SPECIFICATION
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT
VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE Note.7
FREQUENCY RANGE
EFFICIENCY (Typ.)
INPUT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVER TEMPERATURE
SAFETY STANDARDS
WORKING TEMP. Note.5
CURRENT SHARING
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
DC OK REALY CONTACT RATINGS (max.)
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVER VOLTAGE
AC CURRENT (Typ.)
1000ms, 100ms/230VAC at full load
14ms / 230VAC at full load
180 ~ 264VAC 254 ~ 370VDC
47 ~ 63Hz
94%
6A/230VAC
56 ~ 65V
94%
COLD START 50A / 230VAC
<3.5mA / 240VAC
29 ~ 33V
after 30 seconds if the peak load condition is removed
Constant current limiting within 130 ~ 150% rated output power for more than 3 seconds and then shut down o/p voltage, re-power
on to recover
Shut down o/p voltage, recovers automatically after temperature goes down
UL508, TUV EN62368-1 EAC TP TC 004 approved ; (meet EN60204-1)
,,BSMI CNS14336-1
Compliance to EN55032 (CISPR32), EN61204-3 Conduction class B, Radiation class A, EN61000-3-2,-3, BSMI CNS13438EAC TP TC 020,
-30 ~ +70 (Refer to "Derating Curve")℃
Please refer to function manual
60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load
20 ~ 95% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH non-condensing℃
±℃ ℃0.03%/ (0 ~ 50 )
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
69.8K hrs min. MIL-HDBK-217F (25 )℃
110*125.2*150mm (W*H*D)
2.47Kg ; 6pcs/15.8Kg/1.55CUFT
SDR-960-48
48V
20A
0 ~ 20A
960W
250mVp-p
48 ~ 55V
±1.0%
±0.5%
±1.0%
SDR-960-24
24V
40A
0 ~ 40A
960W
180mVp-p
24 ~ 28V
±1.0%
±0.5%
±1.0%
■ Features :
SDR-960 series
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25 / 70% RH℃
ENVIRONMENT
SAFETY &
FUNCTION
EMC
(Note 4)
PROTECTION
RIPPLE & NOISE (max.) Note.2
VOLTAGE TOLERANCE
Note.3
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.℃
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power.
In case the adjacent device is a heat source, 15mm clearance is recommended.
6. 3 seconds peak power max. and the average output power should not exceed the rate power.
7. Derating may be needed under low input voltage. Please check the derating curve for more details.
8. Consult MEAN WELL for deployment of Radiation class B.
9. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
960W Single Output Industrial DIN RAIL with PFC Function
AC input 180~264VAC only
130% peak load capability
110mm slim design
Built-in active PFC function compliance to EN61000-3-2
High efficiency 94% and low power dissipation
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Built-in constant current limiting circuit
Can be installed on DIN rail TS-35/7.5 or 15
UL508(industrial control equipment)approved
EN61000-6-2(EN50082-2) industrial immunity level
Current sharing up to 3840W(3+1)
Built-in DC OK relay contact
100% full load burn-in test
3 years warranty
POWER FACTOR (Typ.) PF 0.95/230VAC at full load≧
EMC IMMUNITY
EMC EMISSION Note.8
PEAK CURRENT
PEAK POWER Note.6
26A52A
1248W (3sec.)
Protection type : Shut down o/p voltage, with auto-recovery or re-power on to recover
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A, EAC TP TC 020
Normally works within 105 ~ 130% rated output power for more than 3 seconds and then shut down o/p voltage with auto-recovery
IEC62368-1TPTC004UL508
R33100
RoHS
CNS14336-1
Bauar
Sicherheit
egel gema
tgepruft
od
be
www.
ID 2000000000
tuv.com
wac g
os
EN62368-1
File Name:SDR-960-SPEC 2020-02-11