDiS in hazardous areas 3.6 Connecting PROFIBUS PA to the AFDiS Direct grounding: Prepare PROFIBUS PA cable 1. Remove the union nut of the cable gland of the AFDiS using the ring spanner. 2. Thread the union nut onto the unprepared- PA cable. 3. Strip the PA cable as shown in the figure. PP PP D Direct grounding: Connect the PROFIBUS PA cable to S1 to S6 1. Open the field distributor: Remove the 4 screws of the enclosure cover using a Phillips screwdriver. 2. Insert the cable under the shield clamp and tighten the screw. 3. Connect the wires to the terminal block in accordance with the pin assignment. Torque 0.35 Nm. 4. Tighten the union nut of the cable gland. Torque 1.3 Nm. Direct grounding: Connect the PROFIBUS PA cable to T1/T2 WARNING Hazardous area - Zone 1 Under no circumstances connect the PA main line to the AFDiS during operation. Before connecting the PROFIBUS PA to the AFDiS, disconnect all the supply voltages of the bus segment! 1. Route the cable for the main line through the cable gland T1/T2 under the shield clamp and tighten the screw. 2. Open the IP30 cover T1/T2. 3. Connect the wires to the terminal block T1/T2 in accordance with the pin assignment. 4. Close the IP30 covers until you hear them engage. 5. Tighten the union nut of the cable gland. Torque 1.3 Nm. NOTICE Impairment of the degree of protection The degree of protection can be impaired if you overtighten the union nut. DP/PA coupler, active field distributors, DP/PA Link and Y Link 52 Operating Instructions, 07/2011, A5E00193841-17 Active field distributor AFDiS in hazardous areas 3.7 Grounding AFDiS Close field distributor 1. Place the enclosure cover on the enclosure base and tighten the 4 screws. Torque 2.4 Nm. NOTICE Impairment of the degree of protection The degree of protection IP66 will not be guaranteed if connections are not used. Close unused connections with a sealing cap. The union nuts with the yellow dust protection caps are not sufficient protection. See also Grounding (Page 44) Connecting the PROFIBUS PA to the active field distributor (AFD) (Page 95) Components of the bus links (Page 245) 3.7 Grounding AFDiS Required accessories Grounding cable, at least 4.0 mm2 Grounding the active field distributor AFDiS 1. Strip the insulation of the grounding cable to 8 mm. 2. Fasten the grounding cable to the right-hand or left-hand grounding terminal of the AFDiS. DANGER Active field distributor AFDiS Connect the grounding cable with the equipotential bonding EB in accordance with EN 60079-14. See also Grounding the active field distributor AFD / AFS (Page 90) DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 53 Active field distributor AFDiS in hazardous areas 3.8 AFDiS maintenance and cleaning 3.8 AFDiS maintenance and cleaning Permitted activities in hazardous areas The table below describes which maintenance activities on AFDiS are permitted during operation. WARNING Hazardous areas Zone 1 and Zone 2: You may open the enclosure of the AFDiS briefly for the permitted maintenance work. Zone 21 and Zone 22: You may not open the enclosure of the AFDiS in areas with dust. Table 3- 5 Permitted activities in hazardous areas Activities Zone 1, Zone 2 Zone 21, Zone 22 Maintenance during operation (visual checks) allowed Warning: The enclosure of the AFDiS must not be opened for this activity in areas with dust . Cleaning allowed Not permitted Maintenance during operation Carry out maintenance every 6 months in the hazardous area. Maintenance of the AFDiS is basically restricted to visual inspections. The AFDiS may be in operation during this. Zone 1/ 2 Zone 21/ 22 Check that the cable entries and grounding terminal of the enclosure are sealed and intact. Check that the cable entries and grounding terminal of the enclosure are sealed and intact. Warning: It is not permitted to open the enclosure of the AFDiS. Check whether there is any water or dust inside the enclosure. If there is, find out how it got there. -- Check that the wiring is secure (connectors, cables). -- DP/PA coupler, active field distributors, DP/PA Link and Y Link 54 Operating Instructions, 07/2011, A5E00193841-17 Active field distributor AFDiS in hazardous areas 3.8 AFDiS maintenance and cleaning Cleaning WARNING Hazardous areas - Zones 21 and 22 The dust layer on the enclosure of the AFDiS must not exceed a depth of 5 mm. Remove the dust layer on the enclosure at regular intervals! During cleaning, make sure there is no risk of explosion! To do this, disconnect the unit from the voltage. Note Following cleaning, run a functional check of the AFDiS. See also Safety instructions for connection (Page 46) Connecting PROFIBUS PA to the AFDiS (Page 50) DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 55 Active field distributor AFDiS in hazardous areas 3.9 Replacing/supplementing the AFDiS 3.9 Replacing/supplementing the AFDiS DANGER Explosion hazard In mixed operation with AFD, disconnect the DP/PA couplers from the power supply before you replace active field distributors AFDiS. DANGER Explosion hazard Observe the safety instructions in chapter "Safety instructions for connection (Page 46)". Replacing / supplementing an active field distributor AFDiS Perform the following steps to replace a defective field distributor: 1. Remove the 4 screws of the enclosure cover using a Phillips screwdriver. 2. Loosen the black and blue union nuts. 3. Disconnect the PA field devices S1 to S6. 4. Open the IP30 covers T1/T2 and disconnect the PA main lines. 5. Replace the module. 6. Connect the PA field devices to the new AFDiS (refer to chapter entitled "Connecting PROFIBUS PA to the active field distributor AFDiS (Page 50)"). 7. Connect the PA main cables T1/T2 to AFDiS and close the IP30 covers until you hear them engage. 8. Tighten the union nuts with 1.3 Nm. 9. Place the enclosure cover on the base and tighten the 4 screws with the plain washers on the enclosure with 2.4 Nm. See also Replacing the active field distributor AFD / AFS (Page 147) LED displays of the active field distributor AFDiS (Page 181) DP/PA coupler, active field distributors, DP/PA Link and Y Link 56 Operating Instructions, 07/2011, A5E00193841-17 4 Application planning 4.1 Installation variants with the DP/PA coupler FDC 157-0 4.1.1 Configuration variants Introduction You can install a maximum of 5 DP/PA couplers FDC 157-0, of which one coupler pair is installed in redundancy mode at the end of the configuration. The bus module BM FDC/FDC is required for operation with ring redundancy and coupler redundancy. DP/PA couplers in the DP/PA link If you use the IM 153-2 together with the DP/PA couplers as DP/PA link, in this case the PROFIBUS DP connections to the DP/PA couplers are not required. The IM 153-2 and the DP/PA couplers are connected via the S7 backplane bus. Diagnostics function The diagnostic function of the DP/PA coupler FDC 157-0 is available if valid PROFIBUS addresses are set on the DP/PA couplers and in the configuration software. Applications The following table lists the applications for the DP/PA coupler FDC 157-0 and the available functions. Table 4- 1 Applications DP/PA coupler FDC 157-0 Applications DP/PA coupler FDC 157-0 Functions Replacement for DP/PA coupler 6ES71570AC82-0XA0 Diagnostics function X X Ring redundancy Coupler redundancy Bus module BM FDC/FDC required Stand-alone mode (without DP/PA link) Operation in the DP/PA link X X Operation in the redundant DP/PA link DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 57 Application planning 4.1 Installation variants with the DP/PA coupler FDC 157-0 See also Combination of non-redundant and redundant DP/PA couplers (Page 68) Configuration variants (Page 70) Setting the PROFIBUS address and redundancy mode (Page 119) 4.1.2 DP/PA coupler in non-redundancy mode You can extend the equipotential bonding line in stand-alone mode as well as in the DP/PA link with AFDs. DP/PA coupler in stand-alone mode )'& 352),%86'3 352),%863$ $)' $)' $)' DP/PA coupler, active field distributors, DP/PA Link and Y Link 58 Operating Instructions, 07/2011, A5E00193841-17 Application planning 4.1 Installation variants with the DP/PA coupler FDC 157-0 DP/PA coupler in the DP/PA link ,0 )'& 352),%86'3 352),%863$ $)' 4.1.3 DP/PA coupler in redundancy mode 4.1.3.1 Ring redundancy with active field distributor (AFD) $)' $)' Ring redundancy The use of a DP/PA coupler pair and of active field distributors increases the availability of the equipotential bonding line. Ring redundancy is created by configuring a ring structure with 2 FDC-157-0 DP/PA couplers and field distributors: Up to 8 field distributors when exclusively using AFD Up to 5 field distributor with mixed use of AFD and AFDiS The active DP/PA coupler FDC 157-0 supplies the equipotential bonding line. In the event of short-circuit or wire break on the PA main line the active DP/PA coupler supplies the cut equipotential bonding line in both directions. PA field device function remains intact. Repairs can be executed during operation. NOTICE Power supply To ensure availability in redundancy mode we recommend using an autonomous power supply module for each DP/PA coupler. DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 59 Application planning 4.1 Installation variants with the DP/PA coupler FDC 157-0 Installation with ring redundancy )'& )'& 352),%86'3 352),%863$ $)' $)' $)' $)' DP/PA coupler, active field distributors, DP/PA Link and Y Link 60 Operating Instructions, 07/2011, A5E00193841-17 Application planning 4.1 Installation variants with the DP/PA coupler FDC 157-0 Ring redundancy: Component behavior in the event of errors Table 4- 2 Ring redundancy: Component behavior in the event of errors Components DP/PA coupler pair Active field distributors PA field devices equipotential bonding line O. K. O. K. O. K. Insulate, and terminate adjacent AFD / ADFiS. O. K. Equipotential bonding line is cut but is still supplied. Error Failure of the energizing DP/PA coupler Switchover to partner coupler. Partner coupler takes over the power supply of the equipotential bonding line. Short circuit or wire break on the PA main line The active energizing DP/PA coupler supplies the cut equipotential bonding line in both directions. The partner coupler is active conducting. Short-circuit on the spur line O. K. Current limit of the AFD / AFDiS is active. O. K. Non-participating field devices remain O.K. Field distributor reports failure on the AFD spur line: green LED flashes, AFDiS: blue LED flashes Field device on the affected spur line fails. See also Connections for ring redundancy (Page 94) DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 61 Application planning 4.1 Installation variants with the DP/PA coupler FDC 157-0 4.1.3.2 Coupler redundancy with active field splitter (AFS) Coupler redundancy The use of a DP/PA coupler pair and of an active field splitter enables redundancy mode on the equipotential bonding line. The active DP/PA coupler FDC 157-0 supplies the equipotential bonding line in this process. Failure of a DP/PA coupler results in switchover to the partner coupler. PA field device function remains intact. Installation with coupler redundancy )'& )'& 352),%86'3 $)6 352),%863$ $)' $)' NOTICE Power supply To ensure availability in redundancy mode we recommend using an autonomous power supply module for each DP/PA coupler. DP/PA coupler, active field distributors, DP/PA Link and Y Link 62 Operating Instructions, 07/2011, A5E00193841-17 Application planning 4.1 Installation variants with the DP/PA coupler FDC 157-0 Installation with coupler redundancy and center feed A cable bushing for looping through the equipotential bonding line is available on the active field splitter (AFS). )'& )'& 352),%86'3 352),%863$ $)6 $)' $)' $)' See also Connections for coupler redundancy (Page 98) DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 63 Application planning 4.1 Installation variants with the DP/PA coupler FDC 157-0 4.1.3.3 Redundancy mode of the DP/PA coupler in the DP/PA link DP/PA coupler with ring redundancy in the DP/PA link ,0 )'& )'& 352),%86'3 352),%863$ $)' $)' $)' $)' DP/PA coupler, active field distributors, DP/PA Link and Y Link 64 Operating Instructions, 07/2011, A5E00193841-17 Application planning 4.1 Installation variants with the DP/PA coupler FDC 157-0 DP/PA coupler with coupler redundancy in the DP/PA link ,0 )'& )'& 352),%86'3 $)6 352),%863$ $)' $)' $)' $)' DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 65 Application planning 4.1 Installation variants with the DP/PA coupler FDC 157-0 4.1.3.4 Redundancy mode of the DP/PA coupler in the redundant DP/PA link DP/PA coupler with ring redundancy in the redundant DP/PA link ,0 ,0 )'& )'& 352),%86'3 352),%863$ $)' $)' $)' $)' DP/PA coupler, active field distributors, DP/PA Link and Y Link 66 Operating Instructions, 07/2011, A5E00193841-17 Application planning 4.1 Installation variants with the DP/PA coupler FDC 157-0 DP/PA coupler with coupler redundancy in the redundant DP/PA link ,0 ,0 )'& )'& 352),%86'3 $)6 352),%863$ $)' $)' $)' $)' DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 67 Application planning 4.1 Installation variants with the DP/PA coupler FDC 157-0 4.1.3.5 Combination of non-redundant and redundant DP/PA couplers Introduction You can install a maximum of 5 DP/PA couplers FDC 157-0, of which one coupler pair is installed in redundancy mode at the end of the configuration. Mixed mode is possible with the following modules: DP/PA coupler FDC 157-0 (6ES7157-0AC83-0XA0) DP/PA coupler Ex [i] (6ES7157-0AD82-0XA0) DP/PA coupler with ring redundancy in the DP/PA link ,0 )'& )'& )'& )'& )'& 352),%86'3 $)' $)' $)' $)' $)' 352),%863$ DP/PA coupler, active field distributors, DP/PA Link and Y Link 68 Operating Instructions, 07/2011, A5E00193841-17 Application planning 4.1 Installation variants with the DP/PA coupler FDC 157-0 DP/PA coupler with coupler redundancy in the DP/PA link ,0 )'& )'& )'& )'& )'& 352),%86'3 $)6 $)' $)' $)' $)' $)' 352),%863$ DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 69 Application planning 4.2 Installation variants with the IM 153-2 4.2 Installation variants with the IM 153-2 4.2.1 Configuration variants With 153-2BAx2 you can configure the following: a DP/PA link with a maximum of 5 DP/PA couplers a Y link with a Y coupler The IM 153-2BA82 is a spare part for IM 153-2BA81 and IM 157 (6ES7157-0AA8x-0XA0). Moreover, the IM 153-2BAxx can be used as an interface module for the distributed I/O device ET 200M. Information on this is to be found in the Distributed I/O device ET 200M operating instructions (http://support.automation.siemens.com/WW/view/en/1142798). Configuration variants in the non-outdoor sector You can implement the combinations listed in the following table in the non-outdoor area using the existing hardware. Table 4- 3 Configuration variants for the links in the non-outdoor sector non-redundant configuration DP/PA coupler IM 153-2 + bus couplers + DP/PA couplers (max. 5 units) BM PS/IM + PS + IM 153-2 + BM FDC (max. 5 units) + DP/PA couplers (max. 5 units) BM IM/IM (7HD10 / 7HD80) + IM 153-2 + BM DP/PA (max. 5 units) + DP/PA couplers (max. 5 units) redundant configuration BM IM/IM (7HD10 / 7HD80) + 2x IM 153-2 + BM FDC (max. 5 units) + DP/PA couplers (max. 5 units) BM IM/IM (7HD10 / 7HD80) + 2x IM 153-2 + BM Y coupler + Y coupler In the table IM 153-2 stands for: IM 153-2 (6ES7153-2BA01-0XB0) IM 153-2 (6ES7153-2BA02-0XB0) IM 153-2 (6ES7153-2BA81-0XB0) IM 153-2 (6ES7153-2BA82-0XB0) DP/PA coupler, active field distributors, DP/PA Link and Y Link 70 Operating Instructions, 07/2011, A5E00193841-17 Application planning 4.2 Installation variants with the IM 153-2 Configuration variants in the outdoor sector You can implement the combinations listed in the following table in the outdoor area using the existing hardware. Table 4- 4 Configuration variants for the links in the outdoor sector non-redundant configuration DP/PA coupler IM 153-2 + bus couplers + DP/PA couplers (max. 5 units) BM IM/IM (7HD80) + IM 153-2 + BM DP/PA (max. 5 units) + DP/PA couplers (max. 5 units) redundant configuration BM IM/IM (7HD80) + 2x IM 153-2 + BM DP/PA (max. 5 units) + DP/PA couplers (max. 5 units) In the table IM 153-2 stands for: IM 153-2 (6ES7153-2BA81-0XB0) IM 153-2 (6ES7153-2BA82-0XB0) References For detailed information on the functions and features of the IM 153-2, please refer to the chapters Functions and Compatibilities. The IM 153-2BAx2 is not only the interface module for the bus couplers DP/PA link and Y link, but also for ET 200M. For the configuration variant options please refer to the Distributed I/O device ET 200M operating instructions (http://support.automation.siemens.com/WW/view/en/1142798). See also Configuration variants (Page 57) 4.2.2 Detecting the configuration variant by means of the IM 153-2 During start-up, the IM 153-2 automatically detects which structure variant (ET 200M or DP/PA-link or Y-link) it is being used in. The IM 153 2 determines its functionality in accordance with this. NOTICE The following structure variants ("mixed structures") are not permissible: Input / output modules and coupler modules in one structure Bus modules BM 2 x 40 / BM 1 x 80 and BM FDC / BM Y coupler in one structure DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 71 Application planning 4.2 Installation variants with the IM 153-2 DP/PA coupler, active field distributors, DP/PA Link and Y Link 72 Operating Instructions, 07/2011, A5E00193841-17 5 Mounting 5.1 Mounting rules Mounting position The IM 153-2, DP/PA coupler and Y coupler module can be mounted in a vertical or horizontal position. WARNING Open equipment The IM 153-2 DP/PA coupler and Y coupler modules are open equipment. This means that they may only be mounted in enclosures, cabinets. or electrical service rooms that can only be accessed by using a key or a tool. Only authorized personnel may have access to the enclosures, cabinets or electrical service rooms. Mounting system The IM 153-2 DP/PA coupler and Y coupler modules are mounted on rails for the S7 mounting system. Free space of 40 mm must be maintained above and below the modules for trouble-free mounting. Additional instructions for installing modules in the S7 mounting system are available in the operating instructions of the SIMATIC- S7-300 CPU 31xC and CPU 31x: Installation (http://support.automation.siemens.com/WW/view/en/36305386) manual. DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 73 Mounting 5.1 Mounting rules Installation location The DP/PA FDC 157-0 coupler or the DP/PA-Koppler Ex [i] or the DP/PA link with DP/PA Ex [i] couplers can be operated in hazardous areas, Zone 2, if they are installed in a suitable enclosure. The bus cable for PROFIBUS PA may lead from the hazardous area zone 2, into the following zones: in the case of 6ES7157-0AD81-0XA0 into zone 0 in the case of 6ES7157-0AD82-0XA0 into zone 0 /zone 20 DANGER In the case of DP/PA coupler Ex [i] 6ES7157-0AD82-0XA0 the intrinsically safe PROFIBUS PA is approved for the following intrinsically safe electrical equipment: - Device category 1G, 2G and 3G for zones 0, 1, and 2 - Device category 1D, 2D and 3D for zones 20, 21, and 22 As a PROFIBUS node you can use the DP/PA coupler Ex [i] of device category 3G in zone 2-type hazardous areas (or in the safe area). If you want to use the DP/PA coupler Ex [i] in zone 21 or 22, then you must install it in an enclosure that is certified and approved for these zones. Enclosure for zone 2 The DP/PA coupler Ex [i], or the DP/PA link with DP/PA coupler Ex [i] must be installed in an enclosure with minimum degree of protection IP 54. A manufacturer's declaration for zone 2 must be submitted for the enclosure (in accordance with EN 60079-15). Use the following threaded cable glands: Power supply and PROFIBUS DP Ex i: Cable gland with manufacturer's declaration for zone 2 PROFIBUS PA Ex i: Degree of protection Ex i DANGER Under some circumstances, sparks capable of ignition or unacceptable surface temperatures can occur during installation. Never install under explosive conditions! Switch off the voltage supply to the plant and adhere to the safety regulations. You can obtain enclosures for zone 2 from: Siemens AG, I IA CE S EN Siemensallee 84 D-76187 Karlsruhe E-mail: helmut.heib@siemens.com (mailto:) DP/PA coupler, active field distributors, DP/PA Link and Y Link 74 Operating Instructions, 07/2011, A5E00193841-17 Mounting 5.2 Mounting the DP/PA coupler 5.2 Mounting the DP/PA coupler 5.2.1 Mounting DP/PA coupler for non-redundant mode Components required Rail for the S7 mounting system DP/PA coupler Mounting the DP/PA coupler Note If you operate multiple DP/PA couplers in one rack in stand-alone mode without ring redundancy and coupler redundancy, then you cannot connect the DP/PA coupler via bus connector nor can you connect it via bus modules. 