https://www.phoenixcontact.com/us/products/2906279
04/14/2017Page3/14
Type 2 surge protection device-VAL-US 60/O-2906279
Technical data
Protective circuit
Rated load current IL80 A
Residual current IPE ≤ 0.45 mA
Standby power consumption PC≤ 35 mVA
Nominal discharge current In (8/20) µs 15 kA
Nominal discharge current In (8/20) µs (L-N) 15 kA
Nominal discharge current In (8/20) µs (L-PEN) 15 kA
Maximum discharge current Imax (8/20) µs 40 kA
Maximum discharge current Imax (8/20) µs (L-N) 40 kA
Maximum discharge current Imax (8/20) µs (L-PEN) 40 kA
Short-circuit current rating ISCCR 25 kA
Voltage protection level Up≤ 0.55 kV
Voltage protection level Up (L-N) ≤ 0.55 kV
Voltage protection level Up (L-PEN) ≤ 0.55 kV
Residual voltage Ures ≤ 0.55 kV (at In)
≤ 0.425 kV (at 10 kA)
≤ 0.325 kV (at 5 kA)
≤ 0.275 kV (at 3 kA)
TOV behavior at UT100 V AC (5 s / withstand mode)
TOV behavior at UT (L-N) 100 V AC (5 s / withstand mode)
TOV behavior at UT (L-PEN) 100 V AC (5 s / withstand mode)
Response time tA≤ 25 ns
Response time tA (L-N) ≤ 25 ns
Response time tA (L-PEN) ≤ 25 ns
Max. backup fuse with branch wiring 125 A AC (gG)
Max. backup fuse with V-type through wiring 80 A AC (gG)
Connection data
Connection method Screw connection
Screw thread M5
Tightening torque 4.5 Nm
30 lbf-in. (UL)
Stripping length 16 mm
Conductor cross section flexible min. 1.5 mm²
Conductor cross section flexible max. 25 mm²
Conductor cross section solid min. 1.5 mm²
Conductor cross section solid max. 35 mm²
Conductor cross section AWG 15 ... 2