Miniature Circuit Breakers and
Supplementary Protectors
Miniature Circuit Breakers and
Supplementary Protectors
1.1 Industrial Circuit Breakers
QUICKLAG®. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-2
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW . . . . . . . . . . . V4-T1-5
QUICKLAG Plug-On Ground Fault and Equipment Protectors,
Types QPGF, QPHGF, QPGFEP, QPHGFEP . . . . . . . . . . . . . . . . . . . . V4-T1-8
Bolt-On Types BAB, QBHW, HBAX, HBAW. . . . . . . . . . . . . . . . . . . . . V4-T1-11
Bolt-On Arc Fault Circuit Interrupter Types QBAF, QBCAF . . . . . . . . . V4-T1-14
Bolt-On Ground Fault and Equipment Protectors,
Types QBGF, QBHGF, QBGFEP, QBHGFEP . . . . . . . . . . . . . . . . . . . . V4-T1-17
Cable-In/Cable-Out Types QC, QCD, QCHW, QHCX, QHCW . . . . . . . V4-T1-20
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-24
Cable-In/Cable-Out Ground Fault and Equipment Protectors,
Types QCGF, QCHGF, QCGFEP, QCHGFEP . . . . . . . . . . . . . . . . . . . . V4-T1-28
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP . . . . . . . . . . . . . . . . . . . . . V4-T1-31
Solenoid Operator—Remote-Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers . . . . . . . . . . . . . . . . . . . V4-T1-34
International Rated Types HQP, BA, QC, GFMB, GFXBC. . . . . . . . . . . V4-T1-37
Special Application Breakers, Types HQP, BA, QC . . . . . . . . . . . . . . . V4-T1-40
1.2 UL 489 DIN Rail Miniature Circuit Breakers
FAZ-NA Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-49
WMZ Circuit Breaker. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-67
1.3 UL 1077 DIN Rail Supplementary Protectors
FAZ Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-82
WMZS Circuit Breaker. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-103
Learn
Online
V4-T1-2 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Miniature Circuit Breakers and Supplementary Protectors
Contents
Description
Quick Reference
QUICKLAG
Quick Reference
Eaton’s QUICKLAG Industrial Circuit Breakers 1 Plug-In, Bolt-On, Cable-In/Cable-Out
Notes
1QUICKLAG circuit breakers are suitable for application in relative humidity 0–95% noncondensing.
2Two-pole DC interrupting ratings based on two poles connected in series. Not UL® listed.
362.5 Vac interrupting rating is 3800 AIC 10–50A and 2500 AIC 55–100A continuous.
Circuit Breaker Type Codes: P Plug-In; B Bolt-On; C Cable-In/Cable-Out; GF Ground Fault, 5 mA; GFEP Ground Fault, 30 mA.
For Types GHBS, GBHS and BABRP solenoid-operated, remote-controlled circuit breakers, see Pages V4-T1-31 to V4-T1-36.
For Type WMZ circuit breakers, see Pages V4-T1-67 to V4-T1-81.
For Types WMZS and SPHM supplementary protectors, see Pages V4-T1-103 to V4-T1-118.
Circuit
Breaker
Type
Circuit Breaker
Type Code
Continuous
Ampere
Rating
at 40°C
Number
of
Poles Vac Vdc
Federal
Spec.
W-C-375b
Interrupting Ratings rms Symmetrical Amperes
Page
Number
Vac Ratings Vdc Ratings 2
120 120/240 240 24–48 62.5 80
HQP P 10–70 1 120/240 24, 48, 62.5 10a, 11a, 12a 10,000 5000 3 V4-T1-6
HQP P 10–125 2 120/240 24, 48, 80 10a, 12a 10,000 5000 5000 5000 V4-T1-6
HQP P 10–100 2, 3 240 10b, 11b, 12b 10,000 V4-T1-6
QPHW P 15–70 1 120/240 24, 48, 62.5 14a 22,000 5000 3V4-T1-6
QPHW P 15–125 2 120/240 24, 48, 80 14a 22,000 5000 5000 5000 V4-T1-6
QPHW P 15–100 2, 3 240 14b 22,000 V4-T1-6
QHPX P 15–70 1 120/240 24, 48, 62.5 42,000 5000 3V4-T1-7
QHPX P 15–100 2 120/240 24, 48, 80 42,000 5000 5000 5000 V4-T1-7
QHPX P 15–100 3 240 42,000 V4-T1-7
QHPW P 15–30 1 120/240 24, 48, 62.5 15a 65,000 5000 3V4-T1-7
QHPW P 15–30 2 120/240 24, 48, 80 15a 65,000 5000 5000 5000 V4-T1-7
QHPW P 15–20 3 240 15b 65,000 V4-T1-7
QPGF P, GF 15–40 1 120 10a, 11a, 12a 10,000 V4-T1-9
QPGF P, GF 15–50 2 120/240 10a, 11a, 12a 10,000 V4-T1-9
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Eaton’s QUICKLAG Industrial Circuit Breakers 1 Plug-In, Bolt-On, Cable-In/Cable-Out, continued
Notes
1QUICKLAG circuit breakers are suitable for application in relative humidity 0–95% noncondensing.
2Two-pole DC interrupting ratings based on two poles connected in series. Not UL listed.
362.5 Vac interrupting rating is 3800 AIC 10–50A and 2500 AIC 55–100A continuous.
Circuit Breaker Type Codes: P Plug-In; B Bolt-On; C Cable-In/Cable-Out; GF Ground Fault, 5 mA; GFEP Ground Fault, 30 mA.
For Types GHBS, GBHS and BABRP solenoid-operated, remote-controlled circuit breakers, see Pages V4-T1-31 to V4-T1-36.
For Type WMZ circuit breakers, see Pages V4-T1-67 to V4-T1-81.
For Types WMZS and SPHM supplementary protectors, see Pages V4-T1-103 to V4-T1-118.
Circuit
Breaker
Type
Circuit Breaker
Type Code
Continuous
Ampere
Rating
at 40°C
Number
of
Poles Vac Vdc
Federal
Spec.
W-C-375b
Interrupting Ratings rms Symmetrical Amperes
Page
Number
Vac Ratings Vdc Ratings 2
120 120/240 240 24–48 62.5 80
QPHGF P, GF 15–30 1 120 10a, 11a, 12a 22,000 V4-T1-9
QPHGF P, GF 15–50 2 120/240 10a, 11a, 12a 22,000 V4-T1-9
QPGFEP P, GFEP 15–40 1 120 10,000 V4-T1-9
QPGFEP P, GFEP 15–50 2 120/240 10,000 V4-T1-9
QPHGFEP P, GFEP 15–30 1 120 22,000 V4-T1-9
BABRSP B 15–30 1 120 10,000 V4-T1-12
BABRSP B 15–30 2 120/240 10,000 V4-T1-12
BRRP P 15–30 1 120 10,000 V4-T1-32
BRRP P 15–30 2 120/240 10,000 V4-T1-32
CLRP P 15–30 1 120 10,000 V4-T1-32
CLRP P 15–30 2 120/240 10,000 V4-T1-32
BAB B 10–70 1 120/240 24, 48, 62.5 10a, 11a, 12a 10,000 5000 3V4-T1-12
BAB B 10–125 2 120/240 24, 48, 80 10a, 12a 10,000 5000 5000 5000 V4-T1-12
BAB B 10–100 2, 3 240 10b, 11b, 12b 10,000 V4-T1-12
BABRP B 15–30 1 120 10,000 V4-T1-32
BABRP B 15–30 2 120/240 10,000 V4-T1-32
QBAF B, AF 15–20 1, 2 120/240 10,000 V4-T1-15
QBCAF B, AF, GF 15–20 1, 2 120/240 10,000 V4-T1-15
QBHW B 15–70 1 120/240 24, 48, 62.5 14a 22,000 5000 3V4-T1-12
QBHW B 15–125 2 120/240 24, 48, 80 14a 22,000 5000 5000 5000 V4-T1-12
QBHW B 15–100 2, 3 240 14b 22,000 V4-T1-12
HBAX B 15–70 1 120/240 24, 48, 62.5 42,000 5000 3V4-T1-13
HBAX B 15–100 2 120/240 24, 48, 80 42,000 5000 5000 5000 V4-T1-13
HBAX B 15–100 3 240 42,000 V4-T1-13
HBAW B 15–30 1 120/240 24, 48, 62.5 15a 65,000 5000 3V4-T1-13
HBAW B 15–30 2 120/240 24, 48, 80 15a 65,000 5000 5000 5000 V4-T1-13
HBAW B 15–20 3 240 15b 65,000 V4-T1-13
QBGF B, GF 15–40 1 120 10a, 11a, 12a 10,000 V4-T1-18
QBGF B, GF 15–50 2 120/240 10a, 11a, 12a 10,000 V4-T1-18
QBHGF B, GF 15–30 1 120 10a, 11a, 12a 22,000 V4-T1-18
QBHGF B, GF 15–30 1 120/240 10a, 11a, 12a 22,000 V4-T1-18
QBGFEP B, GFEP 15–40 1 120 10,000 V4-T1-18
QBGFEP B, GFEP 15–50 2 120/240 10,000 V4-T1-18
QBHGFEP B, GFEP 15–30 1 120 22,000 V4-T1-18
QBHGFEP B, GFEP 15–30 2 120/240 22,000 22,000 V4-T1-18
QC C 10–70 1 120/240 24, 48, 62.5 10a, 11a, 12a 10,000 5000 3V4-T1-41
QC C 10–100 2 120/240 24, 48, 80 10a, 12a 10,000 5000 5000 5000 V4-T1-41
QC C 10–100 2, 3, 4 240 10b, 11b, 12b 10,000 V4-T1-41
QCD C 10–60 1, 2 120/240 24, 48, 62.5 10,000 10,000 3000 3000 V4-T1-23
QCD C 10–100 2, 3 240 24, 48, 62.5 10,000 3000 3000 V4-T1-23
QCF C 10–60 1, 2 120/240 24, 48, 62.5 10,000 10,000 3000 3000 V4-T1-42
V4-T1-4 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Eaton’s QUICKLAG Industrial Circuit Breakers 1 Plug-In, Bolt-On, Cable-In/Cable-Out, continued
Notes
1QUICKLAG circuit breakers are suitable for application in relative humidity 0–95% noncondensing.
2Two-pole DC interrupting ratings based on two poles connected in series. Not UL listed.
362.5 Vac interrupting rating is 3800 AIC 10–50A and 2500 AIC 55–100A continuous.
Circuit Breaker Type Codes: P Plug-In; B Bolt-On; C Cable-In/Cable-Out; GF Ground Fault, 5 mA; GFEP Ground Fault, 30 mA.
For Types GHBS, GBHS and BABRP solenoid-operated, remote-controlled circuit breakers, see Pages V4-T1-31 to V4-T1-36.
For Type WMZ circuit breakers, see Pages V4-T1-67 to V4-T1-81.
For Types WMZS and SPHM supplementary protectors, see Pages V4-T1-103 to V4-T1-118.
.
Circuit
Breaker
Type
Circuit
Breaker
Type Code
Continuous
Ampere
Rating
at 40°C
Number
of
Poles Vac Vdc
Federal
Spec.
W-C-375b
Interrupting Ratings rms Symmetrical Amperes
Page
Number
Vac Ratings Vdc Ratings 2
120 120/240 240 24–48 62.5 80
QCF C 15–20 1, 2 120/240 24, 48, 62.5 22,000 3000 3000 V4-T1-27
QCF C 15–30 2, 3 240 24, 48, 62.5 10,000 3000 3000 V4-T1-27
QCR C 10–60 1, 2 120/240 24, 48, 62.5 10,000 10,000 3000 3000 V4-T1-27
QCR C 15–20 1, 2 120/240 24, 48, 62.5 22,000 3000 3000 V4-T1-27
QCR C 15–30 2, 3 240 24, 48, 62.5 10,000 3000 3000 V4-T1-27
QCHW C 15–70 1 120/240 24, 48, 62.5 14a 22,000 5000 3V4-T1-22
QCHW C 15–100 2 120/240 24, 48, 80 14a 22,000 5000 5000 5000 V4-T1-22
QCHW C 15–100 2, 3 240 14b 22,000 V4-T1-22
QHCX C 15–70 1 120/240 24, 48, 62.5 42,000 5000 3V4-T1-22
QHCX C 15–100 2 120/240 24, 48, 80 42,000 5000 5000 5000 V4-T1-22
QHCX C 15–100 3 240 42,000 V4-T1-22
QHCW C 15–30 1 120/240 24, 48, 62.5 15a 65,000 5000 3V4-T1-22
QHCW C 15–30 2 120/240 24, 48, 80 15a 65,000 5000 5000 5000 V4-T1-22
QHCW C 15–20 3 240 15b 65,000 V4-T1-22
QCGF C, GF 15–40 1 120 10,000 V4-T1-29
QCGF C, GF 15–50 2 120/240 10,000 V4-T1-29
QCHGF C, GF 15–30 1 120 22,000 V4-T1-29
QCHGF C, GF 15–30 2 120/240 22,000 V4-T1-29
QCGFEP C, GFEP 15–40 1 120 10,000 V4-T1-29
QCGFEP C, GFEP 15–50 2 120/240 10,000 V4-T1-29
QCHGFEP C, GFEP 15–30 1 120 22,000 V4-T1-29
QCHGFEP C, GFEP 15–30 2 120/240 22,000 V4-T1-29
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-5
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
QUICKLAG Type HQP Single-Pole
Contents
Description Page
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-2
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-6
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-7
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGF, QPHGF, QPGFEP, QPHGFEP V4-T1-8
Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . . . V4-T1-11
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-14
Bolt-On Ground Fault and Equipment Protectors,
Types QBGF, QBHGF, QBGFEP, QBHGFEP . . . . . . . . V4-T1-17
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-20
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-24
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGF, QCHGF, QCGFEP, QCHGFEP V4-T1-28
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP . . . . . . . . . V4-T1-31
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers. . . . . . . . V4-T1-34
International Rated Types HQP, BA, QC, GFMB, GFXBC V4-T1-37
Special Application Breakers, Types HQP, BA, QC. . . . V4-T1-40
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW
Product Description
All products 15–100A are
HACR rated
Switching duty rated for
120 Vac fluorescent light
applications
Standards and Certifications
Built and listed to UL 489
All products UL and
CSA® listed
V4-T1-6 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Product Selection
QUICKLAG Type: HQP 10,000A Interrupting Capacity Thermal-Magnetic Breakers
QUICKLAG Type: HQP Non-Automatic Switches
QUICKLAG Type: QPHW 22,000A Interrupting Capacity Thermal-Magnetic Breakers
Notes
1 Switching duty rated for 120 Vac fluorescent light applications.
2 For special low-magnetic breaker, order HQP1015L1 or HQP1020L1.
3 Not UL listed.
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole Two-Pole Three-Pole
120/240 Vac 120/240 Vac 240 Vac 240 Vac
Catalog Number Catalog Number Catalog Number Catalog Number
10 HQP1010 HQP2010 HQP3010H 3
15 HQP1015 12 HQP2015 HQP2015H HQP3015H
20 HQP1020 12 HQP2020 HQP2020H HQP3020H
25 HQP1025 HQP2025 HQP2025H HQP3025H
30 HQP1030 HQP2030 HQP2030H HQP3030H
35 HQP1035 HQP2035 HQP2035H HQP3035H
40 HQP1040 HQP2040 HQP2040H HQP3040H
45 HQP1045 HQP2045 HQP2045H HQP3045H
50 HQP1050 HQP2050 HQP2050H HQP3050H
55 HQP1055 HQP2055 HQP2055H HQP3055H
60 HQP1060 HQP2060 HQP2060H HQP3060H
70 HQP1070 HQP2070 HQP2070H HQP3070H
80 HQP2080 HQP2080H HQP3080H
90 HQP2090 HQP2090H HQP3090H
100 HQP1100 HQP2100 HQP2100H HQP3100H
110 HQP2110
125 HQP2125
150 HQP2150
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole Two-Pole Three-Pole
120/240 Vac 120/240 Vac 240 Vac 240 Vac
Catalog Number Catalog Number Catalog Number Catalog Number
50 HQP1050N HQP2050N HQP3050N
60 HQP1060N HQP2060N HQP3060N
100 HQP1100N HQP2100N HQP3100N
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole Two-Pole Three-Pole
120/240 Vac 120/240 Vac 240 Vac 240 Vac
Catalog Number Catalog Number Catalog Number Catalog Number
15 QPHW1015 1QPHW2015 QPHW2015H QPHW3015H
20 QPHW1020 1QPHW2020 QPHW2020H QPHW3020H
25 QPHW1025 QPHW2025 QPHW2025H QPHW3025H
30 QPHW1030 QPHW2030 QPHW2030H QPHW3030H
35 QPHW1035 QPHW2035 QPHW2035H QPHW3035H
40 QPHW1040 QPHW2040 QPHW2040H QPHW3040H
45 QPHW1045 QPHW2045 QPHW2045H QPHW3045H
50 QPHW1050 QPHW2050 QPHW2050H QPHW3050H
55 QPHW1055 QPHW2055 QPHW2055H QPHW3055H
60 QPHW1060 QPHW2060 QPHW2060H QPHW3060H
70 QPHW1070 QPHW2070 QPHW2070H QPHW3070H
80 QPHW2080 QPHW2080H QPHW3080H
90 QPHW2090 QPHW2090H QPHW3090H
100 QPHW2100 QPHW2100H QPHW3100H
110 QPHW2110
125 QPHW2125
QUICKLAG Type HQP
Single-Pole
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-7
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
QUICKLAG Type: QHPX 42,000A Interrupting Capacity Thermal-Magnetic Breakers
QUICKLAG Type: QHPW 65,000A Interrupting Capacity Thermal-Magnetic Breakers
Dimensions
Approximate Dimensions in Inches (mm)
Shipping Data
Note
1Switching duty rated for 120 Vac fluorescent light applications.
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole Two-Pole Three-Pole
120/240 Vac 120/240 Vac 240 Vac 240 Vac
Catalog Number Catalog Number Catalog Number Catalog Number
15 QHPX1015 1QHPX2015 QHPX3015H
20 QHPX1020 1QHPX2020 QHPX3020H
25 QHPX1025 QHPX2025 QHPX3025H
30 QHPX1030 QHPX2030 QHPX3030H
35 QHPX1035 QHPX2035 QHPX3035H
40 QHPX1040 QHPX2040 QHPX3040H
45 QHPX1045 QHPX2045 QHPX3045H
50 QHPX1050 QHPX2050 QHPX3050H
55 QHPX1055 QHPX2055 QHPX3055H
60 QHPX1060 QHPX2060 QHPX3060H
70 QHPX1070 QHPX2070 QHPX3070H
80 QHPX2080 QHPX3080H
90 QHPX2090 QHPX3090H
100 QHPX2100 QHPX3100H
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole Two-Pole Three-Pole
120/240 Vac 120/240 Vac 240 Vac 240 Vac
Catalog Number Catalog Number Catalog Number Catalog Number
15 QHPW1015 1QHPW2015 QHPW3015H
20 QHPW1020 1QHPW2020 QHPW3020H
25 QHPW1025QHPW2025—
30 QHPW1030QHPW2030—
Number
of Poles
Carton
Quantity
Approximate
Weight Lbs (kg) Dimensions
1 24 9.00 (4.1) 12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)
2 12 9.00 (4.1) 12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)
3 8 9.00 (4.1) 12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)
V4-T1-8 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
QUICKLAG Type QPGF Single-Pole
Ground Fault Circuit Breaker
Contents
Description Page
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-2
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW V4-T1-5
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGF, QPHGF, QPGFEP, QPHGFEP
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-9
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-10
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-10
Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . . V4-T1-11
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-14
Bolt-On Ground Fault and Equipment Protectors,
Types QBGF, QBHGF, QBGFEP, QBHGFEP . . . . . . . V4-T1-17
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-20
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-24
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGF, QCHGF, QCGFEP, QCHGFEP V4-T1-28
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP. . . . . . . . . V4-T1-31
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers . . . . . . . V4-T1-34
International Rated Types HQP, BA, QC, GFMB, GFXBC V4-T1-37
Special Application Breakers, Types HQP, BA, QC . . . V4-T1-40
QUICKLAG Plug-On Ground Fault and Equipment Protectors,
Types QPGF, QPHGF, QPGFEP, QPHGFEP
Product Description
QUICKLAG Ground Fault Circuit
Breakers, Class A GFCI
5 mA trip sensitivity
QUICKLAG Ground Fault
Equipment Protectors
30 mA trip sensitivity
Standards and Certifications
Built and listed to UL 489
QUICKLAG Ground Fault Circuit
Breakers, Class A GFCI
Built and tested to UL 943
QUICKLAG Ground Fault
Equipment Protectors
Built and listed to UL 1053
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-9
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Product Selection
Ground Fault Circuit Breakers—5 mA Sensitivity QUICKLAG Type:
QPGF 10,000A Interrupting Capacity Thermal-Magnetic Breakers
QUICKLAG Type: QPHGF 22,000A Interrupting Capacity
Thermal-Magnetic Breakers
Ground Fault Equipment Breakers—30 mA Sensitivity QUICKLAG Type:
QPGFEP 10,000A Interrupting Capacity Thermal-Magnetic Breakers
QUICKLAG Type: QPHGFEP 22,000A Interrupting Capacity
Thermal-Magnetic Breakers
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole
120 Vac 120/240 Vac
Catalog Number Catalog Number
15 QPGF1015 QPGF2015
20 QPGF1020 QPGF2020
25 QPGF1025 QPGF2025
30 QPGF1030 QPGF2030
40 QPGF1040 QPGF2040
50 QPGF2050
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole
120 Vac 120/240 Vac
Catalog Number Catalog Number
15 QPHGF1015 QPHGF2015
20 QPHGF1020 QPHGF2020
25 QPHGF1025 QPHGF2025
30 QPHGF1030 QPHGF2030
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole
120 Vac 120/240 Vac
Catalog Number Catalog Number
15 QPGFEP1015 QPGFEP2015
20 QPGFEP1020 QPGFEP2020
25 QPGFEP1025 QPGFEP2025
30 QPGFEP1030 QPGFEP2030
40 QPGFEP1040 QPGFEP2040
50 QPGFEP2050
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole
120 Vac 120/240 Vac
Catalog Number Catalog Number
15 QPHGFEP1015 QPHGFEP2015
20 QPHGFEP1020 QPHGFEP2020
25 QPHGFEP1025 QPHGFEP2025
30 QPHGFEP1030 QPHGFEP2030
QUICKLAG Type QPGF
Single-Pole
V4-T1-10 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Special Application Ground Fault Circuit Protectors—5 mA Sensitivity
QUICKLAG Type: QPGF 10,000A Interrupting Capacity with Bell Alarm (W1) or
Auxiliary Switch (W2)
Special Application Ground Fault Circuit Protectors—30 mA Sensitivity
QUICKLAG Type: QPGFEP 10,000A Interrupting Capacity with Bell Alarm (W1) or
Auxiliary Switch (W2)
Wiring Diagram
Bell Alarm and Auxiliary Contact Schematic
Dimensions
Approximate Dimensions in Inches (mm)
Shipping Data
Note
Shipped individually or in carton quantities.
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole
120 Vac 120/240 Vac
Catalog Number Catalog Number
15 QPGF1015W1 QPGF2015W1
20 QPGF1020W1 QPGF2020W1
25 QPGF1025W1 QPGF2025W1
30 QPGF1030W1 QPGF2030W1
40 QPGF2040W1
50 QPGF2050W1
15 QPGF1015W2
20 QPGF1020W2
25 QPGF1025W2
30 QPGF1030W2
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole
120 Vac 120/240 Vac
Catalog Number Catalog Number
15 QPGFEP1015W1 QPGFEP2015W1
20 QPGFEP1020W1 QPGFEP2020W1
25 QPGFEP1025W1 QPGFEP2025W1
30 QPGFEP1030W1 QPGFEP2030W1
40 QPGFEP2040W1
50 QPGFEP2050W1
15 QPGFEP1015W2
20 QPGFEP1020W2
25 QPGFEP1025W2
30 QPGFEP1030W2
Blue Wire
Red Wire
Black Wire
Ground
Fault
Breaker
Single-throw double-pole contacts are UL and CSA listed for 5A at 250 Vac.
Bell Alarm (W1)—contacts change state when breaker trips.
Auxiliary Switch (W2)—contacts change state when breaker is opened (or tripped) or closed.
14-inch (355.6 mm) long 18 AWG pigtail wire leads provided.
Blue
Red
NC
NO
Number
of Poles
Carton
Quantity
Approximate
Weight Lbs (kg) Dimensions
1 24 11.00 (5.0) 12.50 x 6.50 x 5.00 (317.5 x 165.1 x 127.0)
2 5 5.00 (2.3) 15.50 x 6.00 x 4.50 (393.7 x 152.4 x 114.3)
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
QUICKLAG Type BAB Single-Pole
Contents
Description Page
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-2
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW V4-T1-5
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGF, QPHGF, QPGFEP, QPHGFEP V4-T1-8
Bolt-On Types BAB, QBHW, HBAX, HBAW
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-12
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-13
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-14
Bolt-On Ground Fault and Equipment Protectors,
Types QBGF, QBHGF, QBGFEP, QBHGFEP . . . . . . . . V4-T1-17
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-20
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-24
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGF, QCHGF, QCGFEP, QCHGFEP V4-T1-28
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP . . . . . . . . . V4-T1-31
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers. . . . . . . . V4-T1-34
International Rated Types HQP, BA, QC, GFMB, GFXBC V4-T1-37
Special Application Breakers, Types HQP, BA, QC. . . . V4-T1-40
Bolt-On Types BAB, QBHW, HBAX, HBAW
Product Description
All products 15–100A are
HACR rated
Switching duty rated
for 120 Vac fluorescent
light applications
Standards and Certifications
Built and listed to UL 489
All products UL and
CSA listed
V4-T1-12 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Product Selection
QUICKLAG Type: BA 10,000A Interrupting Capacity Thermal-Magnetic Breakers
QUICKLAG Type: BA Non-Automatic Switches
QUICKLAG Type: QBHW 22,000A Interrupting Capacity Thermal-Magnetic Breakers
Notes
1 Switching duty rated for 120 Vac fluorescent light applications.
2 For special low-magnetic breaker, order BAB1015L1 or BAB1020L1.
3 Not UL listed.
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole Two-Pole Three-Pole
120/240 Vac 120/240 Vac 240 Vac 240 Vac
Catalog Number Catalog Number Catalog Number Catalog Number
10 BAB1010 BAB2010 BAB2010H 3BAB3010H 3
15 BAB1015 12 BAB2015 BAB2015H BAB3015H
20 BAB1020 12 BAB2020 BAB2020H BAB3020H
25 BAB1025 BAB2025 BAB2025H BAB3025H
30 BAB1030 BAB2030 BAB2030H BAB3030H
35 BAB1035 BAB2035 BAB2035H BAB3035H
40 BAB1040 BAB2040 BAB2040H BAB3040H
45 BAB1045 BAB2045 BAB2045H BAB3045H
50 BAB1050 BAB2050 BAB2050H BAB3050H
55 BAB1055 BAB2055 BAB2055H BAB3055H
60 BAB1060 BAB2060 BAB2060H BAB3060H
70 BAB1070 BAB2070 BAB2070H BAB3070H
80 BAB2080 BAB2080H BAB3080H
90 BAB2090 BAB2090H BAB3090H
100 BAB1100 BAB2100 BAB2100H BAB3100H
110 BAB2110
125 BAB2125
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole Two-Pole Three-Pole
120/240 Vac 120/240 Vac 240 Vac 240 Vac
Catalog Number Catalog Number Catalog Number Catalog Number
50 BAB1050N BAB2050N BAB3050N
60 BAB1060N BAB2060N BAB3060N
100 BAB1100N BAB2100N BAB3100N
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole Two-Pole Three-Pole
120/240 Vac 120/240 Vac 240 Vac 240 Vac
Catalog Number Catalog Number Catalog Number Catalog Number
15 QBHW1015 1QBHW2015 QBHW2015H QBHW3015H
20 QBHW1020 1QBHW2020 QBHW2020H QBHW3020H
25 QBHW1025 QBHW2025 QBHW2025H QBHW3025H
30 QBHW1030 QBHW2030 QBHW2030H QBHW3030H
35 QBHW1035 QBHW2035 QBHW2035H QBHW3035H
40 QBHW1040 QBHW2040 QBHW2040H QBHW3040H
45 QBHW1045 QBHW2045 QBHW2045H QBHW3045H
50 QBHW1050 QBHW2050 QBHW2050H QBHW3050H
55 QBHW1055 QBHW2055 QBHW2055H QBHW3055H
60 QBHW1060 QBHW2060 QBHW2060H QBHW3060H
70 QBHW1070 QBHW2070 QBHW2070H QBHW3070H
80 QBHW2080 QBHW2080H QBHW3080H
90 QBHW2090 QBHW2090H QBHW3090H
100 QBHW2100 QBHW2100H QBHW3100H
110 QBHW2110
125 QBHW2125
QUICKLAG Type BAB
Single-Pole
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-13
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
QUICKLAG Type: HBAX 42,000A Interrupting Capacity Thermal-Magnetic Breakers
QUICKLAG Type: HBAW 65,000A Interrupting Capacity Thermal-Magnetic Breakers
Dimensions
Approximate Dimensions in Inches (mm)
Shipping Data
Note
1Switching duty rated for 120 Vac fluorescent light applications.
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole Two-Pole Three-Pole
120/240 Vac 120/240 Vac 240 Vac 240 Vac
Catalog Number Catalog Number Catalog Number Catalog Number
15 HBAX1015 1HBAX2015 HBAX3015H
20 HBAX1020 1HBAX2020 HBAX3020H
25 HBAX1025 HBAX2025 HBAX3025H
30 HBAX1030 HBAX2030 HBAX3030H
35 HBAX1035 HBAX2035 HBAX3035H
40 HBAX1040 HBAX2040 HBAX3040H
45 HBAX1045 HBAX2045 HBAX3045H
50 HBAX1050 HBAX2050 HBAX3050H
55 HBAX1055 HBAX2055 HBAX3055H
60 HBAX1060 HBAX2060 HBAX3060H
70 HBAX1070 HBAX2070 HBAX3070H
80 HBAX2080 HBAX3080H
80 HBAX2080 HBAX3080H
90 HBAX2090 HBAX3090H
100 HBAX2100 HBAX3100H
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole Two-Pole Three-Pole
120/240 Vac 120/240 Vac 240 Vac 240 Vac
Catalog Number Catalog Number Catalog Number Catalog Number
15 HBAW1015 1HBAW2015 HBAW3015H
20 HBAW1020 1HBAW2020 HBAW3020H
25 HBAW1025 HBAW2025
30 HBAW1030 HBAW2030
Number
of Poles
Carton
Quantity
Approximate
Weight Lbs (kg) Dimensions
1 24 9.00 (4.1) 12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)
2 12 9.00 (4.1) 12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)
3 8 9.00 (4.1) 12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)
V4-T1-14 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Bolt-On Arc Fault Circuit Interrupter QUICKLAG Types QBAF, QBCAF
Contents
Description Page
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-2
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW V4-T1-5
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGF, QPHGF, QPGFEP, QPHGFEP V4-T1-8
Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . . V4-T1-11
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-15
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-16
Bolt-On Ground Fault and Equipment Protectors,
Types QBGF, QBHGF, QBGFEP, QBHGFEP . . . . . . . V4-T1-17
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-20
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-24
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGF, QCHGF, QCGFEP, QCHGFEP V4-T1-28
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP. . . . . . . . . V4-T1-31
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers . . . . . . . V4-T1-34
International Rated Types HQP, BA, QC, GFMB, GFXBC V4-T1-37
Special Application Breakers, Types HQP, BA, QC . . . V4-T1-40
Bolt-On Arc Fault Circuit Interrupter Types QBAF, QBCAF
Product Description
All products HACR rated
Features, Benefits and
Functions
10 and 22 kAIC rating at
120V and 120/240V
Single-pole AFCI
HID ratings for HID (High
Intensity Discharge) lighting
All models are HACR rated
Standards and Certifications
Built and listed to UL 489
UL File E7819 for QBAF
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-15
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Product Selection
QBCAF and QBAF Type AFCIs
Effective immediately, Eaton
AFCIs are available for use in
Sumter panels with a 22 kAIC
rating. This higher rated
breaker will allow us to
win jobs where AFCIs are
specified at higher than
10 kAIC. This breaker
provides standard thermal-
magnetic protection of
branch circuits. This product
will have the same form, fit
and function of the current
bolt-on AFCI (QBCAF and
QBAF Type). Product scope is
below. These breakers are in
Bid Manager™ for Pow-R-
Line 1a, Pow-R-Line 1a-LX,
Pow-R-Line 3a and Pow-R-
Line 4a panelboards. For
series rated combinations,
continue to use the less
expensive 10 kAIC QBCAF
and QBAF offerings.