1. Hook the DP/PA coupler into the S7 mounting rails and swing it down. 2. Screw the DP/PA coupler tight. Dismantling the DP/PA coupler Remove the DP/PA coupler in the reverse sequence. If the DP/PA coupler is already in operation, switch off the 24 V DC power supply for the DP/PA coupler prior to removal. DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 75 Mounting 5.2 Mounting the DP/PA coupler 5.2.2 Mounting the DP/PA coupler for redundancy mode Configuration with bus modules For operation with ring redundancy or coupler redundancy the two FDC 157-0 DP/PA couplers must be installed with the BM FDC 157-0 bus module. Combination with non-redundant DP/PA couplers A combination of non-redundant and redundant DP/PA couplers is possible. You can install a maximum of 5 DP/PA couplers FDC 157-0, of which one coupler pair is installed in redundancy mode at the end of the configuration. Components required Rail for configuration with active bus modules ("Rail for module change during operation") For ring redundancy or coupler redundancy: - Bus module BM FDC/FDC (redundant) - Maximum 2 DP/PA couplers FDC 157-0 Optional for non-redundant DP/PA couplers: - Bus module BM FDC - Maximum 3 DP/PA couplers FDC 157-0 Installing bus modules and modules 1. Hang the BM FDC bus modules first, then the BM FDC/FDC (redundant) bus module on the mounting rail and press them into the rail. 2. Slide the bus modules together, so that the module connections have contact. 3. Insert the DP/PA couplers in the bus modules. To do so use the lateral guides of the bus module. 4. Screw the modules tight. This also fixes the bus modules to the rail. Removing bus modules and modules Remove the DP/PA coupler in the reverse sequence. If the device is already in operation then disconnect its 24-V DC power supply beforehand. DP/PA coupler, active field distributors, DP/PA Link and Y Link 76 Operating Instructions, 07/2011, A5E00193841-17 Mounting 5.2 Mounting the DP/PA coupler 5.2.3 Swapping DP/PA couplers FDC 157-0 Introduction Swapping a DP/PA coupler 157-0 is possible during operation with ring redundancy or coupler redundancy. The PA field devices that are connected to the redundant DP/PA coupler remain in operation. Requirement The following prerequisites must be satisfied to remove a DP/PA coupler FDC 157-0 during operation. The ACT LED of the DP/PA coupler cannot be illuminated. If the ACT LED is illuminated, then multiple PA field devices can fail. The power supply of the DP/PA coupler FDC 157-0 must be disconnected. Removing and inserting modules NOTICE Removing a DP/PA coupler FDC 157-0 It is only possible to remove a DP/PA coupler FDC 157-0 if it is de-energized. Prior to removing an FDC 157-0 DP/PA coupler, disconnect its 24 V DC power supply. NOTICE Failure of a DP/PA coupler FDC 157-0 If you remove an FDC 157-0 DP/PA coupler under voltage then the overvoltage protection can permanently respond. You can reset this switch-off if you turn off the mains for at least 10 seconds. Prior to removing an FDC 157-0 DP/PA coupler, disconnect its 24 V DC power supply. DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 77 Mounting 5.3 Installing the active field distributor AFD and active field splitter AFS 5.3 Installing the active field distributor AFD and active field splitter AFS 5.3.1 Screwing down the active field distributor AFD and active field splitter AFS on substrate Mounting position The active field distributor AFD and active field splitter AFS can be screwed onto a level surface in any position. Requirement The substrate must be level, with load-bearing capacity, and it must be vibration free. Select appropriate fixing accessories for the substrate. Ensure that there is at least 60 mm of free space both to the side and below the modules for connecting the PA main lines and spur lines. Tools required Phillips screwdriver size 4 2 fixing screws M4; dowels depending on the substrate Screwdriver suitable for the screws used Procedure 1. Remove the 4 screws of the enclosure cover using a Phillips screwdriver. 2. Screw the lower part of the enclosure tightly to the substrate with 2 fixing screws. The torque depends on the fixing screws used. You can find the drill hole spacing on the back of the enclosure base. 3. Screw the enclosure cover onto the upper part of the enclosure with the 4 Phillips-recess screws. Torque 2.0 Nm. DP/PA coupler, active field distributors, DP/PA Link and Y Link 78 Operating Instructions, 07/2011, A5E00193841-17 Mounting 5.4 Mounting the DP/PA link 5.4 Mounting the DP/PA link 5.4.1 Mounting the DP/PA link for non-redundant mode Components required Rail for the S7 mounting system IM 153-2 1 to 5 DP/PA couplers one bus connector for each DP/PA coupler (included with it) options for module exchange during operation - Bus module BM PS/IM or BM IM/IM - Bus module BM; DP/PA coupler Typical configuration of the DP/PA link The following figure shows the typical configuration of the DP/PA link with two DP/PA couplers and with front doors open. 36 ,0 %XVFRQQHFWRU QRWYLVLEOH 0RXQWLQJUDLO Figure 5-1 '33$FRXSOHU '33$FRXSOHU %XVFRQQHFWRU QRWYLVLEOH Typical configuration of the DP/PA link for non-redundant mode DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 79 Mounting 5.4 Mounting the DP/PA link Installing the DP/PA link 1. Insert the bus connector that is included with the DP/PA coupler onto the IM 153-2. 2. Hook the IM 153-2 onto the S7 rail and swing it downward. 3. Screw the IM 153-2 tight. 4. If appropriate, insert the bus connector of the next DP/PA coupler onto the right-hand side on the DP/PA coupler. 5. Hook the DP/PA coupler onto the the right-hand side next to the IM 153-2 on the S7 rail and swing it downward. 6. Screw the DP/PA coupler tight. 7. Repeat steps 4 to 6 for the subsequent DP/PA couplers. For the last DP/PA coupler (of a maximum of 5), do not insert a bus connector prior to installation. Inserting / removing DP/PA couplers If you wish to remove or insert DP/PA couplers during operation, you must use busmodules for configuration instead of the bus connectors. Removing the DP/PA link To remove the DP/PA link, proceed in the reverse order. Start with the DP/PA coupler installed on the far right. If the DP/PA link is already in operation, switch off the 24 VDC power supplies prior to dismantling it. See also Accessories for PROFIBUS DP (Page 246) Accessories for PROFIBUS PA (Page 247) DP/PA coupler, active field distributors, DP/PA Link and Y Link 80 Operating Instructions, 07/2011, A5E00193841-17 Mounting 5.4 Mounting the DP/PA link 5.4.2 Mounting the DP/PA link for redundant operation Configuration with bus modules For the redundancy mode, the DP/PA link must configured with bus modules. Components required Rail for configuration with active bus modules ("Rail for module change during operation") 2 x IM 153-2 Bus module BM IM/IM 1 to 5 DP/PA couplers One BM DP/PA coupler bus module per DP/PA coupler Typical configuration The following figure shows the typical configuration of the DP/PA link for the redundancy mode with two power supply modules and with front doors open. 36 36 0RXQWLQJUDLO Figure 5-2 ,0 %0,0,0 QRWYLVLEOH ,0 '33$FRXSOHU %0'33$FRXSOHU QRWYLVLEOH Typical configuration of the DP/PA link for the redundancy mode DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 81 Mounting 5.4 Mounting the DP/PA link Installing bus modules and modules 1. Hook the lower edge of the BM IM/IM bus module onto the rail, press it into the rail (a) and push it to the left until it engages (b). If you are using the 530 mm rail and position the BM IM/IM in the right-hand engaged position, you can install two additional PS 307; 2A or one PS 307; 5A to the left of the bus module. D E (QJDJHG SRVLWLRQ 2. Hook the BM DP/PA coupler bus modules onto the rail and press them down into the rail. 3. Push the bus modules together so that the module connections are in contact. 4. Insert the two IM 153-2 into the BM IM/IM bus module. 5. Inser the DP/PA coupler into the BM DP/PA coupler bus module. To do so use the lateral guides of the bus module. 6. Screw the modules tight. This also fixes the bus modules to the rail. Removing and inserting modules It is possible to remove and insert modules on S7-400H during operation. The following special characteristics should be noted: An IM 153-2 may only be removed and inserted if it is de-energized. Switch off the 24 VDC supply to the IM 153-2 for this purpose. To prevent the underlying master system from failing the DP/PA link should be configured with independently switchable voltage supplies to the two IM 153-2 (for example by using two power supply modules). There is no restriction on removing and inserting the DP/PA coupler, but it causes the nodes connected to it to fail. Removing bus modules and modules To remove the DP/PA link, proceed in the reverse order. If the device is already in operation, switch off the 24 VDC power supplies prior to removing it. See also Accessories for PROFIBUS DP (Page 246) Accessories for PROFIBUS PA (Page 247) DP/PA coupler, active field distributors, DP/PA Link and Y Link 82 Operating Instructions, 07/2011, A5E00193841-17 Mounting 5.5 Mounting the Y link 5.5 Mounting the Y link Configuration with bus modules The Y link must always be configured with bus modules. Components required Rail for configuration with active bus modules ("Rail for module change during operation") 2 x IM 153-2 Bus module BM IM/IM Y coupler Bus module BM Y coupler Typical configuration The following figure shows the typical configuration of Y link with two power supply modules and with front doors open. 36 36 0RXQWLQJUDLO Figure 5-3 ,0 ,0 %0,0,0 QRWYLVLEOH L@ 6KLHOG 6WUDLQUHOLHI DQG 6KLHOGFRQQHFWLRQ 'DWDOLQH3 'DWDOLQH3 '33$FRXSOHU)'& %XVFDEOH 6KLHOG /RRSLQJWKURXJKRI352),%863$ 3$EXVWHUPLQDWRUVZLWFK 6WUDLQUHOLHI DQG 6KLHOGFRQQHFWLRQ 21 2)) 'DWDOLQH3 'DWDOLQH3 'DWDOLQH3 'DWDOLQH3 Figure 6-11 PROFIBUS PA connection DP/PA coupler, active field distributors, DP/PA Link and Y Link 108 Operating Instructions, 07/2011, A5E00193841-17 Connecting 6.7 Connecting PROFIBUS PA on the DP/PA coupler PA bus terminator switch You can loop through the PROFIBUS PA on DP/PA couplers with a PA bus terminator switch. The PA bus terminator switch is available on the following DP/PA couplers: DP/PA coupler FDC 157-0 (6ES7157-0AC83-0XA0) DP/PA coupler (6ES7157-0AC82-0XA0) Note The PA bus terminator switch is used to operate the- DP/PA coupler with ring redundancy without function. NOTICE DP/PA Ex [i] coupler (6ES7157-0AD82-0XA0) In the DP/PA coupler Ex [i] the bus terminator cannot be switched off. Consequently the DP/PA coupler Ex [i] must be located at the beginning or the end of a PA segment. DP/PA coupler PA bus terminator switch ON The bus terminating resistors are activated. PROFIBUS PA may not be looped through. OFF The bus terminating resistors are deactivated. You can loop PROFIBUS PA through and connect bus terminating resistors at both ends of the PA segment . 21 2)) DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 109 Connecting 6.7 Connecting PROFIBUS PA on the DP/PA coupler Procedure Connect the PROFIBUS PA as follows: 1. Strip the insulation from the bus cable as depicted and pull the braided shield over the insulation. 2. Clamp the shield of the bus cable under the cable grip and screw down the cable grip. 3. Fix the wires of the bus lead into the screw-type terminals P+ and P-. Ensure that the wires have the correct polarity. DP/PA coupler, active field distributors, DP/PA Link and Y Link 110 Operating Instructions, 07/2011, A5E00193841-17 Commissioning: DP/PA coupler 7.1 7 Commissioning the DP/PA coupler for stand-alone mode Requirement When you have fully installed and wired the DP/PA coupler and switched on the power supply, the DP/PA coupler is ready to operate. Setting transmission speed The transmission speed must be set at 45.45 kBaud for the DP master. 7.2 Commissioning the DP/PA coupler FDC 157-0 Requirements Before you commission the DP/PA coupler FDC 157-0 the following prerequisites must be satisfied: You must have completely installed and wired the DP/PA couplers. You have fully installed PROFIBUS DP. PROFIBUS DP is ready to operate. You have fully installed PROFIBUS PA. PROFIBUS PA is ready to operate. Configuring the DP/PA coupler FDC 157-0: DP/PA coupler FDC 157-0 configuration as DP slave is required in the following cases: If the diagnostic functions will be effective. If you want to operate the DP/PA couplers with ring redundancy or coupler redundancy. Note If you use the DP/PA coupler FDC 157-0 in redundancy mode (ring redundancy or coupler redundancy), then check whether RETRY = 3 in the properties of the PA master system in the network settings / profile, or set a user-defined profile with a retry limit of 3. DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 111 Commissioning: DP/PA coupler 7.2 Commissioning the DP/PA coupler FDC 157-0 Commissioning the DP/PA coupler FDC 157-0 Basic procedure: 1. Optional: Configuring the DP/PA coupler. 2. Set the PROFIBUS addresses in the DP/PA couplers. 3. Select the redundancy mode on the DP/PA couplers. 4. Switch on the power supply for the DP/PA couplers. 5. Download the configuration to the PLC. DP/PA coupler, active field distributors, DP/PA Link and Y Link 112 Operating Instructions, 07/2011, A5E00193841-17 Commissioning: DP/PA coupler 7.2 Commissioning the DP/PA coupler FDC 157-0 Applications DP/PA coupler FDC 157-0 The following table shows the applications and the available functions for the DP/PA coupler and the settings that are required For ring redundancy and coupler redundancy the settings are required on the DP/PA coupler pair. Table 7- 1 21 21 2)) 21 2)) 21 5,1* 5,1* Applications DP/PA coupler FDC 157-0 and required settings Applications - DP/PA coupler FDC 157-0 (standalone or in the DP/PA link) Functions Non-redundant operation Diagnostic function deactivated 2 of DP/PA coupler 1 Diagnostic function Redundant operation of activated a DP/PA coupler pair Redundant operation of a DP/PA coupler pair Settings on the DP/PA coupler / on the DP/PA coupler pair Settings in the configuration PROFIBUS address = 0 PROFIBUS address = 0 PROFIBUS address> 0 (1 to 125) PROFIBUS address> 0 (1 to 125) Ring redundancy activated 21 21 2)) 21 2)) 21 5,1* 5,1* Redundancy mode Ring redundancy RING ON Coupler redundancy activated 21 21 2)) 21 2)) 21 5,1* 5,1* Redundancy mode Coupler redundancy RING OFF 1 Also as replacement for the DP/PA coupler with order number 6E7157-0AC82-0XA0 2 DP/PA couplers transparent in the DP/PA link. DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 113 Commissioning: DP/PA coupler 7.3 Configuration with a GSD file 7.3 Configuration with a GSD file Introduction With the GSD file you can configure the DP/PA coupler FDC 157-0 with COM PROFIBUS or using a different software program. For this you must install the GSD file via an appropriate import function of the configuration software. The GSD file is available for download on the Internet (http://support.automation.siemens.com/). Configure the DP/PA coupler with COM PROFIBUS or other configuration software 1. Copy the GSD file of the DP/PA coupler into the COM PROFIBUS directory ...COMPB5 \ GSD (preset). Copy the bitmap file into the directory ...COMPB5 \ BITMAPS. 2. Start COM PROFIBUS, then select the menu item File > Read GSD file. Result: The DP/PA coupler will be displayed in the hardware catalog for the slave configuration. 3. Configure the DP/PA coupler with COM PROFIBUS or other configuration software 4. Assign the parameters for the DP/PA coupler with COM PROFIBUS or other configuration software. 5. Save the configuration or download the configuration to the DP master. Note For installation instructions when using other configuration software, refer to the corresponding documentation. DP/PA coupler, active field distributors, DP/PA Link and Y Link 114 Operating Instructions, 07/2011, A5E00193841-17 Commissioning: DP/PA coupler 7.4 Configuring with STEP 7 7.4 Configuring with STEP 7 Introduction The HSP for the configuration of a DP/PA coupler is integrated as of STEP 7 V5.4 and in PCS 7 7.0. Configuration with STEP 7 as of V5.3 SP3 is possible via HW update (HSP0095). Installing the HW update in STEP 7 V3.3 SP3 1. Start STEP 7 and select the menu item Extras > Install new GSD file in the HW Config. 