Monitoring two levels, emptying function
(level : 2, function Dwn LS (Low Sensitivity : 250
Ω
to 5 k
Ω
), Dwn St (Standard Sensitivity : 5 k
Ω
to 100 k
Ω
),
Dwn HS (High Sensitivity : 50 k
Ω
to 1 M
Ω
).
The output relay remains open as long as the level of liquid has not reached the maximum probe. Once the maximum level is reached the contact closes and the tank can then be emptied (valve
opened, pump started, etc). When the level drops below the minimum level the contact opens and interrupts the emptying process.
Note : when monitoring two levels the time delay preventing the wave effect is not in operation.
Note
When the power returns after a power break, the output relay energises immediately if the level of liquid is above the threshold.
Monitoring two levels, filling function
(level : 2, function Up LS (Low Sensitivity : 250
Ω
to 5 k
Ω
) or Up St (Standard Sensitivity : 5 k
Ω
to 100 k
Ω
)
or Up HS (High Sensitivity : 50 k
Ω
to 1 M
Ω
).
The output relay remains on as long as the level of liquid has not reached the maximum probe. As soon as the maximum level is reached the contact opens and pumping stops. When the level drops
below the minimum level the contact closes again and pumping restarts to bring the level of liquid back up.
Note : When monitoring the two levels the time delay preventing the wave effect is not in operation.
Note
When the power returns after a power break, the output relay energises immediately if the level of liquid is below the threshold.
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected