Release date 2014-12-01 16:23 Date of issue 2015-02-16 231393_eng.xml
KFD2-STC4-Ex1.H
1
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
Pepperl+Fuchs Group USA: +1 330 486 0002 Singapore: +65 6779 9091Germany: +49 621 776 2222
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
SMART Transmitter Power Supply
Zone 0, 1, 2
Div. 1, 2
KFD2-STC4-Ex1.H
3
5-
6+
1+
2-
7-
8+
9
250 Ω
HART
HART
mA
mA
24 V DC
14+
15-
Power Rail
24 V DC
HART
Zone 2
Div. 2
Connection
Assembly
1-channel isolated barrier
24 V DC supply (Power Rail)
Input 2-wire and 3-wire SMART transmitters and 2-wire
SMART current sources
Output 0/4 mA ... 20 mA
Terminals with test points
High field voltage 17.6 V DC
Up to SIL2 acc. to IEC 61508
Function
This isolated barrier is used for intrinsic safety applications.
The device supplies 2-wire and 3-wire SMART transmitters
with higher output voltage in a hazardous area, and can also
be used with 2-wire SMART current sources.
It transfers the analog input signal to the safe area as an
isolated current value.
Digital signals may be superimposed on the input signal in the
hazardous or safe area and are transferred bi-directionally.
If the HART communication resistance in the loop is too low,
the internal resistance of 250 between terminals 8 and 9
can be used.
Test sockets for the connection of HART communicators are
integrated into the terminals of the device.
Application
The device supports the following SMART protocols:
•HART
•BRAIN
•Foxboro
2
Features
13
46
2
5
13 15
12
9
10
7
14
11
8
KFD2-STC4-Ex1.H
PWR
Front view
LED green:
Power supply
Removable terminals
green
Removable terminals
blue
Release date 2014-12-01 16:23 Date of issue 2015-02-16 231393_eng.xml
Technical data KFD2-STC4-Ex1.H
2
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
Pepperl+Fuchs Group USA: +1 330 486 0002 Singapore: +65 6779 9091Germany: +49 621 776 2222
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
General specifications
Signal type Analog input
Supply
Connection Power Rail or terminals 14+, 15-
Rated voltage Un20 ... 35 V DC
Ripple within the supply tolerance
Power loss 1.5 W
Power consumption 1.9 W
Input
Connection terminals 1+, 2-, 3 or 5-, 6+
Input signal 0/4 ... 20 mA
Voltage drop 2.4 V at 20 mA (terminals 5, 6)
Input resistance 64 terminals 2-, 3 ; 500 terminals 1+, 3 (250 load)
Available voltage 17.6 V at 20 mA terminals 1+, 3
Output
Connection terminals 7-, 8+, 9
Load 0 ... 800
Output signal 0/4 ... 20 mA (overload > 25 mA)
Ripple 50 µA rms
Transfer characteristics
Deviation at 20 °C (68 °F), 0/4 ... 20 mA
10 µA incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage
Influence of ambient temperature 0.25 µA/K
Frequency range field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 7.5 kHz (-3 dB)
control side into the field side: bandwidth with 0.5 Vpp signal 0.3 ... 7.5 kHz (-3 dB)
Settling time 200 µs
Rise time/fall time 20 µs
Electrical isolation
Output/power supply functional insulation, rated insulation voltage 50 V AC
Directive conformity
Electromagnetic compatibility
Directive 2004/108/EC EN 61326-1:2006
Conformity
Electromagnetic compatibility NE 21:2011
Degree of protection IEC 60529:2001
Protection against electrical shock UL 61010-1:2012
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protection IP20
Mass approx. 200 g
Dimensions 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 in) , housing type B2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection
with Ex-areas
EC-Type Examination Certificate BAS 99 ATEX 7060 , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protection ¬ II (1)G [Ex ia Ga] IIC , ¬ II (1)D [Ex ia Da] IIIC
Input [Ex ia Ga] IIC, [Ex ia Da] IIIC
Supply
Maximum safe voltage Um250 V (Attention! The rated voltage can be lower.)
Equipment terminals 1+, 3-
Voltage Uo 27.2 V
Current Io 93 mA
Power Po 632 mW
Permissible connection values [EEx ia]
Equipment terminals 2-, 3
Voltage Ui 30 V
Current Ii 117 mA
Voltage Uo 3.5 V
Current Io 73 mA
Power Po 64 mW
Permissible connection values [EEx ia]
Equipment terminals 1+, 2 / 3-
Voltage Uo 27.2 V
Current Io 117 mA
Release date 2014-12-01 16:23 Date of issue 2015-02-16 231393_eng.xml
Technical data KFD2-STC4-Ex1.H
3
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
Pepperl+Fuchs Group USA: +1 330 486 0002 Singapore: +65 6779 9091Germany: +49 621 776 2222
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Power Po 639 mW
Permissible connection values [EEx ia]
Equipment terminals 5-, 6+
Voltage Ui 30 V
Current Ii 117 mA
Voltage Uo 8.7 V
Current Io 0 mA
Output
Maximum safe voltage Um250 V (Attention! The rated voltage can be lower.)
EC-Type Examination Certificate DMT 01 ATEX E 133
Group, category, type of protection ¬ I (M1) [Ex ia] I
Statement of conformity TÜV 99 ATEX 1499 X , observe statement of conformity
Group, category, type of protection,
temperature class
¬ II 3G Ex nA II T4 [device in zone 2]
Electrical isolation
Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supply safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 94/9/EC EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 , EN 50303:2000
International approvals
UL approval
Control drawing 116-0173 (cULus)
IECEx approval IECEx BAS 04.0016
Approved for [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
General information
Supplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of
Conformity and instructions have to be observed where applicable. For information see www.pepperl-
fuchs.com.
Power feed module KFD2-EB2
The power feed module is used to supply the devices with 24 V DC via the Power Rail. The fuse-protected power feed module
can supply up to 150 individual devices depending on the power consumption of the devices. Collective error messages received
from the Power Rail activate a galvanically-isolated mechanical contact.
Power Rail UPR-03
The Power Rail UPR-03 is a complete unit consisting of the electrical insert and an aluminium profile rail 35 mm x 15 mm. To
make electrical contact, the devices are simply engaged.
Profile Rail K-DUCT with Power Rail
The profile rail K-DUCT is an aluminum profile rail with Power Rail insert and two integral cable ducts for system and field cables.
Due to this assembly no additional cable guides are necessary.
Power Rail and Profile Rail must not be fed via the device terminals of the individual devices!
Accessories