2. In the next dialog box, select the HW update file to install, and confirm with "OK." Result: The DP/PA coupler FDC 157-0 will be displayed in the hardware catalog in the directory "PROFIBUS DP / DP/PA-Link" and can be configured with STEP 7 Configuring DP/PA couplers with STEP 7 (from STEP 7 V5.4) 1. Start STEP 7 and open your SIMATIC station in the HW Config. 2. Drag a DP/PA coupler FDC 157-0 out of the hardware catalog from the directory "PROFIBUS DP / DP/PA link" to a DP master system (for S7 standard mode). Result: The properties dialog for the PROFIBUS interface of the DP/PA coupler will be displayed. 3. Change the suggested address of the DP/PA coupler if necessary. 4. Assign parameters to the DP/PA coupler and confirm with OK. 5. If the DP/PA coupler is used redundantly then configure the partner DP/PA coupler. To do this repeat steps 2 to 4. 6. Save the configuration or download the configuration to the DP master. Note PROFIBUS address Set the PROFIBUS addresses in the DP/PA couplers via the DIL switches. DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 115 Commissioning: DP/PA coupler 7.4 Configuring with STEP 7 Figure 7-1 Integrating DP/PA couplers in HW Config Configuring PA field devices If you use multiple DP/PA couplers FDC 157-0 in one link then a topological assignment is not possible in HW Config. However you can review the assignment online via the local LifeList. Additional information Additional information on configuring the PA field devices is available in the manual PDM V 6.0 The Process Device Manager (http://support.automation.siemens.com/WW/view/en/21407212) See also Configuring the PROFIBUS PA master system (Page 124) DP/PA coupler, active field distributors, DP/PA Link and Y Link 116 Operating Instructions, 07/2011, A5E00193841-17 Commissioning: DP/PA coupler 7.5 DP/PA coupler FDC 157-0 in the redundant DP/PA link 7.5 DP/PA coupler FDC 157-0 in the redundant DP/PA link Introduction In addition to the ring redundancy and coupler redundancy functions on the PA side, the DP/PA-coupler FDC 157-0 also supports redundancy on the PROFIBUS DP side. For this it is necessary to configure a redundant DP master system of an S7-400H with a redundant DP/PA link IM 153-2. Settings in HW Config Note Only the following configuration ensures that the DP/PA coupler FDC 157-0 can change to the other side of the DP/PA link without bumps if there is a switchover on the overlaid PROFIBUS DP chain. If the DP/PA coupler FDC 157-0 will work as DP slave with diagnostic function then the following settings are required in the HW Config: In the object properties of the DP interface of the H-CPU, select the mode DP master and the DP mode DPV1. In the object properties of the DP/PA coupler, in the station parameters, select the DP alarm mode DPV1. Figure 7-2 HW Config: Configuration of an S7-400H with DP/PA link and DP/PA couplers FDC 157-0 See also Configuring DP/PA link (Page 122) DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 117 Commissioning: DP/PA coupler 7.6 Parameters for diagnostic selection of the DP/PA coupler FDC 157-0 7.6 Parameters for diagnostic selection of the DP/PA coupler FDC 157-0 Device-specific parameters Parameters Value range Module status disable enable disable enable disable enable disable enable disable enable Status LifeList Channel-related diagnostics Coupler diagnostics Signal level monitoring Default setting Efficiency range enable Module disable Module enable Module enable Module disable Module See also Structure of the current value and voltage value (Page 167) DP/PA coupler, active field distributors, DP/PA Link and Y Link 118 Operating Instructions, 07/2011, A5E00193841-17 Commissioning: DP/PA coupler 7.7 Setting the PROFIBUS address and redundancy mode 7.7 Setting the PROFIBUS address and redundancy mode Introduction Activate diagnostic functions of the DP/PA coupler FDC 157-0 by means of the PROFIBUS address. The DP/PA coupler is transparent in the DP/PA link with PROFIBUS address 0. Activate the redundancy mode, ring redundancy or coupler redundancy on the DP/PA coupler pair and in the configuration. Rules Valid PROFIBUS addresses are 1 to 125. Each PROFIBUS address may only be assigned once in the DP master system. The PROFIBUS addresses of both DP/PA couplers must be different. The PROFIBUS addresses set on the DP/PA coupler and in the configuration software must match. The redundancy mode set on the DP/PA coupler pair and in the configuration software must match. DP/PA coupler in the DP/PA link: The configured and set PROFIBUS addresses of the IM 153-2 must match. Tools required Screwdriver with 3 mm blade DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 119 Commissioning: DP/PA coupler 7.7 Setting the PROFIBUS address and redundancy mode Setting the PROFIBUS address and redundancy mode 1. Open the front door of the DP/PA coupler. 2. Set the PROFIBUS address at the DIL switches. 3. Set the redundancy mode at the DIL switches. 4. For center feed: If you loop the equipotential bonding line on the active field splitter (AFS) over the X2 cable bushing, then set the PA bus terminator switch to OFF on both DP/PA couplers. 5. Close the front door of the DP/PA coupler. 21 2)) %86 $''5(66 21 5,1* PA bus terminal switch ON: Bus terminating resistor switched on (default setting). OFF: Bus terminating resistor switched off. Set the PROFIBUS address. Redundancy mode ON: Ring redundancy. OFF: Coupler redundancy (default setting). Changing the PROFIBUS address You can change the PROFIBUS address that has been set at any time. However, the DP/PA coupler does not apply the new setting until the 24 VDC supply has been switched off / on. DP/PA coupler, active field distributors, DP/PA Link and Y Link 120 Operating Instructions, 07/2011, A5E00193841-17 Commissioning: DP/PA link 8 Overview of Contents In this chapter you will learn which steps you must perform to commission the DP/PA link. These steps are explained in detail in the individual sub-sections. 8.1 Commissioning DP/PA link Requirements The following requirements must be met before you commission the DP/PA link: You have fully installed and wired the DP/PA link. You have fully installed PROFIBUS DP. PROFIBUS DP is ready to operate. You have fully installed PROFIBUS PA. PROFIBUS PA is ready to operate. Commissioning DP/PA link 1. Configure the DP/PA link. 2. Set the PROFIBUS address of the IM 153-2. 3. Switch on the voltage supply for the DP/PA link. 4. Download the configuration to the PLC. Configuring the DP/PA link The DP/PA link is configured for the S7 standard and redundant mode with STEP 7. For DP standard master mode, the DP/PA link is configured via DDBF file, for example using COM PROFIBUS. The DP/PA couplers are transitions between the S7 backplane bus of the IM 153-2 and PROFIBUS PA with the PA field devices. Hence it is not necessary to configure the DP/PA coupler. See also Setting the PROFIBUS address of the IM 153-2 (Page 85) DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 121 Commissioning: DP/PA link 8.2 Configuring for S7 standard or redundant mode 8.2 Configuring for S7 standard or redundant mode Overview of Contents The DP/PA link is configured for the S7 standard and redundant modes with STEP 7. 8.2.1 Configuring DP/PA link Configuring DP/PA link 1. Start STEP 7 and in HW Config open your SIMATIC or SIMATIC H station (for redundant mode). 2. Drag an IM 153-2 (6ES7153-2BAx2-0XB0) from the PROFIBUS DP\DP/PA link folder in the hardware catalog to a DP master system (for S7 standard mode) or to the redundant DP master system of an S7-400H (for the redundant mode). Result: The Properties dialog for the PROFIBUS interface of the IM 153-2 is displayed. 3. If necessary, change the proposed address of the IM 153-2 in the higher level DP master system. Result: After closing this dialog a dialog is displayed in which you can select the lowerlevel master system. 4. Select PROFIBUS PA and confirm with OK. Figure 8-1 Dialog for selecting the lower-level master system (PROFIBUS PA) Result: The DP/PA link is inserted into the higher level DP master system together with the lower-level PA master system. DPV0 or DPV1 slave It is only possible to operate the IM 153-2 as a DPV1 slave in conjunction with a DPV1 master. Only then can the additional functions (acyclical services) of a DPV1 slave be used. In STEP 7, HW Config, the mode for the DP master being used can be selected in the Object Properties, if required: "S7-compatible" or "DPV1") DP/PA coupler, active field distributors, DP/PA Link and Y Link 122 Operating Instructions, 07/2011, A5E00193841-17 Commissioning: DP/PA link 8.2 Configuring for S7 standard or redundant mode Switchover time in the redundant mode WARNING Injury to persons may result. With STEP 7 V5.2 modified bus parameters can lead to longer switchover times in the H system when the IM 153-2 is used as a redundant DP slave. Example for the configuration of a DP/PA link for the redundant mode Figure 8-2 HW Config DP/PA link in the hardware catalog Figure 8-3 HW Config Minimum configuration of an S7-400H with DP/PA link See also DP/PA coupler FDC 157-0 in the redundant DP/PA link (Page 117) DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 123 Commissioning: DP/PA link 8.2 Configuring for S7 standard or redundant mode 8.2.2 Configuring the PROFIBUS PA master system Introduction The PA field devices can be integrated in SIMATIC PDM or in STEP 7 as standard slaves via their DDBF files. Configuring with STEP 7 1. If you have not done so so far, start STEP 7 and in HW Config open your SIMATIC or SIMATIC H station (for redundant mode). 2. If the desired PA field devices are not displayed in the PROFIBUS PA file in the hardware catalog: Import the GSD files of the PA field devices using the Options > Install new GSD menu command. 3. Drag the desired PA field devices from the hardware catalog to the PA master system that is displayed behind the IM 153-2. Result During configuration of the PA field devices HW Config checks that the quantity structure is adhered to and displays a relevant error message if it is exceeded. PROFIBUS address of the IM 153-2 in the PA master system In S7 standard mode the IM 153-2 uses the address 2. In redundant mode the two IM 153-2 use the addresses 1 and 2. In addition, the address 125 is blocked for PA field devices. The first possible address for a PA field devices is 3 in both cases. Editing the PA field devices in the user program The process data of the PA field devices should only be accessed via the process images in the user program. DP/PA coupler, active field distributors, DP/PA Link and Y Link 124 Operating Instructions, 07/2011, A5E00193841-17 Commissioning: DP/PA link 8.3 Configuring for DP standard master mode 8.3 Configuring for DP standard master mode 8.3.1 GSD files For DP standard master mode, the DP/PA link and the PA field devices are configured via GSD files, for example with COM PROFIBUS. GSD files Module IDs must be entered into the respective GSD file for each PA field device you wish to use in the DP/PA link. The software tool "GSD-Tool for IM 157 / IM 153-2" is available for this. It is available for download free of charge from the Internet (http://support.automation.siemens.com/WW/view/en/26562190). The GSD files for the PA field devices supplied by Siemens AG are also to be found at this Internet address. Enter the search term "GSD" and select the "Downloads" search area. Creating a GSD file Download the GSD Tool from the aforementioned Internet address and follow the accompanying instructions. Note Disclaimer Siemens AG assumes no liability for damage arising from using the GSD Tool; in particular not for personal, material or financial damage that constitutes consequential damage directly or indirectly connected to the use of the GSD Tool. We offer no support for the application of the GSD Tool. The GSD Tool creates the following GSD file from the added GSD files of the PA field devices to be used for the DP/PA link: sip58052.gsd for IM 153-2. See also GSD files for PA field devices (http://support.automation.siemens.com/WW/view/en/1581624) DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 125 Commissioning: DP/PA link 8.3 Configuring for DP standard master mode 8.3.2 Configuring DP/PA link Procedure Configure the DP/PA link using your configuration tool (for example COM PROFIBUS) like any other DP slave on PROFIBUS DP. For this purpose download the complete GSD file for the DP/PA link to your configuration tool. NOTICE When configuring with GSD file If a DP/PA link with IM 153-2BA02 is configured using the GSD file, it will not start because the "MLFB" user parameter is set to "6ES7 153-2BA01(2)-0XB0" or "6ES7 153-2BA81(2)-0XB0" by default. If you use an IM 153-2BA02 or an IM 153-2BA82, then set the user parameter to 6ES7153-2BA02-0XB0 or 6ES7153-2BA82-0XB0. Parameter assignment and configuration frame The frame length for parameter assignment depends on the number of PA field devices in use and may amount to a maximum of 223 bytes. The frame length for parameter assignment depends on the number of PA field devices in use and may amount to a maximum of 244 bytes. The structure of the parameter assignment and configuration frame is available for download from the Internet (http://support.automation.siemens.com/WW/view/en/13406349). Restrictions Functions that are based on reading the configuration prior to initially assigning the parameters for the DP/PA link, are not supported. For this reason for example the CP 5431 cannot be used as DP master. It is equally not possible to control variables with COM PROFIBUS until the DP/PA link parameters have been assigned. DP/PA coupler, active field distributors, DP/PA Link and Y Link 126 Operating Instructions, 07/2011, A5E00193841-17 Commissioning: DP/PA link 8.3 Configuring for DP standard master mode 8.3.3 How to configure PROFIBUS PA field devices Requirement The product designations for the required PA field devices must have been entered in the GSD file of the IM 153-2. NOTICE For redundant operation only those PA field devices may be configured that have the entries "Begin of Device" or "Begin of Device h supported" in their GSD file. Configuration principle To configure the DP/PA link select the manufacturer's specifications for the PA field devices in your configuration tool (Product and, where applicable module designation). The specifications for the PA field devices must be entered in ascending order corresponding to their addresses. An example of a configuration is shown in the figure below. Procedure 1. In your configuration tool move to the DP slave configuration. 2. Enter the manufacturer designation (for example SIEMENS SITRANS P) for the first PA field device in the "Order number" or "Module" field and apply this in the first slot. Set the PROFIBUS address for the PA field device. Repeat this procedure for all PA field devices in use. 3. Terminate the entries and complete the configuration. The further procedure (for example saving, compiling, ...) is identical to other DP slaves. PROFIBUS address of the IM 153-2 in the PA master system In the PA master system the IM 153-2 uses the address 2. The first possible address for PA field devices is 3. Deployable transducers Transducers may be used that accept a 10-byte parameter assignment frame. Configuring with COM PROFIBUS For SIMATIC S5 PA field devices are integrated via their GSD files as standard slaves in COM PROFIBUS (V3.1 and later). 1. Copy the GSD file of the IM 153-2 into theCOM PROFIBUS directory: ...COMPBxx\GSD. 2. Start COM PROFIBUS and select the File > Read in GSD file menu command. Result: The IM 153-2 is displayed in the hardware catalog during slave configuration. 3. Configure the PA field devices with COM PROFIBUS DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 127 Commissioning: DP/PA link 8.3 Configuring for DP standard master mode Example: View of configuration in COM PROFIBUS The figure below shows an example of the view of a configuration for the DP/PA link using COM PROFIBUS. Figure 8-4 Example of a configuration with COM PROFIBUS How to enter a PROFIBUS address 1. In the "Module" column select the "Begin of Device" of the relevant PA field device and select the "Parameter..." button. 2. In the "Value" column enter the desired PROFIBUS address and confirm with "OK". Figure 8-5 Entering the PROFIBUS address DP/PA coupler, active field distributors, DP/PA Link and Y Link 128 Operating Instructions, 07/2011, A5E00193841-17 Commissioning: Y link 9 Overview of Contents In this chapter you will learn which steps you must perform to commission the Y link. These steps are explained in detail in the individual sub-sections. 9.1 Commissioning Y link Requirements The following requirements must be met before you commission the Y link: You have fully installed and wired the Y link. You have fully installed the H system and the redundant DP master system. PROFIBUS DP is ready to operate. You have fully installed the underlying DP master system and connected it to the Y coupler. PROFIBUS DP is ready to operate. Commissioning Y link 1. Configure the Y link. 2. Configure the underlying DP slaves 3. Switch on the voltage supply for the Y link. 4. Set the PROFIBUS address of the IM 153-2. 5. Download the configuration to the PLC. Configuring the Y link The Y link is configure using STEP 7 for the redundancy mode. For DP standard master mode, the Y link is configured via GSD file, for example with COM PROFIBUS. The Y coupler is a transition between the S7 backplane bus of the IM 153-2 and the underlying PROFIBUS DP with the DP slaves. Hence it is not necessary to configure the Y coupler. See also Setting the PROFIBUS address of the IM 153-2 (Page 85) DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 129 Commissioning: Y link 9.2 Configuring for the redundancy mode 9.2 Configuring for the redundancy mode Overview of Contents The Y link is configure using STEP 7 for the redundancy mode. 9.2.1 How to configure Y link Configuring Y link The Y link is configure in STEP 7. 1. Start STEP 7 and in HW Config open your SIMATIC H station. 