Assembly not available for new installations.
Recommended replacement is the
Quik-Spec™ Coordination Panelboard (QSCP).
See Data Sheet 1160 for details.
0310 BU-SB091107
Fused Lighting & Appliance Panelboard
EP Series Coordination Module™
Form No. EP
Page 1 of 19
Data Sheet #1149
Coordination Module™ Specifications
Voltage Short-Circuit Panel Number of Main
Series Rating Current Rating Dimensions Configuration Circuits Option
EP2M23012GCC 120/208V 100kA* 28" W X 36" H X 5.75" D 3-Phase, 4 Wire 12 Main Lug Only
EP2M23024GCC 120/208V 100kA* 28" W X 36" H X 5.75" D 3-Phase, 4 Wire 24 Main Lug Only
EP2M23036GCC 120/208V 100kA* 28" W X 48" H X 5.75" D 3-Phase, 4 Wire 36 Main Lug Only
EP2M23042GCC 120/208V 100kA* 28" W X 48" H X 5.75" D 3-Phase, 4 Wire 42 Main Lug Only
EP2B_3012GCC 120/240V 100kA* 28" W X 36" H X 5.75" D 3-Phase, 4 Wire 12 Main Breaker
EP2B_3024GCC 120/240V 100kA* 28" W X 36" H X 5.75" D 3-Phase, 4 Wire 24 Main Breaker
EP2B_3036GCC 120/240V 100kA* 28" W X 48" H X 5.75" D 3-Phase, 4 Wire 36 Main Breaker
EP2B_3042GCC 120/240V 100kA* 28" W X 48" H X 5.75" D 3-Phase, 4 Wire 42 Main Breaker
EP3M23012GCC 120/240V 100kA* 28" W X 36" H X 5.75" D 1-Phase, 3 Wire 12 Main Lug Only
EP3M23024GCC 120/240V 100kA* 28" W X 36" H X 5.75" D 1-Phase, 3 Wire 24 Main Lug Only
EP3M23036GCC 120/240V 100kA* 28" W X 48" H X 5.75" D 1-Phase, 3 Wire 36 Main Lug Only
EP3M23042GCC 120/240V 100kA* 28" W X 48" H X 5.75" D 1-Phase, 3 Wire 42 Main Lug Only
EP3B_3012GCC 120/240V 100kA* 28" W X 36" H X 5.75" D 1-Phase, 3 Wire 12 Main Breaker
EP3B_3024GCC 120/240V 100kA* 28" W X 36" H X 5.75" D 1-Phase, 3 Wire 24 Main Breaker
EP3B_3036GCC 120/240V 100kA* 28" W X 48" H X 5.75" D 1-Phase, 3 Wire 36 Main Breaker
EP3B_3042GCC 120/240V 100kA* 28" W X 48" H X 5.75" D 1-Phase, 3 Wire 42 Main Breaker
EP4M23012GCC 277/480V 100kA** 28" W X 36" H X 5.75" D 3-Phase, 4 Wire 12 Main Lug Only
EP4M23024GCC 277/480V 100kA** 28" W X 36" H X 5.75" D 3-Phase, 4 Wire 24 Main Lug Only
EP4M23036GCC 277/480V 100kA** 28" W X 48" H X 5.75" D 3-Phase, 4 Wire 36 Main Lug Only
EP4M23042GCC 277/480V 100kA** 28" W X 48" H X 5.75" D 3-Phase, 4 Wire 42 Main Lug Only
EP4B_3012GCC 277/480V 100kA** 28" W X 36" H X 5.75" D 3-Phase, 4 Wire 12 Main Breaker
EP4B_3024GCC 277/480V 100kA** 28" W X 36" H X 5.75" D 3-Phase, 4 Wire 24 Main Breaker
EP4B_3036GCC 277/480V 100kA** 28" W X 48" H X 5.75" D 3-Phase, 4 Wire 36 Main Breaker
EP4B_3042GCC 277/480V 100kA** 28" W X 48" H X 5.75" D 3-Phase, 4 Wire 42 Main Breaker
* When protected by upstream LPN-RK 100A max, LPJ 200A max or JJN 200A max, otherwise 10kA.
** When protected by upstream LPS-RK 200A max, LPJ 200A max or JJS 200A max, otherwise 14kA.
Main breaker option may impact selective coordination. Coordination must be verified analyzing time current curves and available current.
Feed through lugs available upon request
Catalog Symbol: EP
Voltage Ratings: 120/208V, 120/240V, 277/480V
Main Device Type: MLO (200A), Main Circuit Breaker
(up to 200A)
Enclosure: NEMA 1
Trim: Surface Mount
Agency Information: UL 67, UL 50
The Cooper Bussmann®Coordination Module™
saves you time and money by making it easy to
meet NEC®selective coordination requirements.
The Cooper Bussmann Coordination Module makes it
simple to achieve and verify selective coordination in a fully
fused system. Utilize published fuse coordination ratios to
select the cor rect upstream fuse rating. The ratios ensure
coordination for any level of fault cur rent, so short-circuit
cur rent studies are not required to design a selective
coordinated system.
General Information:
• Use Low-Peak®fuses and a 2:1 ratio to easily achieve
coordination
• Locate open fuses with easyID™ neon indica tor
• Use to comply with 2008 NEC®selective coordination
requirements for emergency, legally required standby and
essential electrical systems per sections 700.27, 701.18,
517.26 and 708.54