SPECIFICATION
DRT-960-24
MODEL
DCVOLTAGE
RATEDCURRENT
CURRENTRANGE
RATEDPOWER
OUTPUT VOLTAGE ADJ.RANGE
LINEREGULATION
LOADREGULATION
SETUP,RISETIME
HOLDUP TIME (Typ.)
VOLTAGERANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
INPUT
INRUSHCURRENT(max.)
LEAKAGECURRENT
OVERTEMPERATURE
SAFETY STANDARDS
HARMONICCURRENT
EMSIMMUNITY
WORKINGTEMP.
WORKINGHUMIDITY
STORAGETEMP.,HUMIDITY
TEMP.COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
PACKING
OVERLOAD
OVERVOLTAGE
ACCURRENT (Typ.)
24V
40A
0~40A
960W
80mVp-p
24~28V
1.0%
0.5%
0.5%
200ms,60ms/400VAC200ms,60ms/500VAC atfullload
14ms/400VAC30ms/500VAC atfullload
Three-Phase340~550VAC(DualphaseoperationpossibleinconnectingL1,L3,FG )Note.5
47~63Hz
91%
2A/400VAC1.6A/500VAC
COLDSTART 50A
<3.5mA /530VAC
105~125% ratedoutputpower
30~36V
Protectiontype:Shutdowno/pvoltage,re-powerontorecover
110 5 (TSW1)detectonheatsinkofpowertransistor85 5 (TSW2)detectonheatsinkofpowerdiode
Protectiontype:Shutdowno/pvoltage,recoversautomaticallyaftertemperaturegoesdown
UL508, UL60950-1, TUVEN60950-1approved
CompliancetoEN55011(CISPR11),EN55022(CISPR22),EN61204-3ClassB
Complianceto EN61000-3-2,-3
CompliancetoEN61000-4-2,3,4,5,6,8,11,ENV50204,EN61204-3,EN61000-6-2(EN50082-2),heavyindustrylevel,criteria A
-20~+60 (Refertooutputloadderatingcurve)
20~90%RHnon-condensing
-40~+85 ,10~95%RH
0.03%/ (0~50
Component: CompliancetoIEC60068-2-610~500Hz,2G10min./1cycle,60min.eachalongX, Y,Zaxes;Mounting:
122.5Khrsmin.MIL-HDBK-217F(25 )
276*125.2*100mm(W*H*D)
3.3Kg;4pcs/14.2Kg/1.14CUFT
FileName:DRT-960-SPEC2009-08-24
DRT-960-48
48V
20A
0~20A
960W
80mVp-p
48~55V
1.0%
0.5%
0.5%
59~66V
960W ThreePhaseIndustrialDINRAIL PowerSupply
Three-Phase AC 340 ~ 550V wide range input
High efficiency 91% and low dissipation
Protections: Short circuit / Overload / Over voltage / Over temperature
Optional parallel function(1+1)
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
EN61000-6-2(EN50082-2) industrial immunity level
100% full load burn-in test
3 years warranty
Features :
DRT-960 series
ENVIRONMENT
SAFETY &
EMC
(Note4)
PROTECTION
WITHSTANDVOLTAGE
ISOLATIONRESISTANCE
I/P-O/P:3KVACI/P-FG:1.5KVACO/P-FG:0.5KVAC
I/P-O/P,I/P-FG,O/P-FG:100MOhms/500VDC /25 /70%RH
EMICONDUCTION&RADIATION
NOTE 1. All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Dual phase operation(connecting L1,L3,FG)is allowed under certain derating to output load. Please refer to the derating curves for details.
RIPPLE&NOISE(max.) Note.2
VOLTAGETOLERANCE Note.3
92%
Protectiontype: Constantcurrentlimiting,unitwillshutdowno/pvoltageafter3sec.,re-powerontorecover