2. Drag an IM 153-2 (6ES7153-2BAx2-0XB0) from the PROFIBUS-DP\DP/PA link directory from the hardware catalog to the redundant DP master system of an S7-400H. Result: The Properties dialog for the PROFIBUS interface of the IM 153-2 is displayed. 3. If necessary, change the proposed address of the IM 153-2 in the higher level DP master system. Result: After closing this dialog a dialog is displayed in which you can select the lowerlevel master system. 4. Select PROFIBUS DP and confirm with OK. Figure 9-1 Dialog for selecting the lower-level master system (PROFIBUS DP) Result: The Y link is inserted into the redundant DP system. The default transmission speed of the lower-level DP master system is 1.5 Mbaud. 5. If you want to change the transmission speed of the lower-level DP master system, double-click on it. Result: The dialog with the properties for the lower-level master system is displayed. - Select the "Properties..." button. Result: The "Properties PROFIBUS" dialog is displayed. - In the "Network settings" tab select a transmission rate ranging from 45.45 kBaud to 12 MBaud and confirm with OK. DP/PA coupler, active field distributors, DP/PA Link and Y Link 130 Operating Instructions, 07/2011, A5E00193841-17 Commissioning: Y link 9.2 Configuring for the redundancy mode DPV0 or DPV1 slave It is only possible to operate the IM 153-2 as a DPV1 slave in conjunction with a DPV1 master. Only then can the additional functions (acyclical services) of a DPV1 slave be used. Switchover time in the redundant mode WARNING Injury to persons may result. With STEP 7 V5.2 modified bus parameters can lead to longer switchover times in the H system when the IM 153-2 is used as a redundant DP slave. DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 131 Commissioning: Y link 9.2 Configuring for the redundancy mode Example of how to configure a Y link Figure 9-2 HW Config Y link in the hardware catalog Figure 9-3 HW Config Minimum configuration of an S7-400H with Y link DP/PA coupler, active field distributors, DP/PA Link and Y Link 132 Operating Instructions, 07/2011, A5E00193841-17 Commissioning: Y link 9.2 Configuring for the redundancy mode 9.2.2 Configuring underlying DP slaves Configuring underlying DP slaves The underlying DP slaves are configured in STEP 7. 1. If you have not done so, start STEP 7 and in HW Config open your SIMATIC H station. 2. If the required DP slaves cannot be configured directly, import the relevant GSD files using the Options > Install new GSD menu command. Result: The DP slaves are displayed in the PROFIBUS-DP\Additional Field Devices directory in the hardware catalog. 3. Drag the required DP slaves from the subdirectories of PROFIBUS-DP out of the hardware catalog to the underlying DP master system. 4. Configure the DP slaves using STEP 7. Result During configuration of the underlying DP slaves HW Config checks that the quantity structure is adhered to and displays a relevant error message if it is exceeded. PROFIBUS address of the IM 153-2 in the underlying DP master system In the underlying DP master system the two IM 153-2 use the addresses 1 and 2. In addition, the address 125 is blocked for DP slaves. The first possible address for an underlying DP slave is 3. Editing the DP slaves in the user program The process data of the DP slaves should only be accessed via the process images in the user program. DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 133 Commissioning: Y link 9.3 Configuring for DP standard master mode 9.3 Configuring for DP standard master mode 9.3.1 GSD files For DP standard master mode, the Y link and the DP slaves are configured via GSD files, for example with COM PROFIBUS. GSD files Module IDs must be entered into the respective GSD file for each DP slave you wish to use in the Y link. The software tool "GSD-Tool for IM 157 / IM 153-2" is available for this. It is available for download free of charge from the Internet (http://support.automation.siemens.com/WW/view/en/26562190). The GSD files for the DP slaves supplied by Siemens AG are also to be found at this Internet address. Enter the search term "GSD" and select the "Downloads" search area. Creating a GSD file Download the GSD Tool from the aforementioned Internet address and follow the accompanying instructions. Note Disclaimer Siemens AG assumes no liability for damage arising from using the GSD Tool; in particular not for personal, material or financial damage that constitutes consequential damage directly or indirectly connected to the use of the GSD Tool. We offer no support for the application of the GSD Tool. The GSD Tool creates the following GSD file from the added GSD files of the DP slaves to be used for the Y link: si058052.gsd for IM 153-2. DP/PA coupler, active field distributors, DP/PA Link and Y Link 134 Operating Instructions, 07/2011, A5E00193841-17 Commissioning: Y link 9.3 Configuring for DP standard master mode 9.3.2 How to configure Y link Procedure Configure the Y link using your configuration tool (for example COM PROFIBUS) just like any other DP slave on PROFIBUS DP. For this purpose download the complete GSD file for the Y link to your configuration tool. NOTICE When configuring with GSD file If a Y link with IM 153-2BA02 is configured using the GSD file, it will not start because the "MLFB" user parameter is set to "6ES7153-2BA01(2)-0XB0" or "6ES7153-2BA81(2)-0XB0" by default. If you use an IM 153-2BA02 or an IM 153-2BA82, then set the user parameter to 6ES7153-2BA02-0XB0 or 6ES7153-2BA82-0XB0. Parameter assignment and configuration frame The frame length for parameter assignment depends on the number of PA field devices in use and may amount to a maximum of 223 bytes. The frame length for parameter assignment depends on the number and configuration of the DP slaves in use and may amount to a maximum of 244 bytes. The structure of the parameter assignment and configuration frame is available for download from the Internet (http://support.automation.siemens.com/WW/view/en/13406349). Restrictions Functions that are based on reading the configuration prior to initially assigning the parameters for the Y link, are not supported. For this reason for example the CP 5431 cannot be used as DP master. It is equally not possible to control variables with COM PROFIBUS until the Y link parameters have been assigned. DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 135 Commissioning: Y link 9.3 Configuring for DP standard master mode 9.3.3 Configuring underlying DP slaves Requirement The product designations for the required DP slaves must have been entered in the GSD file of the IM 153-2. NOTICE For the redundancy mode only those DP slaves may be configured that have the entries "Begin of Device" or "Begin of Device h supported" in their GSD file. Configuration principle To configure the Y link select the manufacturer's specifications for the SP slaves in your configuration tool (Product and, where applicable, module designation). The specifications for the DP slaves must be entered in ascending order corresponding to their addresses. An example of a configuration is shown in the figure below. Procedure 1. In your configuration tool move to the DP slave configuration. 2. Enter the manufacturer designation (for example SIEMENS ET 200S (IM151 BASIC) for the first DP slave in the "Order number" or "Module" field and apply this in the first slot. Set the PROFIBUS address for the DP slave. Repeat this procedure for all of the DP slaves in use. 3. Terminate the entries and complete the configuration. The further procedure (for example saving, compiling, ...) is identical to other DP slaves. PROFIBUS address of the IM 153-2 in the underlying DP master system In the underlying DP master system the two IM 153-2 use the addresses 1 and 2. In addition, the address 125 is blocked for DP slaves. The first possible address for an underlying DP slave is 3. Configuring with COM PROFIBUS For SIMATIC S5 the DP slaves are integrated via their GSD files as a standard slave in COM PROFIBUS (V3.1 and later). 1. Copy the GSD file of the IM 153-2 into theCOM PROFIBUS directory: ...COMPBxx\GSD. 2. Start COM PROFIBUS and select the File > Read in GSD file menu command. Result: The IM 153-2 is displayed in the hardware catalog during slave configuration. 3. Configure the DP slaves using COM PROFIBUS. DP/PA coupler, active field distributors, DP/PA Link and Y Link 136 Operating Instructions, 07/2011, A5E00193841-17 Commissioning: Y link 9.3 Configuring for DP standard master mode Example: View of configuration in COM PROFIBUS The figure below shows an example of the view of a configuration for the Y link using COM PROFIBUS. Figure 9-4 Example of a configuration with COM PROFIBUS How to enter a PROFIBUS address 1. In the "Module" column select the "Begin of Device" of the relevant DP slave and select the "Parameter..."button. 2. In the "Value" column enter the desired PROFIBUS address and confirm with "OK". Figure 9-5 Entering the PROFIBUS address DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 137 Commissioning: Y link 9.3 Configuring for DP standard master mode DP/PA coupler, active field distributors, DP/PA Link and Y Link 138 Operating Instructions, 07/2011, A5E00193841-17 Operation of the DP/PA-Link and Y-Link 10 Terms Some of the following information applies to both the DP/PA link with its PA field devices and to the Y link with its underlying DP slaves. In such instances, the following terminology will be used for the sake of clarity: "Link" stands for DP/PA Link and Y Link "Slaves" stands for PA field devices and underlying DP slaves. "Underlying master system" stands for PA master system and underlying DP master system. 10.1 Start-up delay Definition During start-up, the link includes the slaves of the underlying master system in the data cycle. The slaves are parameterized and configured and the inputs of the slaves are read in. To ensure a reproducible start-up and to prevent inadvertent switching of outputs, the link issues CLEAR frames on the underlying master system during this phase, i.e. the outputs of the slaves are put into a safe state. Configured startup characteristics The start-up behavior depends on the configured startup characteristics relating to the plant configuration. Table 10- 1 Configured startup characteristics Configured startup characteristics Output data are output by the link if ... Starting if required configuration actual configuration all of the slaves are parameterized and configured, or The start-up delay has expired and fewer slaves have been parameterized / configured than had been planned for. Starting if required configuration = actual configuration all of the slaves are parameterized and configured. Comment: If during the start-up delay not all slaves are configured or parameterized, the link automatically repeats the start-up. The status of the start-up delay can be evaluated in the "Status Message" diagnostic block of the diagnostic frame. DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 139 Operation of the DP/PA-Link and Y-Link 10.2 Behavior after certain events in the redundancy mode 10.2 Behavior after certain events in the redundancy mode Behavior of the IM 153-2 The table below shows the behavior of the IM 153-2 following certain events in the redundancy mode. Table 10- 2 Behavior after certain events in the redundancy mode Event Response Master-reserve switchover with a modified configuration The link is switched over bumpless from the active channel to the channel that has up to now been passive. Failure of a CPU If this causes the active channel of the redundant DP master system to fail: see failure of the active channel. Otherwise: see failure of the passive channel. Failure of the active channel. The link is switched over bumpless from the active channel to the channel that has up to now been passive. The channel that has failed is displayed with the relevant IM 153-2 by the "BF" 1 LED. Failure of the passive channel. No impact on the link. The channel that has failed is displayed with the relevant IM 153-2 by the "BF" 1 LED. Failure of an IM 153-2 A diagnostic message is generated in the system. If the active IM 153-2 fails, there is a bumpless switchover to the channel that has been passive up till then. DP/PA coupler, active field distributors, DP/PA Link and Y Link 140 Operating Instructions, 07/2011, A5E00193841-17 Operation of the DP/PA-Link and Y-Link 10.3 Startup characteristics 10.3 Startup characteristics 10.3.1 Startup characteristics of the DP/PA link in non-redundant mode Startup characteristics The flow chart below shows the startup characteristics of the IM 153-2 after POWER ON. 3RZHUXSRIWKH,0 VFKHPDWLF 3RZHURQDWWKH,0 7KH,0HQWHUVWKH'3GDWDF\FOHDQGLVFRQILJXUHGE\WKH'3PDVWHU %LW[ LQGLDJQRVWLFIUDPHLHWKHVWDUWXSGHOD\RIWKH,0LVDFWLYH 352),%863$,0UHDGV DVIDUDVSRVVLEOH WKH3$LQSXWGDWD 3$RXWSXWGDWDDUHVHWWR &/($5 0LVVLQJVODYHVDUHUHDGLQZLWKD $OOVODYHVLQWKHGDWDF\FOH ELW[ LQWKHGLDJQRVWLFIUDPH RU VWDUWXSGHOD\WLPHHODSVHG" 1R Accessible nodes menu command. In the list that is displayed select the required IM 153-2 and select the PLC > PROFIBUS > Update firmware menu command. The remaining procedure is described in the STEP 7 online help. '33$/LQN ,0 3*3& Figure 11-1 Update directly via PROFIBUS DP (PG / PC is directly connected to the IM 153-2) DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 149 Maintenance and service 11.4 Firmware update Update via MPI to the CPU and on via PROFIBUS DP The PD / PC with the update files is connected to the MPI interface of the CPU. The IM 1532 is connected to the 2nd interface of the CPU via PROFIBUS DP. The IM 153-2 has to be integrated into the STEP 7 project on the CPU. Open HW Config and select the desired IM 153-2. Select the PLC > Update firmware menu command. The remaining procedure is described in the STEP 7 online help. HJ&38'3 '33$OLQN 3URJUDPPLQJGHYLFH3& Figure 11-2 ,0 Update via MPI to CPU and on via PROFIBUS DP (PG / PC is connected to CPU) Restart after update In theSTEP 7 user interface it is possible to set whether the IM 153-2 automatically executes a reset after a successful update to start with the newly uploaded firmware. CAUTION If the "Activate firmware after downloading" box is ticked, there will be a brief link failure. If you have not made any provisions for this situation, the update will cause a CPU STOP as a result of rack failure. The IM 153-2 must be reset by switching off the supply voltage before the IM 153-2 starts up with the new firmware when the supply voltage is switched on. If the update was concluded successfully, the start up of the IM 153-2BAx2 takes around 60 seconds longer with the first resetting or switching off/on of the power supply than it would with a normal start up. All further start ups will take the usual time. Update not successful If the update fails, after the supply voltage is switched on / off the IM 153-2 automatically starts with the ("old") firmware that was current up to that time. DP/PA coupler, active field distributors, DP/PA Link and Y Link 150 Operating Instructions, 07/2011, A5E00193841-17 Maintenance and service 11.5 Maintenance 11.5 Maintenance Maintenance The transfer characteristics of the DP/PA couplers, the active field distributors (AFD) and active field splitters (AFS) are stable over long periods and regular maintenance is unnecessary. DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 151 Maintenance and service 11.5 Maintenance DP/PA coupler, active field distributors, DP/PA Link and Y Link 152 Operating Instructions, 07/2011, A5E00193841-17 12 Functions 12.1 IM 153-2 12.1.1 Time synchronization on the underlying master system Properties The IM 153-2 interface module, 6ES7153-2BAx1-0XB0 and higher, supports time synchronization on the lower-level master system. The IM 153-2 sends the current time to the lower-level master system whenever - a time synchronization takes place on the higher level PROFIBUS DP, - if a valid configuration for the lower-level mastersystem is available in the IM 153-2, and - the lower-level master system is operating. Synchronization on the lower-level master system takes place at the synchronization intervals that have been set on the higher level PROFIBUS DP. Compared to the time received on the higher level PROFIBUS DP, accuracy deteriorates slightly. Accuracy within 10 ms is always guaranteed. Operating steps for activation You activate the time synchronization on the lower-level master system by performing the following steps: 1. Complete the higher level PROFIBUS DP with the time master. 2. Activate the time synchronization in the Properties of the DP master. Note In the H system you have to insert a time master in both higher level PROFIBUS DP systems and activate the time synchronization in the Properties of the DP master. Time synchronization then takes place in the lower-level master system. Time-of-day format The time-of-day is distributed to the lower-level system in the ISP format. In this process the entire ISP frame is transferred in exactly the format that the IM 153-2 receives from the higher level PROFIBUS DP. The configuration of the frame and the sequence are described in: InterOperable SystemsTM Project, Fieldbus Specification, System Management Services Rev. 3.0 dated 19.10.1993 (compiled by ISP Foundation) DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 153 Functions 12.1 IM 153-2 12.1.2 Redundancy with IM 153-2 Usage You can operate the IM 153-2BAx2 redundantly on SIMATIC S7-400H (for example in the Y link on CPU 417-4H) according to standard Specification Slave Redundancy V1.2, Nov. 2004 of the PROFIBUS User Organization; Order No: 2.212 - System Redundancy (SR) - Flying Redundancy (FR) Requirements Installation on active bus modules The 6ES7195-7HD10-0XA0 and 6ES7195-7HD80-0XA0 bus modules ensure high availability of the link and shorter switchover times with redundancy. 