Breakers can also be ordered
from Vista.
1-Inch (25.4 mm) Wide Bolt-On Arc Fault Circuit Interrupter
Poles
kAIC
Rating
Ampere
Rating Configuration Catalog Number
Type QBCAF Combination AFCI
Single-pole 10 kAIC 15 Combination AFCI QBCAF1015
20 Combination AFCI QBCAF1020
22 kAIC 15 Combination AFCI QBHCAF1015
20 Combination AFCI QBHCAF1020
Type QBAF Branch Feeder AFCI
Single-pole 10 kAIC 15 Branch Feeder AFCI QBAF1015
20 Branch Feeder AFCI QBAF1020
22 kAIC 15 Branch Feeder AFCI QBHAF1015
20 Branch Feeder AFCI QBHAF1020
QBHCAF
V4-T1-16 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Wiring Diagrams
Single-Pole 120V Load Application
Sourced by 120/240 Vac
Single-Pole Shared Neutral with
Multi-Duplex Receptacle Application
NAB
120/240 Vac
Source
120V
Duplex
Receptacle
Single-Pole
Line B
Neutral
Neutral
Equipment Ground
NA B
120/240 Vac
Source
Two 120V
Duplex
Receptacles
Two-Pole
Line B
Line A
Neutral
Neutral
Equipment Ground
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-17
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
QUICKLAG Type QBGF Single-Pole
Ground Fault Circuit Breaker
Contents
Description Page
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW V4-T1-5
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGF, QPHGF, QPGFEP, QPHGFEP V4-T1-8
Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . . . V4-T1-11
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-14
Bolt-On Ground Fault and Equipment Protectors,
Types QBGF, QBHGF, QBGFEP, QBHGFEP
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-18
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-19
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-19
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-20
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-24
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGF, QCHGF, QCGFEP, QCHGFEP V4-T1-28
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP . . . . . . . . . V4-T1-31
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers. . . . . . . . V4-T1-34
International Rated Types HQP, BA, QC, GFMB, GFXBC V4-T1-37
Special Application Breakers, Types HQP, BA, QC. . . . V4-T1-40
Bolt-On Ground Fault and Equipment Protectors,
Types QBGF, QBHGF, QBGFEP, QBHGFEP
Product Description
QUICKLAG Ground Fault Circuit
Breakers, Class A GFCI
5 mA trip sensitivity
QUICKLAG Ground Fault
Equipment
Protectors
30 mA trip sensitivity
Standards and Certifications
Built and tested to UL 489
QUICKLAG Ground Fault Circuit
Breakers, Class A GFCI
Built and tested to UL 943
QUICKLAG Ground Fault
Equipment Protectors
Built and tested to UL 1053
V4-T1-18 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Product Selection
Ground Fault Circuit Breakers—5 mA Sensitivity QUICKLAG Type:
QBGF 10,000A Interrupting Capacity Thermal-Magnetic Breakers
QUICKLAG Type: QBHGF 22,000A Interrupting Capacity
Thermal-Magnetic Breakers
Ground Fault Equipment Breakers—30 mA Sensitivity QUICKLAG Type:
QBGFEP 10,000A Interrupting Capacity Thermal-Magnetic Breakers
QUICKLAG Type: QBHGFEP 22,000A Interrupting Capacity
Thermal-Magnetic Breakers
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole
120 Vac 120/240 Vac
Catalog Number Catalog Number
15 QBGF1015 QBGF2015
20 QBGF1020 QBGF2020
25 QBGF1025 QBGF2025
30 QBGF1030 QBGF2030
40 QBGF1040 QBGF2040
50 QBGF2050
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole
120 Vac 120/240 Vac
Catalog Number Catalog Number
15 QBHGF1015 QBHGF2015
20 QBHGF1020 QBHGF2020
25 QBHGF1025 QBHGF2025
30 QBHGF1030 QBHGF2030
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole
120 Vac 120/240 Vac
Catalog Number Catalog Number
15 QBGFEP1015 QBGFEP2015
20 QBGFEP1020 QBGFEP2020
25 QBGFEP1025 QBGFEP2025
30 QBGFEP1030 QBGFEP2030
40 QBGFEP1040 QBGFEP2040
50 QBGFEP2050
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole
120 Vac 120/240 Vac
Catalog Number Catalog Number
15 QBHGFEP1015 QBHGFEP2015
20 QBHGFEP1020 QBHGFEP2020
25 QBHGFEP1025 QBHGFEP2025
30 QBHGFEP1030 QBHGFEP2030
QUICKLAG Type QBGF
Single-Pole
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-19
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Special Application Ground Fault Circuit Protectors—5 mA Sensitivity QUICKLAG Type:
QBGF 10,000A Interrupting Capacity with Bell Alarm (W1) or Auxiliary Switch (W2)
Special Application Ground Fault Circuit Protectors—30 mA Sensitivity QUICKLAG Type:
QBGFEP 10,000A Interrupting Capacity with Bell Alarm (W1) or Auxiliary Switch (W2)
Wiring Diagram
Bell Alarm and Auxiliary Contact Schematic
Dimensions
Approximate Dimensions in Inches (mm)
Shipping Data
Note
Shipped individually or in carton quantities.
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole
120 Vac 120/240 Vac
Catalog Number Catalog Number
15 QBGF1015W1 QBGF2015W1
20 QBGF1020W1 QBGF2020W1
25 QBGF1025W1 QBGF2025W1
30 QBGF1030W1 QBGF2030W1
40 QBGF2040W1
50 QBGF2050W1
15 QBGF1015W2
20 QBGF1020W2
25 QBGF1025W2
30 QBGF1030W2
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole
120 Vac 120/240 Vac
Catalog Number Catalog Number
15 QBGFEP1015W1 QBGFEP2015W1
20 QBGFEP1020W1 QBGFEP2020W1
25 QBGFEP1025W1 QBGFEP2025W1
30 QBGFEP1030W1 QBGFEP2030W1
40 QBGFEP2040W1
50 QBGFEP2050W1
15 QBGFEP1015W2
20 QBGFEP1020W2
25 QBGFEP1025W2
30 QBGFEP1030W2
Blue Wire
Red Wire
Black Wire
Ground
Fault
Breaker
Single-throw double-pole contacts are UL and CSA listed for 5A at 250 Vac.
Bell Alarm (W1)—contacts change state when breaker trips.
Auxiliary Switch (W2)—contacts change state when breaker is opened (or tripped) or closed.
14-inch (355.6 mm) long 18 AWG pigtail wire leads provided.
Blue
Red
NC
NO
Number of Poles Approximate Weight Lbs (kg) Dimensions
1 11.00 (5.0) 12.50 x 6.50 x 5.00 (317.5 x 165.1 x 127.0)
2 5.00 (2.3) 15.50 x 6.00 x 4.50 (393.7 x 152.4 x 114.3)
V4-T1-20 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
QUICKLAG Type QC Single-Pole
Contents
Description Page
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-2
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW V4-T1-5
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGF, QPHGF, QPGFEP, QPHGFEP V4-T1-8
Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . . V4-T1-11
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-14
Bolt-On Ground Fault and Equipment Protectors,
Types QBGF, QBHGF, QBGFEP, QBHGFEP . . . . . . . V4-T1-17
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-21
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-23
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-24
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGF, QCHGF, QCGFEP, QCHGFEP V4-T1-28
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP. . . . . . . . . V4-T1-31
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers . . . . . . . V4-T1-34
International Rated Types HQP, BA, QC, GFMB, GFXBC V4-T1-37
Special Application Breakers, Types HQP, BA, QC . . . V4-T1-40
Cable-In/Cable-Out Types QC, QCD, QCHW, QHCX, QHCW
Product Description
All products 10–100A are
HACR rated
Switching duty rated for
120 Vac fluorescent light
applications only
Standards and Certifications
Built and listed to UL 489
All products UL and
CSA listed
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-21
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Product Selection
QUICKLAG Type: QC 10,000A Interrupting Capacity Thermal-Magnetic Breakers
QUICKLAG Type: QC Non-Automatic Switches
Notes
1 Not UL listed.
2 Switching duty rated for 120 Vac fluorescent light applications only.
For special low-magnetic breaker, order QC1015L1 or QC1020L1.Non-automatic switches, see Page V4-T1-42.
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole Two-Pole Three-Pole Four-Pole
120/240 Vac 120/240 Vac 240 Vac 240 Vac 240 Vac
Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number
5QC1005 1QC2005 1———
10 QC1010 QC2010 QC2010H 1QC3010H 1
15 QC1015 2QC2015 QC2015H QC3015H QC4015H
20 QC1020 2QC2020 QC2020H QC3020H QC4020H
25 QC1025 QC2025 QC2025H QC3025H QC4025H
30 QC1030 QC2030 QC2030H QC3030H QC4030H
35 QC1035 QC2035 QC2035H QC3035H QC4035H
40 QC1040 QC2040 QC2040H QC3040H QC4040H
45 QC1045 QC2045 QC2045H QC3045H QC4045H
50 QC1050 QC2050 QC2050H QC3050H QC4050H
55 QC1055 QC2055 QC2055H QC3055H QC4055H
60 QC1060 QC2060 QC2060H QC3060H QC4060H
70 QC1070 QC2070 QC2070H QC3070H QC4070H
70 QC2080 QC2080H QC3080H QC4080H
90 QC2090 QC2090H QC3090H QC4090H
100 QC1100 QC2100 QC2100H QC3100H QC4100H
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole Two-Pole Three-Pole Four-Pole
120/240 Vac 120/240 Vac 240 Vac 240 Vac 240 Vac
Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number
50 QC1050N QC2050N QC3050N
60 QC1060N QC2060N QC3060N
100 QC1100N QC2100N QC3100N
QUICKLAG
Type QC Single-Pole
V4-T1-22 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
QUICKLAG Type: QCHW 22,000A Interrupting Capacity Thermal-Magnetic Breakers
QUICKLAG Type: QHCX 42,000A Interrupting Capacity Thermal-Magnetic Breakers
QUICKLAG Type: QHCW 65,000A Interrupting Capacity Thermal-Magnetic Breakers
Notes
1 Switching duty rated for 120 Vac fluorescent light applications only.
Non-automatic switches, see Page V4-T1-42.
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole Two-Pole Three-Pole Four-Pole
120/240 Vac 120/240 Vac 240 Vac 240 Vac 240 Vac
Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number
15 QCHW1015 1QCHW2015 QCHW2015H QCHW3015H QCHW4015H
20 QCHW1020 1QCHW2020 QCHW2020H QCHW3020H QCHW4020H
25 QCHW1025 QCHW2025 QCHW2025H QCHW3025H QCHW4025H
30 QCHW1030 QCHW2030 QCHW2030H QCHW3030H QCHW4030H
35 QCHW1035 QCHW2035 QCHW2035H QCHW3035H QCHW4035H
40 QCHW1040 QCHW2040 QCHW2040H QCHW3040H QCHW4040H
45 QCHW1045 QCHW2045 QCHW2045H QCHW3045H QCHW4045H
50 QCHW1050 QCHW2050 QCHW2050H QCHW3050H QCHW4050H
55 QCHW1055 QCHW2055 QCHW2055H QCHW3055H QCHW4055H
60 QCHW1060 QCHW2060 QCHW2060H QCHW3060H QCHW4060H
70 QCHW1070 QCHW2070 QCHW2070H QCHW3070H QCHW4070H
70 QCHW2080 QCHW2080H QCHW3080H QCHW4080H
90 QCHW2090 QCHW2090H QCHW3090H QCHW4090H
100 QCHW2100 QCHW2100H QCHW3100H QCHW4100H
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole Two-Pole Three-Pole Four-Pole
120/240 Vac 120/240 Vac 240 Vac 240 Vac 240 Vac
Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number
15 QHCX1015 1QHCX2015 QHCX3015H
20 QHCX1020 1QHCX2020 QHCX3020H
25 QHCX1025 QHCX2025 QHCX3025H
30 QHCX1030 QHCX2030 QHCX3030H
35 QHCX1035 QHCX2035 QHCX3035H
40 QHCX1040 QHCX2040 QHCX3040H
45 QHCX1045 QHCX2045 QHCX3045H
50 QHCX1050 QHCX2050 QHCX3050H
55 QHCX1055 QHCX2055 QHCX3055H
60 QHCX1060 QHCX2060 QHCX3060H
70 QHCX1070 QHCX2070 QHCX3070H
70 QHCX2080 QHCX3080H
90 QHCX2090 QHCX3090H
100 QHCX2100 QHCX3100H
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole Two-Pole Three-Pole Four-Pole
120/240 Vac 120/240 Vac 240 Vac 240 Vac 240 Vac
Catalog Number Catalog Number Catalog Number Catalog Number Catalog Number
15 QHCW1015 1QHCW2015 QHCW3015H
20 QHCW1020 1QHCW2020 QHCW3020H
25 QHCW1025 QHCW2025
30 QHCW1030 QHCW2030
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-23
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
QUICKLAG Type QCD Miniature Circuit Breakers
QCD breakers are used
primarily in HVAC and
industrial applications.
Single-, two- and
three-pole options
Modular construction
DIN mounted
(symmetrical rail 35 x
7.5 DIN/EN 50 022)
QCD same profile as
Type QCR
Flexible power feed
connection:
wire size, position
Same breaker size for
entire rating range
Field mountable
accessories:
finger shroud proof, quick
connect terminals
Other accessories:
jumper unit
QUICKLAG Type QCD 10,000A Interrupting Capacity Thermal-Magnetic Breakers
QUICKLAG Type QCD Non-Automatic Switches
Dimensions
Approximate Dimensions in Inches (mm)
Shipping Data
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole Two-Pole Three-Pole
120/240 Vac 120/240 Vac 240 Vac 240 Vac
Catalog Number Catalog Number Catalog Number Catalog Number
10 QCD1010 QCD2010
15 QCD1015 QCD2015 QCD2015H QCD3015H
20 QCD1020 QCD2020 QCD2020H QCD3020H
25 QCD1025 QCD2025 QCD2025H QCD3025H
30 QCD1030 QCD2030 QCD2030H QCD3030H
35 QCD1035 QCD2035 QCD2035H QCD3035H
40 QCD1040 QCD2040 QCD2040H QCD3040H
45 QCD1045 QCD2045 QCD2045H QCD3045H
50 QCD1050 QCD2050 QCD2050H QCD3050H
55 QCD1055 QCD2055 QCD2055H QCD3055H
60 QCD1060 QCD2060 QCD2060H QCD3060H
70 QCD2070 QCD2070H QCD3070H
80 QCD2080 QCD2080H QCD3080H
90 QCD2090 QCD2090H QCD3090H
100 QCD2090 QCD2090H QCD3100H
QCD2100 QCD2100H
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole Two-Pole Three-Pole
120/240 Vac 120/240 Vac 240 Vac 240 Vac
Catalog Number Catalog Number Catalog Number Catalog Number
60 QCD2060NA
100 ————
Number
of Poles
Carton
Quantity
Approximate
Weight Lbs (kg) Dimensions
1 24 9.00 (4.1) 12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)
2 12 9.00 (4.1) 12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)
3 8 9.00 (4.1) 12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)
QUICKLAG Type QCD
Miniature Circuit
Breaker
V4-T1-24 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Single-Pole Two-Pole Single-Pole Two-Pole
QCR (Rear-Mounted Breakers) QCF (Front-Mounted Breakers)
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF, QCRH, QCFH
Contents
Description Page
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-2
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW V4-T1-5
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGF, QPHGF, QPGFEP, QPHGFEP V4-T1-8
Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . . V4-T1-11
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-14
Bolt-On Ground Fault and Equipment Protectors,
Types QBGF, QBHGF, QBGFEP, QBHGFEP . . . . . . . V4-T1-17
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-20
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-25
QCR and QCF Options and Accessories . . . . . . . V4-T1-27
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGF, QCHGF, QCGFEP, QCHGFEP V4-T1-28
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP. . . . . . . . . V4-T1-31
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers . . . . . . . V4-T1-34
International Rated Types HQP, BA, QC, GFMB, GFXBC V4-T1-37
Special Application Breakers, Types HQP, BA, QC . . . V4-T1-40
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF, QCRH, QCFH
Product Description
Eaton Type QCR circuit
breakers have as a standard
feature provisions for 35 mm
DIN rail rear mounting with
a spring-loaded release.
Optional clips for individual
mounting are available as a
separate accessory.
Type QCF have two threaded
steel inserts to facilitate front
mounting with #6–32 steel
screws. The clamp type
terminals are accessible from
the rear of the breaker so that
cables can be accessed
without removal of the
breaker from the front cover.
Application Description
QCR and QCF circuit breakers
are only 1/2-inch (12.7 mm)
wide per pole and are
excellent for general purpose
industrial applications where
space savings is required.
Features, Benefits
and Functions
1/2-inch (12.7 mm) wide
per pole
Cable-in/cable-out
Black cases with black
handles
Three position handle:
ON, Tripped (center), OFF
Thermal-magnetic
protection
Standards and Certifications
Built and listed to UL 489
UL File No. E7819
CSA File No. LR48907
Type QCR and QCF circuit
breakers are UL listed
circuit breakers that are
suitable for use as branch
circuit protectors
All ratings 15–60A are
HACR rated
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-25
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Product Selection
QCR Breaker Catalog Numbers 1234
Notes
1 Standard breaker terminals are box type lugs.
2 Breakers with T Catalog Number Suffix are suitable for line and load side ring terminal connection
(#10–32 plus/minus terminal screw provided).
3 Breakers with P Catalog Number Suffix are suitable for terminating two 10 AWG Quick-Connect Type Terminals per
phase on breaker load side.
4 Breakers with Shunt Trip (extra pole required on breaker right-hand side) are available on single-, two- and three-pole.
Contact the Customer Support Center at 1-800-356-1243.
5 Breakers with H Catalog Suffix have 240 Vac construction.
6 All 15 and 20A single-pole breakers are SWD (Switching Duty) rated for fluorescent lighting applications.
7 60/75°C Cu/Al wire on all ratings except 60A, which requires Cu only conductor.
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole Two-Pole Three-Pole
120/240 Vac 120/240 Vac 240 Vac 5
Catalog Number Catalog Number Catalog Number Catalog Number
QCR Breaker 10 kAIC Interrupting Ratings
10 QCR1010 QCR2010
QCR1010T QCR2010T
QCR2010P
15 QCR1015 6QCR2015 QCR2015H QCR3015H
QCR1015T 6QCR2015T QCR2015HT QCR3015HT
QCR2015P
20 QCR1020 6QCR2020 QCR2020H QCR3020H
QCR1020T 6QCR2020T QCR2020HT QCR3020HT
QCR2020P
25 QCR1025 QCR2025 QCR2025H QCR3025H
QCR1025T QCR2025T QCR2025HT QCR3025HT
QCR2025P
30 QCR1030 QCR2030 QCR2030H QCR3030H
QCR1030T QCR2030T QCR2030HT QCR3030HT
QCR2030P
35 QCR1035 QCR2035
QCR2035P
40 QCR1040 QCR2040
QCR2040P
45 QCR1045 QCR2045
QCR2045P
50 QCR1050 QCR2050
QCR2050P
55 QCR1055 QCR2055
QCR2055P
60 7QCR1060 QCR2060
QCR2060P
QCR Breaker 22 kAIC Interrupting Ratings
15 QCRH1015 6QCRH2015
QCRH1015T 6QCRH2015T
20 QCRH1020 6QCRH2020
QCRH1020T 6QCRH2020T
Cable-In/Cable-Out,
1/2-Inch Wide
V4-T1-26 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
QCF Breaker Catalog Numbers 123
Notes
1 Standard breaker terminals are box type lugs.
2 Breakers with T Catalog Number Suffix are suitable for line and load side ring terminal connection
(#10–32 plus/minus terminal screw provided).
3 Breakers with Shunt Trip Attachment (extra pole required on breaker right-hand side) are available.
Contact the Customer Support Center.
4 Breakers with H Catalog Suffix have 240 Vac construction.
5 All 15 and 20A single-pole breakers are SWD (Switching Duty) rated for fluorescent lighting applications.
6 60/75°C Cu/Al wire on all ratings except 60A, which requires Cu only conductor.
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole Two-Pole Three-Pole
120/240 Vac 120/240 Vac 240 Vac 4
Catalog Number Catalog Number Catalog Number Catalog Number
QCF Breaker 10 kAIC Interrupting Ratings
10 QCF1010 QCF2010
QCF1010T QCF2010T
15 QCF1015 5QCF2015 QCF2015H QCF3015H
QCF1015T 5QCF2015T QCF2015HT QCF3015HT
20 QCF1020 5QCF2020 QCF2020H QCF3020H
QCF1020T 5QCF2020T QCF2020HT QCF3020HT
25 QCF1025 QCF2025 QCF2025H QCF3025H
QCF1025T QCF2025T QCF2025HT QCF3025HT
30 QCF1030 QCF2030 QCF2030H QCF3030H
QCF1030T QCF2030T QCF2030HT QCF3030HT
35 QCF1035 QCF2035
40 QCF1040 QCF2040
45 QCF1045 QCF2045
50 QCF1050 QCF2050
55 QCF1055 QCF2055
60 6QCF1060 QCF2060
QCF Breaker 22 kAIC Interrupting Ratings
15 QCFH1015 5QCFH2015
QCFH1015T 5QCFH2015T
20 QCFH1020 5QCFH2020
QCFH1020T 5QCFH2020T
Cable-In/Cable-Out,
1/2-Inch Wide
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-27
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
QCR and QCF Options and Accessories
QCR and QCF Standard Box
Terminals
Factory-installed line and load
side breaker terminal to
accommodate14 AWG to
4 AWG wire.
Standard Box Terminals
QCR Quick-Connect Terminals
Factory-installed two-prong
quick-connect terminal on
breaker load side suitable for
terminating two 10 AWG wire
with insulated slip-on
terminals as shown. Line side
terminal is the standard type.
Catalog Suffix “P”
QCR and QCF Ring or Spade Lug
Terminals (10 to 30A Ratings
Only)
Factory-installed line and load
side terminals each equipped
with a #10–32 screw suitable
for terminating one 10 AWG
wire with insulated ring or
spade type terminal as shown.
Catalog Suffix “T”
Available QCR and QCF
Breaker Accessories
Technical Data and Specifications
Single-, two- and
three-pole
10 kAIC at 120/240 Vac,
1060A
22 kAIC at 120/240 Vac,
15–20A
10 kAIC at 240 Vac, 10–30A
3 kAIC at 62.5 Vdc
(single-pole)
3 kAIC at 130 Vdc
(two poles in series)
Normal operating
environment:
0–40°C
5–95% humidity
(noncondensing)
Description
Catalog
Number
Steel mounting clip
mounts QCR breaker if
individual mounting is
required. Quantity two
required for single- and two-
pole and four required
for three-pole breakers.
QCRMTGFT
Removable padlock
device for single-pole
QCR or QCF breaker.
QCRFPL1P
Removable padlock
device for multi-pole
QCR or QCF breaker.
QCRFPLMP
Padlock bracket assem-
bly for QCR or QCF
single- or multi-pole
breakers (OFF only).
QCRFLOFF
Padlock bracket for
QCR, lock-off only.
QCRPLOFF
V4-T1-28 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
QUICKLAG Type QCGF Single-Pole
Ground Fault Circuit Breaker
Contents
Description Page
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-2
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW V4-T1-5
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGF, QPHGF, QPGFEP, QPHGFEP V4-T1-8
Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . . V4-T1-11
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-14
Bolt-On Ground Fault and Equipment Protectors,
Types QBGF, QBHGF, QBGFEP, QBHGFEP . . . . . . . V4-T1-17
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-20
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-24
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGF, QCHGF, QCGFEP, QCHGFEP
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-29
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-30
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-30
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP. . . . . . . . . V4-T1-31
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers . . . . . . . V4-T1-34
International Rated Types HQP, BA, QC, GFMB, GFXBC V4-T1-37
Special Application Breakers, Types HQP, BA, QC . . . V4-T1-40
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGF, QCHGF, QCGFEP, QCHGFEP
Product Description
QUICKLAG Ground Fault Circuit
Breakers, Class A GFCI
5 mA trip sensitivity
QUICKLAG Ground Fault
Equipment Protectors
30 mA trip sensitivity
Standards and Certifications
QUICKLAG Ground Fault Circuit
Breakers, Class A GFCI
Built and tested to UL 943
QUICKLAG Ground Fault
Equipment Protectors
Built and tested to
UL 1053
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-29
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Product Selection
Breaker Catalog Numbers
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole
120 Vac 120/240 Vac
Catalog Number Catalog Number
Ground Fault Circuit Breakers—5 mA Sensitivity
QUICKLAG Type: QCGF 10,000A Interrupting Capacity Thermal-Magnetic Breakers
15 QCGF1015 QCGF2015
20 QCGF1020 QCGF2020
25 QCGF1025 QCGF2025
30 QCGF1030 QCGF2030
40 QCGF1040 QCGF2040
50 QCGF2050
QUICKLAG Type: QCHGF 22,000A Interrupting Capacity Thermal-Magnetic Breakers
15 QCHGF1015 QCHGF2015
20 QCHGF1020 QCHGF2020
25 QCHGF1025 QCHGF2025
30 QCHGF1030 QCHGF2030
Ground Fault Equipment Protectors—30 mA Sensitivity
QUICKLAG Type: QCGFEP 10,000A Interrupting Capacity Thermal-Magnetic Breakers
15 QCGFEP1015 QCGFEP2015
20 QCGFEP1020 QCGFEP2020
25 QCGFEP1025 QCGFEP2025
30 QCGFEP1030 QCGFEP2030
40 QCGFEP1040 QCGFEP2040
50 QCGFEP2050
QUICKLAG Type: QCHGFEP 22,000A Interrupting Capacity Thermal-Magnetic Breakers
15 QCHGFEP1015 QCHGFEP2015
20 QCHGFEP1020 QCHGFEP2020
25 QCHGFEP1025 QCHGFEP2025
30 QCHGFEP1030 QCHGFEP2030
Special Application Ground Fault Circuit Protector—5 mA Sensitivity
QUICKLAG Type: QCGF 10,000A Interrupting Capacity with Bell Alarm (W1) or
Auxiliary Switch (W2)
15 QCGF1015W1 QCGF2015W1
20 QCGF1020W1 QCGF2020W1
25 QCGF1025W1 QCGF2025W1
30 QCGF1030W1 QCGF2030W1
40 QCGF2040W1
50 QCGF2050W1
15 QCGF1015W2
20 QCGF1020W2
25 QCGF1025W2
30 QCGF1030W2
Special Application Ground Fault Equipment Protectors—30 mA Sensitivity
QUICKLAG Type: QCGFEP 10,000A Interrupting Capacity with Bell Alarm (W1) or
Auxiliary Switch (W2)
15 QCGFEP1015W1 QCGFEP2015W1
20 QCGFEP1020W1 QCGFEP2020W1
25 QCGFEP1025W1 QCGFEP2025W1
30 QCGFEP1030W1 QCGFEP2030W1
40 QCGFEP2040W1
50 QCGFEP2050W1
15 QCGFEP1015W2
20 QCGFEP1020W2
25 QCGFEP1025W2
30 QCGFEP1030W2
QUICKLAG Type QCGF
Single-Pole Ground
Fault Circuit Breaker
V4-T1-30 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Wiring Diagram
Bell Alarm and Auxiliary Contact Schematic
Dimensions
Approximate Dimensions in Inches (mm)
Shipping Data
Blue Wire
Red Wire
Black Wire
Ground
Fault
Breaker
Single-throw double-pole contacts are UL and CSA listed for 5A at 250 Vac.
Bell Alarm (W1)—contacts change state when breaker trips.
Auxiliary Switch (W2)—contacts change state when breaker is opened (or tripped) or closed.
14-inch (355.6 mm) long 18 AWG pigtail wire leads provided.
Blue
Red
NC
NO
Number
of Poles
Carton
Quantity
Approximate
Weight Lbs (kg) Dimensions
1 20 11.00 (5.0) 12.50 x 6.50 x 5.00 (317.5 x 165.1 x 127.0)
2 5 5.00 (2.3) 15.50 x 6.00 x 4.50 (393.7 x 152.4 x 114.3)
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-31
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
BABRP and BABRSP Breakers—
Single- and Two-Pole
Contents
Description Page
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-2
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW V4-T1-5
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGF, QPHGF, QPGFEP, QPHGFEP V4-T1-8
Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . . . V4-T1-11
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-14
Bolt-On Ground Fault and Equipment Protectors,
Types QBGF, QBHGF, QBGFEP, QBHGFEP . . . . . . . . V4-T1-17
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-20
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-24
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGF, QCHGF, QCGFEP, QCHGFEP V4-T1-28
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-32
Technical Data and Specifications. . . . . . . . . . . . V4-T1-33
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-33
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers. . . . . . . . V4-T1-34
International Rated Types HQP, BA, QC, GFMB, GFXBC V4-T1-37
Special Application Breakers, Types HQP, BA, QC. . . . V4-T1-40
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP
Product Description
The BABRP and BABRSP
are bolt-on branch circuit
breakers designed for use in
panelboards. The BRRP is a
plug-on branch circuit breaker
designed for use in load-
centers not manufactured
with breakers with a 1-inch
wide format and are listed on
the “Compatibility list for
Classified Applications”—
Pub. 26271. In addition to
providing conventional branch
circuit protection, they include
a unique solenoid-operated
mechanism that provides for
efficient breaker pulse-on and
pulse-off opera
tion when used
with a suitable controller
like
Eaton’s Pow-R-Command™
lighting control system.
These breakers can also be
controlled by pushbutton or
a PLC unit.
Application Description
Eaton’s BABRP, BABRSP,
BRRP and CLRP breakers are
remotely operated molded
case circuit breakers ideally
suited for lighting control
applications or energy
management applications.
