1
1
➜ "Millenium Supply" switch mode power supply
Regulated power supplies
■ Electronic and regulated
■ 85 to 264 VAC input
■ Conforms to global standards
■ Incorporated thermal protection
■ PFC filter option
Specifications
Type Input voltage Output
voltage
Nominal
power
Nominal
current
Reset on
protection
Conforms to
EN 61000-3-2
Weight (kg) Code
89450 without
PFC
100➞240 VAC 12 VDC 60 W 5 A Automatic No 0.44 89 450 110
100➞240 VAC 24 VDC 60 W 2.5 A Automatic No 0.44 89 450 210
100➞240 VAC 24 VDC 100 W 4.2 A Automatic No 0.64 89 450 221
115➞230 VAC 24 VDC 150 W 6.2 A Automatic No 0.73 89 450 231
89450 with
PFC
100➞240 VAC 12 VDC 100 W 8.3 A Automatic Yes 0.64 89 450 122
100➞240 VAC 24 VDC 100 W 4.2 A Automatic Yes 0.64 89 450 222
115➞230 VAC 24 VDC 150 W 6.2 A Automatic Yes 0.97 89 450 232
115➞230 VAC 24 VDC 240 W 10 A Automatic Yes 1.23 89 450 242
Accessories
Designation Weight (kg) Code
Snap-on plate for 35 mm DIN rail 0.085 26 450 100
Mounting bracket 0.035 26 450 101
General characteristics
Certifications UL, cCSAus, CE
Conformity to standards Generic : UL 508, CSA 22.2 no. 60950
Safety : IEC/EN 60950-1
EMC : EN 61000-6-3, EN 61000-6-2
LF harmonic currents : EN 61000-3-2
Output circuit
Status indication Green LED
Operating voltage (Ue) 12 V - 24 V
Nominal output current (A) 5 - 8.3 at 12 V and 2.5 - 4.2 - 6.2 - 10 at 24 V
Output voltage accuracy ±10 %
Line and load regulation ±3 %
Residual ripple <200 mV
Protection against short circuits Continuous, automatic restart
Protection against voltage surges U>1.2U out
Thermal protection Yes
Input circuit
Nominal voltage (V) 100➞240 VAC (60 and 100W) , 115/230 VAC (150 and 240W)
Current consumption Ue=240 2A (60W) - 0.7A (100W) - 2.5A (150W) - 3A (240W)
Ue=100 2A (60W) - 1.4A (100W) - 5A (150W) - 6A (240W)
Operating characteristics
Connection capacity Input : 2 x 4 mm2 + earth
Output : 2 x 4 mm2 (60W) ; doubled for 100, 150 and 240W
Ambient storage temperature -25➞+85
Relative humidity 20➞90 % RH
Vibrations Conforming to EN 61131-2
Operating position Derating curves
MTBF >100.000 hr at 100 % load (at 40°)
Generic immunities Conforming to IEC 61000-6-2
Immunity to electrostatic discharges Conforming to IEC 61000-4-2 level 3 (4 kV contact/8 kV air)
Immunity to electromagnetic discharges Conforming to IEC 61000-4-3 level 3 (10V/m)
Immunity to conducted disturbances Conforming to IEC 61000-4-4 level 3 (2 kV) , EN 61000-4-5, EN 61000-4-6
level 3, EN 61000-4-8 level 4, IEC/EN 61000-4-12 level 3
Immunity to mains supply disturbances Conforming to IEC/EN 61000-4-11 (voltage dips and interruptions)
Incorporated input fuse Yes
Emission Generic : conforming to EN 61000-6-3
Connections Conducted/radiated : conforming to EN 55011, EN 55022 c1B
Dielectric strength Input/output : 3000AC 50/60 Hz 1 min
Input/earth : 1500AC 50/60 Hz 1 min
Output/earth : 500AC 50/60 Hz 1 min
To order, see page 8