2 x IM 153-2 on BM IM/IM bus module The arrangement specifications on the Internet (http://support.automation.siemens.com/WW/view/en/23372259) apply to the active bus modules and interface modules used. System Redundancy (SR) is possible with IM 153-2 as of 6ES7153-2BAx1-0XB0. Flying Redundancy (FR) is possible with IM 153-2 as of 6ES7153-2BAx1-0XB0. - The redundant master system must be configured according to the requirements made of H systems. - For configuring Flying Redundancy the current version of the Java GSD creation tool is required. Note STEP 7 provides no support for configuring an H system with flying redundancy. The SYNC/FREEZE function must not be activated during the redundancy mode. Note If the SYNC / FREEZE in a redundant system is activated nevertheless the user bears the responsibility for the behavior of the H system (for example when switchovers take place). You can only use the IM 153-2 in a redundant system on DP masters that support the "Fail-safe" parameter. On DP masters that do not support this parameter, the IM 153-2 will not start and the BF LED flashes. Tip: You can tell from the GSD file of the DP master whether it supports "Fail-safe". DP/PA coupler, active field distributors, DP/PA Link and Y Link 154 Operating Instructions, 07/2011, A5E00193841-17 Functions 12.1 IM 153-2 Compatible versions If you use the DP/PA link or Y link in a redundant configuration you must use compatible versions for the two IM 153-2. You can replace compatible versions of the IM 153-2 interface module with "System modification during operation". Please refer to the chapter Compatibility to precursor modules for information on compatibilities and arrangement rules. Note The functionalities that can be used are limited to the respective lower order numbers or the earlier version. S7-400H as DP Master You require STEP 7 V5.0 or later and the SIMATIC S7 H Systems software package to configure the S7-400H system. With STEP 7 V5.3 or later you no longer require SIMATIC S7 H-Systems additionally. DP master 1 and DP master 2: Execute the same user program Have the same parameter assignment and configuration for the IM 153-2. Availability in redundancy mode CAUTION Voltage supply for the IM 153-2 Set a separate power supply module for each IM 153-2. This ensures availability in redundant mode with 2 x IM 153-2. See also Compatibility with predecessor modules (Page 37) DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 155 Functions 12.1 IM 153-2 12.1.3 Reading and writing data records Procedure for reading and writing data records Depending on the operating mode of the DP master (S7-compatible or DPV1), data records of the IM 153-2 and the underlying slaves can be read and written by different methods. Reading data records with SFC 59 "RD_REC" or SFB 52 "RDREC" Writing data records with SFC 58 "WR_REC" or SFB 53 "WRREC" Reading and writing data records with a PD / PC via communication links, for example with SIMATIC PDM Table 12- 1 Procedure for reading and writing data records S7-compatible DP master Data records of the IM 153-2 Data records of underlying slaves SFC 59 "RD_REC" Reading with PD / PC SFC 58 "WR_REC" SFC 59 "RD_REC" Writing / reading with PD / PC DPV1 master SFC 59 "RD_REC", SFB 52 "RDREC" SFC 58 "WR_REC", SFB 53 "WRREC" Writing / reading with PD / PC SFC 59 "RD_REC", SFB 52 "RDREC" SFC 58 "WR_REC", SFB 53 "WRREC" Writing / reading with PD / PC Data records of the IM 153-2 Depending on the operating mode of the DP master (S7-compatible or DPV1) the IM 153-2 supports reading and writing of the following data records: on the DPV1 master: - Data records 0 and 1 (diagnostics data, read only) - Data records 255 ...(I&M data) on the S7-compatible master - Data records 0 and 1 (diagnostics data, read only) DP/PA coupler, active field distributors, DP/PA Link and Y Link 156 Operating Instructions, 07/2011, A5E00193841-17 Functions 12.1 IM 153-2 Parameters for SFC 58 "WR_REC" and SFC 59 "RD_REC" You will find the values required for the call parameters LADDR and REC_NUM and possible error information in the return value RET_VAL in the table below. Table 12- 2 Call parameters for SFC 58 "WR_REC" and SFC 59 "RD_REC" LADDR REC_NUM Access Diagnostic data of the IM 153-2 Diagnostic address of the IM 153-2 0 or 1 read only I&M data of the IM 153-2 Diagnostic address of the IM 153-2 255 ... read / write buffered diagnostic data of an underlying slave (out of the IM 153-2) 1 Diagnostic address of the IM 153-2 PROFIBUS address of the underlying slave read only random data record of an underlying DPV1 slave logical address of the underlying slave or the underlying module 3 Data record number2 read / write 2 1 Only on the DPV1 master and for configured slaves 2 depending on the type of the underlying slave or underlying module specify data record of slot 0 diagnostic address specify data record of slot 1 address of slot 1 specify data record of slot 2 address of slot 2 and so on. 3 Error information of the IM 153-2 Table 12- 3 Error information of the IM 153-2 RET_VAL (W#16#...) Description 0000 No error 80B6 The slave or module refuses to read / write a data record or does not recognize this data record. set mode of the DP master to DPV1 80BB Requested service is not supported 80BC Node not available 80BD Data record number incorrect The other functions of the SFC 58 "WR_REC", SFC 59 "RD_REC", SFB 52 "RDREC" and SFB 53 "WRREC" are described in the STEP 7 online help. DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 157 Functions 12.1 IM 153-2 12.1.4 Identification and maintenance data (I&M data) Definition and features Identification and maintenance data (I&M) is information stored in a module to support you in Checking the plant configuration Locating hardware modifications in a plant Correcting errors in a plant Identification data (I data) are information on the module, such as order number and serial number, some of which are printed onto the module enclosure. I data are manufacturer information about the module and are for reading only. Maintenance data (M data) are system-related information, such as the installation location and installation date. M data are created during configuration and written onto the module. Modules can be uniquely identified online by means of the I&M data. As of IM 153-2BAx1, this data is available on the DP/PA link and Y link. Note Only one DP master can access the I&M data of a DP/PA link or Y link at any given point in time. Reading and writing the I&M data with STEP 7 In STEP 7 the I&M data are displayed in the "Module status - IM 153-2" and "Properties - DP slave" tabs (please refer to the STEP 7) online help. The M data of modules can be entered in HW Config (for example in a dialog box during configuration). The I&M data are accessed in accordance with the IEC 61158-6 standard. In the H system the interface module from which the I&M data are to be read must be accessible online. Reading and writing the I&M data without STEP 7 If you want to use the I&M data without using STEP 7 you must access the data as specified in the PROFIBUS Guideline - Order No. 3.502, Version 1.1 of May 2003. You must address the interface module (slot 245 or 246) from which the I&M data are to be read in theH system. Slot 245 identifies the left-hand interface module, slot 246 the righthand interface module on the BM IM/IM. DP/PA coupler, active field distributors, DP/PA Link and Y Link 158 Operating Instructions, 07/2011, A5E00193841-17 Functions 12.1 IM 153-2 Example for reading the I&M data The user can specifically access certain I&M data via Read data record. This requires a twostage access: 1. A directory is stored in data record 248 containing the data record numbers belonging to the various indices (see table below). Table 12- 4 DS 248 configuration for DP/PA link or Y link Content Length (bytes) Coding (hex) 2 00 01 Header information ID of content directory Index of content directory 2 00 00 Length of successive blocks in bytes 2 00 08 Number of blocks 2 00 05 SZL-ID 2 F1 11 relevant data record number 2 00 EA Length of data record 2 00 40 Index 2 00 01 SZL-ID 2 F1 11 relevant data record number 2 00 EB Length of data record 2 00 40 Index 2 00 02 SZL-ID 2 F1 11 relevant data record number 2 00 EC Length of data record 2 00 40 Index 2 00 03 SZL-ID 2 F1 11 relevant data record number 2 00 ED Length of data record 2 00 40 Index 2 00 04 Block information for I&M data 8 bytes of block information for additional data record objects : 48 DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 159 Functions 12.1 IM 153-2 2. The section of the I&M data that is assigned to the corresponding index is to be found under the relevant data record number (see table below: Structure of the I&M data). The length of all data records with I&M data is 64 bytes. The data records are structured according to the principle shown in the followng table. Table 12- 5 Structural principle of data records with I&M data Content Length (bytes) Coding (hex) 2 F1 11 Header information SZL-ID Index 2 00 0x Length of the I&M data 2 00 38 Number of blocks with I&M data 2 00 01 Index 2 00 0x I&M data relating to the respective index (see table below) 54 I&M data Structure of the I&M data The data structures of the I&M data correspond to the specifications of the PROFIBUS Guideline - Order No. 3.502, Version 1.1 of May 2003. Table 12- 6 Structure of the I&M data I&M data Access Default setting Explanation Identification data 0: Index 1 (data record 234) MANUFACTURER_ID Read (2 bytes) 2A hex (= 42 dec) The name of the manufacturer is stored here. (42 dec = SIEMENS AG) ORDER_ID Read (20 bytes) depending on the module The order number of the module is stored here. SERIAL_NUMBER Read (16 bytes) depending on the module The order number of the module is stored here. This facilitates unique identification of the module. HARDWARE_REVISION Read (2 bytes) depending on the module The order version of the module is stored here. Is increased when the product release or the firmware of the module changes. SOFTWARE_REVISION Read (4 bytes) Firmware version Gives information on the firmware version of the module If the firmware version number is increased, then the product release of the module (HARDWARE_REVISION) is also increased. REVISION_COUNTER Read (2 bytes) 0000 hex Reserved PROFILE_ID Read (2 bytes) F600 hex Generic Device PROFILE_SPECIFIC_TYPE Read (2 bytes) 0005 hex on interface modules IM_VERSION Read (2 bytes) 0101 hex Gives information on the version of the I&M data. (0101 hex = Version 1.1) IM_SUPPORTED Read (2 bytes) 000E hex Gives information on the existing I&M data. (Index 2 bis 4) DP/PA coupler, active field distributors, DP/PA Link and Y Link 160 Operating Instructions, 07/2011, A5E00193841-17 Functions 12.1 IM 153-2 I&M data Access Default setting Explanation Maintenance data 1: Index 2 (data record 235) TAG_FUNCTION Read / write (32 bytes) - Enter a system-wide unique identification for the module here. TAG_LOCATION read / write (22 bytes) - Enter the installation location of the module here. Maintenance data 2: Index 3 (data record 236) INSTALLATION_DATE Read / write (16 bytes) - Enter the installation date for the module and, if necessary, the relevant time. RESERVED Read / write (38 bytes) - Reserved - Enter a comment on the module here. Maintenance data 3: Index 4 (data record 237) DESCRIPTOR Read / write (54 bytes) Changes compared to the I&A data up to now To date the I&A data were extended to include some content in the identification data in accordance with the PROFIBUS Guideline. The mechanism for accessing I&M data was amended in accordance with the PROFIBUS Guideline. See also Reading and writing the identification and maintenance data (I&M data) (Page 163) 12.1.5 System modification during operation. 12.1.5.1 System modification in S7 standard mode Procedure Perform the following steps to add a complete new DP/PA link including the underlying PA master system to an existing system while it is operating. 1. Mount the new DP/PA link. 2. Connect the voltage supply of all of the modules, 3. Connect the PROFIBUS PA to the new DP/PA couplers. 4. Plug the bus connector of the DP master system into the PROFIBUS DP interface of the new IM 153-2. The whole sequence of a system modification and the requirements that must be met for it are described in detail in the function manual System modification during operation by means of CiR . You will find the manual on the Internet at this address (http://support.automation.siemens.com) Search for the entry with the number 14044916. DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 161 Functions 12.1 IM 153-2 12.1.5.2 System modification in redundancy mode Procedure Perform the following steps to add a complete new DP/PA link or Y link including the underlying master system to an existing system while it is operating. 1. Mount the new link. 2. Connect the voltage supply of all of the modules, 3. DP/PA link only Connect the PROFIBUS PA to the new DP/PA couplers. Y link only Plug the bus connector of the DP master system onto the PROFIBUS DP interface of the new Y coupler. 4. Plug the bus connector of the active channel of the redundant DP master system onto the PROFIBUS DP interface of one of the IM 153-2. 5. Plug the bus connector of the of the passive channel onto the PROFIBUS DP interface of the other IM 153-2. This sequence is summarized as a single step "Reconfigure the hardware" in the manual: Automation system S7-400H, high availability systems in the chapter:System modifications during operation. It gives a detailed description of the entire sequence of a system modification. You will find the manual on the Internet at this address (http://support.automation.siemens.com) Search for the entry with the number 1186523. DP/PA coupler, active field distributors, DP/PA Link and Y Link 162 Operating Instructions, 07/2011, A5E00193841-17 Functions 12.2 DP/PA coupler FDC 157-0 12.2 DP/PA coupler FDC 157-0 12.2.1 Reading and writing the identification and maintenance data (I&M data) Procedure for reading I&M data You can read and write the identification data in one of the following ways: with STEP 7 Via user interfaces Via communication links With the upload / download mechanism Reading and writing the I&M data with STEP 7 HW Config shows the I&M data in the "Module status - DP/PA coupler" and "Properties - DP slave" tabs. The I&M data are accessed in accordance with the IEC 61158-6 standard. Reading and writing the I&M data with STEP 7 Writing I&M data with a PD / PC via communication links, for example with SIMATIC PDM Write the parameters and I&M data via the following menu items: File > Read full upload to PG / PC. Device > Full download to device. Reading and writing the I&M data via user interfaces Load data records 231 to 234 of the DP/PA coupler. Data record 231 is read-only. Reading data records with SFC 59 "RD_REC" or SFB 52 "RDREC". Write data records with SFC 58 "WR_REC" or SFB 53 "WRREC". Reading and writing the I&M data with the upload / download mechanism Use data record 255 of the DP/PA coupler. The I&M data is accessed in accordance with the standard PROFIBUS Guideline, Profile Guidelines Part 1: Identification & Maintenance Functions, March 2005. Additional information For additional information about SIMATIC PDM, refer to the PDM V6.0 The Process Device Manager manual at (Page 158): See also PDM V6.0 The Process Device Manager (http://support.automation.siemens.com/WW/view/en/21407212) DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 163 Functions 12.2 DP/PA coupler FDC 157-0 12.2.2 Reading the local LifeList Local LifeList The local LifeList renders the status of the PA field device on the equipotential bonding line. If the DP/PA coupler is used in the DP/PA link, then connected PA field devices are only visible in the local LifeList if they are also configured. Reading the local LifeList To read the local LifeList, you have the following options: The local LifeList is displayed in graphical form using SIMATIC PDM. Via user interfaces: Reading data records with SFC 59 "RD_REC" or SFB 52 "RDREC". Load data record 50 of the DP/PA coupler. Via the PROFIBUS DP slave diagnostics Every change to the equipotential bonding line leads to a PROFIBUS DP diagnosis. Note Updating the local LifeList Updating the local LifeList depends on the number of PA field devices. Updating and configuring can take approx. 1 minute. Additional information For Additional information about SIMATIC PDM, refer to the PDM V6.0 The Process Device Manager manual at: Internet (http://support.automation.siemens.com/WW/view/en/21407212) DP/PA coupler, active field distributors, DP/PA Link and Y Link 164 Operating Instructions, 07/2011, A5E00193841-17 Functions 12.2 DP/PA coupler FDC 157-0 12.2.3 Read out of the current value and voltage value 12.2.3.1 User data of the DP/PA coupler User data of the DP/PA coupler The DP/PA coupler with diagnostics functions has input data only. The data contains the current value on the equipotential bonding line and optional voltage on the equipotential bonding line. The variables are represented in IEEE 754 format with one byte quality code in accordance with PROFIBUS PA profiles. This is the Float Format to IEEE Standard 754 Short Real Number (floating point format). Reading the current values and voltage values You can read the current values and voltages values in one of the following ways: PROFIBUS DP (PAE of the CPU) Reading data records with SFC 59 "RD_REC" or SFB 52 "RDREC". Load data record 56 of the DP/PA coupler. Reading records with a PG / PC via communication links, for example with SIMATIC PDM. DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 165 Functions 12.2 DP/PA coupler FDC 157-0 User data frame structure The presentation of a tag in IEEE 754 format requires 4 bytes + 1 status byte. The status byte informs you about the validity of the measured value. %\WH[ %\WH[ %\WH[ %\WH[ %\WH[ %\WH[ %\WH[ %\WH[ %\WH[ %\WH[ Figure 12-1 &XUUHQWYDOXH P$ RQWKHHTXLSRWHQWLDOERQGLQJOLQH 6WDWXVE\WH 2SWLRQDO 9ROWDJHYDOXH P9 RQWKHHTXLSRWHQWLDOERQGLQJOLQH 6WDWXVE\WH User data frame structure Note Input data Only the actively energizing DP/PA coupler delivers a valid PA current vale to slot 1 in the redundant structure. If you insert slot 2 in HW Config, then the passive DP/PA coupler delivers a valid PA voltage value in the redundant structure. Only the PA current value is delivered in stand-alone mode. Voltage measurement on the equipotential bonding line The optional configuration of slot 2 for voltage measurement on the equipotential bonding line is only possible in a setup with ring redundancy. The PA voltage can be measured on the end of the cable only, i.e. on the passive DP/PA coupler. The maximum PA voltage on the actively energizing DP/PA coupler is about 31 V. DP/PA coupler, active field distributors, DP/PA Link and Y Link 166 Operating Instructions, 07/2011, A5E00193841-17 Functions 12.2 DP/PA coupler FDC 157-0 12.2.3.2 Structure of the current value and voltage value Measured values in IEEE format (byte x to byte x+3) Below you can see the presentation of a measured value in IEEE format, and the conversion into a decimal value. %\WH[ %\WH[ %\WH[%\WH[ 9= ([SRQHQW 0DQWLVVD 6 6LJQ %\WH[ %\WH[%\WH[ %\WH[ 0DQWLVVD 0DQWLVVD ([DPSOH&RQYHUVLRQRIDQ,(((YDOXHWRGHFLPDOYDOXH %\WH[ %\WH[ %\WH[ %\WH[ % )+ G ([SRQHQW 9= 0DQWLVVDZLWKELW 0HDVXUHGYDOXH 6[ H[SRQHQW [ PDQWLVVDZLWKELW 0HDVXUHGYDOXH [ [ Figure 12-2 0HDVXUHGYDOXH [[ 0HDVXUHGYDOXH Conversion of an IEEE format to decimal value DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 167 Functions 12.2 DP/PA coupler FDC 157-0 Syntax of an IEEE status byte (byte x+4) The syntax of the status byte corresponds to the PROFIBUS PA profile. The following status codes are used with the DP/PA coupler: %\WH[ 6WDWXVE\WHIRUPHDVXUHGYDOXH /LPLWVUHSRUWVOLPLWYLRODWLRQV 6XEVWDWXVGLIIHUHQWLDWHVDQGUHILQHVWKHTXDOLW\RIWKHFRUUHVSRQGLQJPHDVXUHG YDOXH6LJQLILFDQFHLVGHSHQGHQWRQ4XDOLW\ 4XDOLW\GHVFULEHVWKHIXQGDPHQWDOTXDOLW\RIWKHPHDVXUHGYDOXH 6WDWXVFRGHV + EDGQRQVSHFLILF + XQFHUWDLQ LQLWLDOYDOXH QRQPHDVXUHGYDOXH + EDG PDLQWHQDQFHDODUP VKRUWFLUFXLWZLUHEUHDN 3$UHGXQGDQF\IDXOW'33$bFRXSOHUGHIHFWEDGVLJQDOOHYHO + EDG PDLQWHQDQFHDODUP /RZHUOLPLWYLRODWHG + EDG PDLQWHQDQFHDODUP 8SSHUOLPLWYLRODWHG + XQFHUWDLQ PDLQWHQDQFHGHPDQGHG 3DUDPHWHUL]DWLRQHUURUUHGXQGDQF\PRGHRISDUWQHULQFRUUHFW + XQFHUWDLQ PDLQWHQDQFHGHPDQGHG /RZHUOLPLWYLRODWHG $+ XQFHUWDLQ PDLQWHQDQFHGHPDQGHG 8SSHUOLPLWYLRODWHG + JRRG 2. QRHUURU + JRRG /RZHUOLPLWYLRODWHG + JRRG 8SSHUOLPLWYLRODWHG Figure 12-3 Syntax of an IEEE status byte Note Maintenance alarm / maintenance demanded The status codes linked to "maintenance alarm" or "maintenance demanded" are only displayed if the diagnostics of the DP/PA coupler are activated. The status codes influence the respective bits in the PA status of the diagnostics frame. DP/PA coupler, active field distributors, DP/PA Link and Y Link 168 Operating Instructions, 07/2011, A5E00193841-17 Functions 12.2 DP/PA coupler FDC 157-0 Limits The following limit values are preset: PA current: Lower/upper limit: 0 mA / 1000 mA PA voltage: Lower/upper limit: 15.5 V/35 V You can change the limit values in data record 128 of the DP/PA coupler. Errors when writing the data record mean that current or default limit values are not used. The data record is unacknowledged. 