Features, Benefits and Functions
Bolt-on line-side terminal
(BABRP, BABRSP—
Type BA)
Plug-on line-side terminal
(BRRP—Type BR, CLRP—
Type CL)
Cable connected load-side
terminal
Four-position control
terminal
Bi-metal assembly for
thermal overload
protection
Fast-acting short-circuit
protection
Arc-chute assembly for
fast-acting arc extinction
Three-position handle: OFF,
TRIP (Center), ON
Handle permits manual
switching when control
power is lost
Mechanical trip indicator
15 and 20A breakers SWD
(switching duty) rated
HID ratings for HID (high
intensity discharge) lighting
All models HACR rated
Status feedback of control
circuit (BABRSP)
Series rated (BABRP,
BABRSP only)
BRRP series rated same
as BR breakers
BABRP, BABRSP same
as BA breakers
V4-T1-32 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Product Selection
BABRP UL 489 and CSA 22.2 Interrupting
Ratings
BABRP and BABRSP Wire Harness
BABRSP UL 489 and CSA 22.2 Interrupting
Ratings
Number
of Poles
Interrupting Capacity (Symmetrical Amperes)
Ampere
Rating 1
Vac (50/60 Hz) Catalog
Number 120 120/240 277/480
1 15 10,000 BABRP1015
20 10,000 BABRP1020
25 10,000 BABRP1025
30 10,000 BABRP1030
2 15 10,000 BABRP2015
20 10,000 BABRP2020
25 10,000 BABRP2025
30 10,000 BABRP2030
Description
Catalog
Number
This 60-inch (1524.0 mm) wire pigtail provides
a connection from a single BABRP’s control plug to
a customer’s pushbutton, relay or PLC. Each box
contains 12 pigtails. Wires are 22 AWG, 600V.
Order in multiples of 12.
SLBKRPTL1
Number
of Poles
Interrupting Capacity (Symmetrical Amperes)
Ampere
Rating 1
Vac (50/60 Hz) Catalog
Number120 120/240 277/480
1 15 10,000 BABRSP1015
20 10,000 BABRSP1020
25 10,000 BABRSP1025
30 10,000 BABRSP1030
2 15 10,000 BABRSP2015
20 10,000 BABRSP2020
25 10,000 BABRSP2025
30 10,000 BABRSP2030
QUICKLAG Type QCGF
Single-Pole Ground
Fault Circuit Breaker
BRRP UL 489 and CSA 22.2 Interrupting
Ratings
CLRP UL 489 and CSA 22.2 Interrupting
Ratings
Note
1Continuous current rating at 40°C.
Number
of Poles
Interrupting Capacity (Symmetrical Amperes)
Ampere
Rating
Vac (50/60 Hz) Catalog
Number120 120/240
1 15 10,000 BRRP115
20 10,000 BRRP120
25 10,000 BRRP125
30 10,000 BRRP130
2 15 10,000 BRRP215
20 10,000 BRRP220
25 10,000 BRRP225
30 10,000 BRRP230
Number
of Poles
Interrupting Capacity (Symmetrical Amperes)
Ampere
Rating
Vac (50/60 Hz) Catalog
Number120 120/240
1 15 10,000 CLRP115
20 10,000 CLRP120
25 10,000 CLRP125
30 10,000 CLRP130
2 15 10,000 CLRP215
20 10,000 CLRP220
25 10,000 CLRP225
30 10,000 CLRP230
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-33
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Technical Data and Specifications
Solenoid Operating Data
Power requirements: 24
Vac/dc (20.4V minimum–
30V maximum)
Controlled signal:
+AC/DC 8 ms minimum
with zero cross, 300 ms
maximum
AC: 1.3 cycles minimum,
18 cycles or 300 ms
maximum
DC: 8 ms minimum,
300 ms maximum
Maximum duty cycle of
6 OPEN/CLOSE cycles
per minute
Current draw: open 1A,
close 3/4A
Blue wire: power input
(see power requirements)
Black wire: remote opening
Red wire: remote closing
Yellow wire: feedback
status from power input,
maximum 0.50A draw
(BABRSP only)
Operation
Tripping system—the
BABRP, BABRSP, BRRP
and CLRP circuit breakers
have a permanent trip
unit that contains a factory
preset thermal (overload)
trip element in each pole
Operating mechanism—
the BABRP, BABRSP, BRRP
and CLRP circuit breakers
have an over-center toggle
mechanism that provides
quick-make, quick-break
operation. The operating
mechanism is trip free. An
internal cross-bar provides
a common tripping of all
multi-pole circuit breakers
Operating/Application Data
Ambient temperature:
0 to 40°C
Nominal pulse magnitude:
24 Vac/dc
Frequency: 50/60 Hz
Maximum breaker cycling:
6 operations per minute
Tolerance: +10% to –15%
of nominal voltage
Humidity: 0 to 95%
noncondensing
Wiring Diagrams
Control Circuit for the BABRP and BABRSP
Line
Remote
Contact
Breaker
Contact
RM
bRM
a
Red
Black
Yellow
Blue
On
Coil Off
Coil Remote
Status
Load Line
Remote
Contact
Breaker
Contact
RM
bRM
a
Red
Black
Yellow
Blue
On
Coil Off
Coil Remote
Status
BKR
a
BABRP BABRSP
Load
V4-T1-34 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
GHBS and GHQRSP
Contents
Description Page
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-2
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW V4-T1-5
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGF, QPHGF, QPGFEP, QPHGFEP V4-T1-8
Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . . V4-T1-11
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-14
Bolt-On Ground Fault and Equipment Protectors,
Types QBGF, QBHGF, QBGFEP, QBHGFEP . . . . . . . V4-T1-17
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-20
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-24
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGF, QCHGF, QCGFEP, QCHGFEP V4-T1-28
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP. . . . . . . . . V4-T1-31
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-35
Technical Data and Specifications . . . . . . . . . . . . V4-T1-36
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-36
International Rated Types HQP, BA, QC, GFMB, GFXBC V4-T1-37
Special Application Breakers, Types HQP, BA, QC . . . V4-T1-40
Solenoid Operator—Remote-Controlled Latching
for Type GHBS, GBHS and GHQRSP Breakers
Product Description
Eaton’s GHBS, GBHS and
GHQRSP circuit breakers
are bolt-on branch circuit
breakers designed for use
in 277/480 Vac panelboards.
In addition to providing
conventional branch circuit
protection, they include a
unique solenoid-operated
mechanism that provides
for efficient breaker pulse-on
and pulse-off operation
when used with a suitable
controller like Eaton’s
Pow-R-Command lighting
control system.
Features, Benefits
and Functions
Bolt-on line-side terminal
Cable-connected load-side
terminal
Status switch—remote
status and breaker status
available from internal
auxiliary switches
Bi-metal assembly for
thermal overload
protection
Fast-acting short-circuit
protection
Arc-runner and arc-chute
assembly for fast-acting arc
extinction
Three-position breaker
handle: OFF, TRIP (Center),
ON
Visual indication of the
remotely operated
contact’s position (open,
closed or trip)
Remote override handle
permits manual switching
when control power is lost
15 and 20A breakers SWD
(switching duty) rated.
15 and 20A breakers HID
rated for HID (High
intensity discharge) lighting
All models HACR rated
Series rated with various
Eaton main circuit breakers
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-35
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Product Selection
GHBS UL 489 Interrupting Ratings
GBHS CSA 22.2 Interrupting Ratings (Not UL Listed)
GHQRSP UL 489 and CSA 22.2 Interrupting Ratings
Notes
1 Continuous current rating at 40°C.
2 All UL listed circuit breakers are HID (high intensity discharge) rated.
Number
of Poles
Interrupting Capacity (Symmetrical Amperes)
Ampere
Rating 1
Vac (50/60 Hz)
Catalog Number 120 240 277/480
1 15 65,000 14,000 GHBS1015D
20 65,000 14,000 GHBS1020D
30 65,000 14,000 GHBS1030D
2 15 65,000 14,000 GHBS2015D
20 65,000 14,000 GHBS2020D
30 65,000 14,000 GHBS2030D
Number
of Poles
Interrupting Capacity (Symmetrical Amperes)
Ampere
Rating 1
Vac (50/60 Hz)
Catalog Number347/600
1 15 10,000 GBHS1015D
20 10,000 GBHS1020D
2 15 10,000 GBHS2015D
20 10,000 GBHS2020D
Number
of Poles
Interrupting Capacity (Symmetrical Amperes)
Ampere
Rating
1
Vac (50/60 Hz)
Catalog Number
2
120 120/240 277 480Y/277
1 15 65,000 65,000 14,000 14,000
GHQRSP1015
20 65,000 65,000 14,000 14,000
GHQRSP1020
30 65,000 65,000 14,000 14,000
GHQRSP1030
2 15 65,000 65,000 14,000 14,000
GHQRSP2015
20 65,000 65,000 14,000 14,000
GHQRSP2020
30 65,000 65,000 14,000 14,000
GHQRSP2030
GHBS—Single-Pole
V4-T1-36 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Technical Data and Specifications
Solenoid Operating Data
Power requirements: 24
Vac/dc (20.4V minimum–
30V maximum)
Controlled signal: +AC/
DC 8 ms minimum with
zero cross, 300 ms
maximum
AC: 1.3 cycles minimum,
18 cycles or 300 ms
maximum
DC: 8 ms minimum,
300 ms maximum
Maximum duty cycle of
6 OPEN/CLOSE cycles
per minute
Current draw: open 1A,
close 3/4A
Blue wire: power input
(see power requirements)
Black wire: remote opening
Red wire: remote closing
Yellow wire: feedback
status from power input,
maximum 0.50A draw
Operation
Mechanism manually
operated by external handle
allowing ON, OFF and RESET
operation. Handle assumes a
center TRIP position after
performing protective
response.
Operating/Application Data
Ambient temperature:
0–40°C
Frequency: 48–62 Hz
Humidity: 0–95%
noncondensing
Terminal Type
Circuit Breaker
Type
Circuit Breaker
Amperes
Screw
Head Type
Terminal
Type Range
GHQRSP 15–20 Slotted Clamp #14–#4 AWG
Wiring Diagrams
Typical Single-Pole Circuit Breaker Schematic Diagram for
GHBS and GBHS Breakers
Typical Single-Pole Circuit Breaker Schematic Diagram for
GHQRSP Breakers
Dimensions
Approximate Dimensions in Inches (mm)
Dimensions per Pole
Notes
1Purchase separate AMP Inc. conductor plug #640426-3.
2Excluding line terminal.
3Excluding handle.
1
Line
Breaker
Contact
Remote
Contact
Load
Yellow
GHQRSP
Red
Status
Black
On
Coil
Off
Coil
Blue
Power
Input
Circuit Breaker Type Width Height 2Length 3
GHQRSP 1.00 (25.4) 4.63 (117.6) 2.81 (71.4)
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-37
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
International Rated
Contents
Description Page
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-2
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW V4-T1-5
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGF, QPHGF, QPGFEP, QPHGFEP V4-T1-8
Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . . . V4-T1-11
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-14
Bolt-On Ground Fault and Equipment Protectors,
Types QBGF, QBHGF, QBGFEP, QBHGFEP . . . . . . . . V4-T1-17
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-20
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-24
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGF, QCHGF, QCGFEP, QCHGFEP V4-T1-28
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP . . . . . . . . . V4-T1-31
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers. . . . . . . . V4-T1-34
International Rated Types HQP, BA, QC, GFMB, GFXBC
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-38
Technical Data and Specifications. . . . . . . . . . . . V4-T1-39
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-39
Special Application Breakers, Types HQP, BA, QC. . . . V4-T1-40
International Rated Types HQP, BA, QC, GFMB, GFXBC
Product Description
QUICKLAG International Circuit
Breakers
Bolt-on Type BA
QUICKLAG International Ground
Fault Circuit Breakers
Plug-on Type GFMB
Cable-in/cable-out Type
GFXBC
Standards and Certifications
QUICKLAG International Circuit
Breakers
Built and test certified to
BS3871, Pt. 1
50/60 Hz, 40°C
QUICKLAG International Ground
Fault Circuit Breakers
Built and test certified to
BS3871, Pt. 1; BS3871,
Section 31-C; BS4293
50/60 Hz, 40°C; 30 mA
sensitivity
V4-T1-38 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Product Selection
Breaker Catalog Numbers
Breaker Catalog Numbers—Ground Fault Single-Pole 30 mA Sensitivity
Note
For other 240/415V applications, please contact the Customer Support Center at 1-800-356-1243.
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole Three-Pole
240/415 Vac 240/415 Vac 240/415 Vac
Catalog Number Catalog Number Catalog Number
3000A Interrupting Capacity (M3) Bolt-On Thermal-Magnetic Circuit Breakers
10 BAB1010E BAB2010E BAB3010E
15 BAB1015E BAB2015E BAB3015E
16 ———
20 BAB1020E BAB2020E BAB3020E
25 BAB1025E BAB2025E BAB3025E
30 BAB1030E BAB2030E BAB3030E
32 ———
40 BAB1040E BAB2040E BAB3040E
50 BAB1050E BAB2050E BAB3050E
60 BAB1060E BAB2060E BAB3060E
70 BAB1070E BAB2070E BAB3070E
90 BAB2090E BAB3090E
100 BAB2100E BAB3100E
6000A Interrupting Capacity (M6) Bolt-On Thermal-Magnetic Circuit Breakers
15 BAB1015HE BAB2015HE BAB3015HE
20 BAB1020HE BAB2020HE BAB3020HE
25 BAB1025HE BAB2025HE BAB3025HE
30 BAB1030HE BAB2030HE BAB3030HE
40 BAB1040HE BAB2040HE BAB3040HE
50 BAB1050HE BAB2050HE BAB3050HE
60 BAB1060HE BAB2060HE BAB3060HE
70 BAB1070HE BAB2070HE BAB3070HE
90 BAB2090HE BAB3090HE
100 BAB2100HE BAB3100HE
Continuous
Ampere Rating
at 40°C
240/415 Vac
Catalog Number
3000A Interrupting Capacity (M3) Plug-On Thermal-Magnetic Circuit Breakers
10 GFMB110B2
15 GFMB115B2
16 GFMB116B2
20 GFMB120B2
25 GFMB125B2
30 GFMB130B2
32 GFMB132B2
40 GFMB140B2
BAB
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-39
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Technical Data and Specifications
Interrupting Ratings
Dimensions
Approximate Dimensions in Inches (mm)
Shipping Data
Ratings Suffix E Suffix HE
International Circuit Breakers
NEMA®
120/240 Vac
10,000 AIC 10,000 AIC
BS3871 220/380,
240/415 Vac
3000 AIC 6000 AIC
International Ground Fault Circuit Breakers
BS3871 220/380,
240/415 Vac
3000 AIC
Miniature
Circuit Breaker
Number
of Poles
Standard Carton
Quantity
Approximate Carton
Weight Lbs (kg)
Approximate
Standard Carton
QUICKLAG Type B 1 24 9.00 (4.1) 12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)
2 12 9.00 (4.1) 12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)
3 8 9.00 (4.1) 12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)
QUICKLAG Ground Fault
Type P—All 1 20 11.00 (5.0) 12.50 x 6.50 x 5.00 (317.5 x 165.1 x 127.0)
Types B and C—All 1 20 11.00 (5.0) 12.50 x 7.00 x 5.50 (317.5 x 177.8 x 139.7)
Types P and B—All 2 5 5.00 (2.3) 12.50 x 6.00 x 4.50 (317.5 x 152.4 x 114.3)
V4-T1-40 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
QUICKLAG Type P Switching Neutral
Contents
Description Page
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-2
QUICKLAG Plug-On Types HQP, QPHW, QHPX, QHPW V4-T1-5
QUICKLAG Plug-On Ground Fault and Equipment
Protectors, Types QPGF, QPHGF, QPGFEP, QPHGFEP V4-T1-8
Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . . V4-T1-11
Bolt-On Arc Fault Circuit Interrupter Types
QBAF, QBCAF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-14
Bolt-On Ground Fault and Equipment Protectors,
Types QBGF, QBHGF, QBGFEP, QBHGFEP . . . . . . . V4-T1-17
Cable-In/Cable-Out Types QC, QCD, QCHW,
QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-20
Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF,
QCRH, QCFH. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-24
Cable-In/Cable-Out Ground Fault and Equipment
Protectors, Types QCGF, QCHGF, QCGFEP, QCHGFEP V4-T1-28
Solenoid-Operated, Remote-Controlled Latching
Types BABRP, BABRSP, BRRP and CLRP . . . . . . . . . V4-T1-31
Solenoid Operator—Remote Controlled Latching for
Type GHBS, GBHS and GHQRSP Breakers . . . . . . . V4-T1-34
International Rated Types HQP, BA, QC, GFMB, GFXBC V4-T1-37
Special Application Breakers, Types HQP, BA, QC
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-41
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-43
Factory Modifications and Installed Terminals . . V4-T1-46
Technical Data and Specifications . . . . . . . . . . . . V4-T1-47
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-48
Special Application Breakers, Types HQP, BA, QC
Product Description
Breakers
Plug-on Type HQP:
10–30A, single- and
two-pole, 10 kAIC
Bolt-on Type BA: 10–30A,
single- and two-pole,
10 kAIC
Cable-in Type QC: 10–30A,
single- and two-pole,
10 kAIC
Switching neutral QUICKLAG
breakers available in single-
and two-pole configurations,
plus neutral pole for
applications in accordance
with NEC® 514.5, 240.22 and
380.2. A single-pole device
takes two pole spaces, and a
two-pole device takes three
pole spaces.
QUICKLAG HID (High Intensity
Discharge) Breakers
Plug-on Type HQP:
15–60A, single- and
two-pole, 10 kAIC
Bolt-on Type BA: 15–60A,
single- and two-pole,
10 kAIC
Cable-in Type QC: 15–60A,
single- and two-pole,
10 kAIC
Breakers designed
specifically for use with high
intensity discharge (HID)
lighting applications. (UL
listed as standard lighting
breakers.)
Molded Case Switches—Non-
automatic QUICKLAG Molded
Case Switch
Plug-on Type HQP: 50,
60,100A, single-, two- and
three-pole
Bolt-on Type BA: 50,
60,100A, single-, two- and
three-pole
Cable-in Type QC: 50,
60,100A, single-, two- and
three-pole
Standards and Certifications
All products UL and
CSA listed
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-41
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Product Selection
Breaker Catalog Numbers
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole Two-Pole Three-Pole
120/240 Vac 120/240 Vac 240 Vac 240 Vac
Catalog Number Catalog Number Catalog Number Catalog Number
QUICKLAG Type: HQP Switching Neutral Thermal-Magnetic Breakers
10 HQP2010B HQP3010B
15 HQP2015B HQP3015B
20 HQP2020B HQP3020B
25 HQP2025B HQP3025B
30 HQP2030B HQP3030B
QUICKLAG Type: BA Switching Neutral Thermal-Magnetic Breakers
10 BAB2010C BAB3010C
15 BAB2015C BAB3015C
20 BAB2020C BAB3020C
25 BAB2025C BAB3025C
30 BAB2030C BAB3030C
QUICKLAG Type: QC Switching Neutral Thermal-Magnetic Breakers
10 QC2010B QC3010B
15 QC2015B QC3015B
20 QC2020B QC3020B
25 QC2025B QC3025B
30 QC2030B QC3030B
QUICKLAG Type: HQP HID (High Intensity Discharge) Thermal-Magnetic Breakers
15 HQP1015D HQP2015D
20 HQP1020D HQP2020D
25 HQP1025D HQP2025D
30 HQP1030D HQP2030D
35 HQP1035D HQP2035D
40 HQP1040D HQP2040D
50 HQP1050D HQP2050D
60 HQP1060D HQP2060D
QUICKLAG Type: BA HID (High Intensity Discharge) Thermal-Magnetic Breakers
15 BAB1015D BAB2015D
20 BAB1020D BAB2020D
25 BAB1025D BAB2025D
30 BAB1030D BAB2030D
35 BAB1035D BAB2035D
40 BAB1040D BAB2040D
50 BAB1050D BAB2050D
60 BAB1060D BAB2060D
QUICKLAG Type: QC HID (High Intensity Discharge) Thermal-Magnetic Breakers
15 QC1015D QC2015D
20 QC1020D QC2020D
25 QC1025D QC2025D
30 QC1030D QC2030D
35 QC1035D QC2035D
40 QC1040D QC2040D
50 QC1050D QC2050D
60 QC1060D QC2060D
QUICKLAG Type P
Switching Neutral
V4-T1-42 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Breaker Catalog Numbers, continued
Continuous
Ampere Rating
at 40°C
Single-Pole Two-Pole Two-Pole Three-Pole
120/240 Vac 120/240 Vac 240 Vac 240 Vac
Catalog Number Catalog Number Catalog Number Catalog Number
QUICKLAG Type: HQP Non-Automatic Switches
50 HQP1050N HQP2050N HQP3050N
60 HQP1060N HQP2060N HQP3060N
100 HQP1100N HQP2100N HQP3100N
QUICKLAG Type: BA Non-Automatic Switches
50 BAB1050N BAB2050N BAB3050N
60 BAB1060N BAB2060N BAB3060N
100 BAB1100N BAB2100N BAB3100N
QUICKLAG Type: QC Non-Automatic Switches
50 QC1050N QC2050N QC3050N
60 QC1060N QC2060N QC3060N
100 QC1100N QC2100N QC3100N
QUICKLAG Type: QCD Non-Automatic Switches
60 QCD2060NA
100 ————
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-43
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Accessories 1
Handle Locks: Non-Padlockable 2
Handle Locks: Padlockable 2
Notes
1 See Page V4-T1-27 for QCR and QCF accessories.
2 Can lock in ON or OFF position.
Description Order in Multiples of Catalog Number
QUICKLAG Type P, B, C—single-pole 10 QL1NPL
QUICKLAG Type P, B, C—two- and three-pole 10 QL23NPL
Description Order in Multiples of Catalog Number
QUICKLAG Type P, B, C—single-pole 10 QL1PL
QUICKLAG Type P, B and ground fault—single-, two- and three-pole 10 QL123PL
QUICKLAG Type C —single-, two- and three-pole 10 QC123PL
QUICKLAG Type P, B—single-, two- and three-pole (off only) 10 QL123PLOFF
QUICKLAG Type C—single-, two- and three-pole (off only) 10 QC123PLOFF
QL1NPL
QL23NPL
QL1PL
QL123PL
QC123PL
V4-T1-44 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Mounting Hardware
Note
1 Suitable for ground fault breakers.
Description Order in Multiples of Catalog Number
QUICKLAG Type C face mounting clip 24 QCFCLIP
QUICKLAG Type C face mounting plate—single-pole 10 QC1FP
QUICKLAG Type C face mounting plate—two-pole 10 QC2FP
QUICKLAG Type C face mounting plate—three-pole 10 QC3FP
QUICKLAG Type C face mounting plate and lock-off (off only)—two-pole 110 QC2FPLOFF
QUICKLAG Type C face mounting plate and lock-off (off only)—three-pole 10 QC3FPLOFF
QUICKLAG Type C base mounting clamp 10 QCBCLIP
QUICKLAG Type mounting plate—six poles total 10 QC6BP
QCFCLIP
QC1FP
QC2FP
QC3FP
QCBCLIP
QC6BP
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-45
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Mounting Hardware, continued
Dummy Breakers
Miscellaneous
Handle Tie
Description Order in Multiples of Catalog Number
QUICKLAG Type C base mounting plate—six poles total—heavy-duty screw-secured 10 QC6BPS
QUICKLAG Type C (QCD) 2-way jumper unit with cover 10 QCDJ2
QUICKLAG Type C (QCD) 4-way jumper unit with cover 10 QCDJ4
QUICKLAG Type C (QCD) 6-way jumper unit with cover 10 QCDJ6
QUICKLAG Type C (QCD) 2-way jumper unit, no cover 10 QCDJ2T
QUICKLAG Type C (QCD) 4-way jumper unit, no cover 10 QCDJ4T
QUICKLAG Type C (QCD) 6-way jumper unit, no cover 10 QCDJ6T
QUICKLAG Type QCD Finger protection attachment 10 QCDFP
QUICKLAG Type QCD 4-prong Quick Connect 10 QCDQUICK
QUICKLAG Type C DIN rail adapter 6 QCDINADAPT
QUICKLAG Type QCD ring lug attachment 10 QCDRING
Description Order in Multiples of Catalog Number
QUICKLAG Type P 1HQP1000
QUICKLAG Type B 1BAB1000
QUICKLAG Type C 1QC1000
QUICKLAG Type C clear choice breaker 4 QC30SAMPLE
Description Order in Multiples of Catalog Number
QUICKLAG Type C Spacer 1 QCRSPACER
Description Order in Multiples of Catalog Number
QUICKLAG handle tie—single-pole 100 QL1HT
QCDJ4
QCDINADAPT
QCDRING
QCRSPACER
QL1HT
V4-T1-46 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Factory Modifications and Installed Terminals
Factory Modifications 1
Spare Terminal Hardware Screws (Lugs not Included)
Notes
1Contact Eaton for factory modifications available for QCR and QCF breakers.
2Q = 32 Vdc; Q1 = 32–40 Vdc; Q2 = 37.5 Vdc; Q3 = 45 Vdc; Q4 = 48 Vdc; Q5 = 50 Vdc; Q6 = 62.5 Vdc; Q7 = 75 Vdc (2P); Q8 = 80 Vdc (2P); Q9 = 125 Vdc (QCR 2P); Q10 = 62.5 Vdc (QCR 1P).
Type of Modification Breaker Type Catalog Suffix
Shunt trip (requires one extra pole space on right side)
120, 208, 240 Vac
Draws 2.6A at 120V, draws 11A at 24 Vdc QUICKLAG Types P, B and C S
Shunt trip (requires one extra pole space on right side)
24, 48 Vac/dc
Draws 2.6A at 120V, draws 11A at 24 Vdc QUICKLAG Types P, B and C S1
Special calibration (50°C) (no UL) QUICKLAG Types P, B and C V
Shock testing QUICKLAG Types P, B and C L
Freeze testing QUICKLAG Types P, B and C Y
Moisture-fungus treatment QUICKLAG Types P, B, C and ground fault F
Marine duty QUICKLAG Types P, B, C H08
Naval duty QUICKLAG Types P, B, C H09
400 Hz calibration QUICKLAG Types P, B, C G
Specific DC ratings (breaker marked with a max. Vdc rating) QUICKLAG Types P, B, C Q thru Q9 2
Terminal Type Description Order in Multiples of Catalog Number
1 QUICKLAG terminal screw 10 QLLDTSA
2 QUICKLAG terminal screw 10 QLLDTSB
3 QUICKLAG terminal screw 10 QLLDTSC
5 QUICKLAG binding head terminal screw and clamp 10 QLBHTSE
6 and 7 QUICKLAG terminal screw 10 QLLNTSFG
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-47
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Technical Data and Specifications
Factory-Installed Breaker Terminals
Note
1Clamp on line side only.
Breaker
Type
Continuous
Ampere
Rating
Standard Line Terminal Standard Load Terminal Optional Terminals
Terminal
Type
Wire
Type
Wire
Range (AWG)
Terminal
Type
Wire
Type
Wire
Range (AWG) Line Load
QUICKLAG Type P
HQP, QPHW,
QHPX, QHPW
10–30 Plug-on female clips that mate
with the bus stabs 1 Cu/Al 14–4 N/A 3
35–50 2 Cu/Al 14–4 N/A 3
55–125 3 Cu/Al 8–1/0 N/A
QUICKLAG ground fault
QPGF, QPGFEP,
QPHGF, QPHGFEP
10–40 Plug-on female clips that mate
with the bus stabs 1 (single-pole) Cu/Al 14–4 N/A 3
10–40 1 Cu/Al N/A 3
10–30 1 Cu 14–8 N/A
QUICKLAG Type B
BAB, QBHW,
HBAX, HBAW
10–40 Extended tangs that bolt
directly to the bus 1 (single- and two-pole) Cu/Al 14–4 N/A 3
35–50 2 (three-pole) Cu/Al 14–4 N/A 3
55–125 3 Cu/Al 8–1/0 N/A
QUICKLAG ground fault
QBGF, QBGFEP,
QBHGFEP, QBHGF
10–40 Extended tangs that bolt
directly to the bus 1 (single-pole) Cu/Al 14–4 N/A N/A
10–40 1 Cu/Al 14–8 N/A N/A
10–30 1 Cu 14–8 N/A N/A
QUICKLAG Type C
QC, QCHW,
QHCX, QHCW
10–20 5 Cu/Al TBD 5 Cu/Al 14–10 6, 7 6, 7, 8
25–60 6 Cu/Al TBD 2 Cu/Al 14–4 5, 7 5, 6, 7, 8
70–100 7 Cu/Al TBD 3 Cu/Al 8–1/0 5 5, 7, 8
QUICKLAG
QCR, QCF 10–55 1 Cu/Al TBD 1 Cu/Al 14–4 N/A N/A
60 1 Cu TBD 1 Cu 14–4 N/A N/A
QUICKLAG ground fault
QCGF, QCGFEP,
QCHGF, QCHGFEP
10–20 6 Cu/Al TBD 14–8 Cu/Al 14–4 6, 7 5
25–50 6 Cu/Al TBD 1 Cu/Al 14–4 5, 7 5
10–30 6
QUICKLAG
QCD 10–60 9 Cu/Al 14–4 9 Cu/Al 14–4 See Accessories
70–100 10 Cu 4–1/0 10 Cu 4–1/0 See Accessories
4-Prong Quick Connect
12 3 5
67 8
1
Steel Box Lug Steel Box Lug Steel Box Lug
Aluminum Box Lug Aluminum Box Lug
Steel Ring Type
9
QCD Terminal Assembly
10–60A
10
QCD Terminal Assembly
70–100A
V4-T1-48 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.1
Miniature Circuit Breakers and Supplementary Protectors
Industrial Circuit Breakers
Dimensions
Approximate Dimensions in Inches (mm)
Shipping Data
Miniature
Circuit Breaker
Number
of Poles
Standard
Carton
Quantity
Approximate
Carton Weight
Lbs (kg)
Approximate Standard
Carton
QUICKLAG Types B, P, C–all 1 24 9.00 (4.1) 12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)
QUICKLAG Types B, P, C–all 2 12 9.00 (4.1) 12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)
QUICKLAG Types B, P, C–all 3 8 9.00 (4.1) 12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)
QUICKLAG ground fault Type P–all 1 20 11.00 (5.0) 12.50 x 6.50 x 5.00 (317.5 x 165.1 x 127.0)
Types B and C–all 1 20 11.00 (5.0) 12.50 x 7.00 x 5.50 (317.5 x 177.8 x 139.7)
Types P and B–all 2 5 5.00 (2.3) 12.50 x 6.00 x 4.50 (317.5 x 152.4 x 114.3)
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-49
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Optimum and Efficient Protection for Every Application
FAZ-NA Circuit Breakers
Contents
Description Page
FAZ-NA Circuit Breakers
Catalog Number Selection . . . . . . . . . . . . . . . . V4-T1-50
Product Selection . . . . . . . . . . . . . . . . . . . . . . . V4-T1-51
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-55
Technical Data and Specifications . . . . . . . . . . V4-T1-57
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-66
WMZ Circuit Breaker. . . . . . . . . . . . . . . . . . . . . . . V4-T1-67
FAZ-NA Circuit Breakers
Product Overview
Optimum product quality,
tested reliability and safety
stand for best protection of
personnel, installations and
plant. Eaton’s FAZ-NA DIN rail
mountable circuit breaker is
designed for use in branch
service applications.
Powerful Offering for Machine
and System Builders
The FAZ-NA is available with
B, C and D characteristics in
accordance with UL® 489,
CSA® C22.2 No.5; UL 1077,
CSA C22.2 No.235 and IEC
60947-2. These devices are
CE marked.
