SUPPLY VOLTAGE (UN) 12, 24, 48, 110/125 V AC/DC (non polarized)
230/240 V AC
OPERATING RANGE AC (50/60 Hz)/DC: (0.85...1.1)UN
POWER CONSUMPTION AC: ≤2 VA
DC: ≤2 W
DIELECTRIC STRENGTH 2 (DPDT) - 3 CO (3PDT) 4 CO (4PDT)
between coil and contacts: 2,000 V 2,000 V
between open contacts: 1,000 V 1,000 V
between adjacent contacts: 2,000 V 1,550 V
between frame and live parts: 1,500 V 1,500 V
MECHANICAL LIFE 10 · 106cycles
PROTECTION CATEGORY IP 40
DELAY SETTING 0.1 s...10h (see time scales)
REPEATABILITY ± 2%
SETTING ACCURACY - FULL RANGE ± 5%
RECOVERY TIME ≤20 ms
AMBIENT TEMPERATURE (–20...+60)°C
POWER LOST IN THE ENVIRONMENT 85.x2.8.230 85.x3.8.230 85.x4.8.230
- without load: 0.6 W 0.6 W 0.6 W
- at full load: 3.7 W 4.7 W 3.3 W
CONTACT SPECIFICATIONS
14
2 CO (DPDT) 3 CO (3PDT) 4 CO (4PDT)
RATED CURRENT 10 A 10 A 5 A
MAXIMUM PEAK CURRENT 20 A 20 A 10 A
RATED VOLTAGE 250 V AC 250 V AC 250 V AC
MAXIMUM SWITCHING VOLTAGE 400 V AC 400 V AC 400 V AC
NOMINAL RATE IN AC1 2,500 VA 2,500 VA 1,250 VA
NOMINAL RATE IN AC15 (230 V) 500 VA 500 VA 250 VA
BREAKING CAPACITY IN DC1 see diagram H 85 see diagram H 85 see diagram H 85
SINGLE PHASE MOTOR RATING (230 V AC) 0.37 kW/0.6 HP 0.37 kW/0.6 HP 0.125 kW/0.2 HP
ELECTRICAL LIFE IN AC1 see diagram F 85/2 see diagram F 85/2 see F 85/1
CONTACT RESISTANCE: initial ≤50 mΩ≤50 mΩ≤50 mΩ
CONTACT MATERIAL AgNi AgNi AgNi
WORKING CONDITIONS:
in conformity with EC Directive on EMC (89/336), the timer has a high level of immunity, both from radiated and
conducted disturbances (according
to EN 61812-1). However, the timer (and its supply and control wiring) must be installed as far as possible from
disturbance sources (such as transformers contactors, circuit-breakers and their power cables).
TECHNICAL DATA
85 Series
Miniature Plug-in Timers 5 - 10 A