12.2.4 Data records You need this information if you go beyond the standard applications from STEP 7 and SIMATIC PDM. Requirements The DP/PA coupler gives the user data records that are addressed via slot 0 or 1. The PROFIBUS DP data records are based on the PROFIBUS PA profile. The profile is available from PROFIBUS International (PI) on the Internet at: Internet (http://www.profibus.com) Data records on slot 0 Table 12- 7 Data records from the DP/PA coupler on slot 0 Data record no. Read / Write Size in bytes Description 1 r 14 PA diagnostics (diagnostics frame bytes 1 to 14) 18 r 32 TAG, determined from I&M list 1. 24 r 16 Software revision 26 r 2 Device Man ID, determined from I&M list 0. 27 r 16 Device ID 50 r 16 Local LifeList (1 bit status per station) 1 bit per PA field device, the offset corresponds to the station number. Coding 0: PA field device not available. Coding 1: PA field device available on the local equipotential bonding line. 56 r 10 Mapping of the input data See User data frame. 10 bytes of input data are also provided with a configuration with only one slot: PA current and PA voltage. 60 r Max. 72 Mapping the diagnostics frame See Diagnostics frame. 61 r 8 Mapping the PA redundancy status DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 169 Functions 12.2 DP/PA coupler FDC 157-0 Data record no. Read / Write Size in bytes Description See PA redundancy status. 62 r 16 See Diagnostic record. 128 r/w 12 Parameter assignment of the limit value for PA current and PA voltage 231 r/w 64 I&M list 0 (rating plate) 232 r/w 64 I&M list 1 (TAG) 233 r/w 64 I&M list 2 (date) r/w 64 I&M list 3 (descriptor) 234 The data structures of the I&M data correspond to the specifications of the PROFIBUS Guideline - Order No. 3.502, Version 1.1 of May 2003. 255 r/w 68 Upload / Download mechanism for I&M objects This data set is structured according to the following standard: PROFIBUS Profile Guidelines Part 1: Identification & Maintenance Functions. Data records on slot 1 Table 12- 8 Data records from the DP/PA coupler on slot 1 Data record no. Read / Write Size in bytes Description 0 r 12 Header (device management) 1 r 8 Composite List Directory Entries (device management) Reading and writing data records To read and write records, use the following SFCs: Reading the data record with SFC 59 "RD_REC" or SFB 52 "REC". Write the data record with SFC 58 "WR_REC" or SFB 53 "WR_REC". Additional information For more detailed information on SFCs, refer to the System Software for S7-300/400 System and Standard Functions manual. Internet (http://support.automation.siemens.com/WW/view/en/1214574) See also Identification and maintenance data (I&M data) (Page 158) DP/PA coupler, active field distributors, DP/PA Link and Y Link 170 Operating Instructions, 07/2011, A5E00193841-17 Functions 12.2 DP/PA coupler FDC 157-0 12.2.5 Diagnostic record 62 Structure of diagnostics record 62 Bytes 0 to 5 of data record 62 contain the standard diagnostics, bytes 6 to 15 the PA status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bFRXSOHUGHIHFW %\WH 3DUDPHWHUL]DWLRQHUURU 0LVVLQJSURFHVVYROWDJH %\WH 3$UHGXQGDQF\IDXOW ([WHUQDOHUURU $PELJXRXVHUURUEDGVLJQDOOHYHO %\WH + DOZD\V %\WH + DOZD\V Figure 12-4 Structure of diagnostics record 62 DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 171 Functions 12.2 DP/PA coupler FDC 157-0 12.2.6 Address space of the inputs Introduction The address range of the process input image that is occupied is dependent on the configuration, i.e. by the selection of the relevant entry in the configuring software. Assignment of the process input image (PII) The DP/PA coupler FDC 157-0 has 5 or (optional) 10 bytes of input data. These contain the current value on the equipotential bonding line, as well as (optional) the PA voltage in IEEE754 format (32 bit floating point number) with one byte quality code in accordance with the PROFIBUS PA profile. Structure of the configuration frame The DP/PA coupler has slot modeling as the modular slave. Slot 0 is the proxy for the entire slave Slot 1 is always available Slot 2 can be configured (optional) Module I/O data in bytes Consistency DP ID Slot 1 5/0 byte entire length 94H Slot 2 5/0 byte entire length 94 H DP/PA coupler, active field distributors, DP/PA Link and Y Link 172 Operating Instructions, 07/2011, A5E00193841-17 Interrupt, error and system messages 13.1 Diagnostics by means of LED displays 13.1.1 The LED displays of the IM 153-2 13 Introduction PA field devices and DP slaves communicate on the same basis. Hence the following simplified terminology is used in this section: "Slaves" stands for PA field devices and lower-level DP slaves. "Lower-level master system" stands for PA master system and lower-level DP master system. Status and error messages of the IM 153-2 Table 13- 1 Status and error messages of the IM 153-2 6) %) %) 6) %) %) %DWFKHUURU UHG %XVIDXOWKLJKHUOHYHO352),%86'3 UHG %XVIDXOWORZHUOHYHO352),%86 UHG $&7 21 $&7 21 ,0KDVDQDFWLYHFKDQQHO \HOORZ 9SRZHUVXSSO\,0 JUHHQ DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 173 Interrupt, error and system messages 13.1 Diagnostics by means of LED displays LEDs SF Off BF 1 Off Meaning BF 2 Off ACT Off Remedy ON Off No voltage present on the IM 153-2. Switch on the power supply module. Applied supply voltage is not within permissible range. Check the voltage applied Hardware fault of the IM 153-2 Replace the IM 153-2. * * * * On Supply voltage is applied to the IM 153-2. - On On On On On All LEDs are switched on for approx. 1 s. IM 153-2 is starting. - Off Off Off Off On In the non-redundant mode: The IM 153-2 is exchanging data with the DP master and the lowerlevel slaves. - In the redundant mode: the IM 153-2 is passive and ready for switchover. - On Only in the redundant mode: The IM 153-2 is active and exchanging data with the DP master and the lower-level slaves. - Off Off Off Off Off Flashes * rapidly On The start-up delay is active on the IM 153-2. If the IM 153-2 does not fully start up within 20 s, then check in the configuration whether whether the start-up is enabled when desired layout actual layout. * Off On On In the non-redundant mode: The IM 153-2 has not been configured Check whether the CPU or the DP master is in the RUN mode. In the redundant mode: the IM 153-2 is passive and not ready for switchover. Check whether the H system is in the redundant system state.** No connection to the DP master. Check that the bus connector is correctly inserted. * On * On Off Off On Possible causes: * Flashes * Off On Bus communication to the IM 153-2 is interrupted. Check if the bus cable to the DP master is interrupted. The DP master is not in operation. Switch the On / Off switch for 24 VDC on the power supply module off and on again. Check the configuration. Check the PROFIBUS address. No data exchange is taking place between DP master and IM 153-2. DP/PA coupler, active field distributors, DP/PA Link and Y Link 174 Operating Instructions, 07/2011, A5E00193841-17 Interrupt, error and system messages 13.1 Diagnostics by means of LED displays LEDs SF On BF 1 Off Meaning BF 2 Off ACT Off Remedy ON On In non-redundant mode: All slaves are exchanging data. At least one slave has reported an error. or Inadmissible PROFIBUS address Evaluate the diagnosis of the IM 153-2 and control the reported slaves. DP/PA link only: Check the status bytes in the slave user data. Read the slave device status using a configuration tool, for example SIMATIC PDM). or Set a valid PROFIBUS address for the IM 153-2. On Off Off On On In the redundant mode: the IM 153-2 is passive and ready for switchover. There is an error on the active IM 153-2. Evaluate the LED display on the active IM 153-2. In the redundant mode: The IM 153-2 is active. All slaves are exchanging data. At least one slave has reported an error. Evaluate the diagnosis of the IM 153-2 and control the reported slaves. Evaluate the diagnoses of the lower-level slaves using the online view of HW Config. DP/PA link only: Check the status bytes in the slave user data. Read the slave device status using a configuration tool, for example SIMATIC PDM). On Off Flashes * On The configured structure of the link does not correspond to the actual structure. or Check the configuration and structure of the link. or Evaluate the diagnosis of the IM 153-2 and control the reported The IM 153-2 has no cyclical data exchange to at least one configured slaves (connection, address, parameterization, configuration). slave. Flashes Flashes Flashes Flashes Flashes In the current mode the IM 153-2 is not compatible with the redundant IM 153-2. * You will find information on compatibilitiy between the versions of IM 153-2 and IM 157 in the chapter Compatibility to precursor modules. Not relevant ** After the transition to the redundant system state the "SF" LED flashes for another 20 seconds. See also Compatibility with predecessor modules (Page 37) DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 175 Interrupt, error and system messages 13.1 Diagnostics by means of LED displays 13.1.2 LED displays of the DP/PA coupler FDC 157-0 Status and error messages of the DP/PA coupler FDC 157-0 Table 13- 2 6) %) '3 3$ $&7 21 Status and error messages of the DP/PA coupler FDC 157-0 %DWFKHUURU UHG %XVIDXOW UHG %XVPRQLWRULQJ352),%86'3 \HOORZ %XVPRQLWRULQJ352),%863$ \HOORZ '33$FRXSOHUDFWLYDWHGIHHGLQJWUDQVPLWWLQJ \HOORZ RQO\ZLWK3$UHGXQGDQF\ 9SRZHUVXSSO\IRU'33$FRXSOHU JUHHQ LEDs SF BF DP Meaning PA ACT ON Remedy * * * * * On Voltage is applied to the DP/PA coupler. The DP/PA coupler is ready to operate. - Off Off * * Off On DP/PA coupler without diagnostic message - On Off * * Off On DP/PA coupler with diagnostic message - * * * * Off Off There is no voltage applied to the DP/PA coupler. Error in the DP/PA coupler. Check the 24 V voltage supply of the DP/PA coupler, Contact your Siemens representative. * * * * * Flashe s PROFIBUS PA overloaded Check the number of connected PA field devices and the total current. * Flashe s * * * On DP/PA coupler not or not correctly configured. Check the PROFIBUS addresses in the configuration and on the DP/PA coupler. Causes: PROFIBUS addresses do not match in the configuration and on the DP/PA coupler. Redundancy mode DP/PA coupler, active field distributors, DP/PA Link and Y Link 176 Operating Instructions, 07/2011, A5E00193841-17 Interrupt, error and system messages 13.1 Diagnostics by means of LED displays LEDs SF * BF On DP Off Meaning PA ACT ON Off * Flashe s PROFIBUS DP frames are not being received. Remedy Check that the bus connector is correctly inserted. Check if the bus cable to the DP master is interrupted. Causes: The DP master is not in operation. Bus cable is damaged. Bus modules are not connected correctly. Check if the bus modules are correctly connected. Connector to backplane bus is defective. Check the 24 V voltage supply of the DP/PA coupler. Off Off On Flashe s On On PROFIBUS PA frames are being received - On Off On Off On On PROFIBUS PA frames are not being received, for example Check the PA field devices on the PROFIBUS PA Check if the bus segments are terminated properly. Off * On * * * * * * On On * The voltage to PROFIBUS PA is not within the permissible range (short circuit, overload). No response from a PA field device. The PA field device is possibly not being addressed. No DP master available. Diagnostics not available / not possible Illegal PROFIBUS addresses of the DP/PA coupler Check the PROFIBUS addresses of the DP/PA coupler. DP/PA coupler is the active energizing coupler. ** * Not relevant ** If the ACT LED it illuminated for both DP/PA couplers, then both DP/PA couplers are active: one DP/PA coupler powers its equipotential bonding line, the other passes through. DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 177 Interrupt, error and system messages 13.1 Diagnostics by means of LED displays 13.1.3 LED displays of the DP/PA coupler Status and error messages of the DP/PA coupler Table 13- 3 Status and error messages of the DP/PA coupler '3 3$ '3 3$ %XVPRQLWRULQJ352),%86'3 \HOORZ %XVPRQLWRULQJ352),%863$ \HOORZ 21 21 9SRZHUVXSSO\IRU'33$FRXSOHU JUHHQ LEDs DP PA Meaning Remedy ON * * On Voltage is applied to the DP/PA coupler. The DP/PA coupler is ready to operate. - * * Off There is no voltage applied to the DP/PA coupler, Check the 24 V voltage supply of the DP/PA coupler, or or Error in the DP/PA coupler. Contact your Siemens representative. * * Flashe s PROFIBUS PA overloaded Check the number of connected PA field devices and the total current. Flashe s * On PROFIBUS DP frames are being received - Off * On PROFIBUS DP frames are not being received Check that the bus connector is correctly inserted. Check if the bus cable to the DP master is interrupted. Check if the bus modules are correctly connected. Check the 24 V voltage supply of the DP/PA coupler, Causes: The DP master is not in operation. Bus cable is damaged. Bus modules are not connected correctly. Connector to backplane bus is defective * Flashe s On PROFIBUS PA frames are being received - * Off On PROFIBUS PA frames are not being received, for example Check the PA field devices on the PROFIBUS PA Check if the bus segments are terminated properly. * the voltage to PROFIBUS PA is not within the permissible range (short circuit, overload). No response from a PA field device. The PA field device is possibly not being addressed. Not relevant DP/PA coupler, active field distributors, DP/PA Link and Y Link 178 Operating Instructions, 07/2011, A5E00193841-17 Interrupt, error and system messages 13.1 Diagnostics by means of LED displays 13.1.4 LED displays of the Y coupler Status and error messages of the Y coupler Table 13- 4 Status messages of the Y coupler '3 '3 21 '3 '3 21 %XVPRQLWRULQJLQWHUQDO352),%86'3 \HOORZ %XVPRQLWRULQJORZHUOHYHO352),%86'3 \HOORZ 9SRZHUVXSSO\ 35 V; latching cutoff Power failure bypass Min. 5 ms Electrical isolation of the 24 V power supply PROFIBUS DP / PROFIBUS PA Yes PROFIBUS DP / supply Yes PROFIBUS PA / supply Yes All electric circuits / FE Yes Insulation tested with 500 VDC DP/PA coupler, active field distributors, DP/PA Link and Y Link 232 Operating Instructions, 07/2011, A5E00193841-17 Technical specifications 14.3 Technical data DP/PA coupler FDC 157-0 (6ES7157-0AC83-0XA0) DP/PA coupler power consumption (24 VDC) Max. 2.3 A Output current PA section (for dimensioning the PA configuration) 1A Power loss of the module Max. 13.4 W Status, interrupts, diagnostics Status display No Interrupts None Diagnostics function Yes Group error Red LED "SF" Bus fault Red LED "BF" PROFIBUS DP bus monitoring Yellow LED "DP" PROFIBUS PA bus monitoring Yellow LED "PA" DP/PA coupler monitoring Yellow LED "ACT" Monitoring 24 V power supply Green "ON" LED Data for selecting the PA field devices Connection to DP/PA couplers max. power consumption of the PA field devices together 1 A Field devices with certification for PROFIBUS PA Field devices are located outside the hazardous area max. 31 PA field devices can be connected DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 233 Technical specifications 14.4 Technical specifications of DP/PA coupler Ex [i] (6ES7157-0AD82-0XA0) 14.4 Technical specifications of DP/PA coupler Ex [i] (6ES7157-0AD82-0XA0) Technical specifications Order number 6ES7157-0AD82-0XA0 Dimensions and weight Dimension W x H x D (mm) 80 x 125 x 130 Weight Approx. 