Application Description
Feeder and branch circuit
protection for:
Convenience receptacle
circuits (internal/external)
Motor control circuits
Load circuits leaving the
equipment (external)
HACR internal/external
equipment (heating,
air
conditioning, refrigeration)
PLC I/O points
Computers
Power supplies
Control instrumentation
Relays
UPS
Power conditioners
Features
Complete range of UL 489
listed DIN rail mounted
miniature circuit breakers
up to 40A current rating
Standard ratings of 10 kAIC
up to 277/480 Vac
Select amperages available
at 14 kAIC up to 277/480
Vac and 10 kAIC up to 125
Vdc per pole
Current limiting design
provides fast short-circuit
interruption that reduces
the let-through energy,
which can damage the
circuit
Suitable for branch circuit
device protection
Thermal-magnetic
overcurrent protection
Three levels of short-
circuit protection,
categorized by B, C
and D curves
Trip-free design—breaker
can not be defeated by
holding the handle in the
ON position
Captive screws cannot
be lost
SWD (switching duty)—
suitable for switching
fluorescent lighting loads
(In ≤ 20A)
Fulfill UL 489, CSA C22.2
No.5 and also IEC 60947-2
Standard
For use in applications for
which UL 1077 or CSA
C22.2 No.235 are also
allowed
Field-installable shunt trip
and auxiliary switch
subsequent mounting
Separate version for ring-
tongue connection (Type
FAZ-RT), terminal screws
can be removed (on
both sides)
Module width of only
17.7 mm (per pole)
Contact Position Indicator
(red/green)
Easy installation on DIN rail
Possibility for sealing the
toggle in ON or OFF
position
Device Printing on Front and Side
Installation options
These branch circuit breakers
are available in two terminal
configurations: standard box
terminals that accept multiple
conductors and ring-tongue
terminals, ideally suited to
demanding requirements of
the semi-conductor industry.
All breakers mount on
standard 35 mm DIN rail.
Bus connectors and feeder
terminal facilitate mounting
and wiring of multiple
miniature circuit breaker
arrays in control panel
assemblies. These circuit
breakers can also be
reverse feed.
V4-T1-50 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Standards and Certifications
FAZ-NA complies with
the latest national and
international standards.
UL 489
Standard for molded
case circuit breakers
(MCCB) for feeder and
branch circuit protection
Products meet the
requirements of the
National Electrical Code®
(NEC®)
CSA C22.2 No.5
Standard for molded
case circuit breakers
(MCCB) for feeder and
branch circuit protection
(corresponds closely to
UL 489 Standard)
Products meet the
requirements of the
Canadian Electrical Code
(CEC)
RoHS compliant
VDE compliant
ABS compliant
Catalog Number Selection
Notes
1In = Rated current for instantaneous trip characteristics.
2B curve starts at 1 ampere.
Breaker Family
FAZ = FAZ UL
circuit breaker Ampere Rating 2
0.5 =0.5A
1=1A
1.5 =1.5A
2=2A
3=3A
4=4A
5=5A
6=6A
7=7A
8=8A
10 = 10A
13 = 13A
15 = 15A
16 = 16A
20 = 20A
25 = 25A
30 = 30A
32 = 32A
35 = 32A
40 = 40A
Trip
Characteristics 1
B = 3–5X In
C = 5–10X In
D = 10–20X In
Number of Poles
1 = Single-pole
2 = Two-pole
3 = Three-pole
Single Package
SP = Single package for
C and D curve
single-pole only
Blank = Standard
packaging
Terminal
NA = UL 489 branch
circuit with screw
terminals
RT = UL 489 branch
circuit with ring
tongue terminals
DC = UL 489 branch
circuit at 125 Vdc
per pole
FAZ C 6 / 1 NA SP
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-51
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Product Selection
FAZ-NA B Curve
UL approved (UL 489) and CSA Certified (CSA C22.2 No.5-02)
as branch circuit breakers
Interrupting capacity: 10 kA UL/CSA; 15 kA IEC 60947-2
Current limiting device
UL file number E235139
FAZ-NA UL 489 Circuit Breakers—10 kAIC,
14 kAIC B Curve (15–25A)
Single-Pole 1Two-Pole Three-Pole
Amperes
Catalog
Number
Catalog
Number
Catalog
Number
B Curve (3–5X In Current Rating)
1FAZ-B1/1-NA FAZ-B1/2-NA FAZ-B1/3-NA
1.5 FAZ-B1.5/1-NA FAZ-B1.5/2-NA FAZ-B1.5/3-NA
2FAZ-B2/1-NA FAZ-B2/2-NA FAZ-B2/3-NA
3FAZ-B3/1-NA FAZ-B3/2-NA FAZ-B3/3-NA
4FAZ-B4/1-NA FAZ-B4/2-NA FAZ-B4/3-NA
5FAZ-B5/1-NA FAZ-B5/2-NA FAZ-B5/3-NA
6FAZ-B6/1-NA FAZ-B6/2-NA FAZ-B6/3-NA
7FAZ-B7/1-NA FAZ-B7/2-NA FAZ-B7/3-NA
8FAZ-B8/1-NA FAZ-B8/2-NA FAZ-B8/3-NA
10 FAZ-B10/1-NA FAZ-B10/2-NA FAZ-B10/3-NA
13 FAZ-B13/1-NA FAZ-B13/2-NA FAZ-B13/3-NA
15 FAZ-B15/1-NA FAZ-B15/2-NA FAZ-B15/3-NA
16 FAZ-B16/1-NA FAZ-B16/2-NA FAZ-B16/3-NA
20 FAZ-B20/1-NA FAZ-B20/2-NA FAZ-B20/3-NA
25 FAZ-B25/1-NA FAZ-B25/2-NA FAZ-B25/3-NA
30 FAZ-B30/1-NA FAZ-B30/2-NA FAZ-B30/3-NA
32 FAZ-B32/1-NA FAZ-B32/2-NA FAZ-B32/3-NA
35 2FAZ-B35/1-NA FAZ-B35/2-NA FAZ-B35/3-NA
40 2FAZ-B40/1-NA FAZ-B40/2-NA FAZ-B40/3-NA
Single-Pole
Two-Pole
Three-Pole
FAZ-RT UL 489 Circuit Breakers with
Ring-Tongue Terminals—10 kAIC, 14 kAIC
B Curve (15–25A)
Notes
1 Two-piece order. Quantities of two per box.
2 240 Vac rated only.
Single-Pole 1Two-Pole Three-Pole
Amperes
Catalog
Number
Catalog
Number
Catalog
Number
B Curve with Ring-Tongue Terminals
(3–5X In Current Rating)
1FAZ-B1/1-RT FAZ-B1/2-RT FAZ-B1/3-RT
1.5 FAZ-B1.5/1-RT FAZ-B1.5/2-RT FAZ-B1.5/3-RT
2FAZ-B2/1-RT FAZ-B2/2-RT FAZ-B2/3-RT
3FAZ-B3/1-RT FAZ-B3/2-RT FAZ-B3/3-RT
4FAZ-B4/1-RT FAZ-B4/2-RT FAZ-B4/3-RT
5FAZ-B5/1-RT FAZ-B5/2-RT FAZ-B5/3-RT
6FAZ-B6/1-RT FAZ-B6/2-RT FAZ-B6/3-RT
7FAZ-B7/1-RT FAZ-B7/2-RT FAZ-B7/3-RT
8FAZ-B8/1-RT FAZ-B8/2-RT FAZ-B8/3-RT
10 FAZ-B10/1-RT FAZ-B10/2-RT FAZ-B10/3-RT
13 FAZ-B13/1-RT FAZ-B13/2-RT FAZ-B13/3-RT
15 FAZ-B15/1-RT FAZ-B15/2-RT FAZ-B15/3-RT
16 FAZ-B16/1-RT FAZ-B16/2-RT FAZ-B16/3-RT
20 FAZ-B20/1-RT FAZ-B20/2-RT FAZ-B20/3-RT
25 FAZ-B25/1-RT FAZ-B25/2-RT FAZ-B25/3-RT
30 FAZ-B30/1-RT FAZ-B30/2-RT FAZ-B30/3-RT
32 FAZ-B32/1-RT FAZ-B32/2-RT FAZ-B32/3-RT
35 2FAZ-B35/1-RT FAZ-B35/2-RT FAZ-B35/3-RT
40 2FAZ-B40/1-RT FAZ-B40/2-RT FAZ-B40/3-RT
0.0005
t [sec]
N
I / I
7200
3600
1200
600
300
120
60
30
10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.005
0.01
0.002
0.001
5040302015
1098765432
1
1.13
1.45
1
1
B
2
3
Specied non-tripping
current
INT = 1.13 x IN for t > 1 h
Specied tripping current
IT = 1.45 x IN for t < 1 h
2.55 IN:
t = 1–60 s (IN < 32A)
t = 1–120 s (IN > 32A)
Type B: 3 x IN: t > 0.1 s
Type B: 5 x IN: t < 0.1 s
Single-Pole
Two-Pole
Three-Pole
V4-T1-52 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
FAZ-NA C Curve
UL approved (UL 489) and CSA Certified (CSA C22.2 No.5-02)
as branch circuit breakers
Interrupting capacity: 10 kA UL/CSA; 15 kA IEC 60947-2
Current limiting device
UL file number E235139
FAZ-NA UL 489 Circuit Breakers—10 kAIC,
14 kAIC C Curve (15–25A)
Single-Pole 1Two-Pole Three-Pole
Amperes
Catalog
Number
Catalog
Number
Catalog
Number
C Curve (5–10X In Current Rating)
0.5 FAZ-C0.5/1-NA-SP FAZ-C0.5/2-NA FAZ-C0.5/3-NA
1FAZ-C1/1-NA-SP FAZ-C1/2-NA FAZ-C1/3-NA
1.5 FAZ-C1.5/1-NA-SP FAZ-C1.5/2-NA FAZ-C1.5/3-NA
2FAZ-C2/1-NA-SP FAZ-C2/2-NA FAZ-C2/3-NA
3FAZ-C3/1-NA-SP FAZ-C3/2-NA FAZ-C3/3-NA
4FAZ-C4/1-NA-SP FAZ-C4/2-NA FAZ-C4/3-NA
5FAZ-C5/1-NA-SP FAZ-C5/2-NA FAZ-C5/3-NA
6FAZ-C6/1-NA-SP FAZ-C6/2-NA FAZ-C6/3-NA
7FAZ-C7/1-NA-SP FAZ-C7/2-NA FAZ-C7/3-NA
8FAZ-C8/1-NA-SP FAZ-C8/2-NA FAZ-C8/3-NA
10 FAZ-C10/1-NA-SP FAZ-C10/2-NA FAZ-C10/3-NA
13 FAZ-C13/1-NA-SP FAZ-C13/2-NA FAZ-C13/3-NA
15 FAZ-C15/1-NA-SP FAZ-C15/2-NA FAZ-C15/3-NA
16 FAZ-C16/1-NA-SP FAZ-C16/2-NA FAZ-C16/3-NA
20 FAZ-C20/1-NA-SP FAZ-C20/2-NA FAZ-C20/3-NA
25 FAZ-C25/1-NA-SP FAZ-C25/2-NA FAZ-C25/3-NA
30 FAZ-C30/1-NA-SP FAZ-C30/2-NA FAZ-C30/3-NA
32 FAZ-C32/1-NA-SP FAZ-C32/2-NA FAZ-C32/3-NA
35 2FAZ-C35/1-NA-SP FAZ-C35/2-NA FAZ-C35/3-NA
40 2FAZ-C40/1-NA-SP FAZ-C40/2-NA FAZ-C40/3-NA
Single-Pole
Two-Pole
Three-Pole
FAZ-RT UL 489 Circuit Breakers with
Ring-Tongue Terminals—10 kAIC, 14 kAIC
C Curve (15–25A)
Notes
1 Option for single packaging on single-pole C and D curves only;
add suffix SP when ordering.
2 240 Vac rated only.
Single-Pole 1Two-Pole Three-Pole
Amperes
Catalog
Number
Catalog
Number
Catalog
Number
C Curve with Ring-Tongue Terminals
(5–10X In Current Rating)
0.5 FAZ-C0.5/1-RT-SP FAZ-C0.5/2-RT FAZ-C0.5/3-RT
1FAZ-C1/1-RT-SP FAZ-C1/2-RT FAZ-C1/3-RT
1.5 FAZ-C1.5/1-RT-SP FAZ-C1.5/2-RT FAZ-C1.5/3-RT
2FAZ-C2/1-RT-SP FAZ-C2/2-RT FAZ-C2/3-RT
3FAZ-C3/1-RT-SP FAZ-C3/2-RT FAZ-C3/3-RT
4FAZ-C4/1-RT-SP FAZ-C4/2-RT FAZ-C4/3-RT
5FAZ-C5/1-RT-SP FAZ-C5/2-RT FAZ-C5/3-RT
6FAZ-C6/1-RT-SP FAZ-C6/2-RT FAZ-C6/3-RT
7FAZ-C7/1-RT-SP FAZ-C7/2-RT FAZ-C7/3-RT
8FAZ-C8/1-RT-SP FAZ-C8/2-RT FAZ-C8/3-RT
10 FAZ-C10/1-RT-SP FAZ-C10/2-RT FAZ-C10/3-RT
13 FAZ-C13/1-RT-SP FAZ-C13/2-RT FAZ-C13/3-RT
15 FAZ-C15/1-RT-SP FAZ-C15/2-RT FAZ-C15/3-RT
16 FAZ-C16/1-RT-SP FAZ-C16/2-RT FAZ-C16/3-RT
20 FAZ-C20/1-RT-SP FAZ-C20/2-RT FAZ-C20/3-RT
25 FAZ-C25/1-RT-SP FAZ-C25/2-RT FAZ-C25/3-RT
30 FAZ-C30/1-RT-SP FAZ-C30/2-RT FAZ-C30/3-RT
32 FAZ-C32/1-RT-SP FAZ-C32/2-RT FAZ-C32/3-RT
35 2FAZ-C35/1-RT-SP FAZ-C35/2-RT FAZ-C35/3-RT
40 2FAZ-C40/1-RT-SP FAZ-C40/2-RT FAZ-C40/3-RT
0.0005
t [sec]
N
I / I
7200
1.13
1.45
3600
1200
600
300
120
60
30
10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.005
0.01
0.002
0.001
5040302015
1098765432
1
1
C
2
Specied non-tripping
current
INT = 1.13 x IN for t > 1 h
Specied tripping current
IT = 1.45 x IN for t < 1 h
Type C: 5 x IN: t > 0.1 s
Type C: 10 x IN: t < 0.1 s
Single-Pole
Two-Pole
Three-Pole
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-53
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
FAZ-NA D Curve
UL approved (UL 489) and CSA Certified (CSA C22.2 No.5-02)
as branch circuit breakers
Interrupting capacity: 10 kA UL/CSA; 15 kA IEC 60947-2
Current limiting device
UL file number E235139
FAZ-NA UL 489 Circuit Breakers—10 kAIC,
14 kAIC D Curve (13–20A)
Single-Pole 1Two-Pole Three-Pole
Amperes
Catalog
Number
Catalog
Number
Catalog
Number
D Curve (10–20X In Current Rating)
0.5 FAZ-D0.5/1-NA-SP FAZ-D0.5/2-NA FAZ-D0.5/3-NA
1FAZ-D1/1-NA-SP FAZ-D1/2-NA FAZ-D1/3-NA
1.5 FAZ-D1.5/1-NA-SP FAZ-D1.5/2-NA FAZ-D1.5/3-NA
2FAZ-D2/1-NA-SP FAZ-D2/2-NA FAZ-D2/3-NA
3FAZ-D3/1-NA-SP FAZ-D3/2-NA FAZ-D3/3-NA
4FAZ-D4/1-NA-SP FAZ-D4/2-NA FAZ-D4/3-NA
5FAZ-D5/1-NA-SP FAZ-D5/2-NA FAZ-D5/3-NA
6FAZ-D6/1-NA-SP FAZ-D6/2-NA FAZ-D6/3-NA
7FAZ-D7/1-NA-SP FAZ-D7/2-NA FAZ-D7/3-NA
8FAZ-D8/1-NA-SP FAZ-D8/2-NA FAZ-D8/3-NA
10 FAZ-D10/1-NA-SP FAZ-D10/2-NA FAZ-D10/3-NA
13 FAZ-D13/1-NA-SP FAZ-D13/2-NA FAZ-D13/3-NA
15 FAZ-D15/1-NA-SP FAZ-D15/2-NA FAZ-D15/3-NA
16 FAZ-D16/1-NA-SP FAZ-D16/2-NA FAZ-D16/3-NA
20 FAZ-D20/1-NA-SP FAZ-D20/2-NA FAZ-D20/3-NA
25 FAZ-D25/1-NA-SP FAZ-D25/2-NA FAZ-D25/3-NA
30 FAZ-D30/1-NA-SP FAZ-D30/2-NA FAZ-D30/3-NA
32 FAZ-D32/1-NA-SP FAZ-D32/2-NA FAZ-D32/3-NA
35 2FAZ-D35/1-NA-SP FAZ-D35/2-NA FAZ-D35/3-NA
40 2FAZ-D40/1-NA-SP FAZ-D40/2-NA FAZ-D40/3-NA
Single-Pole
Two-Pole
Three-Pole
FAZ-RT UL 489 Circuit Breakers with
Ring-Tongue Terminals—10 kAIC, 14 kAIC
D Curve (13–20A)
Notes
1 Option for single packaging on single-pole C and D curves only;
add suffix SP when ordering.
2 240 Vac rated only.
Single-Pole 1Two-Pole Three-Pole
Amperes
Catalog
Number
Catalog
Number
Catalog
Number
D Curve with Ring-Tongue Terminals
(10–20X In Current Rating)
0.5 FAZ-D0.5/1-RT-SP FAZ-D0.5/2-RT FAZ-D0.5/3-RT
1FAZ-D1/1-RT-SP FAZ-D1/2-RT FAZ-D1/3-RT
1.5 FAZ-D1.5/1-RT-SP FAZ-D1.5/2-RT FAZ-D1.5/3-RT
2FAZ-D2/1-RT-SP FAZ-D2/2-RT FAZ-D2/3-RT
3FAZ-D3/1-RT-SP FAZ-D3/2-RT FAZ-D3/3-RT
4FAZ-D4/1-RT-SP FAZ-D4/2-RT FAZ-D4/3-RT
5FAZ-D5/1-RT-SP FAZ-D5/2-RT FAZ-D5/3-RT
6FAZ-D6/1-RT-SP FAZ-D6/2-RT FAZ-D6/3-RT
7FAZ-D7/1-RT-SP FAZ-D7/2-RT FAZ-D7/3-RT
8FAZ-D8/1-RT-SP FAZ-D8/2-RT FAZ-D8/3-RT
10 FAZ-D10/1-RT-SP FAZ-D10/2-RT FAZ-D10/3-RT
13 FAZ-D13/1-RT-SP FAZ-D13/2-RT FAZ-D13/3-RT
15 FAZ-D15/1-RT-SP FAZ-D15/2-RT FAZ-D15/3-RT
16 FAZ-D16/1-RT-SP FAZ-D16/2-RT FAZ-D16/3-RT
20 FAZ-D20/1-RT-SP FAZ-D20/2-RT FAZ-D20/3-RT
25 FAZ-D25/1-RT-SP FAZ-D25/2-RT FAZ-D25/3-RT
30 FAZ-D30/1-RT-SP FAZ-D30/2-RT FAZ-D30/3-RT
32 FAZ-D32/1-RT-SP FAZ-D32/2-RT FAZ-D32/3-RT
35 2FAZ-D35/1-RT-SP FAZ-D35/2-RT FAZ-D35/3-RT
40 2FAZ-D40/1-RT-SP FAZ-C40/2-RT FAZ-D40/3-RT
0.0005
t [sec]
N
I / I
7200
3600
1200
600
300
120
60
30
10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.005
0.01
0.002
0.001
5040302015
1098765432
1
1.13
1.45
D
1
1
2
3
Specied non-tripping
current
INT = 1.13 x IN for t > 1 h
Specied tripping current
IT = 1.45 x IN for t < 1 h
2.55 IN:
t = 1–60 s (IN < 32A)
t = 1–120 s (IN > 32A)
Type D: 10 x IN: t > 0.1 s
Type D: 20 x IN: t < 0.1 s
Single-Pole
Two-Pole
Three-Pole
V4-T1-54 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
FAZ-NA-DC C Curve
UL approved (UL 489) and CSA Certified (CSA C22.2 No.5-02)
as Branch Circuit Breakers
Interrupting capacity: 10 kA at 125 Vdc UL/CSA, 10 kA
at 250 Vdc
125 Vdc for one-pole, 250 Vdc for two-pole in series
Current limiting device
Polarity (+/–) sensitive and not for use on photovoltaic
string application
UL file number E235139
FAZ-NA-DC UL 489 Circuit Breakers—
10 kAIC at 125 Vdc Per Pole
Note
1 Option for single packaging on single-pole C curves only; add
suffix SP when ordering.
Single-Pole 1Two-Pole
Amperes
Catalog
Number
Catalog
Number
C Curve (5–10X In Current Rating)
2FAZ-C2/1-NA-DC-SP FAZ-C2/2-NA-DC
3FAZ-C3/1-NA-DC-SP FAZ-C3/2-NA-DC
4FAZ-C4/1-NA-DC-SP FAZ-C4/2-NA-DC
5FAZ-C5/1-NA-DC-SP FAZ-C5/2-NA-DC
6FAZ-C6/1-NA-DC-SP FAZ-C6/2-NA-DC
7FAZ-C7/1-NA-DC-SP FAZ-C7/2-NA-DC
8FAZ-C8/1-NA-DC-SP FAZ-C8/2-NA-DC
10 FAZ-C10/1-NA-DC-SP FAZ-C10/2-NA-DC
13 FAZ-C13/1-NA-DC-SP FAZ-C13/2-NA-DC
15 FAZ-C15/1-NA-DC-SP FAZ-C15/2-NA-DC
16 FAZ-C16/1-NA-DC-SP FAZ-C16/2-NA-DC
20 FAZ-C20/1-NA-DC-SP FAZ-C20/2-NA-DC
25 FAZ-C25/1-NA-DC-SP FAZ-C25/2-NA-DC
30 FAZ-C30/1-NA-DC-SP FAZ-C30/2-NA-DC
32 FAZ-C32/1-NA-DC-SP FAZ-C32/2-NA-DC
35 FAZ-C35/1-NA-DC-SP FAZ-C35/2-NA-DC
40 FAZ-C40/1-NA-DC-SP FAZ-C40/2-NA-DC
Single-Pole
Two-Pole
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-55
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Accessories
FAZ-NA UL 489 Breakers
Description Catalog Number
Two-pole contact or auxiliary
contact/trip indicating contact
Z-NHK 1
Auxiliary contact Z-IHK-NA
Shunt trip 110–415 Vac FAZ-XAA-NA110-415VAC
Shunt trip 12–110 Vac FAZ-XAA-NA12-110VAC
Padlock hasp IS/SPE-1TE
Contact
Auxiliary Contact
Shunt Trip
Padlock Hasp
FAZ-NA UL 489 Breakers, continued
Notes
1Voltage of FAZ-NA circuit breaker is limited to 300V with this auxiliary contact installed.
2Do not cut commoning link.
3A maximum of three commoning links may be used in conjunction. Each breaker connected to
the commoning link must have the same number of poles for proper use.
4Not for use with ring-tongue circuit breakers.
5Bus may be center fed for high current capacity.
Description Catalog Number
Busbar—single-pole, 6 terminals 2345 Z-SV/UL-16/1P-1TE/6
Busbar—single-pole, 12 terminals 2345 Z-SV/UL-16/1P-1TE/12
Busbar—single-pole, 18 terminals 2345 Z-SV/UL-16/1P-1TE/18
Busbar—two-pole, 6 terminals 2345 Z-SV/UL-16/2P-2TE/6
Busbar—two-pole, 12 terminals 2345 Z-SV/UL-16/2P-2TE/12
Busbar—two-pole, 18 terminals 2345 Z-SV/UL-16/2P-2TE/18
Busbar—three-pole, 6 terminals 2345 Z-SV/UL-16/3P-3TE/6
Busbar—three-pole, 12 terminals 2345 Z-SV/UL-16/3P-3TE/12
Busbar—three-pole, 18 terminals 2345 Z-SV/UL-16/3P-3TE/18
Three-pole busbar shroud ZV-BS-UL
Extension terminal—
35 mm2 (2–14 AWG)
Z-EK/35/UL
Bus connector—conductors up to
50 mm2 (~1/0 AWG)
Z-EB/50/UL
Busbar
Busbar Shroud
Bus Connector
Extension Terminal
V4-T1-56 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Tripping Signal Switch Z-NHK, Z-IHK-NA
Design according to IEC/EN 60947-5-1, IEC/EN 62019
Field installable
The specified minimum voltages are per contact—take into
account particularly in case of series connection
Self-cleaning contacts
Contact material and design particularly suitable for extra
low voltage
Z-NHK: the function of one of the two change-over
contacts can be switched from “auxiliary switch” to
“tripping signal switch”
Tripping signal contact transmits message of electric tripping,
not mechanical switch-off
Test key for contact function “electrical tripping”
Z-IHK-NA: will allow for > 480Y/277 Vac rating
Connection Diagram
Busbar Connection Example
Z-NHK
21
4.11
1.11
1.14
1.12
4.12/4.14
4.14/4.12
13
22
14
Same Polarity
Z-IHK-NA
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-57
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Technical Data and Specifications
Trip Curve Chart
Eaton FAZ-NA branch circuit
breakers are available with
“B,” “C” and “D” tripping
characteristics. B-curve
devices are suitable for
applications where low
levels of inrush current
are expected.
C-curve devices are suitable
for applications where
medium levels of inrush
current are expected.
Applications include small
transformers, lighting, pilot
devices, control circuits and
coils. C-curve devices provide
a medium magnetic trip point.
D-curve devices are suitable
for applications where high
levels of inrush current are
expected. The high magnetic
trip point prevents nuisance
tripping in high inductive
applications such as motors,
transformers and power
supplies.
Eaton FAZ-NA devices are
current limiting, which means
they interrupt fault currents
within one half cycle of the
fault. Current limiting devices
offer superior protection by
reducing peak let-through
current and energy.
Tripping Characteristics
V4-T1-58 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Miniature Circuit Breakers FAZ-NA Technical Data
Description Specification
Electrical
Design according to UL 489, CSA C22.2 No.5, IEC 60947-2
Rated voltage FAZ-NA
UL/CSA 10 kAIC at 277/480V from 0.5A to 32A
14 kAIC at select amperages
B and C Curves (15–25A), D Curve (13–20A)
UL/CSA 10 kAIC at 240 Vac for 35A and 40A
UL/CSA 10 kAIC at 48 Vdc per pole
IEC 947-2 15 kAIC at 240/415 Vac
Rated voltage FAZ-NA-DC
UL/CSA 10 kAIC at 125 Vdc per pole (two poles maximum)
10 kAIC at 250 Vdc with two poles connected in series
Rated frequency 50/60 Hz
Characteristic B, C, D
Endurance ≥ 20,000 operations
Line voltage connection Suitable for reverse feed
Mechanical
Frame size 45 mm
Device height 105 mm
Device width 17.7 mm per pole
Terminal protection Finger and hand touch safe according to BGV A3, OVE-EN 6
Mounting Quick fastening with two lock-in positions on IEC/EN 60715
Upper and lower terminals Open mouth/lift terminals
Terminal capacity One wire: AWG 18–6
Two wires: AWG 18–10
Terminal fastening torque AWG 18–21: 21 lb-in
AWG 10–8: 25 lb-in
AWG 6: 36 lb-in
Mounting Independent of position
Calibration temperature
UL 489, CSA C22.2 No.5 40°C
IEC 60947-2 30°C
Two-Pole
Three-Pole
Connection Diagrams
Single-Pole
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-59
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Power Loss at ln
Characteristic B Characteristic C Characteristic D
Single-Pole Two-Pole Three-Pole Single-Pole Two-Pole Three-Pole Single-Pole Two-Pole Three-Pole
In [A] P [W] P [W] P [W] P [W] P [W] P [W] P [W] P [W] P [W]
0.5 ———1.6 3.2 4.7 1.6 3.2 4.8
1.0 1.1 2.2 3.4 1.1 2.2 3.4 0.8 1.5 2.3
1.5 2.2 4.4 6.6 1.3 2.6 3.9 1.0 2.1 3.1
2.0 1.4 2.8 4.3 1.4 2.8 4.3 1.0 2.1 3.1
3.0 2.1 4.2 6.4 1.2 2.4 3.6 1.2 2.4 3.6
4.0 1.4 2.9 4.3 1.4 2.9 4.3 1.4 2.9 4.3
5.0 1.8 3.7 5.5 1.9 3.7 5.6 1.5 2.9 4.4
6.0 1.7 3.5 5.2 1.2 2.3 3.5 1.2 2.3 3.5
7.0 2.0 4.0 6.0 1.4 2.8 4.3 1.4 2.8 4.3
8.0 2.0 3.9 5.9 1.4 2.8 4.2 1.2 2.4 3.7
10.0 1.8 3.6 5.3 1.8 3.6 5.3 1.5 3.0 4.5
13.0 2.4 4.7 7.1 2.4 4.7 7.1 2.0 4.1 6.1
15.0 1.9 3.8 5.6 1.9 3.8 5.6 1.5 3.1 4.6
16.0 2.1 4.3 6.4 2.1 4.3 6.4 1.7 3.5 5.2
20.0 2.9 5.8 8.7 2.9 5.8 8.7 1.8 3.7 5.5
25.0 3.1 6.2 9.3 3.1 6.2 9.3 2.6 5.1 7.7
30.03.06.09.03.06.09.02.75.48.1
32.0 3.4 6.8 10.2 3.4 6.8 10.2 3.1 6.2 9.3
35.0 4.0 8.1 12.1 3.7 7.4 11.0 3.8 7.6 11.3
40.0 4.0 8.1 12.1 4.0 8.1 12.1 3.9 7.8 11.6
V4-T1-60 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Let-Through Energy
Characteristic B (1–32A), 277V
Characteristic C (0.5–32A), 277V
Characteristic B (35–40A), 240V
Characteristic C (40A), 240V
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-61
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Characteristic D (0.5–32A), 277V Characteristic D (40A), 240V
V4-T1-62 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Influence of Ambient Temperature T on Load Carrying Capacity
Load Carrying Capacity of Adjoining Miniature
Circuit Breakers
Device Market
Current Rating In
(A) at 40°C
In (A) at Higher Ambient Temperature
15°C 20°C 25°C 30°C 40°C 50°C 55°C 60°C
0.50.60.50.50.50.50.50.50.5
1.01.11.11.11.01.01.00.90.9
1.51.71.61.61.61.51.41.41.4
2.02.22.22.12.12.01.91.91.8
3.03.33.23.23.13.02.92.92.8
4.04.44.34.24.24.03.83.83.7
5.05.55.45.35.25.04.84.74.6
6.06.66.56.46.26.05.85.65.5
7.07.77.67.47.37.06.76.66.4
8.08.88.68.58.38.07.77.57.4
10.0 11.0 10.8 10.6 10.4 10.0 9.6 9.4 9.2
13.0 14.3 14.0 13.8 13.5 13.0 12.5 12.5 12.0
15.0 16.5 16.2 15.9 15.6 15.0 14.4 14.1 13.8
16.0 17.6 17.3 17.0 16.6 16.0 15.4 15.0 14.7
20.0 22.0 21.6 21.2 20.8 20.0 19.2 18.8 18.4
25.0 27.5 27.0 26.5 26.0 25.0 24.0 23.3 23.0
30.0 33.0 32.4 31.8 31.2 30.0 28.8 28.2 27.6
32.0 35.2 34.6 33.9 33.3 32.0 30.7 30.1 29.4
40.0 44.0 43.2 42.4 41.6 40.0 38.4 37.6 36.8
Ambient Temperature T [°C]
Maximum Load IL at ambient temperature T: IL (T) = IN KT(T)
Load Factor KT [I/IN]
Number of Circuit Breakers
Rated Diversity Factor
12345678
0.70
0.80
0.90
1.0 0
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-63
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Contact and Auxiliary Contact
Description Z-NHK Z-IHK-NA
Electrical
Contact function 2CO 1NO + 1NC
Rated voltage 230V 250V
Frequency 50/60 Hz 50/60 Hz
Rated current 2A 6A
Rated thermal current Ith 2A 6A
Utilization category AC13
Rated operational current Ie3A/250 Vac 3A/250 Vac
Utilization category AC15
Rated operational current Ie2A/250 Vac 2A/250 Vac
Utilization category DC12
Rated operational current Ie0.5A/110 Vdc 0.5A/110 Vdc
0.25A/220 Vdc
Rated insulation voltage UI250 Vac 250 Vac
Minimum operational voltage per contact Umin 5 Vdc 5 Vdc
Minimum operational current Imin 10 mA DC 10 mA AC/DC
Rated peak withstand voltage Uimp (1.2/50µ) 2.5 kV 4 kV
Conditional short-circuit current Ik with backup fuse 6A 1 kA 1 kA
Max. backup fuse, overload and short circuit 6A gL
Mechanical
Tripping indicator “electrical tripping” Blue/white
Frame size 45 mm 45 mm
Device height 80 mm 80 mm
Device width 8.8 mm (0.5MU) 8.8 mm (0.5MU)
Mounting Onto switching device
Degree of protection, built-in IP40 IP40
Terminal protection Finger and hand touch safe
According to BGV A3, ÖVE-EN 6
Finger and hand touch safe
According to BGV A3, ÖVE-EN 6
Terminals Lift terminals Lift terminals
Terminal capacity 20–14 AWG 0.5–2.5 mm2
Terminal screws M3 (Posidrive Z0) M3 (Posidrive Z0)
Fastening torque of terminal screws 7 lb-in Max. 1.2 Nm
Z-NHK
Z-IHK-NA
V4-T1-64 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Shunt trip release FAZ-XAA-NA
Remote release for subsequent mounting onto FAZ-NA/RT
Additional installation of standard auxiliary switch is possible
Position indicator red–green
Shunt Trip Release FAZ-XAA-NA
Busbar block UL 489 (pin)
Tested according to UL 489
Do not cut
Extension terminal 35 mm2 Z-EK/35/UL for copper conductors
Incoming terminal 50 mm2 Z-EB/50/UL
For covering of not used pins, use busbar tag shrouds ZV-BS-UL
Busbar Block UL 489 (Pin)
Description FAZ-XAA-NA12-110VAC FAZ-XAA-NA110-415VAC
Electrical
Can be
mounted onto
FAZ-NA / FAZ-NA-DC /
FAZ-RT
FAZ-NA / FAZ-NA-DC /
FAZ-RT
Operational
voltage range
12–110 Vac
12–60 Vdc
110–415 Vac
110–230 Vdc
Frequency 50/60 Hz 50/60 Hz
Mechanical
Frame size 45 mm 45 mm
Device height 105 mm 105 mm
Device width 17.5 mm 17.5 mm
Mounting Quick fastening with two lock-in positions on EN 50022
Degree of protection, built-in IP40 IP40
Terminal protection Finger and hand touch safe according to BGV A3, ÖVE-EN 6
Terminals Open mouthed/lift Open mouthed/lift
Terminal capacity
One and two wires
18–10 AWG 18–10 AWG
Description UL 489 IEC/EN 60947-2
Electrical
Rated operational voltage 480/277 Vac
96 Vdc
Rated frequency 50/60 Hz
Rated voltage 480 Vac 690 Vac
Overvoltage category III
Rated impulse withstand voltage Uimp —9.5 kV
Rated current 80A at 40°C 80A at 30°C
Rated conditional short-circuit current AC with 350A gG 15 kA
Short-circuit current 10 kA
Mechanical
Busbar cross section 16 mm2 Cu
Flame class according to UL 94 V0
Pollution degree 2
Comparative tracking index CTI 600
Minimum clearance (internal/external) > 9.5/25.4 mm
Minimum creepage distance (internal/external) > 12.7/50.8 mm
Resistance to climatic conditions According to
DIN/EN 60068
Connection Diagram
1
2
Connection Diagrams
Single-Pole Busbar
Two-Pole Busbar
Three-Pole Busbar
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-65
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Application Guidelines
Example of UL 489 and UL 1077 Application
UL 489 circuit breakers
Used for branch circuit protection, internal/external receptacles, external motors and HACR equipment
(heating, air conditioning and refrigeration).
