SPECIFICATION
DR-4505 DR-4512 DR-4515 DR-4524
MODEL
DCVOLTAGE
RATEDCURRENT
CURRENTRANGE
RATEDPOWER
OUTPUT VOLTAGE ADJ.RANGE
LINEREGULATION
LOADREGULATION
SETUP,RISETIME
HOLDUP TIME (Typ.)
VOLTAGERANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
ACCURRENT (Typ.)
INPUT
INRUSHCURRENT (Typ.)
LEAKAGECURRENT
OVERTEMPERATURE
SAFETY STANDARDS
HARMONICCURRENT
EMSIMMUNITY
WORKINGHUMIDITY
WORKINGTEMP.
STORAGETEMP.,HUMIDITY
TEMP.COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVERVOLTAGE
5V 12V 15V 24V
5A 3.5A 2.8A 2A
0~5A 0~3.5A 0~2.8A 0~2A
25W 42W 42W 48W
100mVp-p 200mVp-p 240mVp-p
13.5~16.5V
480mVp-p
21.6~26.4V
2.0% 1.0% 1.0% 1.0%
10.8~13.2V4.75~5.5V
1.0% 1.0% 1.0% 1.0%
1.0% 1.0% 1.0% 1.0%
800ms,60ms/230VAC atfullload
100ms/230VAC atfullload
85~264VAC120~370VDC
47~63Hz
72% 77% 77% 80%
1.5A/115VAC0.75A/230VAC
COLDSTART 28A/115VAC56A/230VAC
<1mA /240VAC
105~150% ratedoutputpower
Protectiontype: Constantcurrentlimiting,recoversautomaticallyafterfaultconditionisremoved
5.75~6.75V
Protectiontype: Shutoffo/pvoltage,clampingbyzenerdiode
13.8~16.2V 17.25~20.25V 27.6~32.4V
Tj135 typically (U1)detectonheatsinkofpowertransistor
Protectiontype:Shutdowno/pvoltage,re-powerontorecover
-10~+50 (Refertooutputloadderatingcurve)
20~90%RHnon-condensing
-20~+85 ,10~95%RH
0.03%/ (0~50
10~500Hz,2G10min./1cycle,periodfor60min. eachalongX, Y,Zaxes;Mounting:CompliancetoIEC60068-2-6
364.6Khrsmin.MIL-HDBK-217F(25 )
93*78*67mm(L*W*H)
0.31Kg;48pcs/16.1Kg/1.3CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
FileName:DR-45-SPEC2008-04-07
UL508, TUVEN60950-1approved
CompliancetoEN55011,EN55022(CISPR22)ClassB
Complianceto EN61000-3-2,-3
CompliancetoEN61000-4-2,3,4,5,6,8,11,ENV50204,EN55024,EN61000-6-2(EN50082-2),heavyindustrylevel,criteria A
45WSingleOutputIndustrialDINRailPowerSupply DR-45 series
Universal AC input/Full range
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
LED indicator for power on
100% full load burn-in test
Fix switching frequency at 100KHz
3 years warranty
Features :
RIPPLE&NOISE(max.) Note.2
VOLTAGETOLERANCE Note.3
ENVIRONMENT
PROTECTION
SAFETY &
EMC
(Note4)
WITHSTANDVOLTAGE
ISOLATIONRESISTANCE
I/P-O/P:3KVACI/P-FG:1.5KVACO/P-FG:0.5KVAC
I/P-O/P,I/P-FG,O/P-FG:100MOhms/500VDC
EMICONDUCTION&RADIATION
46.5
77
93
InstallDINrail TS35/7.5or TS35/15
8.5
78
7.5
67
29
46.5
TerminalPinNo. Assignment
PinNo. PinNo.
2
1 6,7
3
4,5
8
9
Assignment Assignment
FG
DCOUTPUT -V
AC/L
AC/N
DCOUTPUT+V
LED
+V ADJ.
1
7
4
2
3
5
6
8
9
PWM
CIRCUIT
DETECTION
EMI
FILTER
RECTIFIERS
&
FILTER
POWER
SWITCH-
FILTER
&
RECTIFIERS +V
-V
ING
CONTROL
I/P
FG
-10 0 10 20 30 40 50 60 (VERTICAL)
20
40
60
80
100
Ta=25
20080
8
70
12
16
20
24
140100 120 180160
28
32
260240220
50
100
150
200
250
300
350
BlockDiagram
StaticCharacteristics(24V)
AMBIENTTEMPERATURE( ) INPUTVOLTAGE(V)60Hz
LOAD(%)
OUTPUTVOLTAGE(V)
OUTPUTRIPPLE(mVp-p)
fosc:100KHz
MechanicalSpecification
FileName:DR-45-SPEC2008-04-07
35
DeratingCurve
CaseNo.918A Unit:mm
45WSingleOutputIndustrialDINRailPowerSupply DR-45 series