550 g Module-specific data Transmission speed on PROFIBUS DP 45.45 kBaud Transmission speed on PROFIBUS PA 31.25 kBaud Bus protocol PROFIBUS DP Ignition protection as accompanying equipment II 3G (1) GD Ex nA [ia] [iaD] IIC T4 Voltages, currents, potentials Rated supply voltage 24 VDC (20.4 V to 28.8 V) Polarity reversal protection Yes Power failure bypass Min. 5 ms PA interface Output voltage 13 VDC to 14 VDC Output current at: Max. 110 mA Electrical isolation of the 24 V power supply to PROFIBUS DP Yes to PROFIBUS PA Yes Insulation tested with 500 VAC DP/PA coupler power consumption (24 VDC) Max. 400 mA Power loss of the module Typically 7 W Status, interrupts, diagnostics Status display No Interrupts None Diagnostics function Yes PROFIBUS DP bus monitoring Yellow LED "DP" PROFIBUS PA bus monitoring Yellow LED "PA" Monitoring 24 V power supply Green "ON" LED Ex [i] characteristic data Uo = 15 V Io = 247 mA Po = 1.95 W Um = 250 V AC Ta = -25 to +60 C DP/PA coupler, active field distributors, DP/PA Link and Y Link 234 Operating Instructions, 07/2011, A5E00193841-17 Technical specifications 14.5 Technical specifications Y coupler (6ES7197-1LB00-0XA0) Connectable cables (PA) R' 15 to 150 /km L' 0.4 to 1 mH/km C' 80 to 200 nF/km Length max. 1000 m; for safety reasons (Ex protection) Data for selecting the PA field devices Connection to DP/PA couplers Field devices with certification for PROFIBUS PA max. 31 PA field devices can be connected Power consumption of all PA field devices: max. 110 mA Approval data of the PA field devices must conform to the Ex [i] characteristic data of the DP/PA coupler: 14.5 Ui 15 V Ii 247 mA Pi 1.95 W Technical specifications Y coupler (6ES7197-1LB00-0XA0) Technical specifications Order number 6ES7197-1LB00-0XA0 Dimensions and weight Dimension W x H x D (mm) 40 x 125 x 130 Weight Approx. 200 g Module-specific data Transmission speed for the lower-level DP master system 45.45; 93.75; 187.5; 500 kBaud 1.5; 3; 6; 12 MBaud Bus protocol PROFIBUS DP Length of parameter assignment frame Max. 244 bytes Voltages, currents, potentials Power supply via bus module Power consumption Max. 300 mA Power loss of the module Typically 1 W Electrical isolation from lower-level DP master system Yes Insulation tested with 500 VDC DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 235 Technical specifications 14.6 Technical data - active field splitter (AFS) (6ES7157-0AF82-0XA0) Status, interrupts, diagnostics Status display No Interrupts None Diagnostics function Yes Bus monitoring of internal PROFIBUS DP Yellow LED "DP 1" Bus monitoring of external PROFIBUS DP Yellow LED "DP 2" Monitoring of the power supply Green "ON" LED Data for connecting DP slaves 14.6 DP slaves can be connected max. 64, only if RS 485 repeaters or OLM / OBT are used, otherwise max. 31 Termination of the lower-level DP master system Active terminator resistor (BUS TERMINATOR) Use of RS 485 repeaters Max. 8 Use of OLM / OBT Yes Technical data - active field splitter (AFS) (6ES7157-0AF82-0XA0) Technical specifications Product version 02 Protection class IP65 Dimensions and weight Dimension W x H x D (mm) 125 X 57 x 80; with screw gland 175 x 57 x 105 Weight Approx. 700 g Voltages, currents, potentials Rated supply voltage 16 VDC to 32 VDC Polarity reversal protection Yes Overvoltage protection Yes Power failure bypass 5 ms Internal power consumption Max. 25 mA Output current PA section (for dimensioning the PA configuration) 1A Power loss of the module Max. 1 W Status, interrupts, diagnostics Status display No Interrupts None Diagnostics function Yes Status PA main line PA1, PA2 Green LED Fault PA main line PA1, PA2 Red LED Data for selecting the PA field devices Connection to DP/PA couplers max. power consumption of the PA field devices together 1 A Field devices with certification for PROFIBUS PA max. 31 PA field devices can be connected DP/PA coupler, active field distributors, DP/PA Link and Y Link 236 Operating Instructions, 07/2011, A5E00193841-17 Technical specifications 14.7 Technical data - active field distributor (AFD) (6ES7157-0AF81-0XA0) 14.7 Technical data - active field distributor (AFD) (6ES7157-0AF81-0XA0) Technical specifications Product version 02 Protection class IP65 Dimensions and weight Dimension W x H x D (mm) 125 X 57 x 80; with screw gland 175 x 57 x 105 Weight Approx. 700 g Voltages, currents, potentials Rated supply voltage 16 VDC to 32 VDC Tmax 35 V Polarity reversal protection Internal power consumption Yes Max. 25 mA; with an open main connection line 59 mA Status, interrupts, diagnostics Status display No Interrupts None Diagnostics function Yes Status PA main line PA1, PA2 Green LED Fault PA main line PA1, PA2 Red LED Status / fault PA spur line X1 to X4 Green LED Data for selecting the PA field devices Connection Current Imax pro PA spur line X1 to X4 Field devices with certification for PROFIBUS PA max. 4 PA field devices can be connected 60 mA DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 237 Technical specifications 14.8 Technical specifications of active field distributor AFDiS (6ES7157-0AG83-0XA0) 14.8 Technical specifications of active field distributor AFDiS (6ES7157-0AG83-0XA0) Technical specifications Order number 6ES7157-0AG83-0XA0 Product version 01 Dimensions and weight Dimension W x H x D (mm) 380 x 85 x 170 Weight 4500 g Supply voltages Description Via bus; no auxiliary power necessary Nominal value Lower limit of permissible range (DC) 16 V Upper limit of permissible range (DC) 32 V Polarity reversal protection (only in connection Yes; up to 1 A with DP/PA coupler) Overvoltage protection No Current consumption/power loss Power consumption At 28 V input voltage <= 64 mA + (0.838 * aggregate current of all the field devices) At 24 V input voltage <= 67 mA + (1.008 * aggregate current of all the field devices) At 20 V input voltage <= 74 mA + (1.246 * aggregate current of all the field devices) Short-circuit at all the spur lines At 28 V input voltage 92 mA At 24 V input voltage 100 mA At 20 V input voltage 110 mA Power loss, min. 1.4 W Power loss, max. 5.9 W Interfaces PROFIBUS DP No PROFIBUS PA Yes FOUNDATION Fieldbus H1 Yes DP/PA coupler, active field distributors, DP/PA Link and Y Link 238 Operating Instructions, 07/2011, A5E00193841-17 Technical specifications 14.8 Technical specifications of active field distributor AFDiS (6ES7157-0AG83-0XA0) Connections Main cables Number 2 Terminals (internal) Screw-type terminals (3-pin) Cable gland (enclosure) M16 Cable type Type A Min. cable diameter 4 mm Max. cable diameter 9 mm Min. conductor cross-section 0.2 mm2 Max. conductor cross-section 2.5 mm2 Automatic bus terminator Yes Spur cables Number n 6 Connecting terminals Screw-type terminals (3-pin) Cable gland M16 Cable type Type A Min. cable diameter 4 mm Max. cable diameter 9 mm Min. conductor cross-section 0.2 mm2 Max. conductor cross-section 2.5 mm2 Short-circuit-proof Yes Intrinsically-safe acc. to FISCO Yes Max. DC current of the field devices spur line 1 60 mA Max. DC current of the field devices spur line 2 to 6 40 mA Max. DC total current of all the field devices 180 mA Short-circuit current (test current) 5 mA Debounce logic Yes Max. no-load voltage 15.3 V Max. current output to field devices 260 mA Grounding Direct grounding Via connection bar Interrupts, diagnostics, status information Status display Yes Interrupts None Diagnostics function Yes Diagnostic indicator LED Yes Data transfer Between main line and spur lines Repeater function Electrical isolation Between main line and spur lines Yes Test voltage 2550 VDC 2s DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 239 Technical specifications 14.8 Technical specifications of active field distributor AFDiS (6ES7157-0AG83-0XA0) Environmental requirements Operating temperature min. -40 C max. 70 C Storage/transport temperatures min. -40 C max. 85 C Relative humidity Operation, max. 95% Degree of protection IP66 Installation Zone 2 / Zone 22 Yes Zone 1 / Zone 21 Yes Class I Zone 2 / Division 2 Yes Class I Zone 1 Yes DP/PA coupler, active field distributors, DP/PA Link and Y Link 240 Operating Instructions, 07/2011, A5E00193841-17 A Appendix A.1 Dimension drawings A.1.1 Active field distributor AFD/AFS Figure A-1 AFD / AFS dimension drawing DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 241 Appendix A.1 Dimension drawings Figure A-2 AFD / AFS dimension drawing side view DP/PA coupler, active field distributors, DP/PA Link and Y Link 242 Operating Instructions, 07/2011, A5E00193841-17 Appendix A.1 Dimension drawings Active field distributor AFDiS A.1.2 Figure A-3 AFDiS dimension drawing front DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 243 Appendix A.1 Dimension drawings Figure A-4 AFDiS dimension drawing side view DP/PA coupler, active field distributors, DP/PA Link and Y Link 244 Operating Instructions, 07/2011, A5E00193841-17 Appendix A.2 Order numbers A.2 Order numbers A.2.1 Components of the bus links Components of the bus links Table A- 1 Order numbers for the components of the bus couplers Component Order number IM 153-2 High Feature 6ES7153-2BA02-0XB0 IM 153-2 High Feature Outdoor 6ES7153-2BA82-0XB0 DP/PA coupler FDC 157-0 6ES7157-0AC83-0XA0 DP/PA coupler Ex [i] 6ES7157-0AD82-0XA0 Y coupler 6ES7197-1LB00-0XA0 Bus module BM PS/IM 6ES7195-7HA00-0XA0 Bus module BM PS/IM SIPLUS extreme 6AG1195-7HA00-2XA0 Bus module BM IM/IM 6ES7195-7HD10-0XA0 Bus module BM IM/IM Outdoor 6ES7195-7HD80-0XA0 Bus module BM FDC 6ES7195-7HF80-0XA0 Bus module BM FDC/FDC (redundant) 6ES7195-7HG80-0XA0 Bus module BM Y coupler 6ES7654-7HY00-0XA0 Active field distributor (AFD) 6ES7157-0AF81-0XA0 Active field distributor AFDiS 6ES7157-0AG83-0XA0 Active field splitter (AFS) 6ES7157-0AF82-0XA0 Complete package Y link: 6ES7197-1LA04-0XA0 2 x IM 153-2 High Feature 1 x bus module BM IM/IM 1 x Y coupler 1 x bus module BM Y coupler Complete package Y link: 2 x IM 153-2 High Feature Outdoor 1 x bus module BM IM/IM 1 x Y coupler 1 x bus module BM Y coupler 6ES7197-1LA11-0XA0 DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 245 Appendix A.2 Order numbers Table A- 2 Order number for configuration accessories Component Order number Mounting rail for the "module exchange in operation" function 482.6 mm 530 mm 620 mm 2000 mm 6ES7195 1GA00 0XA0 6ES7195 1GF30 0XA0 6ES7195 1GG30 0XA0 6ES7195 1GC00 0XA0 Bus connector for S7 mounting rails (each DP/PA 6ES7390 0AA00 0AA0 coupler includes one) Covers (included are 4 backplane bus covers and 6ES7195 1JA00 0XA0 1 bus module cover) A.2.2 Cable gland for active field splitter AFS Can be ordered at: Jacob GmbH (http://www.jacob-gmbh.de/en/) order number 50.616 M/EMC Fastener for HSK-Ex standard cable glands Can be ordered from: Hummel Elektrotechnik GmbH (http://www.hummel-group.com/) order number 1.296.0901.11 Sealing caps for unused connections on AFDiS (10 units) 6ES7157-0AG80-1XA1 Accessories for PROFIBUS DP Accessories for PROFIBUS DP Table A- 3 Order numbers for PROFIBUS DP accessories Accessories Order number PROFIBUS DP bus connector (up to 12 MBaud) without PD port 6ES7972-0BA12-0XA0 with PD port 6ES7972-0BB12-0XA0 PROFIBUS DP FastConnect connector without PD port 6ES7972-0BA50-0XA0 with PD port 6ES7972-0BB50-0XA0 PROFIBUS DP bus cable normal (flexible) 6XV1830-0AH10 Drum cable (strong) 6XV1830-3BH10 PROFIBUS DP terminator 6ES7972-0DA00-0XA0 DP/PA coupler, active field distributors, DP/PA Link and Y Link 246 Operating Instructions, 07/2011, A5E00193841-17 Appendix A.2 Order numbers A.2.3 Accessories for PROFIBUS PA Accessories for PROFIBUS PA Table A- 4 Order numbers for PROFIBUS PA accessories Accessories Order number PROFIBUS PA bus cable (cable type A) 6XV1830-5AH10 Configuration With the SpliTConnect Connector System Create the configuration with the SpliTConnect connector system. The SpliTConnect connection system permits an easy-to-install configuration of PROFIBUS PA segments conforming to IEC 61784-1:2002 Ed1 CP 3/2 with field device connection points in intrinsically safe and non-intrinsically safe areas. The SpliTConnect connector system consists of the following components: Accessories Description Order number SpliTConnect Tap T-connector for PA field device 6GK1905-0AA00 SpliTConnect M12 Outlet Connecting element for M12 connection 6GK1905-0AB10 SpliTConnect Coupler Connecting element between the taps 6GK1905-0AC00 SpliTConnect M12 Terminator (Ex) Terminator resistor for potentially explosive 6GK1905-0AD00 areas SpliTConnect M12 Terminator Terminator resistor for non-explosion hazardous areas 6GK1905-0AE00 SpliTConnect M12 Jack Connecting element for M12 connection 6GK1905-0AF00 Bus terminating element The SpliTConnect tap can also be extended as a bus terminating element. Wiring with the (FastConnect) fast installation cable Wire the PROFIBUS PA segments with the fast installation cable (FastConnect cable): Accessories Description Order number FC PROFIBUS PA (blue) Fast installation cable 6XV1830-5EH10 FC PROFIBUS PA (black) 6XV1830-5FH10 DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 247 Appendix A.3 Basics about PROFIBUS PA Stripping Strip the FastConnect cables with the FastConnect stripping tool. You can remove the outer covering and the braided shield with accurately to the millimeter in a single step with the FastConnect stripping tool Accessories Description Order number FastConnect Stripping Tool Stripping tool 6GK1905-6AA00 Blade Cassettes Spare blade cassettes 6GK1905-6AB00 Additional information For additional information please refer to the ST PI Catalog. A.3 Basics about PROFIBUS PA PROFIBUS PA PROFIBUS PA is the PROFIBUS for Process-Automation (PA) and is based on IEC 617841:2002 Ed1 CP 3/2 for transmission technology and protocol and on the PA profile. PROFIBUS PA = PROFIBUS DP communication protocol + synchronous transmission technology + Power supply to the PA field devices Connectable field devices You can connect any field device to the bus coupler DP/PA link that is suitable for PROFIBUS PA. Measuring transducers, valves, actuators etc. networked via a serial bus system for use in the chemicals industry and process engineering with field device feed via the data cable also for applications in the potentially explosive area (ignition protection type Ex [ia]) DP/PA coupler, active field distributors, DP/PA Link and Y Link 248 Operating Instructions, 07/2011, A5E00193841-17 Appendix A.3 Basics about PROFIBUS PA A.3.1 Intrinsic safety Intrinsic safety The basis for the intrinsic safety type of ignition protection consists in the necessity for a specific amount of ignition energy for ignition to take place in a potentially explosive atmosphere. In an intrinsically safe power circuit this minimum ignition energy is not present, neither in normal operation nor in case of fault. The intrinsic safety of a power circuit is achieved by limiting current and voltage so as to avoid sparks and high temperatures as possible sources of ignition. This limits the intrinsic safety type of ignition protection to relatively low output power circuits. Spark ignition So-called spark ignition is excluded because sparks that can normally occur owing to short circuit or ground fault during operation when a power circuit is opened or closed are excluded because current and voltage are limited as well as owing to the avoidance of major inductivities. Heat ignition In normal operation and in case of failure heat ignition is not possible because excessive heating of the equipment and leads in the intrinsically safe power circuit is excluded. Additional information For additional information on the topics intrinsic safety and explosion protection please refer to: Automation Systems S7-300, ET 200M Ex I/O Modules manual (http://support.automation.siemens.com/WW/view/en/1096709) Investigation of intrinsic safety for field bus systems; PTB Report W-53, Braunschweig, March 1993 PROFIBUS PA Commissioning Guide, Notes on using the IEC 61158-2 technology for PROFIBUS, (German art. no. 2.091 , English art. no. 2.092) PROFIBUS-Nutzerorganisation e. V. (http://www.profibus.com) Haid-und-Neu-Strae 7, D-76131 Karlsruhe DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 249 Appendix A.3 Basics about PROFIBUS PA A.3.2 Field device supply via PROFIBUS PA Operating principle When the DP/PA link bus coupler is used the field devices can be supplied via the data cable from PROFIBUS PA. Installation The aggregate current of all the field devices must not exceed the maximum output power of the DP/PA coupler. The maximum output power therefore limits the number of field devices that can be connected to the PROFIBUS PA. 352),%863$ ,PD[ , , , ,Q '33$FRXSOHUb([b>L@ )LHOGGHYLFH 7\SHRISURWHFWLRQ([>L@,,& ,PD[P$ '&9 )LHOGGHYLFH 352),%86'3 )LHOGGHYLFH )LHOGGHYLFH Q 3RWHQWLDOO\H[SORVLYHDWPRVSKHUH 352),%863$ ,PD[ , , , ,P '33$FRXSOHU ,PD[$ )LHOGGHYLFH '&9 )LHOGGHYLFH )LHOGGHYLFH )LHOGGHYLFH Q 352),%86'3 Figure A-5 Remote supply to field devices Extension You must use a further DP/PA coupler if you exceed the maximum output current of the DP/PA coupler. See also Configuration of PROFIBUS PA with the DP/PA link bus coupler (Page 251) DP/PA coupler, active field distributors, DP/PA Link and Y Link 250 Operating Instructions, 07/2011, A5E00193841-17 Appendix A.3 Basics about PROFIBUS PA A.3.3 Configuration of PROFIBUS PA with the DP/PA link bus coupler Configuration The figure below describes the configuration of a PROFIBUS PA system with one DP master Configuration with DP/PA link Configuration with DP/PA couplers '3PDVWHU '3PDVWHU 0D['33$ FRXSOHUVSHU,0 0D[3$ILHOG GHYLFHVSHU'33$OLQN 0D[3$ILHOGGHYLFHV SHU'33$FRXSOHU Rules The following rules apply when configuring PROFIBUS PA: a maximum of 31 PA field buses may be present in a physical PROFIBUS PA segment. Onlyone supply device (= DP/PA couplers) can be connected in a given physical PROFIBUS PA segment. a maximum of 64 PA field devices may be attached in a DP/PA link. The maximum number of connectable PA field devices per physical PROFIBUS PA segment or per DP/PA coupler is limited by the maximum output current of the DP/PA coupler and the I/O data to be transmitted. See also Technical specifications of DP/PA coupler Ex [i] (6ES7157-0AD82-0XA0) (Page 234) DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 251 Appendix A.3 Basics about PROFIBUS PA A.3.4 Line and star-type topology Topology The topology of PROFIBUS PA may be in linear or stellar form. 6WDU 6SXUOLQH 0DLQOLQH %XVWHUPLQDWLQJHOHPHQW 352),%863$ 7MXQFWLRQ /LQH 'LVWULEXWLRQ 6WXEOLQH '33$FRXSOHU ZLWK LQWHJUDWHGEXV WHUPLQDWLQJHOHPHQW '&9 Figure A-6 352),%86'3 Line and star-type topology Network extension The maximum length of the main line and the spur lines of a standard PROFIBUS PA cable (cable type A according to PNO) if the maximum current is drawn from DP/PA couplers is: 560 m for DP/PA couplers 920 m for DP/PA Ex [i] couplers Note If the aggregate power consumption is low and the PA field devices have a distributed arrangement, longer lines may be used. Bus terminator for PROFIBUS PA To ensure perfect operation the end of a PROFIBUS PA cable must definitely be equipped with a bus terminator. An RC element connected in series must be used for the bus terminator (R = 100 2 %; C = 1 F 20 %). DP/PA coupler, active field distributors, DP/PA Link and Y Link 252 Operating Instructions, 07/2011, A5E00193841-17 Appendix A.3 Basics about PROFIBUS PA Spur lines The maximum permissible length of a spur line can be found in the following table. Please pay attention to the maximum length of the aggregate line. Table A- 5 Spur line length for the DP/PA couplers Number of spur lines maximum length of a spur line DP/PA coupler DP/PA coupler Ex [i] 1 to 12 max. 120 m max. 60 m 13 to 14 max. 90 m max. 60 m 15 to 18 max. 60 m max. 60 m 19 to 24 max. 30 m max. 30 m See also Accessories for PROFIBUS DP (Page 246) Accessories for PROFIBUS PA (Page 247) DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 253 Appendix A.3 Basics about PROFIBUS PA DP/PA coupler, active field distributors, DP/PA Link and Y Link 254 Operating Instructions, 07/2011, A5E00193841-17 Glossary Address The address of a node is used for localising it in the network. It has to be unique in the entire network. Aggregate current Total current of all PA field devices Automation system An automation system is a programmable control system, consisting of at least one CPU, various input and output modules as well as operating and monitoring devices. Bus A common transfer route to which all nodes are connected; it has two defined ends. Bus connector Physical connection between bus node and bus line. Coupler The DP/PA coupler connects a PROFIBUS PA segment to a PROFIBUS DP segment. PROFIBUS PA and PROFIBUS DP are coupled to one another in terms of data but are separate in terms of the transmission physics. Diagnostic interrupt Diagnostics-capable components report system errors they have detected to the central CPU by means of diagnostic interrupts. In SIMATIC S7: When an error is detected or disappears (e.g. wire break), provided the interrupt is enabled, the module initiates a diagnostic interrupt. The CPU interrupts the processing of the user program and lower priority priority classes and processes the diagnostic interrupt block (OB 82). In SIMATIC S5: The diagnostic interrupt is shown within the device-related diagnostics You can identify errors, such as wire break, by cyclically scanning the diagnostic bits. DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 255 Glossary Diagnostics Diagnostics is the detection, localisation, classification, display and further evaluation of errors, faults and messages. Diagnostics provides monitoring functions that run automatically while the plant is in operation. This increases the availability of plants by reducing commissioning times and downtimes. DP master A master that behaves in conformity with IEC 61784-1:2002 Ed1 CP 3/1 is termed a DP master. DP slave A slave that is operated on the PROFIBUS bus with the PROFIBUS DP protocol and that behaves in conformity with IEC 61784-1:2002 Ed1 CP 3/1 is termed a DP slave. DP standard is the bus protocol of the distributed I/O system in compliance with IEC 617841:2002 Ed1 CP 3/1 DPV0 Cyclical data exchange between the central control system and slaves Configuration using GSD files Diagnostics DPV1 Extension of DPV0: Acyclical data exchange between the central control system and slaves Integration in engineering systems via EDD or FDT / DTM Transferable PLC software function blocks (IEC 61131-3) Fail-safe communication (PROFIsafe) Interrupts Electromagnetic compatibility Electromagnetic compatibility is the capacity of electrical equipment to function faultlessly in a specified environment without affecting the environment in an inadmissible manner. DP/PA coupler, active field distributors, DP/PA Link and Y Link 256 Operating Instructions, 07/2011, A5E00193841-17 Glossary Equipment, associated A piece of electrical equipment that contains both intrinsically safe and non-intrinsically safe power circuits and is configured so that the non-intrinsiclly safe power circuits cannot impede the intrinsicaly safe ones. Equipment, electrical Components, power circuits or parts of power circuits that are normally to be found in their entirety in a single enclosure. Equipment, intrinsically safe, electrical A piece of electrical equipment in which all power circuits are intrinsically safe. Equipotential bonding Electrical connection (equipotential bonding conductor) that brings the bodies of electrical equipment and external conductive bodies to an equal or almost equal potential level to prevent disturbing or dangerous voltages between these bodies. Field bus The field bus is a serial bus system for the distributed integration of field devices in an automation system Floating Having no conductive connection to ground Ground The conductive earth whose electrical potential can be set equal to zero at any point. Ground refers to the entirety of all interconnected inactive parts of a piece of equipment that cannot possess a dangerous contact voltage, even in the event of a malfunction. Ground The conductive earth whose electrical potential can be set equal to zero at any point. Ground refers to the entirety of all interconnected inactive parts of a piece of equipment that cannot possess a dangerous contact voltage, even in the event of a malfunction. Ground terminal PE Name of the connector on electrical equipment used in hazardous areas and to which the equipotential bonding system is connected. DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 257 Glossary Grounding Grounding means connecting an electrically conductive part to a grounding system by means of the ground electrode. GSD file All slave-specific properties are stored in a Device Data Base File (DDBF file). The format of the DDBF file is to be found in the PROFIBUS guideline: Specification for PROFIBUS Device Description and Device Integration Vol.1: GSD V4.1, 07/2001 of the PROFIBUSNutzerorganisation (PNO). H system High availability system consisting of at least two central modules or two separate devices, for example PCs (master / reserve). The user program is processed identically in the master and in ther reserve devices. Hazardous area (Ex area) Area in which a potentially explosive gas atmosphere is present or expected in such quantities that special measures with regard to the design, installation and use of equipment are required. HW Config Integral part of STEP 7 for configuring hardware. Identification and maintenance data Identification data (I data) is information on the module, some of which are printed onto the module enclosure. I data are for reading only. Maintenance data (M data) is plant-dependent information such as installation location, installation date etc. M data are created during configuration and written onto the module. Identification and maintenance data (I&M) is information stored in a module to support you in Checking the plant configuration Locating hardware modifications in a plant Correcting errors in a plant Modules can be uniquely identified online by means of the I&M data. Master When a master is in possession of the token, it can send data to other nodes and request data from other nodes (= active node). DP master are, for example, the CPU 315-2 DP or the IM 308-C. DP/PA coupler, active field distributors, DP/PA Link and Y Link 258 Operating Instructions, 07/2011, A5E00193841-17 Glossary Parameter assignment Parameter assignment is the transfer of slave parameters from master to the slave. PNO PROFIBUS user organization Power supply unit A power supply unit supplies power to the field devices and the distributed process I/Os connected to them. PROFIBUS PROcess FIeld BUS, process and field bus standard as defined in the field bus standard (IEC 61784-1:2002 Ed1 CPF 3 PROFIBUS and PROFINET). It specifies functional, electrical, and mechanical properties for a bit-serial field bus system. PROFIBUS is available with the protocols: DP (=distributed I/O) and FMS (= Field bus Message Specification) PROFIBUS address For the purpose of unique identification on PROFIBUSDP, each node must be given a PROFIBUS address. PC / PD or the ET 200 Handheld have the PROFIBUS address "0". DP master and DP slaves have a PROFIBUS address from the 1 to 125 range. PROFIBUS DP PROFIBUS bus system with the DP protocol. DP stands for the German equivalent of distributed I/O. PROFIBUS PA PA stands for Process Automation and increases the range of usage of the PROFIBUS DP family to include the field of process engineering. Process engineering refers to both the intrinsically safe sectors of the chemicals industry and to the non-intrinsically safe sectors, such as nuclear power plant automation, the food industry and waste water technology. Redundant systems Redundant systems are characterized by the multiple (redundant) presence of important automation components. If a redundant component fails there the processing of the program is not interrupted. DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 259 Glossary Reference potential The potential to which voltages of participating circuits are referenced when they are viewed and/or measured. Segment A segent or bus segment is a self-contained section of a serial bus system. SELV Safety extra low voltage (SELV) is voltage < AC 30 V / DC 60 V that generates via a safety transformer, accumulator etc. SIMATIC PDM SIMATIC PDM (Process Device Manager) is a universal tool that is not manufacturerspecific and is used for configuring, parameterizing, commissioning and diagnosing intelligent process devices. SIMATIC PDM makes it possible to configure a large variety of process devices with a single software on a standardized user interface. Supply unit A supply unit supplies power to the line. Terminating resistor A terminating resistor is a resistor that terminates the data transmission line to avoid reflections. Time synchronization Time synchronization ensures that all clocks run synchronously. A master clock distributes the time in a configurable cycle to all other components in the automation system that have a clock. The components use this distributed time to set their own clocks. TN-S system In a TN-S system, the neutral conductor (N) and protective conductor (PE) are routed separately from each other. The neutral conductor is connected to the grounded protective conductor at a central point, and only there. The conductor can be grounded any number of times. Token In network technology a token refers to a bit pattern that is passed from one bus node to another, enabling that node to access the bus. DP/PA coupler, active field distributors, DP/PA Link and Y Link 260 Operating Instructions, 07/2011, A5E00193841-17 Glossary Transmission speed The transmission speed specifies the number of bits transmitted per second. Type of protection The special measures applied to electrical equipment to prevent the ignition of a potentially explosive ambient atmosphere. Update Following (compatible) functional extensions or improvements to performance you should update the IM 153-2 interface module to the respective most recent firmware version. DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 261 Glossary DP/PA coupler, active field distributors, DP/PA Link and Y Link 262 Operating Instructions, 07/2011, A5E00193841-17 Index A Accessories for PROFIBUS DP, 246 for PROFIBUS PA, 247 Active field distributor (AFD) replace, 147 Technical specifications, 237 Active Field Distributor AFD, 33 Active field splitter (AFS) replace, 147 Technical specifications, 236 AFD Functions, 33 Grounding, 33 Properties, 33 AFDiS, 34 Grounding, 53 Mounting, 44 replace, 56 Safety information, 43 supplement, 56 AFS, 32 Functions, 32 Grounding, 32 Properties, 32 Aggregate cable, 252 Aggregate current of the connected PA field devices, 250 Ambient conditions mechanical, 227 Operation, 227 Transport and storage, 226 Appendix Change to redundancy, 146 expand, 146 Applications DP/PA coupler FDC 157-0, 57 Settings, 113 Arc-over, 40 ATEX mark, 216, 219 Availability DP/PA coupler FDC 157-0, 21 B Bus module BM FDC/FDC (redundant), 37 Bus terminal resistors Y coupler, 104 Bus terminating resistor DP/PA coupler, 109 C CE mark, 216, 219, 221, 223 Center feed, 63, 101, 120 Changes compared to previous manual, 4 compatibility Bus module BM FDC/FDC (redundant), 37 DP/PA coupler FDC 157-0, 37 Components For DP/PA coupler in redundancy mode, 76 for DP/PA coupler in stand-alone mode, 75 for the DP/PA link in non-redundant mode, 79 for the DP/PA link in redundant mode, 81 for Y link, 83 Order numbers, 245 Conditions of use, 227 Configuration frame, 126, 135 Configuring Configuration for DP/PA link, 127 DP slaves, 133 DP slaves for Y link, 136 DP/PA coupler, 115 DP/PA link, 122, 126 GSD file, 114 PROFIBUS PA system, 124 Y link, 130, 135 Connecting AFDiS Examples, 49 Rules, 49 Safety information, 46 Coupler redundancy, 62 Power supply, 62 Current value Limits, 169 Current values read, 165 DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 263 Index D Default diagnosis, 185 Degree of protection, 230 Delivery condition DP/PA coupler FDC 157-0, 37 Device identifier, 187 Device-related diagnostics Module status, 189 Status message, 191 Device-specific parameters DP/PA coupler, 118 Diagnostic interrupt, 198 Diagnostics function Settings, 113 Disposal, 5 Distributed I/O, 14 DP slaves Configuring, 133 configuring for Y link, 136 DP/PA coupler commissioning for stand-alone operation, 111 Configuring with STEP 7, 115 Device-specific parameters, 118 in the DP/PA link, 64 Installation with coupler redundancy, 62 Installation with ring redundancy, 59 Mounting for non-redundant mode, 75 Mounting for redundancy mode, 76 Properties, 23 removing, 76 replace, 146 wiring for stand-alone operation, 93 DP/PA coupler Ex [i] Technical specifications, 234 DP/PA coupler FDC 157-0 Applications, 21 Availability, 21 Commissioning, 112 Configuration frame, 172 Error types, 214 Input data, 172 Properties, 22 Technical specifications, 232 DP/PA coupler FDC 157-0 overvoltage protection, 77 DP/PA link configuring with COM PROFIBUS, 125 Mounting for non-redundant mode, 79 Mounting for redundancy mode, 81 Startup characteristics in the non-redundant mode, 141 wiring for non-redundant mode, 102 wiring for redundant mode, 103 DPV0 / DPV1 DP/PA link in redundant mode, 122 DP/PA link in the S7 standard mode, 122 Y link, 131 E Electrical isolation, 87 Electrical properties, 87 Electromagnetic compatibility, 224 Equipment, 40 open, 73 Error types DP/PA coupler FDC 157-0, 214 Explosion hazard, 39, 46 Explosion-proof equipment, 40 F Failure DP/PA coupler FDC 157-0, 77 PA field devices, 77 Failure of components of the redundant DP master system, 140 Field device supply, 250 Field distributor AFDiS cleaning, 55 Functions, 35 Grounding, 53 Maintaining, 54 Mounting, 44 Properties, 35 Repeater function, 36 replace, 56 Special properties, 35 supplement, 56 Technical specifications, 238 Field distributors AFD/AFS Grounding, 90 Mounting on substrate, 78 Flying Redundancy, 154 Functions DP/PA coupler FDC 157-0, 57 G Grounding, 87 GSD file DP/PA coupler, 114 DP/PA coupler, active field distributors, DP/PA Link and Y Link 264 Operating Instructions, 07/2011, A5E00193841-17 Index H H status, 194 Heat ignition, 249 I Identification data, 163 Identifier-related diagnostics, 187 IECEx AFDiS, 224 IEEE status byte, 168 IM 153-2 Technical specifications, 231 Increased-safety enclosure e, 40 Input data, 166 DP/PA coupler FDC 157-0, 172 Installation with coupler redundancy, 62 with ring redundancy, 60 Insulation test, 230 Interferences Pulse-shaped, 225 Sinusoidal, 225 Internet Service & Support, 6 Interrupt routing, 198 Interrupts, 196 Intrinsic safety, 249 Intrinsic safety i, 40 IP30 cover, 47 L Limits PA current, 169 PA voltage, 169 Literature, 249 Local LifeList, 164 Installation, 211 Read, 211 M Manufacturer ID, 207 Master->Reserve switchover, 140 Maximum configuration, 251 Mixed operation, 16 Module replacement, 145 Module status, 189 Mounting position, 73 Mounting system, 73 N non-redundancy mode, 27 O Order numbers, 245 Overvoltage protection, 77 P PA bus terminator switch, 101 PA field devices Configuration for DP/PA link, 127 Parameter assignment frame, 126, 135 Power supply, 105 Connecting, 105 for the DP/PA link in non-redundant mode, 102 for the DP/PA link in redundant mode, 103 for Y link, 104 Process input image, 172 PROFIBUS address set, 120 PROFIBUS address of the DP master, 187 PROFIBUS address of the IM 153-2 in the PA master system, 124, 127 in the underlying DP master system, 133, 136 set, 85 PROFIBUS DP Connecting, 106 PROFIBUS PA Bus terminal switch, 109 Commissioning guide, 107, 249 Connecting, 107 Extension, 250 Field device supply, 250 Properties AFD, 33 AFS, 32 DP/PA coupler FDC 157-0, 22 Field distributor AFDiS, 35 Protection class, 230 Proxy diagnostic interrupt, 198 R Radio Interference Emission, 226 DP/PA coupler, active field distributors, DP/PA Link and Y Link Operating Instructions, 07/2011, A5E00193841-17 265 Index Rated voltage, 230 Reading data records, 156 Reconfiguring the hardware, 162 Recycling, 5 Redundancy Flying, 154 System, 154 Redundancy mode Coupler redundancy, 62 Ring redundancy, 59 set, 120 Reference potential grounded, 90 ungrounded, 92 Remove / insert DP/PA coupler, 77 DP/PA coupler FDC 157-0, 77 IM 153-2, Interrupt, Y coupler, Repeater function AFDiS, 36 Ring redundancy, 59, 62 Behavior in the event of errors, 61 Power supply, 59 Rules Connecting AFDiS, 49 T Technical support, 5 Terminating resistor, 101, 120 Test voltages, 230 Topology, 252 Training center, 5 Type of protection, 249 Types of protection, 40 U User data frame, 166 V Vibrations, 227 Voltage measurement, 166 Voltage value Limits, 169 Voltage values read, 165 W Wirebreak, S Y Safety information AFDiS, 43 Connecting AFDiS, 46 Service & Support, 6 Settings Diagnostics function, 113 Redundancy mode, 113 Short-circuit, 59 Slave diagnostics, 183 Spark ignition, 249 Sparks, 40 Startup characteristics DP/PA link in the non-redundant mode, 141 Start-up delay, 139, 192 Station status, 186 Status message, 191 System modification during operation., 161, 162 System Redundancy, 154 Y coupler Technical specifications, 235 Y link Configuring, 130 configuring with COM PROFIBUS, 134 Mounting, 83 wiring, 104 Z Zones, 39 DP/PA coupler, active field distributors, DP/PA Link and Y Link 266 Operating Instructions, 07/2011, A5E00193841-17