UL 1077 supplementary protectors
Used for overcurrent protection within appliances or electrical equipment, where branch circuit protection
is already provided or not required.
Note: UL 4 89 devices can be used in place of UL 1077; UL 1077 devices cannot be used in place of UL 489.
Electronics
Internal Receptacle
UL 489
Breaker
UL 489
Branch
UL 1077
UL 1077
UL 1077
UL 489
Branch
UL 489
Branch
UL 489
Branch
External
Receptacle
External
Motor
M
M
External
Motor
Motor
Controller
Other
Sensitive
Devices
HACR
Example of UL 489 and UL 1077 Application
V4-T1-66 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Dimensions
Approximate Dimensions in Inches (mm)
Miniature Circuit Breakers
Accessories
Z-EK/35/UL
4.13
(105.0)
Single-Pole Two-Pole Three-Pole
.70
(17.7)
.70
(17.7)
1.39
(35.3)
2.09
(53.1)
.70
(17.7)
.70
(17.7)
4.13
(105.0)
4.13
(105.0)
Z-SV/UL-16.../18 Z-EK/35/UL
Z-SV/UL-16/6 Z-SV/UL-18...12 ZV-BS-UL
Description UL 489 IEC/EN 60947-2
Ue480 Vac/96 Vdc 240/415 Vac
f 50/60 Hz 50/60 Hz
Uimp —9.5 kV
Ie80A at 40°C 80A at 30°C
#2–14 AWG 60/75°C Cu 2.5–35 mm2 Cu
0.56 in 14 mm
Lockout Attachment—IS/SPE-ITE
Z-EB/50/UL
Description UL 489 IEC/EN 60947-2
Ue480 Vac/96 Vdc 240/415 Vac
f 50/60 Hz 50/60 Hz
Uimp —9.5 kV
Ie115A at 40°C 160A at 30°C
#1–14 AWG 60/75°C Cu 1.5–50 mm2 Cu
0.56 in 14 mm
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-67
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Optimum and Efficient Protection for Every Application
WMZ Circuit Breakers
Contents
Description Page
FAZ-NA Circuit Breakers . . . . . . . . . . . . . . . . . . . . V4-T1-49
WMZ Circuit Breaker
Standards and Certifications . . . . . . . . . . . . . . V4-T1-68
Catalog Number Selection . . . . . . . . . . . . . . . . V4-T1-69
Product Selection . . . . . . . . . . . . . . . . . . . . . . . V4-T1-70
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-72
Technical Data and Specifications . . . . . . . . . . V4-T1-73
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-80
WMZ Circuit Breaker
Product Overview
Optimum product quality,
tested reliability and safety
stand for best protection of
personnel, installations and
plant. Eaton’s WMZ DIN rail
mountable circuit breaker is
designed for use in branch
service applications.
Application Description
Feeder and branch circuit
protection for:
Convenience receptacle
circuits (internal/external)
Motor control circuits
Load circuits leaving the
equipment (external)
HACR internal/external
equipment (heating, air
conditioning, refrigeration)
PLC I/O points
Computers
Power supplies
Control instrumentation
Relays
UPS
Power conditioners
Features
Complete range of UL 489
listed DIN rail mounted
miniature circuit breakers
up to 40A current rating
Standard ratings of 10 kAIC
at 277/480 Vac
Select amperages available
at 14 kAIC at 277/480 Vac
and 10 kAIC at125 Vdc
Current limiting design
provides fast short-circuit
interruption that reduces
the let-through energy,
which can damage
the circuit
Suitable for branch circuit
device protection
Thermal-magnetic
overcurrent protection
Two levels of short-
circuit protection,
categorized by C and
D curves
Trip-free design—breaker
can not be defeated by
holding the handle in the
ON position
Captive screws cannot
be lost
SWD (switching duty)—
suitable for switching
fluorescent lighting loads
(In d 20A)
For use in applications for
which UL 1077 or CSA
C22.2 No.235 are also
allowed
Field-installable shunt trip
and auxiliary switch
subsequent mounting
Separate version for ring-
tongue connection (Type
WMZT….T), terminal
screws can be removed
(on both sides)
Module width of only
17.7 mm (per pole)
Contact Position Indicator
(red/green)
Easy installation on DIN rail
Possibility for sealing the
toggle in ON or OFF
position
V4-T1-68 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Device Printing on Front and Side
Installation options
These branch circuit breakers
are available in two terminal
configurations: standard box
terminals that accept multiple
conductors and ring-tongue
terminals, ideally suited to
demanding requirements of
the semi-conductor industry.
All breakers mount on
standard 35 mm DIN rail.
Bus connectors and feeder
terminal facilitate mounting
and wiring of multiple
miniature circuit breaker
arrays in control panel
assemblies. These circuit
breakers can also be
reverse feed.
Conductor Type
Calibration
Te m p e ra t u r e
UL/CSA
Rated Voltage
UL/CSA
Breaker Status
Indicator
Rated Current
Catalog Number
Standards and Certifications
UL 489
Standard for molded case
circuit breakers (MCCB) for
feeder and branch circuit
protection
Products meet the
requirements of the
National Electrical Code®
(NEC)
Powerful Offering for Machine
and System Builders
The WMZ is available with
C and D characteristics in
accordance with UL 489,
CSA C22.2 No.5; UL 1077,
CSA C22.2 No.235 and
IEC 60947-2.
CSA C22.2 No.5
Standard for molded case
circuit breakers for feeder
and branch circuit
protection (corresponds
closely to UL 489
Standard)
Products meet the
requirements of the
Canadian Electrical Code
(CEC)
These devices are RoHS
compliant
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-69
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Catalog Number Selection
Notes
1Limited curve and ampere offerings.
2125 Vdc for single-pole, 250 Vdc for two-pole in series.
3Not offered for Type WMZD.
Breaker Family
WMZ = WMZ UL
circuit breaker
Ampere Rating
X0 = 0.5A
01 = 1A
X1 = 1.5A
02 = 2A
03 = 3A
04 = 4A
05 = 5A
06 = 6A
07 = 7A
08 = 8A
10 = 10A
13 = 13A
15 = 15A
16 = 16A
20 = 20A
25 = 25A
30 = 30A
32 = 32A
40 = 40A
Breaker Type
T =10 kAIC
H =14 kAIC
D =10 kAIC/DC 12
Number of Poles
1 = Single-pole
2 = Two-pole
3 = Three-pole 3
Protective Curve
C = C Curve (5–10X In)
D = D Curve (10–20X In) 3
Terminal
T = Ring terminals
[blank] = Standard box
terminals
WMZ T 1 C 16 T
V4-T1-70 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Product Selection
WMZT
WMZT UL 489 Circuit Breakers—10 kAIC
Single-Pole Two-Pole Three-Pole
Amperes
Catalog
Number
Catalog
Number
Catalog
Number
C Curve (5–10X In Current Rating)
0.5 WMZT1CX0 WMZT2CX0 WMZT3CX0
1WMZT1C01 WMZT2C01 WMZT3C01
1.5 WMZT1CX1 WMZT2CX1 WMZT3CX1
2WMZT1C02 WMZT2C02 WMZT3C02
3WMZT1C03 WMZT2C03 WMZT3C03
4WMZT1C04 WMZT2C00 WMZT3C04
5WMZT1C05 WMZT2C05 WMZT3C05
6WMZT1C06 WMZT2C06 WMZT3C06
7WMZT1C07 WMZT2C07 WMZT3C07
8WMZT1C08 WMZT2C08 WMZT3C08
10 WMZT1C10 WMZT2C10 WMZT3C10
13 WMZT1C13 WMZT2C13 WMZT3C13
15 WMZT1C15 WMZT2C15 WMZT3C15
16 WMZT1C16 WMZT2C16 WMZT3C16
20 WMZT1C20 WMZT2C20 WMZT3C20
25 WMZT1C25 WMZT2C25 WMZT3C25
30 WMZT1C30 WMZT2C30 WMZT3C30
32 WMZT1C32 WMZT2C32 WMZT3C32
40 WMZT1C40 WMZT2C40 WMZT3C40
D Curve (10–20X In Current Rating)
0.5 WMZT1DX0 WMZT2DX0 WMZT3DX0
1WMZT1D01 WMZT2D01 WMZT3D01
1.5 WMZT1DX1 WMZT2DX1 WMZT3DX1
2WMZT1D02 WMZT2D02 WMZT3D02
3WMZT1D03 WMZT2D03 WMZT3D03
4WMZT1D04 WMZT2D04 WMZT3D04
5WMZT1D05 WMZT2D05 WMZT3D05
6WMZT1D06 WMZT2D06 WMZT3D06
7WMZT1D07 WMZT2D07 WMZT3D07
8WMZT1D08 WMZT2D08 WMZT3D08
10 WMZT1D10 WMZT2D10 WMZT3D10
13 WMZT1D13 WMZT2D13 WMZT3D13
15 WMZT1D15 WMZT2D15 WMZT3D15
16 WMZT1D16 WMZT2D16 WMZT3D16
20 WMZT1D20 WMZT2D20 WMZT3D20
25 WMZT1D25 WMZT2D25 WMZT3D25
30 WMZT1D30 WMZT2D30 WMZT3D30
32 WMZT1D32 WMZT2D32 WMZT3D32
40 WMZT1D40 WMZT2D40 WMZT3D40
Single-Pole
Two-Pole
Three-Pole
WMZT UL 489 Circuit Breakers with
Ring-Tongue Terminals—10 kAIC
Notes
Interrupting capacity: 10 kA UL/CSA; 15 kA IEC 60947.
Optional connections for ring-tongue terminals.
Single-Pole Two-Pole Three-Pole
Amperes
Catalog
Number
Catalog
Number
Catalog
Number
C Curve with Ring-Tongue Terminals
(5–10X In Current Rating)
0.5 WMZT1CX0T WMZT2CX0T WMZT3CX0T
1WMZT1C01T WMZT2C01T WMZT3C01T
1.5 WMZT1CX1T WMZT2CX1T WMZT3CX1T
2WMZT1C02T WMZT2C02T WMZT3C02T
3WMZT1C03T WMZT2C03T WMZT3C03T
4WMZT1C04T WMZT2C04T WMZT3C04T
5WMZT1C05T WMZT2C05T WMZT3C05T
6WMZT1C06T WMZT2C06T WMZT3C06T
7WMZT1C07T WMZT2C07T WMZT3C07T
8WMZT1C08T WMZT2C08T WMZT3C08T
10 WMZT1C10T WMZT2C10T WMZT3C10T
13 WMZT1C13T WMZT2C13T WMZT3C13T
15 WMZT1C15T WMZT2C15T WMZT3C15T
16 WMZT1C16T WMZT2C16T WMZT3C16T
20 WMZT1C20T WMZT2C20T WMZT3C20T
25 WMZT1C25T WMZT2C25T WMZT3C25T
30 WMZT1C30T WMZT2C30T WMZT3C30T
32 WMZT1C32T WMZT2C32T WMZT3C32T
40 WMZT1C40T WMZT2C40T WMZT3C40T
D Curve with Ring-Tongue Terminals
(10–20X In Current Rating)
0.5 WMZT1DX0T WMZT2DX0T WMZT3DX0T
1WMZT1D01T WMZT2D01T WMZT3D01T
1.5 WMZT1DX1T WMZT2DX1T WMZT3DX1T
2WMZT1D02T WMZT2D02T WMZT3D02T
3WMZT1D03T WMZT2D03T WMZT3D03T
4WMZT1D04T WMZT2D04T WMZT3D04T
5WMZT1D05T WMZT2D05T WMZT3D05T
6WMZT1D06T WMZT2D06T WMZT3D06T
7WMZT1D07T WMZT2D07T WMZT3D07T
8WMZT1D08T WMZT2D08T WMZT3D08T
10 WMZT1D10T WMZT2D10T WMZT3D10T
13 WMZT1D13T WMZT2D13T WMZT3D13T
15 WMZT1D15T WMZT2D15T WMZT3D15T
16 WMZT1D16T WMZT2D16T WMZT3D16T
20 WMZT1D20T WMZT2D20T WMZT3D20T
25 WMZT1D25T WMZT2D25T WMZT3D25T
30 WMZT1D30T WMZT2D30T WMZT3D30T
32 WMZT1D32T WMZT2D32T WMZT3D32T
40 WMZT1D40T WMZT2D40T WMZT3D40T
Single-Pole
Two-Pole
Three-Pole
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-71
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
WMZH
WMZH UL 489 Circuit Breakers — 14 kAIC
WMZH UL 489 Circuit Breakers with Ring-
To n g u e Te r m i n a l s
Single-Pole Two-Pole Three-Pole
Amperes
Catalog
Number
Catalog
Number
Catalog
Number
C Curve (5–10X In Current Rating)
15 WMZH1C15 WMZH2C15 WMZH3C15
16 WMZH1C16 WMZH2C16 WMZH3C16
20 WMZH1C20 WMZH2C20 WMZH3C20
25 WMZH1C25 WMZH2C25 WMZH3C25
D Curve (10–20X In Current Rating)
13 WMZH1D13 WMZH2D13 WMZH3D13
15 WMZH1D15 WMZH2D15 WMZH3D15
16 WMZH1D16 WMZH2D16 WMZH3D16
20 WMZH1D20 WMZH2D20 WMZH3D20
Single-Pole Two-Pole Three-Pole
Amperes
Catalog
Number
Catalog
Number
Catalog
Number
C Curve (5–10X In Current Rating)
15 WMZH1C15T WMZH2C15T WMZH3C15T
16 WMZH1C16T WMZH2C16T WMZH3C16T
20 WMZH1C20T WMZH2C20T WMZH3C20T
25 WMZH1C25T WMZH2C25T WMZH3C25T
D Curve (10–20X In Current Rating)
13 WMZH1D13T WMZH2D13T WMZH3D13T
15 WMZH1D15T WMZH2D15T WMZH3D15T
16 WMZH1D16T WMZH2D16T WMZH3D16T
20 WMZH1D20T WMZH2D20T WMZH3D20T
Single-Pole
Two-Pole
Three-Pole
Single-Pole
Two-Pole
Three-Pole
WMZD
WMZD UL 489 Circuit Breakers—10 kAIC
at 125 Vdc Per Pole
Notes
Interrupting capacity: 10 kA UL/CSA; 15 kA IEC 60947.
Optional connections for ring-tongue terminals.
Single-Pole Two-Pole
Amperes
Catalog
Number
Catalog
Number
C Curve (5–10X In Current Rating)
2WMZD1C02 WMZD2C02
3WMZD1C03 WMZD2C03
4WMZD1C04 WMZD2C04
5WMZD1C05 WMZD2C05
6WMZD1C06 WMZD2C06
7WMZD1C07 WMZD2C07
8WMZD1C08 WMZD2C08
10 WMZD1C10 WMZD2C10
13 WMZD1C13 WMZD2C13
15 WMZD1C15 WMZD2C15
16 WMZD1C16 WMZD2C16
20 WMZD1C20 WMZD2C20
25 WMZD1C25 WMZD2C25
30 WMZD1C30 WMZD2C30
32 WMZD1C32 WMZD2C32
40 WMZD1C40 WMZD2C40
Single-Pole
Two-Pole
V4-T1-72 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Accessories
WMZ UL 489 Breakers
Description Catalog Number
Two-pole contact or auxiliary contact/trip indicating contact WMZSAUXTRIP
Auxiliary contact WMZTAUX
Shunt trip 110–415 Vac WMZTST415
Shunt trip 12–110 Vac WMZTST110
Padlock hasp WMZPLK
Busbar—single-pole, 6 terminals WMZT1P6T
Busbar—single-pole, 12 terminals WMZT1P12T
Busbar—single-pole, 18 terminals WMZT1P18T
Busbar—two-pole, 6 terminals WMZT2P6T
Busbar—two-pole, 12 terminals WMZT2P12T
Busbar—two-pole, 18 terminals WMZT2P18T
Busbar—three-pole, 6 terminals WMZT3P6T
Busbar—three-pole, 12 terminals WMZT3P12T
Busbar—three-pole, 18 terminals WMZT3P18T
Three-pole busbar shroud WMZT3PSHROUD
Extension terminal—35 mm2 (2–14 AWG) WMZT35EXT
Bus connector—conductors up to 50 mm2 (~1/0 AWG) WMZTBCON
Tripping Signal Switch WMZSAUXTRIP, WMZTAUX
Design according to IEC/EN 60947-5-1, IEC/EN 62019 and UL
Field installable
The specified minimum voltages are per contact—take into
account particularly in case of series connection
Self-cleaning contacts
Contact material and design particularly suitable for extra
low voltage
WMZSAUXTRIP: the function of one of the two change-over
contacts can be switched from “auxiliary switch” to “tripping
signal switch”
Attention: The voltage of the WMZT...circuit breaker is limited
to 300V with this auxiliary installed.
Tripping signal contact transmits message of electric tripping,
not mechanical switch-off
Test key for contact function “electrical tripping”
WMZTAUX: will allow for > 480Y/277 Vac rating
Connection Diagram
WMZSAUXTRIP
21
4.11
1.11
1.14
1.12
4.12/4.14
4.14/4.12
13
22
14
Same Polarity
WMZTAUX
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-73
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Technical Data and Specifications
Trip Curve Chart
Eaton WMZ branch circuit
breakers are available with
“C” and “D” tripping
characteristics.
C-curve devices are suitable
for application where medium
levels of inrush current are
expected. Applications
include small transformers,
lighting, pilot devices, control
circuits and coils. C-curve
devices provide a medium
magnetic trip point.
D-curve devices are suitable
for applications where high
levels of inrush current are
expected. The high magnetic
trip point prevents nuisance
tripping in high inductive
applications such as motors,
transformers and power
supplies.
Eaton WMZ devices are
current limiting, which means
they interrupt fault currents
within one-half cycle of the
fault. Current limiting devices
offer superior protection by
reducing peak let-through
current and energy.
Tripping Characteristics
Tripping characteristic
acc. to UL 489
Conventional non-tripping
current
Int = 1.0 IN (T=40°)
Conventional tripping current
It = 1.35 IN: t < 1 h (T=25°)
2.0 IN: t = 12 – 120 s (T=25°)
Instantaneous tripping
acc. to IEC 60898-1
type C: 5 IN: t > 0.1 s
10 IN: t < 0.1 s
type D: 10 IN: t > 0.1 s
20 IN: t < 0.1 s
V4-T1-74 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Miniature Circuit Breakers WMZ Technical Data
Description Specification
Electrical
Design according to UL 489, CSA C22.2 No.5, IEC 60947-2
Rated voltage WMZT
UL/CSA
UL/CSA
UL/CSA
IEC 947-2
10 kAIC at 277/480V from 0.5A to 32A
10 kAIC at 240 Vac for 40A
10 kAIC at 48 Vdc per pole
15 kAIC at 240/415 Vac
Rated voltage WMZD
UL/CSA 10 kAIC at 125 Vdc per pole (two poles max.)
10 kAIC at 250 Vdc with two poles connected in series
Rated voltage WMZH
UL/CSA
IEC 947-2
14 kAIC at 277/480V at listed amperages
15 kAIC at 240/415 Vac
Rated frequency 50/60 Hz
Rated breaking capacity WMZT
UL/CSA
IEC 947-2
10 kA
15 kA
Rated breaking capacity WMZH
UL/CSA
IEC 947-2
14 kA
15 kA
Characteristic C, D
Endurance 20,000 operations
Line voltage connection Suitable for reverse feed
Mechanical
Frame size 45 mm
Device height 105 mm
Device width 17.7 mm per pole
Mounting Quick fastening with two lock-in positions on
IEC/EN 60715
Upper and lower terminals Open mouth/lift terminals
Terminal capacity One wire AWG 18–6
Two wires AWG 8–10
Terminal fastening torque AWG 18–21: 21 lb-in
AWG 10–8: 25 lb-in
AWG 6: 36 lb-in
Mounting Independent of position
Calibration temperature
UL 489, CSA C22.2 No.5
IEC 60947-2
40°C
30°C
Two-Pole
Three-Pole
Connection Diagrams
Single-Pole
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-75
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Power Loss at ln
Characteristic C Characteristic D
Single-Pole Two-Pole Three-Pole Single-Pole Two-Pole Three-Pole
In [A] P [W]P [W]P [W]P [W]P [W]P [W]
0.51.63.24.71.63.24.8
1.01.12.23.40.81.52.3
1.51.32.63.91.02.13.1
2.01.42.84.31.02.13.1
3.01.22.43.61.22.43.6
4.01.42.94.31.42.94.3
5.01.93.75.61.52.94.4
6.01.22.33.51.22.33.5
7.01.42.84.31.42.84.3
8.01.42.84.21.22.43.7
10.0 1.8 3.6 5.3 1.5 3.0 4.5
13.0 2.4 4.7 7.1 2.0 4.1 6.1
15.0 1.9 3.8 5.6 1.5 3.1 4.6
16.0 2.1 4.3 6.4 1.7 3.5 5.2
20.0 2.9 5.8 8.7 1.8 3.7 5.5
25.0 3.1 6.2 9.3 2.6 5.1 7.7
30.0 3.0 6.0 9.0 2.7 5.4 8.1
32.0 3.4 6.8 10.2 3.1 6.2 9.3
35.0 3.7 7.4 11.0 3.8 7.6 11.3
40.0 4.0 8.1 12.1 3.9 7.8 11.6
V4-T1-76 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Let-Through Energy
Characteristic C (0.5–32A), 277V
Characteristic D (0.5–32A), 277V
Characteristic C (40A), 240V
Characteristic D (40A), 240V
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-77
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Influence of Ambient Temperature T on Load Carrying Capacity
Device Market
Current Rating In
(A) at 40°C
In (A) at Higher Ambient Temperature
15°C 20°C 25°C 30°C 40°C 50°C 55°C 60°C
0.50.60.50.50.50.50.50.50.5
1.01.11.11.11.01.01.00.90.9
1.51.71.61.61.61.51.41.41.4
2.02.22.22.12.12.01.91.91.8
3.03.33.23.23.13.02.92.92.8
4.04.44.34.24.24.03.83.83.7
5.05.55.45.35.25.04.84.74.6
6.06.66.56.46.26.05.85.65.5
7.07.77.67.47.37.06.76.66.4
8.08.88.68.58.38.07.77.57.4
10.0 11.0 10.8 10.6 10.4 10.0 9.6 9.4 9.2
13.0 14.3 14.0 13.8 13.5 13.0 12.5 12.5 12.0
15.0 16.5 16.2 15.9 15.6 15.0 14.4 14.1 13.8
16.0 17.6 17.3 17.0 16.6 16.0 15.4 15.0 14.7
20.0 22.0 21.6 21.2 20.8 20.0 19.2 18.8 18.4
25.0 27.5 27.0 26.5 26.0 25.0 24.0 23.3 23.0
30.0 33.0 32.4 31.8 31.2 30.0 28.8 28.2 27.6
32.0 35.2 34.6 33.9 33.3 32.0 30.7 30.1 29.4
40.0 44.0 43.2 42.4 41.6 40.0 38.4 37.6 36.8
V4-T1-78 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
WMZ UL 489 Auxiliary and Trip Indicating Contacts
Description WMZSAUXTRIP WMZTAUX
Electrical
Contact function 2CO 1NO + 1NC
Rated voltage 230V 250V
Frequency 50/60 Hz 50/60 Hz
Rated current 2A 6A
Rated thermal current Ith 2A 6A
Utilization category AC13 rated operational current Ie3A/250 Vac 3A/250 Vac
Utilization category AC15 rated operational current Ie2A/250 Vac 2A/250 Vac
Utilization category DC12 rated operational current Ie0.5A/110 Vdc 0.5A/110 Vdc
0.25A/220 Vdc
Rated insulation voltage UI250 Vac 250 Vac
Minimum operational voltage per contact Umin 5 Vdc 5 Vdc
Minimum operational current Imin 10 mA DC 10 mA AC/DC
Rated peak withstand voltage Uimp (1.2/50µ) 2.5 kV 4 kV
Conditional short-circuit current Ik with back-up fuse 6A 1 kA 1 kA
Max. back-up fuse, overload and short circuit 6A gL
Mechanical
Tripping indicator “electrical tripping” Blue/white
Frame size 45.0 mm 45.0 mm
Device height 80.0 mm 80.0 mm
Device width 8.8 mm (0.5MU) 8.8 mm (0.5MU)
Mounting Onto switching device
Degree of protection, built-in IP40 IP40
Terminal protection Finger and hand touch safe according to BGV A3, ÖVE-EN 6 Finger and hand touch safe according to BGV A3, ÖVE-EN 6
Terminals Lift terminals Lift terminals
Terminal capacity 20–14 AWG 0.5–2.5 mm2
Terminal screws M3 (Pozidrive Z0) M3 (Pozidrive Z0)
Fastening torque of terminal screws 7 lb-in Max. 1.2 Nm
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-79
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Shunt Trip Release WMZTST
Remote release for subsequent mounting onto WMZT
Additional installation of standard auxiliary switch is possible
Position indicator red–green
Shunt Trip Release WMZTST
Busbar Block UL 489 (Pin)
Tested according to UL 489
Do not cut
Extension terminal 35 mm2 WMZT35EXT for copper conductors
For covering of not used pins, use busbar tag shrouds WMZT3PSHROUD
Busbar Block UL 489 (Pin)
Description WMZTST110 WMZTST415
Electrical
Can be mounted onto WMZT/WMZH/WMZD WMZT/WMZH/WMZD
Operational voltage range 12–110 Vac 110–415 Vac
12–60 Vdc 110–230 Vdc
Frequency 50/60 Hz 50/60 Hz
Mechanical
Frame size 45.0 mm 45.0 mm
Device height 105.0 mm 105.0 mm
Device width 17.5 mm 17.5 mm
Mounting Quick fastening with two lock-in positions on EN 50022
Degree of protection, built-in IP40 IP40
Terminal Protection Finger and hand touch safe according to BGV A3, ÖVE-EN 6
Terminals Open mouthed/lift Open mouthed/lift
Terminal capacity 1 and 2 wires 18–10 AWG 18–10 AWG
Connection Diagram
1
2
Description UL 489 IEC/EN 60947-2
Electrical
Rated operational voltage 480/277 Vac
96 Vdc
Rated frequency 50/60 Hz
Rated voltage 690 Vac
Overvoltage category III
Rated impulse withstand voltage Uimp —9.5 kV
Rated current 80A 80A
Rated conditional short-circuit current AC with 350A gG 15 kA
Short-circuit current 10 kA
Mechanical
Busbar cross section 16 mm2 Cu
Flame class according to UL 94 V0
Pollution degree 2
Comparative tracking index CTI 600
Minimum clearance (internal/external) > 9.5/25.4 mm
Minimum creepage distance (internal/external) > 12.7/50.8 mm
Resistance to climatic conditions According to DIN/
EN60068
Connection Diagrams
Single-Pole Busbar
Two-Pole Busbar
Three-Pole Busbar
V4-T1-80 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Dimensions
Approximate Dimensions in Inches (mm)
WMZ
WMZT35EXT Lockout Attachment
Z-SV/UL-16.../18 Z-EK/35/UL
Z-SV/UL-16/6 Z-SV/UL-18...12 ZV-BS-UL
Description UL 489 IEC/EN 60947-2
# 2–14 AWG 2.5–35 mm2
60/75°C Cu Cu
0.56 in 14 mm
Tested according to Tightening torque of
terminal screws
UL 486A # 14 AWG ≥ 2.3 Nm
UL 486B # 8–12 AWG ≥ 2.8 Nm
UL 486E # 6–1 AWG 4 Nm
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-81
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.2
Miniature Circuit Breakers and Supplementary Protectors
UL 489 DIN Rail Miniature Circuit Breakers
Approximate Dimensions in Inches (mm)
Miniature Circuit Breakers WMZ
WMZ UL 489
WMZSAUXTRIP WMZTAUX
0.70
(17.7)
4.13
(105.0) 1.77
(45.0)
0.39
(10.0)
1.73
(44.0)
2.36
(60.0)
0.20
(5.0)
0.35
(8.8)
1.73
(44.0)
2.36
(60.0)
3.15
(80.0)
1.77
(45.0)
0.22
(5.5)
3.78
(96.0) 1.77
(45.0)
2.82
(71.6)
1.73
(44.0)
2.08 (53.0)
2.36 (60.0)
0.20
(5.5)
0.35
(8.8)
0.39
(10.0)
V4-T1-82 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
Optimum and Efficient Protection for Every Application
FAZ Circuit Breakers
Contents
Description Page
FAZ Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . V4-T1-82
Catalog Number Selection . . . . . . . . . . . . . . . . . V4-T1-83
Standards and Certifications . . . . . . . . . . . . . . . V4-T1-83
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-84
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-90
Technical Data and Specifications . . . . . . . . . . . V4-T1-93
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-100
WMZS Circuit Breaker . . . . . . . . . . . . . . . . . . . . . V4-T1-103
FAZ Circuit Breakers
Product Overview
Optimum product quality,
tested reliability and safety
stand for best protection of
personnel, installations and
plant. Eaton’s FAZ DIN rail
mountable circuit breaker is
designed for use in control
panel applications.
