Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Eaton’s QUICKLAG Industrial Circuit Breakers 1 Plug-In, Bolt-On, Cable-In/Cable-Out, continued
Notes
1QUICKLAG circuit breakers are suitable for application in relative humidity 0–95% noncondensing.
2Two-pole DC interrupting ratings based on two poles connected in series. Not UL listed.
362.5 Vac interrupting rating is 3800 AIC 10–50A and 2500 AIC 55–100A continuous.
Circuit Breaker Type Codes: P Plug-In; B Bolt-On; C Cable-In/Cable-Out; GF Ground Fault, 5 mA; GFEP Ground Fault, 30 mA.
For Types GHBS, GBHS and BABRP solenoid-operated, remote-controlled circuit breakers, see Pages V4-T1-31 to V4-T1-36.
For Type WMZ circuit breakers, see Pages V4-T1-67 to V4-T1-81.
For Types WMZS and SPHM supplementary protectors, see Pages V4-T1-103 to V4-T1-118.
Circuit
Breaker
Type
Circuit Breaker
Type Code
Continuous
Ampere
Rating
at 40°C
Number
of
Poles Vac Vdc
Federal
Spec.
W-C-375b
Interrupting Ratings rms Symmetrical Amperes
Page
Number
Vac Ratings Vdc Ratings 2
120 120/240 240 24–48 62.5 80
QPHGF P, GF 15–30 1 120 — 10a, 11a, 12a 22,000 — — — — — V4-T1-9
QPHGF P, GF 15–50 2 120/240 — 10a, 11a, 12a — 22,000 — — — — V4-T1-9
QPGFEP P, GFEP 15–40 1 120 — — 10,000 — — — — — V4-T1-9
QPGFEP P, GFEP 15–50 2 120/240 — — — 10,000 — — — — V4-T1-9
QPHGFEP P, GFEP 15–30 1 120 — — 22,000 — — — — — V4-T1-9
BABRSP B 15–30 1 120 — — 10,000 — — — — — V4-T1-12
BABRSP B 15–30 2 120/240 — — — 10,000 — — — — V4-T1-12
BRRP P 15–30 1 120 — — 10,000 — — — — — V4-T1-32
BRRP P 15–30 2 120/240 — — — 10,000 — — — — V4-T1-32
CLRP P 15–30 1 120 — — 10,000 — — — — — V4-T1-32
CLRP P 15–30 2 120/240 — — — 10,000 — — — — V4-T1-32
BAB B 10–70 1 120/240 24, 48, 62.5 10a, 11a, 12a — 10,000 — 5000 3—V4-T1-12
BAB B 10–125 2 120/240 24, 48, 80 10a, 12a — 10,000 — 5000 5000 5000 V4-T1-12
BAB B 10–100 2, 3 240 — 10b, 11b, 12b — — 10,000 — — — V4-T1-12
BABRP B 15–30 1 120 — — 10,000 — — — — — V4-T1-32
BABRP B 15–30 2 120/240 — — — 10,000 — — — — V4-T1-32
QBAF B, AF 15–20 1, 2 120/240 — — — 10,000 — — — — V4-T1-15
QBCAF B, AF, GF 15–20 1, 2 120/240 — — — 10,000 — — — — V4-T1-15
QBHW B 15–70 1 120/240 24, 48, 62.5 14a — 22,000 — 5000 3—V4-T1-12
QBHW B 15–125 2 120/240 24, 48, 80 14a — 22,000 — 5000 5000 5000 V4-T1-12
QBHW B 15–100 2, 3 240 — 14b — — 22,000 — — — V4-T1-12
HBAX B 15–70 1 120/240 24, 48, 62.5 — — 42,000 — 5000 3—V4-T1-13
HBAX B 15–100 2 120/240 24, 48, 80 — — 42,000 — 5000 5000 5000 V4-T1-13
HBAX B 15–100 3 240 — — — 42,000 — — — V4-T1-13
HBAW B 15–30 1 120/240 24, 48, 62.5 15a — 65,000 — 5000 3—V4-T1-13
HBAW B 15–30 2 120/240 24, 48, 80 15a — 65,000 — 5000 5000 5000 V4-T1-13
HBAW B 15–20 3 240 — 15b — — 65,000 — — — V4-T1-13
QBGF B, GF 15–40 1 120 — 10a, 11a, 12a 10,000 — — — — — V4-T1-18
QBGF B, GF 15–50 2 120/240 — 10a, 11a, 12a — 10,000 — — — — V4-T1-18
QBHGF B, GF 15–30 1 120 — 10a, 11a, 12a 22,000 — — — — — V4-T1-18
QBHGF B, GF 15–30 1 120/240 — 10a, 11a, 12a — 22,000 — — — — V4-T1-18
QBGFEP B, GFEP 15–40 1 120 — — 10,000 — — — — — V4-T1-18
QBGFEP B, GFEP 15–50 2 120/240 — — — 10,000 — — — — V4-T1-18
QBHGFEP B, GFEP 15–30 1 120 — — 22,000 — — — — — V4-T1-18
QBHGFEP B, GFEP 15–30 2 120/240 — — 22,000 22,000 — — — — V4-T1-18
QC C 10–70 1 120/240 24, 48, 62.5 10a, 11a, 12a — 10,000 — 5000 3—V4-T1-41
QC C 10–100 2 120/240 24, 48, 80 10a, 12a — 10,000 — 5000 5000 5000 V4-T1-41
QC C 10–100 2, 3, 4 240 — 10b, 11b, 12b — — 10,000 — — — V4-T1-41
QCD C 10–60 1, 2 120/240 24, 48, 62.5 — 10,000 10,000 — 3000 3000 — V4-T1-23
QCD C 10–100 2, 3 240 24, 48, 62.5 — — 10,000 — 3000 3000 — V4-T1-23
QCF C 10–60 1, 2 120/240 24, 48, 62.5 — 10,000 10,000 — 3000 3000 — V4-T1-42