Powerful offering for machine
and system builders
The FAZ is available with B,
C, D, K, S, and Z characteristics
in accordance with UL 1077,
CSA C22.2 No.235 and IEC
60947-2. These devices are
CE marked.
Application Description
Supplementary protection
Control circuits
Lighting
Business equipment
Appliances
Features
Complete range of UL
1077 recognized DIN
rail mounted miniature
circuit breakers up to
63A current rating
Standard ratings of 10 kAIC
up to 277/480 Vac
Current limiting design
provides fast short-circuit
interruption that reduces
the let-through energy,
which can damage
the circuit
Suitable for supplementary
protection
Thermal-magnetic
overcurrent protection
Six levels of short-circuit
protection, categorized
by B, C, D, K, S, and
Z curves
Trip-free design—breaker
can not be defeated by
holding the handle in the
ON position
Captive screws cannot
be lost
Fulfill UL 1077, CSA C22.2
No.235 and also IEC
60947-2 Standard
Field-installable shunt trip
and auxiliary switch
subsequent mounting
Module width of only
17.7 mm (per pole)
Contact position indicator
(red/green)
Easy installation on DIN rail
Possibility for sealing
the toggle in ON or
OFF position
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-83
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Standards and Certifications
FAZ complies with the latest
national and international
standards.
UL 1077, CSA C22.2
No. 235
Apply to supplementary
protectors intended for
use as overcurrent, or
overvoltage or
undervoltage protection
within an appliance or
other electrical
equipment where
branch circuit protection
is already provided, or is
not required
RoHS compliant
VDE compliant
Devices with B, C,
and D curves are
VDE compliant
CCC
Devices with B, C,
and D curves are
CCC compliant
ABS compliant
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
Discover These Advanced Features
Catalog Number Selection
Note
1In = Rated current for instantaneous trip characteristics.
Breakers install on
standard DIN rail
Available in one-, two-,
three-, four-pole, 1+N
and 3+N models
Color-coded indicator
provides breaker
status for easy
troubleshooting
Captive Posidrive
terminal screws with
finger and back-of-
hand protection (IP20)
Trip-free design;
breaker cannot be
defeated by holding
the handle in the
ON position
Breaker information
printed on the front of
the device for quick
identification
Breaker Family
FAZ = Supplementary
protector Ampere Rating
0.5 =0.5A
1=1A
2=2A
3=3A
4=4A
5=5A
6=6A
7=7A
8=8A
10 =10A
13 = 13A
15 = 15A
16 = 16A
20 = 20A
25 = 25A
30 = 30A
32 = 32A
40 = 40A
50 = 50A
63 = 63A
Trip
Characteristics 1
B = 3–5X In
C = 5–10X In
D = 10–20X In
K = 8–12X In
S = 13–17X In
Z = 2–3X In
Number of Poles
1 = Single-pole
2 = Two-pole
3 = Three-pole
4 = Single-pole
1N = Single-pole +
neutral
3N = Three-pole +
neutral
Single Package
SP = Single packaging of single-
pole curve B, C and D for
select amperes only
Blank = Standard packaging
FAZ C 6 / 1 SP
V4-T1-84 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
Product Selection
FAZ B curve (3–5X In current rating)
Designed for resistive or slightly inductive loads
Response time of instantaneous trip: 3–5X In current rating
UL recognized and CSA Certified as supplementary protectors
For international and domestic use (conform to IEC 60947-2)
UL file number 177451
Suitable for applications where protection against low-level
short-circuit faults in control wiring is desired. Instantaneous trip
is 3–5X continuous rating of device (In). Applications include PLC
wiring, business equipment, lighting, appliances and some
motors. Low magnetic trip point.
B Curve (3–5X In Current Rating)—
Designed for Resistive or Slightly
Inductive Loads 1
B Curve (3–5X In Current Rating)
Designed for Resistive or Slightly
Inductive Loads, continued 1
Notes
1 In North America, these switches are UL recognized and CSA Certified as supplementary protection devices. Per the intent of NEC (National Electrical Code), Article 240,
and CEC (Canadian Electrical Code), Part 1 C22.1, supplementary breakers cannot be used as a substitute for the branch circuit protective device. They can be used to
provide overcurrent protection within an appliance or other electrical equipment where branch circuit overcurrent protection is already provided, or is not required.
2 Option for single packaging on single-pole B, C and D curves only; add suffix SP when ordering.
Single-Pole 2Two-Pole Three-Pole
Amperes
Catalog
Number
Catalog
Number
Catalog
Number
1FAZ-B1/1-SP FAZ-B1/2 FAZ-B1/3
2FAZ-B2/1-SP FAZ-B2/2 FAZ-B2/3
3FAZ-B3/1-SP FAZ-B3/2 FAZ-B3/3
4FAZ-B4/1-SP FAZ-B4/2 FAZ-B4/3
5FAZ-B5/1-SP FAZ-B5/2 FAZ-B5/3
6FAZ-B6/1-SP FAZ-B6/2 FAZ-B6/3
7FAZ-B7/1-SP FAZ-B7/2 FAZ-B7/3
8FAZ-B8/1-SP FAZ-B8/2 FAZ-B8/3
10 FAZ-B10/1-SP FAZ-B10/2 FAZ-B10/3
12 FAZ-B12/1-SP FAZ-B12/2 FAZ-B12/3
13 FAZ-B13/1-SP FAZ-B13/2 FAZ-B13/3
15 FAZ-B15/1-SP FAZ-B15/2 FAZ-B15/3
16 FAZ-B16/1-SP FAZ-B16/2 FAZ-B16/3
20 FAZ-B20/1-SP FAZ-B20/2 FAZ-B20/3
25 FAZ-B25/1-SP FAZ-B25/2 FAZ-B25/3
30 FAZ-B30/1-SP FAZ-B30/2 FAZ-B30/3
32 FAZ-B32/1-SP FAZ-B32/2 FAZ-B32/3
40 FAZ-B40/1-SP FAZ-B40/2 FAZ-B40/3
50 FAZ-B50/1-SP FAZ-B50/2 FAZ-B50/3
63 FAZ-B63/1-SP FAZ-B63/2 FAZ-B63/3
Single-Pole
Two-Pole
Three-Pole
Amperes
Four-Pole
Single-Pole
+ Neutral
Three-Pole
+ Neutral
Catalog
Number
Catalog
Number
Catalog
Number
1FAZ-B1/4 FAZ-B1/1N FAZ-B1/3N
2FAZ-B2/4 FAZ-B2/1N FAZ-B2/3N
3FAZ-B3/4 FAZ-B3/1N FAZ-B3/3N
4FAZ-B4/4 FAZ-B4/1N FAZ-B4/3N
5FAZ-B5/4 FAZ-B5/1N FAZ-B5/3N
6FAZ-B6/4 FAZ-B6/1N FAZ-B6/3N
7FAZ-B7/4 FAZ-B7/1N FAZ-B7/3N
8FAZ-B8/4 FAZ-B8/1N FAZ-B8/3N
10 FAZ-B10/4 FAZ-B10/1N FAZ-B10/3N
12 FAZ-B12/4 FAZ-B12/1N FAZ-B12/3N
13 FAZ-B13/4 FAZ-B13/1N FAZ-B13/3N
15 FAZ-B15/4 FAZ-B15/1N FAZ-B15/3N
16 FAZ-B16/4 FAZ-B16/1N FAZ-B16/3N
20 FAZ-B20/4 FAZ-B20/1N FAZ-B20/3N
25 FAZ-B25/4 FAZ-B25/1N FAZ-B25/3N
30 FAZ-B30/4 FAZ-B30/1N FAZ-B30/3N
32 FAZ-B32/4 FAZ-B32/1N FAZ-B32/3N
40 FAZ-B40/4 FAZ-B40/1N FAZ-B40/3N
50 FAZ-B50/4 FAZ-B50/1N FAZ-B50/3N
63 FAZ-B63/4 FAZ-B63/1N FAZ-B63/3N
0.0005
t [sec]
N
I / I
7200
3600
1200
600
300
120
60
30
10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.005
0.01
0.002
0.001
5040302015
1098765432
1
1.13
1.45
1
1
B
2
3
Specied non-tripping
current
INT = 1.13 x IN for t > 1 h
Specied tripping current
IT = 1.45 x IN for t < 1 h
2.55 IN:
t = 1–60 s (IN < 32A)
t = 1–120 s (IN > 32A)
Type B: 3 x IN: t > 0.1 s
Type B: 5 x IN: t < 0.1 s
Four-Pole
Single-Pole + Neutral
Three-Pole + Neutral
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-85
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
FAZ C curve (5–10X In current rating)
Designed for inductive loads
Response time of instantaneous trip: 5–10X In current rating
UL recognized and CSA Certified as supplementary protectors
For international and domestic use (conform to IEC 60947-2)
UL file number 177451
Suitable for applications where medium levels of inrush current
are expected. Instantaneous trip is 5–10X rating of device (In).
Applications include small transformers, lighting, pilot devices,
control circuits and coils. Medium magnetic trip point.
C Curve (5–10X In Current Rating)—
Designed Inductive Loads 1
C Curve (5–10X In Current Rating)—
Designed Inductive Loads, continued 1
Notes
1 In North America, these switches are UL recognized and CSA Certified as supplementary protection devices. Per the intent of NEC (National Electrical Code), Article 240,
and CEC (Canadian Electrical Code), Part 1 C22.1, supplementary breakers cannot be used as a substitute for the branch circuit protective device. They can be used to
provide overcurrent protection within an appliance or other electrical equipment where branch circuit overcurrent protection is already provided, or is not required.
2 Option for single packaging on single-pole B, C and D curves only; add suffix SP when ordering.
Single-Pole 2Two-Pole Three-Pole
Amperes
Catalog
Number
Catalog
Number
Catalog
Number
0.5 FAZ-C0.5/1-SP FAZ-C0.5/2 FAZ-C0.5/3
1FAZ-C1/1-SP FAZ-C1/2 FAZ-C1/3
1.6 FAZ-C1.6/1-SP FAZ-C1.6/2 FAZ-C1.6/3
2FAZ-C2/1-SP FAZ-C2/2 FAZ-C2/3
3FAZ-C3/1-SP FAZ-C3/2 FAZ-C3/3
4FAZ-C4/1-SP FAZ-C4/2 FAZ-C4/3
5FAZ-C5/1-SP FAZ-C5/2 FAZ-C5/3
6FAZ-C6/1-SP FAZ-C6/2 FAZ-C6/3
7FAZ-C7/1-SP FAZ-C7/2 FAZ-C7/3
8FAZ-C8/1-SP FAZ-C8/2 FAZ-C8/3
10 FAZ-C10/1-SP FAZ-C10/2 FAZ-C10/3
13 FAZ-C13/1-SP FAZ-C13/2 FAZ-C13/3
15 FAZ-C15/1-SP FAZ-C15/2 FAZ-C15/3
16 FAZ-C16/1-SP FAZ-C16/2 FAZ-C16/3
20 FAZ-C20/1-SP FAZ-C20/2 FAZ-C20/3
25 FAZ-C25/1-SP FAZ-C25/2 FAZ-C25/3
30 FAZ-C30/1-SP FAZ-C30/2 FAZ-C30/3
32 FAZ-C32/1-SP FAZ-C32/2 FAZ-C32/3
40 FAZ-C40/1-SP FAZ-C40/2 FAZ-C40/3
50 FAZ-C50/1-SP FAZ-C50/2 FAZ-C50/3
63 FAZ-C63/1-SP FAZ-C63/2 FAZ-C63/3
Single-Pole
Two-Pole
Three-Pole
Four-Pole
Single-Pole
+ Neutral
Three-Pole
+ Neutral
Amperes
Catalog
Number
Catalog
Number
Catalog
Number
0.5 FAZ-C0.5/4 FAZ-C0.5/1N FAZ-C0.5/3N
1FAZ-C1/4 FAZ-C1/1N FAZ-C1/3N
1.6 FAZ-C1.6/4 FAZ-C1.6/1N FAZ-C1.6/3N
2FAZ-C2/4 FAZ-C2/1N FAZ-C2/3N
3FAZ-C3/4 FAZ-C3/1N FAZ-C3/3N
4FAZ-C4/4 FAZ-C4/1N FAZ-C4/3N
5FAZ-C5/4 FAZ-C5/1N FAZ-C5/3N
6FAZ-C6/4 FAZ-C6/1N FAZ-C6/3N
7FAZ-C7/4 FAZ-C7/1N FAZ-C7/3N
8FAZ-C8/4 FAZ-C8/1N FAZ-C8/3N
10 FAZ-C10/4 FAZ-C10/1N FAZ-C10/3N
13 FAZ-C13/4 FAZ-C13/1N FAZ-C13/3N
15 FAZ-C15/4 FAZ-C15/1N FAZ-C15/3N
16 FAZ-C16/4 FAZ-C16/1N FAZ-C16/3N
20 FAZ-C20/4 FAZ-C20/1N FAZ-C20/3N
25 FAZ-C25/4 FAZ-C25/1N FAZ-C25/3N
30 FAZ-C30/4 FAZ-C30/1N FAZ-C30/3N
32 FAZ-C32/4 FAZ-C32/1N FAZ-C32/3N
40 FAZ-C40/4 FAZ-C40/1N FAZ-C40/3N
50 FAZ-C50/4 FAZ-C50/1N FAZ-C50/3N
63 FAZ-C63/4 FAZ-C63/1N FAZ-C63/3N
0.0005
t [sec]
N
I / I
7200
1.13
1.45
3600
1200
600
300
120
60
30
10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.005
0.01
0.002
0.001
5040302015
1098765432
1
1
C
2
Specied non-tripping
current
INT = 1.13 x IN for t > 1 h
Specied tripping current
IT = 1.45 x IN for t < 1 h
Type C: 5 x IN: t > 0.1 s
Type C: 10 x IN: t < 0.1 s
Four-Pole
Single-Pole + Neutral
Three-Pole + Neutral
V4-T1-86 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
FAZ D curve (10–20X In current rating)
Designed for highly inductive loads
Response time of instantaneous trip: 10–20X In current rating
UL recognized and CSA Certified as supplementary protectors
For international and domestic use (conform to IEC 60947-2)
UL file number 177451
Suitable for applications where high levels of inrush current are
expected. Instantaneous trip is 10–20X rating of device (In). The
high magnetic trip point prevents nuisance tripping in high
inductive applications such as motors, transformers and
power supplies.
D Curve (10–20X In Current Rating)—
Designed for Inductive Loads 1
D Curve (10–20X In Current Rating)—
Designed for Inductive Loads, continued 1
Notes
1 In North America, these switches are UL recognized and CSA Certified as supplementary protection devices. Per the intent of NEC (National Electrical Code), Article 240,
and CEC (Canadian Electrical Code), Part 1 C22.1, supplementary breakers cannot be used as a substitute for the branch circuit protective device. They can be used to
provide overcurrent protection within an appliance or other electrical equipment where branch circuit overcurrent protection is already provided, or is not required.
2 Option for single packaging on single-pole B, C and D curves only; add suffix SP when ordering.
3 IEC 60947-2 only.
Single-Pole 2Two-Pole Three-Pole
Amperes
Catalog
Number
Catalog
Number
Catalog
Number
0.5 FAZ-D0.5/1-SP FAZ-D0.5/2 FAZ-D0.5/3
1FAZ-D1/1-SP FAZ-D1/2 FAZ-D1/3
2FAZ-D2/1-SP FAZ-D2/2 FAZ-D2/3
3FAZ-D3/1-SP FAZ-D3/2 FAZ-D3/3
4FAZ-D4/1-SP FAZ-D4/2 FAZ-D4/3
5FAZ-D5/1-SP FAZ-D5/2 FAZ-D5/3
6FAZ-D6/1-SP FAZ-D6/2 FAZ-D6/3
7FAZ-D7/1-SP FAZ-D7/2 FAZ-D7/3
8FAZ-D8/1-SP FAZ-D8/2 FAZ-D8/3
10 FAZ-D10/1-SP FAZ-D10/2 FAZ-D10/3
13 FAZ-D13/1-SP FAZ-D13/2 FAZ-D13/3
15 FAZ-D15/1-SP FAZ-D15/2 FAZ-D15/3
16 FAZ-D16/1-SP FAZ-D16/2 FAZ-D16/3
20 FAZ-D20/1-SP FAZ-D20/2 FAZ-D20/3
25 FAZ-D25/1-SP FAZ-D25/2 FAZ-D25/3
30 FAZ-D30/1-SP FAZ-D30/2 FAZ-D30/3
32 FAZ-D32/1-SP FAZ-D32/2 FAZ-D32/3
40 FAZ-D40/1-SP FAZ-D40/2 FAZ-D40/3
50 3FAZ-D50/1-SP FAZ-D50/2 FAZ-D50/3
63 3FAZ-D63/1-SP FAZ-D63/2 FAZ-D63/3
Single-Pole
Two-Pole
Three-Pole
Four-Pole
Single-Pole
+ Neutral
Three-Pole
+ Neutral
Amperes
Catalog
Number
Catalog
Number
Catalog
Number
0.5 FAZ-D0.5/4 FAZ-D0.5/1N FAZ-D0.5/3N
1FAZ-D1/4 FAZ-D1/1N FAZ-D1/3N
2FAZ-D2/4 FAZ-D2/1N FAZ-D2/3N
3FAZ-D3/4 FAZ-D3/1N FAZ-D3/3N
4FAZ-D4/4 FAZ-D4/1N FAZ-D4/3N
5FAZ-D5/4 FAZ-D5/1N FAZ-D5/3N
6FAZ-D6/4 FAZ-D6/1N FAZ-D6/3N
7FAZ-D7/4 FAZ-D7/1N FAZ-D7/3N
8FAZ-D8/4 FAZ-D8/1N FAZ-D8/3N
10 FAZ-D10/4 FAZ-D10/1N FAZ-D10/3N
13 FAZ-D13/4 FAZ-D13/1N FAZ-D13/3N
15 FAZ-D15/4 FAZ-D15/1N FAZ-D15/3N
16 FAZ-D16/4 FAZ-D16/1N FAZ-D16/3N
20 FAZ-D20/4 FAZ-D20/1N FAZ-D20/3N
25 FAZ-D25/4 FAZ-D25/1N FAZ-D25/3N
30 FAZ-D30/4 FAZ-D30/1N FAZ-D30/3N
32 FAZ-D32/4 FAZ-D32/1N FAZ-D32/3N
40 FAZ-D40/4 FAZ-D40/1N FAZ-D40/3N
50 cFAZ-D50/4 FAZ-D50/1N FAZ-D50/3N
63 cFAZ-D63/4 FAZ-D63/1N FAZ-D63/3N
0.0005
t [sec]
N
I / I
7200
3600
1200
600
300
120
60
30
10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.005
0.01
0.002
0.001
5040302015
1098765432
1
1.13
1.45
D
1
1
2
3
Specied non-tripping
current
INT = 1.13 x IN for t > 1 h
Specied tripping current
IT = 1.45 x IN for t < 1 h
2.55 IN:
t = 1–60 s (IN < 32A)
t = 1–120 s (IN > 32A)
Type D: 10 x IN: t > 0.1 s
Type D: 20 x IN: t < 0.1 s
Four-Pole
Single-Pole + Neutral
Three-Pole + Neutral
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-87
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
FAZ K curve (8–12X In current rating)
Designed for motors, transformers and upstream electronics
Response time of instantaneous trip: 8–12X In current rating
UL recognized and CSA Certified as supplementary protectors
For international and domestic use (conform to IEC 60947-2)
UL file number 177451
Suitable for applications where medium levels of inrush current
are expected. Instantaneous trip is 8–12X rating of device (In).
Applications include small transformers, lighting, pilot devices,
control circuits and coils. Medium magnetic trip point.
K Curve (8–12X In Current Rating)—
Designed for Inductive Loads 12
K Curve (8–12X In Current Rating)
Designed for Inductive Loads, continued
12
Notes
1 In North America, these switches are UL recognized and CSA Certified as supplementary protection devices. Per the intent of NEC (National Electrical Code), Article 240,
and CEC (Canadian Electrical Code), Part 1 C22.1, supplementary breakers cannot be used as a substitute for the branch circuit protective device. They can be used to
provide overcurrent protection within an appliance or other electrical equipment where branch circuit overcurrent protection is already provided, or is not required.
2 These breakers are available by special order and may result in additional delivery time.
3 Two-piece box order, quantities of 2.
Single-Pole 3Two-Pole Three-Pole
Amperes
Catalog
Number
Catalog
Number
Catalog
Number
0.5 FAZ-K0.5/1 FAZ-K0.5/2 FAZ-K0.5/3
1FAZ-K1/1 FAZ-K1/2 FAZ-K1/3
1.6 FAZ-K1.6/1 FAZ-K1.6/2 FAZ-K1.6/3
2FAZ-K2/1 FAZ-K2/2 FAZ-K2/3
3FAZ-K3/1 FAZ-K3/2 FAZ-K3/3
4FAZ-K4/1 FAZ-K4/2 FAZ-K4/3
6FAZ-K6/1 FAZ-K6/2 FAZ-K6/3
8FAZ-K8/1 FAZ-K8/2 FAZ-K8/3
10 FAZ-K10/1 FAZ-K10/2 FAZ-K10/3
13 FAZ-K13/1 FAZ-K13/2 FAZ-K13/3
16 FAZ-K16/1 FAZ-K16/2 FAZ-K16/3
20 FAZ-K20/1 FAZ-K20/2 FAZ-K20/3
25 FAZ-K25/1 FAZ-K25/2 FAZ-K25/3
32 FAZ-K32/1 FAZ-K32/2 FAZ-K32/3
40 FAZ-K40/1 FAZ-K40/2 FAZ-K40/3
50 FAZ-K50/1 FAZ-K50/2 FAZ-K50/3
63 FAZ-K63/1 FAZ-K63/2 FAZ-K63/3
Single-Pole
Two-Pole
Three-Pole
Four-Pole 3
Single-Pole
+ Neutral
Three-Pole
+ Neutral
Amperes
Catalog
Number
Catalog
Number
Catalog
Number
0.5 FAZ-K0.5/4 FAZ-K0.5/1N FAZ-K0.5/3N
1FAZ-K1/4 FAZ-K1/1N FAZ-K1/3N
1.6 FAZ-K1.6/4 FAZ-K1.6/1N FAZ-K1.6/3N
2FAZ-K2/4 FAZ-K2/1N FAZ-K2/3N
3FAZ-K3/4 FAZ-K3/1N FAZ-K3/3N
4FAZ-K4/4 FAZ-K4/1N FAZ-K4/3N
6FAZ-K6/4 FAZ-K6/1N FAZ-K6/3N
8FAZ-K8/4 FAZ-K8/1N FAZ-K8/3N
10 FAZ-K10/4 FAZ-K10/1N FAZ-K10/3N
13 FAZ-K13/4 FAZ-K13/1N FAZ-K13/3N
16 FAZ-K16/4 FAZ-K16/1N FAZ-K16/3N
20 FAZ-K20/4 FAZ-K20/1N FAZ-K20/3N
25 FAZ-K25/4 FAZ-K25/1N FAZ-K25/3N
32 FAZ-K32/4 FAZ-K32/1N FAZ-K32/3N
40 FAZ-K40/4 FAZ-K40/1N FAZ-K40/3N
50 FAZ-K50/4 FAZ-K50/1N FAZ-K50/3N
63 FAZ-K63/4 FAZ-K63/1N FAZ-K63/3N
Specied
non-tripping current
Int = 1.05 u In
for t > 1 h
Specied
tripping current
It = 1.30 u In
for t < 1 h
U-rated Current
1 2
3 4 5 6 7 8 9 10 15 20 30 40 50
7200
3600
1200
600
300
120
60
30
10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.01
0.005
0.002
0.001
0.0005
t (sec)
1.13
1.45
K
Four-Pole
Single-Pole + Neutral
Three-Pole + Neutral
V4-T1-88 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
FAZ S curve (13–17X In current rating)
Designed for control circuits with high inrush
Response time of instantaneous trip: 13–17X In current rating
UL recognized and CSA Certified as supplementary protectors
For international and domestic use (conform to IEC 60947-2)
UL file number 177451
Suitable for applications where high levels of inrush current are
expected. Instantaneous trip is 13–17X rating of device (In). The
high magnetic trip point prevents nuisance tripping in high
inductive applications such as motors, transformers and
power supplies.
S Curve (13–17X In Current Rating)—
Designed for Inductive Loads 12
Notes
1 In North America, these switches are UL recognized and CSA
Certified as supplementary protection devices. Per the intent of
NEC (National Electrical Code), Article 240, and CEC (Canadian
Electrical Code), Part 1 C22.1, supplementary breakers cannot be
used as a substitute for the branch circuit protective device.
They can be used to provide overcurrent protection within an
appliance or other electrical equipment where branch circuit
overcurrent protection is already provided, or is not required.
2 These breakers are available by special order and may result in
additional delivery time.
3 Two-piece box order, quantities of 2.
Single-Pole 3Two-Pole
Amperes
Catalog
Number
Catalog
Number
1FAZ-S1/1 FAZ-S1/2
2FAZ-S2/1 FAZ-S2/2
3FAZ-S3/1 FAZ-S3/2
4FAZ-S4/1 FAZ-S4/2
6FAZ-S6/1 FAZ-S6/2
10 FAZ-S10/1 FAZ-S10/2
16 FAZ-S16/1 FAZ-S16/2
20 FAZ-S20/1 FAZ-S20/2
25 FAZ-S25/1 FAZ-S25/2
32 FAZ-S32/1 FAZ-S32/2
40 FAZ-S40/1 FAZ-S40/2
Single-Pole
Two-Pole
Specied
non-tripping current
Int = 1.05 u In
for t > 1 h
Specied
tripping current
It = 1.30 u In
for t < 1 h
U-rated Current
1 2
3 4 5 6 7 8 9 10 15 20 30 40 50
7200
3600
1200
600
300
120
60
30
10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.01
0.005
0.002
0.001
0.0005
t (sec)
1.05
1.30
S
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-89
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
FAZ Z curve (2–3X In current rating)
Designed for protection of electronic devices
Response time of instantaneous trip: 2–3X In current rating
UL recognized and CSA Certified as supplementary protectors
For international and domestic use (conform to IEC 60947-2)
Suitable for applications where low levels of inrush current
are expected. Instantaneous trip is 2–3X rating of device (In).
Applications include small transformers, lighting, pilot devices,
control circuits and coils. Medium magnetic trip point.
Z Curve (2–3X In Current Rating)—
Designed for Inductive Loads 12 Z Curve (2–3X In Current Rating)—
Designed for Inductive Loads, continued
12
Notes
1 In North America, these switches are UL recognized and CSA Certified as supplementary protection devices. Per the intent of NEC (National Electrical Code), Article 240,
and CEC (Canadian Electrical Code), Part 1 C22.1, supplementary breakers cannot be used as a substitute for the branch circuit protective device. They can be used to
provide overcurrent protection within an appliance or other electrical equipment where branch circuit overcurrent protection is already provided, or is not required.
2 These breakers are available by special order and may result in additional delivery time.
3 Two-piece box order, quantities of 2.
Single-Pole 3Two-Pole
Amperes
Catalog
Number
Catalog
Number
0.5 FAZ-Z0.5/1 FAZ-Z0.5/2
1FAZ-Z1/1 FAZ-Z1/2
1.6 FAZ-Z1.6/1 FAZ-Z1.6/2
2FAZ-Z2/1 FAZ-Z2/2
3FAZ-Z3/1 FAZ-Z3/2
4FAZ-Z4/1 FAZ-Z4/2
6FAZ-Z6/1 FAZ-Z6/2
8FAZ-Z8/1 FAZ-Z8/2
10 FAZ-Z10/1 FAZ-Z10/2
13 FAZ-Z13/1 FAZ-Z13/2
16 FAZ-Z16/1 FAZ-Z16/2
20 FAZ-Z20/1 FAZ-Z20/2
25 FAZ-Z25/1 FAZ-Z25/2
32 FAZ-Z32/1 FAZ-Z32/2
40 FAZ-Z40/1 FAZ-Z40/2
50 FAZ-Z50/1 FAZ-Z50/2
63 FAZ-Z63/1 FAZ-Z63/2
Single-Pole
Two-Pole
Three-Pole Four-Pole
Amperes
Catalog
Number
Catalog
Number
0.5 FAZ-Z0.5/3 FAZ-Z0.5/4
1FAZ-Z1/3 FAZ-Z1/4
1.6 FAZ-Z1.6/3 FAZ-Z1.6/4
2FAZ-Z2/3 FAZ-Z2/4
3FAZ-Z3/3 FAZ-Z3/4
4FAZ-Z4/3 FAZ-Z4/4
6FAZ-Z6/3 FAZ-Z6/4
8FAZ-Z8/3 FAZ-Z8/4
10 FAZ-Z10/3 FAZ-Z10/4
13 FAZ-Z13/3 FAZ-Z13/4
16 FAZ-Z16/3 FAZ-Z16/4
20 FAZ-Z20/3 FAZ-Z20/4
25 FAZ-Z25/3 FAZ-Z25/4
32 FAZ-Z32/3 FAZ-Z32/4
40 FAZ-Z40/3 FAZ-Z40/4
50 FAZ-Z50/3 FAZ-Z50/4
63 FAZ-Z63/3 FAZ-Z63/4
U-rated Current
1 2 3 4 5 6 7 8 9 10 15 20 30 40 50
7200
3600
1200
600
300
120
60
30
10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.01
0.005
0.002
0.001
0.0005
t (sec)
1.05
1.30
Specied
non-tripping current
Int = 1.05 u In
for t > 1 h
Specied
tripping current
It = 1.30 u In
for t < 1 h
Z
Four-Pole
Three-Pole
V4-T1-90 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
Accessories
FAZ Auxiliary Contacts and Voltage Trips
Allowable Combinations of Accessories
Circuit Diagram Description
Rated Operational
Voltage
Catalog
Number
Standard Auxiliary Contacts
1NO/1NC
Installs on left side of FAZ or shunt trip
Max. one per FAZ (1077) device
Switches when FAZ is tripped
electrically or manually
230 Vac FAZ-XHIN11
1 changeover contact
Installs on left side of FAZ or shunt trip
Max. one per FAZ (1077) device
Switches when FAZ is tripped
electrically or manually
230 Vac FAZ-XHINW1
Auxiliary/Trip Indicating Contact
Two-pole auxiliary mode
Trip indicating mode
Small selector screw changes mode
Two Form C (changeover) contacts
Installs on left side of FAZ or shunt trip
Auxiliary contacts switch when FAZ is
tripped electrically or manually
Trip indicating contact switches only
when FAZ is tripped electrically
230 Vac FAZ-XAM002
Undervoltage Trip
Prevents FAZ from operating unless
voltage is present
Installs on left side of FAZ
Includes test button
115 Vac FAZ-XUA(115VAC)
230 Vac FAZ-XUA(230VAC)
400 Vac FAZ-XUA(400VAC)
Shunt Trip
Allows remote trip of FAZ
Installs on left side of FAZ
12–110 Vac
12–60 Vdc
FAZ-XAA-C-12-110VAC
110–415 Vac
110–230 Vdc
FAZ-XAA-C-110-
415VAC
12 14
11
D2
U
D1
C2
C1
AUX
TRIP
AUX AUX AUX
TRIP
FAZ FAZ FAZ
Circuit
Breaker
or
Circuit
Breaker
Shunt
Trip
or
Circuit
Breaker
UnderV
Trip
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-91
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
Busbar System
Note
1Bus may be center fed for high current capacity.
Description Rated Operational Current
Number of Poles
per Device
Number of
Terminals
Catalog
Number 1
Without Auxiliary Contacts
For connecting FAZ supplementary protectors without auxiliary
contacts. May be fed from line or load side.
80A 1 57 BB-UL-18/1P-1M/57
256BB-UL-18/2P-2M/56
357BB-UL-18/3P-3M/57
100A 1 57 BB-UL-25/1P-1M/57
256BB-UL-25/2P-2M/56
357BB-UL-25/3P-3M/57
Auxiliary/Trip Indicating Contacts
For connecting FAZ supplementary protectors with auxiliary
contacts. May be fed from line or load side.
80A 1 37 BB-UL-18/1P-1,5M/37
246BB-UL-18/2P+AS-2,5M/46
348BB-UL-18/3P+AS-3,5M/48
100A 1 37 BB-UL-25/1P-1,5M/37
246BB-UL-25/2P+AS-2,5M/46
348BB-UL-25/3P+AS-3,5M/48
WMZS WMZS WMZS
FAZFAZ
V4-T1-92 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
Pin Type Incoming Supply Terminals
Pin Type Incoming Supply Terminals—
Single-Phase Only
Protective Accessories
Description
Catalog
Number
Accommodates conductors
from 6–35 mm2/#10–2 AWG
4–5.5 Nm/35–50 lb-in
Two- and three-pole
BB-UL-TEP/35
Description
Catalog
Number
Accommodates conductors
from 6–35 mm2/#10–2 AWG
4–5.5 Nm/35–50 lb-in
BB-UL-TEPA/35
Description
Catalog
Number
For covering
unused terminals
BB-IP/5
Prevents reactivation of the device
during maintenance
Holds one padlock
IS/SPE-1TE
Incoming Terminal
Incoming Terminal
Busbar Terminal Cover
Padlock Hasp
Bus Incoming Supply Terminals
Busbar End Cap
Description
Catalog
Number
50 mm2
#14–1 AWG
75 Deg wire
115 A/Y, 480V UL
160 A/Y 690V IEC
BB-UL-TE/50
Description Poles
Catalog
Number
Install after cutting busbar
Protects end of busbar
2 and 3 BB-UL-EC/3
1BB-UL-EC/1
Incoming Terminal
Fork Connector
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-93
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
Technical Data and Specifications
Trip Curves Chart
Eaton FAZ supplementary
protectors are available with
six different tripping
characteristics, including
Type B, C, D, K, S and Z.
Definitions for each trip curve
are contained on the ordering
pages and can be used to
determine the optimal
characteristic for your
application. For example,
low-level short-circuit faults in
control wiring, such as PLCs,
are best protected by devices
with Type B trip characteristics
(3–5X continuous rating of the
device (In).
Even though not required by
NEC or CEC for supplementary
protectors, Eaton’s FAZ
devices are current limiting,
which means that they
interrupt fault currents
within one half cycle. Current
limiting devices offer superior
protection by reducing
peak let-through current
and energy.
Tripping Characteristics
I/In
ZBCKS
D
1 2 3 4 5 6 7 8 9 10 15 20 30 40 50
7200
3600
1200
600
300
120
60
30
10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.01
0.005
0.002
0.001
0.0005
t (sec)
1.05
1.30
1.13
1.45
Time-current characteristic acc. to UL 1077
Conventional
non-tripping current
Int = 1.13 IN: t > 1 h
Conventional tripping
current
It = 1.45 IN: t < 1 h
2.55 IN:
t = 1–60 s (IN < 32A)
t = 1–120 s (IN < 32A)
Type B: 3 IN: t > 0.1 s
Type B: 5 IN: t < 0.1 s
Type C: 5 IN: t > 0.1 s
Type C: 10 IN: t < 0.1 s
Type D: 10 IN: t > 0.1 s
Type D: 20 IN: t < 0.1 s
V4-T1-94 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
FAZ Miniature Circuit Breakers Technical Data
Description B Curve C Curve D Curve
Electrical
Approvals UR (UL 1077), CSA (CSA 22.2 No. 235), CE
Standards IEC/EN 60947-2
Short-circuit trip response 3–5 In5–10 In10–20 In
Supplementary Protectors—UL/CSA
Current range 1–63A 0.5–63A 0.5–40A
Maximum voltage ratings—UL/CSA
Single-pole, single-pole + neutral
Two-, three-pole, four-pole and
three-pole + neutral
Two poles in series
277 Vac
48 Vdc
480Y/277 Vac
96 Vdc
277 Vac
48 Vdc
480Y/277 Vac
96 Vdc
277 Vac
48 Vdc
480Y/277 Vac
96 Vdc
Thermal tripping characteristics
Single-pole
Multi-pole
1.35 x In @ 40°C
1.45 x In @ 40°C
1.35 x In @ 40°C
1.45 x In @ 40°C
1.35 x In @ 40°C
1.45 x In @ 40°C
Short-circuit ratings (at max. voltage)
Single-pole
Two-, three-pole
Single-pole
Two poles in series
10 kA (5 kA for 40–63A device)
10 kA (5 kA for 40–63A device)
10 kA @ 48 Vdc
10 kA @ 96 Vdc
10 kA (5 kA for 40–63A device)
10 kA (5 kA for 40–63A device)
10 kA @ 48 Vdc
10 kA @ 96 Vdc
5 kA
5 kA
10 kA @ 48 Vdc
10 kA @ 96 Vdc
Miniature Circuit Breaker—IEC
Current range 1–63A 0.5–63A 0.5–63A
Maximum voltage ratings—IEC 68898-1
Single-pole
Two-, three-pole
230 Vac
230/400 Vac
230 Vac
230/400 Vac
230 Vac
230/400 Vac
Maximum voltage ratings—IEC 60947-2
Single-pole
Two-, three-pole
Two poles in series
240 Vac
48 Vdc
240/415 Vac
96 Vdc
240 Vac
48 Vdc
240/415 Vac
96 Vdc
240 Vac
48 Vdc
240/415 Vac
96 Vdc
Thermal tripping characteristics
Single-pole
Multi-pole
> 1 hour @ 1.05 x In
< 1 hour @ 1.3 x In
> 1 hour @ 1.05 x In
< 1 hour @ 1.3 x In
> 1 hour @ 1.05 x In
< 1 hour @ 1.3 x In
Interrupt ratings (at max. voltage)
IEC 60947-2
IEC 60898
Operational switching capacity
Max. backup fuse [gL/gG]
Rated impulse withstand—Uimp
Rated insulation voltage—Ui
15 kA
10 kA
7.5 kA
125A
4000 Vac
440 Vac
15 kA
10 kA
7.5 kA
125A
4000 Vac
440 Vac
15 kA (10 kA for 50 and 63A)
10 kA (50 and 63A not available)
7.5 kA
125A
4000 Vac
440 Vac
Environmental/General
Selectivity class
Lifespan (operations)
Shock (IEC 68-2-22)
Operating temperature range
Shipment and short-term storage
Housing material
3
> 10,000 (1 operation = ON/OFF)
10g–120 ms
–40 to +167°F (–40 to +75°C)
–40 to +185°F (–40 to +85°C)
Nylon
3
> 10,000 (1 operation = ON/OFF)
10g–120 ms
–40 to +167°F (–40 to +75°C)
–40 to +185°F (–40 to +85°C)
Nylon
3
> 10,000 (1 operation = ON/OFF)
10g–120 ms
–40 to +167°F (–40 to +75°C)
–40 to +185°F (–40 to +85°C)
Nylon
Mechanical
Standard front dimension
Device height
Terminal protection
Mounting width per pole
80 mm
Finger and back-of-hand proof to IEC 536
17.5 mm
80 mm
Finger and back-of-hand proof to IEC 536
17.5 mm
80 mm
Finger and back-of-hand proof to IEC 536
17.5 mm
Mounting
Degree of protection
Terminals top and bottom
Supply connection
IEC/EN 60715 top-hat rail
IP20
Twin-purpose terminals
Line or load side
IEC/EN 60715 top-hat rail
IP20
Twin-purpose terminals
Line or load side
IEC/EN 60715 top-hat rail
IP20
Twin-purpose terminals
Line or load side
Terminal capacity [mm2]
Torque
Imperial torque
Thickness of busbar material
Mounting position
1 x 25 (AWG 4–18)/2 x 10 (AWG 8–18)
2.4 Nm
21 lb-in (AWG 18–12), 25 lb-in
(AWG 10–8), 36 lb-in (AWG 6–4)
0.8–2 mm
As required
1 x 25 (AWG 4–18)/2 x 10 (AWG 8–18)
2.4 Nm
21 lb-in (AWG 18–12), 25 lb-in
(AWG 10–8), 36 lb-in (AWG 6–4)
0.8–2 mm
As required
1 x 25 (AWG 4–18)/2 x 10 (AWG 8–18)
2.4 Nm
21 lb-in (AWG 18–12), 25 lb-in
(AWG 10–8), 36 lb-in (AWG 6–4)
0.8–2 mm
As required
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-95
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
FAZ Miniature Circuit Breakers Technical Data, continued
Description B Curve C Curve D Curve
Electrical
Approvals UR (UL 1077), CSA (CSA 22.2 No. 235), CE
Standards IEC/EN 60947-2, E177451, 204453
Short-circuit trip response 8–12 In13–17 In2–3 In
Supplementary Protectors—UL/CSA
Current range 0.5–63A 0.5–40A 1–63A
Maximum voltage ratings—UL/CSA
Single-pole, single-pole + neutral
Two-, three-, four-pole and
three-pole + neutral
Two poles in series
277 Vac
48 Vdc
480Y/277 Vac
96 Vdc
277 Vac
48 Vdc
480Y/277 Vac
96 Vdc
277 Vac
48 Vdc
480Y/277 Vac
96 Vdc
Thermal tripping characteristics
Single-pole
Multi-pole
1.35 x In @ 40°C
1.45 x In @ 40°C
1.35 x In @ 40°C
1.45 x In @ 40°C
1.35 x In @ 40°C
1.45 x In @ 40°C
Short-circuit ratings (at max. voltage)
Single-pole
Single-pole + neutral
Two-, three-, four-pole
Two poles in series
5 kA @ 277 Vac
5 kA @ 277 Vac
5 kA @ 480Y/277 Vac
5 kA @ 277 Vac
5 kA @ 277 Vac
5 kA @ 480Y/277 Vac
5 kA @ 277 Vac
5 kA @ 277 Vac
5 kA @ 480Y/277 Vac
Miniature Circuit Breaker—IEC
Current range 0.5–63A 0.5–40A 1–63A
Maximum voltage ratings—IEC 60947-2
Single-pole, single-pole + neutral
Two-, three-, four-pole,
three-pole + neutral
240 Vac
240/415 Vac
240 Vac
240/415 Vac
240 Vac
240/415 Vac
Thermal tripping characteristics
Single-pole
Multi-pole
> 1 Hour @ 1.05 x In
< 1 Hour @ 1.3 x In
> 1 Hour @ 1.05 x In
< 1 Hour @ 1.3 x In
> 1 Hour @ 1.05 x In
< 1 Hour @ 1.3 x In
Interrupt ratings (at max. voltage)
IEC 60947-2
Operational switching capacity
Max. backup fuse [gL/gG]
Rated impulse withstand—Uimp
Rated insulation voltage—Ui
15 kA
7.5 kA
125A
4000 Vac
440 Vac
10 kA
7.5 kA
125A
4000 Vac
440 Vac
10 kA
7.5 kA
125A
4000 Vac
440 Vac
Environmental/General
Selectivity class
Lifespan (operations)
Shock (IEC 68-2-22)
Operating temperature range
Shipment and short-term storage
Housing material
3
> 10,000 (1 operation = ON/OFF)
10g–120 ms
–40 to +167°F (–40 to +75°C)
–40 to +185°F (–40 to +85°C)
Nylon
3
> 10,000 (1 operation = ON/OFF)
10g–120 ms
–40 to +167°F (–40 to +75°C)
–40 to +185°F (–40 to +85°C)
Nylon
3
> 10,000 (1 operation = ON/OFF)
10g–120 ms
–40 to +167°F (–40 to +75°C)
–40 to +185°F (–40 to +85°C)
Nylon
Mechanical
Standard front dimension
Device height
Terminal protection
Mounting width per pole
80 mm
Finger and back-of-hand proof to IEC 536
17.7 mm
80 mm
Finger and back-of-hand proof to IEC 536
17.7 mm
80 mm
Finger and back-of-hand proof to IEC 536
17.7 mm
Mounting
Degree of protection
Terminals top and bottom
Supply connection
IEC/EN 60715 top-hat rail
IP20
Twin-purpose terminals
Line or load side
IEC/EN 60715 top-hat rail
IP20
Twin-purpose terminals
Line or load side
IEC/EN 60715 top-hat rail
IP20
Twin-purpose terminals
Line or load side
Terminal capacity [mm2]
Torque
Imperial torque
Thickness of busbar material
Mounting position
1 x 25 (AWG 4–18) / 2 x 10 (AWG 8–18)
2.4 Nm
21 lb-in (AWG 18–12), 25 lb-in
(AWG 10–8), 36 lb-in (AWG 6–4)
0.8–2 mm
As required
1 x 25 (AWG 4–18) / 2 x 10 (AWG 8–18)
2.4 Nm
21 lb-in (AWG 18–12), 25 lb-in
(AWG 10–8), 36 lb-in (AWG 6–4)
0.8–2 mm
As required
1 x 25 (AWG 4–18) / 2 x 10 (AWG 8–18)
2.4 Nm
21 lb-in (AWG 18–12), 25 lb-in
(AWG 10–8), 36 lb-in (AWG 6–4)
0.8–2 mm
As required
V4-T1-96 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
Let-Through Energy I2t
Characteristic B and C
Characteristic D
2 A
1 A
0.5 A
10 A
13 A
16 A
20 A
25 A
32 A
40 A
50 A
63 A
4 A
3 A
6 A
0.5
1.5 1512345678910
10
3
10
4
10
5
8
6
4
2
1.5
8
6
4
2
8
6
4
3
1.5
∫i2dt
[A2s]
Icc rms [kA]
10 A
13 A
16 A
20 A
25 A
32 A
40 A
6 A
0.5
1.5 1512345678910
10
3
10
4
10
5
8
6
4
2
1.5
8
6
4
2
8
6
4
1.5
∫i2dt
[A2s]
Icc rms [kA]
Let-Through Energy ID
Characteristic B and C
Characteristic D
63 A
40 A
50 A
32 A
20 A
25 A
16 A
13 A
10 A
6 A
4 A
3 A
2 A
1 A
0.5 A
0.5
1.5 1512345678910
10
3
10
4
9
8
7
6
5
4
3
2
1.5
5
2
lD
[A]
Icc rms [kA]
40 A
32 A
20 A
25 A
16 A
13 A
10 A
6 A
0.5
1.5 1512345678910
10
3
10
4
9
8
7
6
5
4
3
2
1.5
5
2
lD
[A]
Icc rms [kA]
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-97
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
Let-Through Energy I2t
Characteristic K
Characteristic Z
63 A
40 A 50 A
32 A
20 A 25 A
16 A
13 A
10 A
6 A
4 A
3 A
2 A
1 A
1.6 A
0.5 A
0.5
1.512345678910
103
104
8
6
4
3
2
1.5
5
l
D
[A]
I
cc rms
[kA]
63 A
40 A 50 A
32 A
20 A 25 A
16 A
10 A
6 A
8 A
4 A
3 A
2 A
1 A
1.6 A
0.5 A
0.5
1.512345678910
103
104
8
6
4
3
2
1.5
5
l
D
[A]
I
cc rms
[kA]
Characteristic S
40 A
32 A
20 A
25 A
16 A
10 A
6 A
4 A
3 A
2 A
1 A
0.5 1.512345678910
103
104
8
6
4
3
2
1.5
5
l
D
[A]
I
cc rms
[kA]
V4-T1-98 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
Influence of the Ambient Temperature on the Thermal Tripping Behavior
Corrected values of the rated current dependent on the ambient temperature
Influence of the Mains Frequency
Influence of the mains frequency on the tripping behavior IMA
of the instantaneous release
Load Carrying Capacity of Adjoining Miniature Circuit Breakers
In (A)
Ambient Temperature T
–40°C –30°C –20°C –10°C 0°C 10°C 20°C 30°C 35°C 40°C 45°C 50°C 55°C 60°C 65°C 70°C 75°C
0.16 0.20 0.20 0.19 0.19 0.18 0.17 0.17 0.16 0.16 0.15 0.15 0.15 0.14 0.14 0.14 0.14 0.13
0.25 0.32 0.31 0.30 0.29 0.28 0.27 0.26 0.25 0.25 0.24 0.24 0.23 0.23 0.22 0.22 0.21 0.21
0.50 0.64 0.62 0.60 0.58 0.56 0.54 0.52 0.50 0.49 0.48 0.47 0.46 0.45 0.44 0.43 0.42 0.41
0.75 0.96 0.93 0.90 0.87 0.84 0.81 0.78 0.75 0.74 0.73 0.71 0.69 0.68 0.66 0.65 0.64 0.62
1.00 1.30 1.20 1.20 1.20 1.10 1.10 1.00 1.00 0.99 0.97 0.95 0.93 0.90 0.89 0.87 0.85 0.83
1.50 1.90 1.90 1.80 1.70 1.70 1.60 1.60 1.50 1.50 1.50 1.40 1.40 1.40 1.30 1.30 1.30 1.20
1.60 2.00 2.00 1.90 1.90 1.80 1.70 1.70 1.60 1.60 1.50 1.50 1.50 1.40 1.40 1.40 1.40 1.30
2.00 2.60 2.50 2.40 2.30 2.20 2.20 2.10 2.00 2.00 1.90 1.90 1.90 1.80 1.80 1.70 1.70 1.70
2.50 3.20 3.10 3.00 2.90 2.80 2.70 2.60 2.50 2.50 2.40 2.40 2.30 2.30 2.20 2.20 2.10 2.10
3.00 3.80 3.70 3.60 3.50 3.40 3.30 3.10 3.00 3.00 2.90 2.80 2.80 2.70 2.70 2.60 2.50 2.50
3.50 4.50 4.40 4.20 4.10 3.90 3.80 3.70 3.50 3.40 3.40 3.30 3.20 3.20 3.10 3.00 3.00 2.90
4.00 5.10 5.00 4.80 4.70 4.50 4.30 4.20 4.00 3.90 3.90 3.80 3.70 3.60 3.50 3.50 3.40 3.30
5.00 6.40 6.20 6.00 5.80 5.60 5.40 5.20 5.00 4.90 4.80 4.70 4.60 4.50 4.40 4.30 4.20 4.10
6.00 7.70 7.50 7.20 7.00 6.70 6.50 6.30 6.00 5.90 5.80 5.70 5.60 5.40 5.30 5.20 5.10 5.00
7.00 9.00 8.70 8.40 8.20 7.80 7.60 7.40 7.00 6.90 6.80 6.70 6.50 6.30 6.20 6.10 6.00 5.80
8.00 10.20 9.90 9.60 9.30 9.00 8.70 8.40 8.00 7.90 7.70 7.60 7.40 7.20 7.10 6.90 6.80 6.60
10.00 13.00 12.00 12.00 12.00 11.00 11.00 10.00 10.00 9.90 9.70 9.50 9.30 9.00 8.90 8.70 8.50 8.30
12.00 15.00 15.00 14.00 14.00 13.00 13.00 13.00 12.00 12.00 12.00 11.00 11.00 11.00 11.00 10.00 10.00 10.00
13.00 17.00 16.00 16.00 15.00 15.00 14.00 14.00 13.00 13.00 13.00 12.00 12.00 12.00 12.00 11.00 11.00 11.00
15.00 19.00 19.00 18.00 17.00 17.00 16.00 16.00 15.00 15.00 15.00 14.00 14.00 14.00 13.00 13.00 13.00 12.00
16.00 20.00 20.00 19.00 19.00 18.00 17.00 17.00 16.00 16.00 15.00 15.00 15.00 14.00 14.00 14.00 14.00 13.00
20.00 26.00 25.00 24.00 23.00 22.00 22.00 21.00 20.00 20.00 19.00 19.00 19.00 18.00 18.00 17.00 17.00 17.00
25.00 32.00 31.00 30.00 29.00 28.00 27.00 26.00 25.00 25.00 24.00 24.00 23.00 23.00 22.00 22.00 21.00 21.00
32.00 41.00 40.00 38.00 37.00 36.00 35.00 33.00 32.00 32.00 31.00 30.00 30.00 29.00 28.00 28.00 27.00 26.00
35.00 45.00 43.00 41.00 41.00 38.00 38.00 36.00 35.00 35.00 34.00 33.00 32.00 32.00 32.00 30.00 29.00 29.00
40.00 51.00 50.00 48.00 47.00 45.00 43.00 42.00 40.00 39.00 39.00 38.00 37.00 36.00 35.00 35.00 34.00 33.00
50.00 64.00 62.00 60.00 58.00 56.00 54.00 52.00 50.00 49.00 48.00 47.00 46.00 45.00 44.00 43.00 42.00 41.00
63.00 81.00 78.00 76.00 73.00 71.00 68.00 66.00 63.00 62.00 61.00 60.00 58.00 57.00 56.00 55.00 53.00 52.00
Mains Frequency f [Hz]
16 2/3 50 60 100 200 300 400
IMA(f)IMA (50 Hz) [%] 91 100 101 106 115 134 141
Number of Circuit Breakers
Rated Diversity Factor
12345678
0.70
0.80
0.90
1.0 0
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-99
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
Accessories Technical Data
Description
FAZ-XHIN
FAZ-XAM002 FAZ-XAA-C FAZ-XUA
Electrical
Contact function 1A + 1B
2 C/O
Rated operational voltage Un250 Vac 115 Vac
230 Vac
400 Vac
Voltage range 12–110 Vac
12–60 Vdc
Voltage range 110–415 Vac
110–230 Vdc
Closing threshold [x Un]—0.8
Tripping threshold [x Un]—0.5
Rated frequency ƒ 50/60 Hz 50/60 Hz 50/60 Hz
General use (UL/CSA)
AC—230/240 Vac
DC—110/120 Vdc
2/2A
0.5/0.5A
Pilot duty A600/Q600
Conventional free air thermal current Ith 4A
Rated operational current
AC-13 Ie
AC-15 Ie
DC-13 Ie
3A (250 Vac)
2A (250 Vac)
0.5A (110 Vdc)
Rated insulation voltage Ui250 Vac
Minimum operating voltage per contract Umin 5 Vdc
Rated impulse withstand voltage (1.2/50) Uimp 2.5 kV
Rated conditional short-circuit current with 6A backup fuse ISC 1 kA
Max. admissible backup fuse 4A gL
Mechanical
Standard front dimension 45 mm 45 mm 45 mm
Device height 80 mm 80 mm 80 mm
Mounting width 8.8 mm 17.6 mm 17.8 mm
Mounting On MCB IEC/EN 60715 top-hat rail IEC/EN 60715 top-hat rail
Degree of protection enclosed
IP40 IP40 IP40
Terminal protection Protection against
electric shock to IEC 536
Protection against
electric shock to IEC 536
Protection against
electric shock to IEC 536
Terminals Lift terminals Twin-purpose terminals Twin-purpose terminals
Terminal capacity
Solid
Flexible
0.5–2.5 mm2
0.5–2.5 mm21–2.5 mm2
1–2.5 mm22 x (1–2.5) mm2
2 x (1–2.5) mm2
Tightening torque of terminal screws 0.8–1.0 Nm (7–9 lb-in) 2.4 Nm (21 lb-in) 0.8 Nm (7 lb-in)
V4-T1-100 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
Dimensions
Approximate Dimensions in Inches (mm)
Miniature Circuit Breakers
FAZ
Auxiliary Contacts
FAZ-XHI11 and FAZ-XH1NW1 FAZ-XAM002
Shunt Releases Undervoltage Releases
FAZ-XAA FAZ-XUA
2.79
(70.8)
1.77
(45.0)
0.74
(9.4)
2.36
(60.0)
1.73
(44.0)
0.22
(5.5)
2.09
(53.1)
1.40
(35.4)
0.70
(17.8)
3.15
(80.0)
0.35
(8.8)
3.15
(80.0) 1.77
(45.0)
2.36
(60.0)
1.73
(44.0)
0.22
(5.5)
0.35
(8.8)
3.15
(80.0)
1.77
(45.0)
2.36
(60.0)
1.73
(44.0)
0.22
(5.5)
0.70
(17.8)
3.15
(80.0)
1.03
(26.2)
1.20
(30.5) 0.39
(10.0)
1.77
(45.0)
2.36
(60.0)
1.73
(44.0)
0.22
(5.5)
0.70
(17.8)
3.15
(80.0) 1.77
(45.0)
2.36
(60.0)
1.73
(44.0)
0.22
(5.5)
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-101
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
Approximate Dimensions in Inches (mm)
Busbar and Accessory Weights and Dimensions
Unit Weight (kg) Length Width Height
Catalog
Number
0.29 39.72 (1009.0) 0.59 (15.0) 0.59 (15.0) BB-UL-18/1P-1M/57
0.64 39.02 (991.0) 0.87 (22.0) 1.46 (37.0) BB-UL-18/2P-2M/56
0.83 39.72 (1009.0) 0.87 (22.0) 1.46 (37.0) BB-UL-18/3P-3M/57
0.26 38.78 (985.0) 0.59 (15.0) 0.59 (15.0) BB-UL-18/1P-1.5M/37
0.63 39.72 (1009.0) 0.87 (22.0) 1.46 (37.0) BB-UL-18/2P+AS-2.5M/46
0.79 38.66 (982.0) 0.87 (22.0) 1.46 (37.0) BB-UL-18/3P+AS-3.5M/48
0.36 39.72 (1009.0) 0.59 (15.0) 0.59 (15.0) BB-UL-25/1P-1M/57
0.79 39.02 (991.0) 0.87 (22.0) 1.46 (37.0) BB-UL-25/2P-2M/56
1.04 39.72 (1009.0) 0.87 (22.0) 1.46 (37.0) BB-UL-25/3P-3M/57
0.31 38.78 (985.0) 0.59 (15.0) 0.59 (15.0) BB-UL-25/1P-1.5M/37
0.73 39.72 (1009.0) 0.87 (22.0) 1.46 (37.0) BB-UL-25/2P+AS-2.5M/46
0.97 38.66 (982.0) 0.87 (22.0) 1.46 (37.0) BB-UL-25/3P+AS-3.5M/48
0.03 2.36 (60.0) 0.67 (17.0) 1.14 (29.0) BB-UL-TEP/35
0.03 1.42 (36.0) 0.67 (17.0) 1.14 (29.0) BB-UL-TEPA/35
0.03 1.57 (40.0) 0.71 (18.0) 1.18 (30.0) BB-UL-TE/50
0.003 3.35 (85.0) 0.47 (12.0) 0.94 (24.0) BB-IP/5
0.001 0.55 (14.0) 0.20 (5.0) 0.39 (10.0) BB-UL-EC/3
0.001 0.94 (24.0) 0.87 (22.0) 0.39 (10.0) BB-UL-EC/1
L W
H
L1 L2 L1 L2 L1 L2 L1 L2 L1 L2 L1 L2
V4-T1-102 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
Application Guidelines
Example of UL 489 and UL 1077 Application
UL 489 circuit breakers
Used for branch circuit protection, internal/external receptacles, external motors and HACR equipment
(heating, air conditioning and refrigeration).
UL 1077 supplementary protectors
Used for overcurrent protection within appliances or electrical equipment, where branch circuit protection
is already provided or not required.
Note: UL 4 89 devices can be used in place of UL 1077; UL 1077 devices cannot be used in place of UL 489.
Electronics
Internal Receptacle
UL 489
Breaker
UL 489
Branch
UL 1077
UL 1077
UL 1077
UL 489
Branch
UL 489
Branch
UL 489
Branch
External
Receptacle
External
Motor
M
M
External
Motor
Motor
Controller
Other
Sensitive
Devices
HACR
Example of UL 489 and UL 1077 Application
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-103
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
WMZS Circuit Breakers
Contents
Description Page
FAZ Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . V4-T1-82
WMZS Circuit Breaker
Standards and Certifications. . . . . . . . . . . . . . . . V4-T1-104
Catalog Number Selection . . . . . . . . . . . . . . . . . V4-T1-104
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-105
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-107
Technical Data and Specifications. . . . . . . . . . . . V4-T1-110
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T1-117
WMZS Circuit Breaker
Product Overview
Optimum product quality,
tested reliability and safety
stand for best protection of
personnel, installations and
plant. Eaton’s WMZS DIN rail
mountable circuit breaker is
designed for use in control
panel applications.The WMZS
is available with B, C and D
characteristics in accordance
with UL 1077, CSA C22.2
No.235 and IEC 60947-2.
Application Description
Supplementary protection:
Control circuits
Lighting
Business equipment
Appliances
Features
Complete range of
UL 1077 Recognized DIN
rail mounted miniature
circuit breakers up to 63A
current rating
Standard ratings of 10 kAIC
at 277/480 Vac
Current limiting design
provides fast short-circuit
interruption that reduces
the let-through energy,
which can damage the
circuit
Offers supplementary
protection
Thermal-magnetic
overcurrent protection
Three levels of short-
circuit protection,
categorized by B, C
and D curves
Trip-free design—breaker
can not be defeated by
holding the handle in the
ON position
Captive screws cannot
be lost
Fulfill UL 1077, CSA C22.2
No.235 and also IEC
60947-2 Standard
Field-installable shunt trip
and auxiliary switch
subsequent mounting
Module width of only 0.69
inches (17.5 mm) per pole
Contact Position Indicator
(red/green)
Easy installation on DIN rail
Possibility for sealing the
toggle in ON or OFF
position
V4-T1-104 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
Advanced Features
Catalog Number Selection
Breakers install on
standard DIN rail
Available in single-,
two- and three-pole
models
Color-coded indicator
provides breaker status
for easy troubleshooting
Captive posidrive terminal
screws with finger and back-
of-hand protection (IP20)
Trip-free design; breaker
cannot be defeated by
holding the handle in the
ON position
Breaker information
printed on the front of
the device for quick
identification
Breaker Family
WMZS = Supplementary Protector Number of Poles
1 = Single-pole
2 = Two-pole
3 = Three-pole
Protective Curve
B = B Curve (3–5X In)
C = C Curve (5–10X In)
D = D Curve (10–20X In)
Ampere Rating
00 = 0.5A
01 = 1A
02 = 2A
03 = 3A
04 = 4A
05 = 5A
06 = 6A
07 = 7A
08 = 8A
10 = 10A
13 = 13A
15 = 15A
16 = 16A
20 = 20A
25 = 25A
30 = 30A
32 = 32A
40 = 40A
50 = 50A
63 = 63A
WMZS 1 B 10
Standards and Certifications
Worldwide Acceptance
WMZS Supplementary
Protectors are UL Recognized
for use in the United States in
accordance with NFPA® 70
(NEC). The devices comply
with UL 1077 and CSA 22.2
No. 235, meeting the
requirements for
supplementary protectors.
These devices are for
international and domestic
use, and also comply with
IEC 60947-2 and are
CE marked. These devices
are RoHS compliant.
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-105
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
Product Selection
WMZS Product Selection—B Curve (3–5X In Current Rating)
Suitable for applications where protection against low level short
circuit faults in control wiring is desired. Instantaneous trip is
3–5X continuous rating of device (In). Applications include PLC
wiring, business equipment, lighting, appliances and some
motors. Low magnetic trip point.
B Curve (3–5X In Current Rating)—
Designed for Resistive or Slightly
Inductive Loads 123
Single-Pole Two-Pole Three-Pole
Amperes
Catalog
Number
Catalog
Number
Catalog
Number
6WMZS1B06 WMZS2B06 WMZS3B06
7WMZS1B07 WMZS2B07 WMZS3B07
8WMZS1B08 WMZS2B08 WMZS3B08
10 WMZS1B10 WMZS2B10 WMZS3B10
13 WMZS1B13 WMZS2B13 WMZS3B13
15 WMZS1B15 WMZS2B15 WMZS3B15
16 WMZS1B16 WMZS2B16 WMZS3B16
20 WMZS1B20 WMZS2B20 WMZS3B20
25 WMZS1B25 WMZS2B25 WMZS3B25
30 WMZS1B30 WMZS2B30 WMZS3B30
32 WMZS1B32 WMZS2B32 WMZS3B32
40 WMZS1B40 WMZS2B40 WMZS3B40
50 WMZS1B50 WMZS2B50 WMZS3B50
63 WMZS1B63 WMZS2B63 WMZS3B63
Single-Pole
Two-Pole
Three-Pole
WMZS Product Selection—C Curve (5–10X In Current Rating)
Suitable for applications where medium levels of inrush current
are expected. Instantaneous trip is 5–10X rating of device (In).
Applications include small transformers, lighting, pilot devices,
control circuits, and coils. Medium magnetic trip point.
C Curve (5–10X In Current Rating)—
Designed for Inductive Loads 145
Notes
1In North America, these switches are UL recognized and CSA certified as Supplementary
Protection devices. Per the intent of NEC (National Electrical Code), Article 240, and CEC
(Canadian Electrical Code), Part 1 C22.1, supplementary breakers cannot be used as a
substitute for the branch circuit protective device. They can be used to provide overcurrent
protection within an appliance or other electrical equipment where branch circuit overcurrent
protection is already provided, or is not required.
2Designed for resistive or slightly inductive loads.
3Response time of instantaneous trip: 3–5X In current rating.
4Designed for inductive loads.
5Response time of instantaneous trip: 5–10X In current rating.
Single-Pole Two-Pole Three-Pole
Amperes
Catalog
Number
Catalog
Number
Catalog
Number
0.5 WMZS1C00 WMZS2C00 WMZS3C00
1WMZS1C01 WMZS2C01 WMZS3C01
2WMZS1C02 WMZS2C02 WMZS3C02
3WMZS1C03 WMZS2C03 WMZS3C03
4WMZS1C04 WMZS2C04 WMZS3C04
5WMZS1C05 WMZS2C05 WMZS3C05
6WMZS1C06 WMZS2C06 WMZS3C06
7WMZS1C07 WMZS2C07 WMZS3C07
8WMZS1C08 WMZS2C08 WMZS3C08
10 WMZS1C10 WMZS2C10 WMZS3C10
13 WMZS1C13 WMZS2C13 WMZS3C13
15 WMZS1C15 WMZS2C15 WMZS3C15
16 WMZS1C16 WMZS2C16 WMZS3C16
20 WMZS1C20 WMZS2C20 WMZS3C20
25 WMZS1C25 WMZS2C25 WMZS3C25
30 WMZS1C30 WMZS2C30 WMZS3C30
32 WMZS1C32 WMZS2C32 WMZS3C32
40 WMZS1C40 WMZS2C40 WMZS3C40
50 WMZS1C50 WMZS2C50 WMZS3C50
63 WMZS1C63 WMZS2C63 WMZS3C63
Single-Pole
Two-Pole
Three-Pole
V4-T1-106 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
WMZS Product Selection—D Curve (10–20X In Current Rating)
Suitable for applications where high levels of inrush current are
expected. Instantaneous trip is 10–20X rating of device (In).
The high magnetic trip point prevents nuisance tripping in high
inductive applications such as motors, transformers and
power supplies.
D Curve (10–20X In Current Rating)—
Designed for Inductive Loads 123
Notes
1In North America, these switches are UL recognized and CSA certified as Supplementary
Protection devices. Per the intent of NEC (National Electrical Code), Article 240, and CEC
(Canadian Electrical Code), Part 1 C22.1, supplementary breakers cannot be used as a
substitute for the branch circuit protective device. They can be used to provide overcurrent
protection within an appliance or other electrical equipment where branch circuit overcurrent
protection is already provided, or is not required.
2Designed for highly inductive loads.
3Response time of instantaneous trip: 10–20X In current rating.
Single-Pole Two-Pole Three-Pole
Amperes
Catalog
Number
Catalog
Number
Catalog
Number
0.5 WMZS1D00 WMZS2D00 WMZS3D00
1WMZS1D01 WMZS2D01 WMZS3D01
2WMZS1D02 WMZS2D02 WMZS3D02
3WMZS1D03 WMZS2D03 WMZS3D03
4WMZS1D04 WMZS2D04 WMZS3D04
5WMZS1D05 WMZS2D05 WMZS3D05
6WMZS1D06 WMZS2D06 WMZS3D06
7WMZS1D07 WMZS2D07 WMZS3D07
8WMZS1D08 WMZS2D08 WMZS3D08
10 WMZS1D10 WMZS2D10 WMZS3D10
13 WMZS1D13 WMZS2D13 WMZS3D13
15 WMZS1D15 WMZS2D15 WMZS3D15
16 WMZS1D16 WMZS2D16 WMZS3D16
20 WMZS1D20 WMZS2D20 WMZS3D20
25 WMZS1D25 WMZS2D25 WMZS3D25
30 WMZS1D30 WMZS2D30 WMZS3D30
32 WMZS1D32 WMZS2D32 WMZS3D32
40 WMZS1D40 WMZS2D40 WMZS3D40
Single-Pole
Two-Pole
Three-Pole
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-107
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
Accessories
WMZS Auxiliary Contacts and Voltage Trips
Allowable Combinations of Accessories
Module Circuit Diagram Description
Rated Operational
Voltage
Catalog
Number
Standard Auxiliary Contacts
1NO/1NC
Installs on left side of WMZS or shunt trip
Max. one per WMZS (1077) device
Switches when WMZS is tripped
electrically or manually
230 Vac WMZSAUX
Auxiliary/Trip Indicating Contact
Small selector screw changes mode
Two Form C (changeover) contacts
Installs on left side of WMZS or shunt trip
Auxiliary contacts switch when WMZS is
tripped electrically or manually
Trip indicating contact switches only when
WMZS is tripped electrically
230 Vac WMZSAUXTRIP
Undervoltage Trip
Prevents WMZS from operating unless
voltage is present
Installs on left side of WMZS
Includes test button
115 Vac WMZSUVR115
230 Vac WMZSUVR230
400 Vac WMZSUVR400
Shunt Trip
Allows remote trip of WMZS
Installs on left side of WMZS
110–415 Vac WMZSST415
110–230 Vdc
12–110 Vac WMZSST110
12–60 Vdc
2
14 1112
H
1
2 4 1.12 4.14
1.14 4.12
1.11
OFF
4.11N
D2
U
D1
C2
C1
AUX
TRIP
AUX AUX AUX
TRIP
FAZ FAZ FAZ
Circuit
Breaker
or
Circuit
Breaker
Shunt
Trip
or
Circuit
Breaker
UnderV
Trip
V4-T1-108 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
Busbar System
Description
Rated Operational
Current (A)
Number of Poles
per Device
Number of
Terminals
Catalog
Number
Without Auxiliary Contacts
For connecting WMZS Supplementary Protectors without auxiliary
contacts. May be fed from line or load side.
80 1 57 WMZS1P57T
256WMZS2P56T
357WMZS3P57T
100 1 57 WMZS1P57T25
256WMZS2P56T25
357WMZS3P57T25
Auxiliary/Trip Indicating Contact
For connecting WMZS Supplementary Protectors with auxiliary
contacts. May be fed from line or load side.
80 1 37 WMZS1P37TAUX
246WMZS2P46TAUX
348WMZS3P48TAUX
100 1 37 WMZS1P37T25AUX
246WMZS2P46T25AUX
348WMZS3P48T25AUX
WMZS WMZS WMZS
WMZS WMZS
35 lb-in
(4 Nm)
22 lb-in
(2.5 Nm)
WMZSBCONA
WMZS35EXT
WMZS3CAP
or
WMZS1CAP
WMZSBBTC
50 lb-in
(5.5 Nm)
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-109
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
Pin Type Incoming Supply Terminals
Protective Accessories
Description
Catalog
Number
Accommodates conductors from
6–35 mm2 /#10–2 AWG
4–5.5 Nm/35–50 16 lb-in
Finger-safe connection
WMZS35EXT
Description
Catalog
Number
For covering unused terminals WMZSBBTC
Prevents reactivation of the device during
maintenance
Holds one padlock
WMZPLK
Incoming Terminal
Busbar Terminal Cover
Padlock Hasp
Bus Incoming Supply Terminals
Busbar End Cap
Description
Catalog
Number
50 mm2
#14–1 AWG
75 Deg Wire
115A/Y, 480V UL
160A/Y 690V IEC
WMZSBCONA
Description
Number
of Poles
Catalog
Number
Install after cutting busbar
Protects end of busbar
2 and 3 WMZS3CAP
1WMZS1CAP
Incoming Terminal
Fork Connector
Two- and Three-Pole
Fork Connector
Two- and Three-Pole
V4-T1-110 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
Technical Data and Specifications
Trip Curve Charts
Three Tripping Curves
to Choose
Eaton WMZS Supplementary
Protectors are available with
three different tripping
characteristics, including
Type B, C and D. Definitions
for each trip curve are
contained on the ordering
pages and can be used to
determine the optimal
characteristic for your
application. For example,
low level short-circuit faults
in control wiring, such as
PLCs, are best protected
by devices with Type B trip
characteristics (3 to 5X
continuous rating of the
device (In).
Even though not required by
NEC or CEC for Supplementary
Protectors, Eaton’s WMZS
devices are current limiting,
which means they interrupt
fault currents within one
half cycle. Current limiting
devices offer superior
protection by reducing
peak let-through current
and energy.
WMZS Tripping Curves
0.0005
t [sec]
N
I / I
7200
3600
1200
600
300
120
60
30
10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.005
0.01
0.002
0.001
5040302015
1098765432
1
9
5
4
3
3
2
D
C
B
7
8
6
1
Time-current characteristic acc. to UL 1077
conventional
non-tripping current
I
nt
= 1.13 I
N
: t > 1 h
conventional tripping
current
I
t
= 1.45 I
N
: t < 1 h
2.55 I
N
:
t = 1 – 60 s (I
N
< 32A)
t = 1 – 120 s (I
N
< 32A)
Type B: 3 I
N
: t > 0.1 s
Type B: 5 I
N
: t < 0.1 s
Type C: 5 I
N
: t > 0.1 s
Type C: 10 I
N
: t < 0.1 s
Type D: 10 I
N
: t > 0.1 s
Type D: 20 I
N
: t < 0.1 s
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-111
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
B Curve
C Curve
0.0005
t [sec]
N
I / I
7200
1.13
1.45
3600
1200
600
300
120
60
30
10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.005
0.01
0.002
0.001
5040302015
1098765432
1
7
3
2
1
1
D
C
B
5
6
4
Specied non-tripping
current
I
NT
= 1.13 x I
N
for t > 1 h
Specied tripping current
I
T
= 1.45 x I
N
for t < 1 h
2.55 I
N
:
t = 1 – 60 s (I
N
< 32A)
t = 1 – 120 s (I
N
> 32A)
Type B: 3 x I
N
: t > 0.1 s
Type B: 5 x I
N
: t < 0.1 s
Type C: 5 x I
N
: t > 0.1 s
Type C: 10 x I
N
: t < 0.1 s
Type D: 10 x I
N
: t > 0.1 s
Type D: 20 x I
N
: t < 0.1 s
0.0005
t [sec]
N
I / I
7200
1.13
1.45
3600
1200
600
300
120
60
30
10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.005
0.01
0.002
0.001
5040302015
1098765432
1
7
3
2
1
1
D
C
B
5
6
4
Specied non-tripping
current
I
NT
= 1.13 x I
N
for t > 1 h
Specied tripping current
I
T
= 1.45 x I
N
for t < 1 h
2.55 I
N
:
t = 1 – 60 s (I
N
< 32A)
t = 1 – 120 s (I
N
> 32A)
Type B: 3 x I
N
: t > 0.1 s
Type B: 5 x I
N
: t < 0.1 s
Type C: 5 x I
N
: t > 0.1 s
Type C: 10 x I
N
: t < 0.1 s
Type D: 10 x I
N
: t > 0.1 s
Type D: 20 x I
N
: t < 0.1 s
D Curve
0.0005
t [sec]
N
I / I
7200
1.13
1.45
3600
1200
600
300
120
60
30
10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.005
0.01
0.002
0.001
5040302015
1098765432
1
7
3
2
1
1
D
C
B
5
6
4
Specied non-tripping
current
I
NT
= 1.13 x I
N
for t > 1 h
Specied tripping current
I
T
= 1.45 x I
N
for t < 1 h
2.55 I
N
:
t = 1 – 60 s (I
N
< 32A)
t = 1 – 120 s (I
N
> 32A)
Type B: 3 x I
N
: t > 0.1 s
Type B: 5 x I
N
: t < 0.1 s
Type C: 5 x I
N
: t > 0.1 s
Type C: 10 x I
N
: t < 0.1 s
Type D: 10 x I
N
: t > 0.1 s
Type D: 20 x I
N
: t < 0.1 s
V4-T1-112 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
WMZ Miniature Circuit Breaker Technical Data
Description B Curve C Curve D Curve
Electrical
Approvals UR (UL 1077), CSA (CSA 22.2 No. 235), CE
Standards IEC/EN 60947-2
Short-circuit trip response 3–5 In5–10 In10–20 In
Supplementary Protectors—UL/CSA
Current range 6–63A 0.5–63A 0.5–40A
Maximum voltage ratings—UL/CSA
Single-pole
Two-, three-pole
Two poles in series
277 Vac
48 Vdc
480Y/277 Vac
96 Vdc
277 Vac
48 Vdc
480Y/277 Vac
96 Vdc
277 Vac
48 Vdc
480Y/277 Vac
96 Vdc
Thermal tripping characteristics
Single-pole
Multi-pole
1.35 x In at 40°C
1.45 x In at 40°C
1.35 x In at 40°C
1.45 x In at 40°C
1.35 x In at 40°C
1.45 x In at 40°C
Short-circuit ratings (at max. voltage)
Single-pole
Two-, three-pole
Single-pole
Two poles in series
10 kA (5 kA for 40–63A device)
10 kA (5 kA for 40–63A device)
10 kA at 48 Vdc
10 kA at 96 Vdc
10 kA (5 kA for 40–63A device)
10 kA (5 kA for 40–63A device)
10 kA at 48 Vdc
10 kA at 96 Vdc
5 kA
5 kA
10 kA at 48 Vdc
10 kA at 96 Vdc
Miniature Circuit Breaker—IEC
Current range 6–63A 0.5–63A 0.5–40A
Maximum voltage ratings—IEC 60947-2
Single-pole
Two-, three-pole
230 Vac
48 Vdc
230/400 Vac
230 Vac
48 Vdc
230/400 Vac
230 Vac
48 Vdc
230/400 Vac
Maximum voltage ratings—IEC 60898
Single-pole
Two-, three-pole
240 Vac
48 Vdc
240/415 Vac
240 Vac
48 Vdc
240/415 Vac
240 Vac
48 Vdc
240/415 Vac
Thermal tripping characteristics
Single-pole
Multi-pole
> 1 hour at 1.05 x In
< 1 hour at 1.3 x In
> 1 hour at 1.05 x In
< 1 hour at 1.3 x In
> 1 hour at 1.05 x In
< 1 hour at 1.3 x In
Interrupting ratings (at max. voltage)
IEC 60947-2
IEC 60898
15 kA
10 kA
15 kA
10 kA
15 kA
10 kA
Operational switching capacity 7.5 kA 7.5 kA 7.5 kA
Max. back-up fuse [gL/gG] 125A 125A 125A
Rated impulse withstand—Uimp 4000 Vac 4000 Vac 4000 Vac
Rated insulation voltage—Ui440 Vac 440 Vac 440 Vac
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-113
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
WMZ Miniature Circuit Breaker Technical Data, continued
Description B Curve C Curve D Curve
Environmental/General
Selectivity class 3 3 3
Lifespan (operations) > 10,000 (1 operation = ON/OFF) > 10000 (1 operation = ON/OFF) > 10000 (1 operation = ON/OFF)
Shock (IEC 68-2-22) 10g–120 ms 10g–120 ms 10g–120 ms
Operating temperature range 23° to 104°F (–5° to 40°C) 23° to 104°F (–5° to 40°C) 23° to 104°F (–5° to 40°C)
Shipment and short-term storage –40° to 185°F (–40° to 85°C) –40 to 185°F (–40° to 85°C) –40° to 185°F (–40° to 85°C)
Housing material Nylon Nylon Nylon
Mechanical
Standard Front Dimension
Device height
Terminal protection
Mounting width per pole
80 mm
Finger and back-of-hand proof to IEC 536
17.5 mm
80 mm
Finger and back-of-hand proof to IEC 536
17.5 mm
80 mm
Finger and back-of-hand proof to IEC 536
17.5 mm
Mounting IEC/EN 60715 top-hat rail IEC/EN 60715 top-hat rail IEC/EN 60715 top-hat rail
Degree of protection IP20 IP20 IP20
Terminals top and bottom Twin-purpose terminals Twin-purpose terminals Twin-purpose terminals
Supply connection Line or load side Line or load side Line or load side
Terminal capacity [mm2] 1 x 25 (AWG 4–18) / 2 x 10 (AWG 8–18) 1 x 25 (AWG 4–18) / 2 x 10 (AWG 8–18) 1 x 25 (AWG 4–18) / 2 x 10 (AWG 8–18)
Torque 2.4 Nm 2.4 Nm 2.4 Nm
Imperial torque 21 lb-in (AWG 18–12), 25 lb-in
(AWG 10–8), 36 lb-in (AWG 6–4)
21 lb-in (AWG 18–12), 25 lb-in
(AWG 10–8), 36 lb-in (AWG 6–4)
21 lb-in (AWG 18–12), 25 lb-in
(AWG 10–8), 36 lb-in (AWG 6–4)
Thickness of busbar material 0.8–2 mm 0.8–2 mm 0.8–2 mm
Mounting position As required As required As required
V4-T1-114 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
Let-Through Energy I2t
Characteristic B and C
Characteristic D
2 A
1 A
0.5 A
10 A
13 A
16 A
20 A
25 A
32 A
40 A
50 A
63 A
4 A
3 A
6 A
0.5
1.5 1 512345678910
103
104
105
8
6
4
2
1.5
8
6
4
2
8
6
4
3
1.5
i2dt
[A2s]
Icc rms [kA]
WMZS-...-B4HI
10 A
13 A
16 A
20 A
25 A
32 A
40 A
6 A
0.5
1.5 1 512345678910
103
104
105
8
6
4
2
1.5
8
6
4
2
8
6
4
1.5
i2dt
[A2s]
Icc rms [kA]
Let-Through Current ID
Characteristic B and C
Characteristic D
63 A
40 A 50 A
32 A
20 A
25 A
16 A
13 A
10 A
6 A
4 A
3 A
2 A
1 A
0.5 A
0.5
1.5 1 512345678910
103
104
9
8
7
6
5
4
3
2
1.5
5
2
lD
[A]
Icc rms [kA]
40 A 32 A
20 A
25 A
16 A
13 A
10 A
6 A
0.5
1.5 1 512345678910
103
104
9
8
7
6
5
4
3
2
1.5
5
2
lD
[A]
Icc rms [kA]
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-115
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
Influence of the Ambient Temperature on the Thermal Tripping Behavior
Corrected values of the rated current dependent on the ambient temperature
Influence of the Mains Frequency
Influence of the mains frequency on the tripping behavior IMA of the instantaneous release
Load Carrying Capacity of Adjoining Miniature Circuit Breakers
Ambient Temperature T
In (A) –25°C –20°C –10°C 0°C 10°C 20°C 30°C 35°C 40°C 45°C 50°C 55°C 60°C
0.16 0.2 0.19 0.19 0.18 0.17 0.17 0.16 0.16 0.15 0.15 0.15 0.14 0.14
0.25 0.31 0.3 0.29 0.28 0.27 0.26 0.25 0.25 0.24 0.24 0.23 0.23 0.22
0.5 0.61 0.6 0.58 0.56 0.54 0.52 0.5 0.49 0.48 0.47 0.46 0.45 0.44
0.75 0.92 0.9 0.87 0.84 0.81 0.78 0.75 0.74 0.73 0.71 0.69 0.68 0.66
1 1.2 1.2 1.2 1.1 1.1 1 1 0.99 0.97 0.95 0.93 0.9 0.89
1.51.81.81.71.71.61.61.51.51.51.41.41.41.3
1.62 1.91.91.81.71.71.61.61.51.51.51.41.4
2 2.4 2.4 2.3 2.2 2.2 2.1 2 2 1.9 1.9 1.9 1.8 1.8
2.53.13 2.92.82.72.62.52.52.42.42.32.32.2
3 3.7 3.6 3.5 3.4 3.3 3.1 3 3 2.9 2.8 2.8 2.7 2.7
3.54.34.24.13.93.83.73.53.43.43.33.23.23.1
4 4.94.84.74.54.34.24 3.93.93.83.73.63.5
5 6.1 6 5.8 5.6 5.4 5.2 5 4.9 4.8 4.7 4.6 4.5 4.4
6 7.37.27 6.76.56.36 5.95.85.75.65.45.3
7 8.68.48.17.97.67.47 6.96.86.76.66.46.3
8 9.8 9.6 9.3 9 8.7 8.4 8 7.9 7.7 7.6 7.4 7.2 7.1
10 12 12 12 11 11 10 10 9.9 9.7 9.5 9.3 9 8.9
12 15 14 14 13 13 13 12 12 12 11 11 11 11
13 16 16 15 15 14 14 13 13 13 12 12 12 12
15 18 18 17 17 16 16 15 15 15 14 14 14 13
16 20 19 19 18 17 17 16 16 15 15 15 14 14
20 24 24 23 22 22 21 20 20 19 19 19 18 18
25 31 30 29 28 27 26 25 25 24 24 23 23 22
32 39 38 37 36 35 33 32 32 31 30 30 29 28
40 49 48 47 45 43 42 40 39 39 38 37 36 35
50 61 60 58 56 54 52 50 49 48 47 46 45 44
63 77 76 73 71 68 66 63 62 61 60 58 57 56
Mains Frequency f [Hz]
Description 16 2/3 50 60 100 200 300 400
IMA(f)IMA (50 Hz) [%] 91 100 101 106 115 134 141
Number of Circuit Breakers
Rated Diversity Factor
12345678
0.70
0.80
0.90
1.0 0
V4-T1-116 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
Accessories Technical Data
Description
WMZSAUX
WMZSAUXTRIP WMZSST WMZSUVR
Electrical
Contact function 1A + 1B
2 C/O
Rated operational voltage Un250 Vac 115 Vac—WMZSUVR115
230 Vac—WMZSUVR230
400 Vac—WMZSUVR400
Voltage range WMZSST110 12–110 Vac
12–60 Vdc
Voltage range WMZSST415 110–415 Vac
110–230 Vdc
Closing threshold [x Un]——0.8
Tripping threshold [x Un]— 0.5
Rated frequency ƒ 50/60 Hz 50/60 Hz 50/60 Hz
General use (UL/CSA)
AC—230/240 Vac 2/2A
DC—110/120 Vdc 0.5/0.5A
Pilot duty A600/Q600
Conventional free air thermal current Ith 4A
Rated operational current
AC-13 Ie3A (250 Vac)
AC-15 Ie2A (250 Vac)
DC-13 Ie0.5A (110 Vdc)
Rated insulation voltage Ui250 Vac
Minimum operating voltage per contract Umin 5 Vdc
Rated impulse withstand voltage (1.2/50µ) Uimp 2.5 kV
Rated conditional short-circuit current with 6A
back-up fuse ISC
1 kA
Max. admissible back-up fuse 4A gL
Mechanical
Standard front dimension 45 mm 45 mm 45 mm
Device height 80 mm 80 mm 80 mm
Mounting width 8.8 mm 17.6 mm 17.8 mm
Mounting On MCB IEC/EN 60715 top-hat rail IEC/EN 60715 top-hat rail
Degree of protection enclosed IP40 IP40 IP40
Terminal protection Protection against electric shock to IEC 536 Protection against electric shock to IEC 536 Protection against electric shock to IEC 536
Terminals Lift terminals Twin-purpose terminals Twin-purpose terminals
Terminal capacity
Solid 0.5 – 2.5 mm21–2.5 mm22 x (1–2.5) mm2
Flexible 0.5 – 2.5 mm21–2.5 mm22 x (1–2.5) mm2
Tightening torque of terminal screws 0.8 – 1.0 Nm (7–9 lb-in) 2.4 Nm (21 lb-in) 0.8 Nm (7 lb-in)
Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com V4-T1-117
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
Dimensions
Approximate Dimensions in Inches (mm)
Miniature Circuit Breakers
WMZS
Auxiliary Contacts Shunt Releases
WMZSAUX WMZSST
Undervoltage Releases
WMZSAUXTRIP WMZSUVR
3.15
(80.0)
1P 2P 3P
0.69
(17.5)
1.38
(35.0)
3.15
(80.0)
2.07
(52.5)
3.15
(80.0)
1.77
(45.0)
0.43
(11.0)
1.73
(44.0)
2.36
(60.0)
0.22
(5.5)
1.20
(30.5) 0.18
(4.5)
3.15
(80.0)
3.36
(85.4)
0.35
(8.9)
0.13
(3.4)
1.77
(45.0)
0.22
(5.5)
0.38
(9.6)
0.08
(2.0)
1.73
(44.0)
2.36
(60.0)
1.03
(26.2)
3.15
(80.0)
0.69
(17.6)
0.13
(3.4)
1.77
(45.0)
0.22
(5.5)
0.39
(10.0)
1.73
(44.0)
2.36
(60.0)
3.15
(80.0)
0.35
(9.0)
1.77
(45.0)
0.22
(5.5)
0.38
(9.6)
1.73
(44.0)
2.36
(60.0)
0.70
(17.8)
3.15
(80.0)
1.77
(45.0)
0.22
(5.5)
1.73
(44.0)
2.36
(60.0)
V4-T1-118 Volume 4—Circuit Protection CA08100005E—March 2013 www.eaton.com
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1.3
Miniature Circuit Breakers and Supplementary Protectors
UL 1077 DIN Rail Supplementary Protectors
Approximate Dimensions in Inches (mm)
Busbar and Accessory Weights and Dimensions
Catalog
Number
Unit
Weight Lbs (kg) Length Width Height
WMZS1P57T 0.64 (0.29) 39.72 (1009.0) 0.59 (15.0) 0.59 (15.0)
WMZS2P56T 1.41 (0.64) 39.02 (991.0) 0.87 (22.0) 1.46 (37.0)
WMZS3P57T 1.83 (0.83) 39.72 (1009.0) 0.87 (22.0) 1.46 (37.0)
WMZS1P37TAUX 0.57 (0.26) 38.78 (985.0) 0.59 (15.0) 0.59 (15.0)
WMZS2P46TAUX 1.39 (0.63) 39.72 (1009.0) 0.87 (22.0) 1.46 (37.0)
WMZS3P48TAUX 1.74 (0.79) 38.66 (982.0) 0.87 (22.0) 1.46 (37.0)
WMZS1P57T25 0.79 (0.36) 39.72 (1009.0) 0.59 (15.0) 0.59 (15.0)
WMZS2P56T25 1.74 (0.79) 39.02 (991.0) 0.87 (22.0) 1.46 (37.0)
WMZS3P57T25 2.29 (1.04) 39.72 (1009.0) 0.87 (22.0) 1.46 (37.0)
WMZS1P37T25AUX 0.68 (0.31) 38.78 (985.0) 0.59 (15.0) 0.59 (15.0)
WMZS2P46T25AUX 1.61 (0.73) 39.72 (1009.0) 0.87 (22.0) 1.46 (37.0)
WMZS3P48T25AUX 2.14 (0.97) 38.66 (982.0) 0.87 (22.0) 1.46 (37.0)
WMZS35EXT 0.07 (0.03) 2.36 (60.0) 0.67 (17.0) 1.14 (29.0)
WMZSBCONA 0.07 (0.03) 1.57 (40.0) 0.71 (18.0) 1.18 (30.0)
WMZSBBTC 0.007 (0.003) 3.35 (85.0) 0.47 (12.0) 0.94 (24.0)
WMZS1CAP 0.002 (0.001) 0.55 (14.0) 0.20 (5.0) 0.39 (10.0)
WMZS3CAP 0.002 (0.001) 0.94 (24.0) 0.87 (22.0) 0.39 (10.0)
L W
H
L1 L2 L1 L2 L1 L2 L1 L2 L1 L2 L1 L2