General Purpose Relay MJN 343
Latching - DC
Note: 120% of nominal or greater (one second duration single pulse) unlatch voltage - - above this the relay latches again.
Maximum continuous voltage: 120% of nominal (one coil only).
■Characteristics
Note: A latch pulse of 50 ms minimum at nominal voltage is recommended to insure positive latching.
Nominal
voltage
Latch coil
resistance in
Ohms ± 10%
Unlatch coil
resistance in
Ohms ± 10%
Nominal coil power Coil
voltages
Insulation
resistance
Operate voltage
(latch/unlatch) at 25°C (77°F)
(see note)
5 VDC 14 45 1.2 W 5 to 110 VDC 1,000 MΩ
min. @ 500
VDC
75% of nominal
6 VDC 20 64
12 VDC 80 275
24 VDC 330 1,070
48 VDC 1,290 2,850
110 VDC 5,125 10,750
Operate time 15 ms nominal; 20 ms maximum
Release time 6 ms nominal; 10 ms maximum
Latch time 13 ms nominal with a one second pulse of nominal voltage (See note)
Unlatch time 13 ms nominal with a one second pulse of nominal unlatch voltage after latching with
a one second pulse of nominal latching voltage (See note)
Operating
ambient
temperature
AC: 1 & 2 pole Operating -45° to 60°C (-49° to 140°F)
Storage -65° to 100°C (-85° to 212°F)
AC: 3 pole Operating -45° to 45°C (-49° to 113°F)
Storage -65° to 100°C (-85° to 212°F)
DC: 1, 2 & 3
pole
Operating -45° to 70°C (-49° to 158°F)
Storage -65° to 100°C (-85° to 212°F)
Insulation material High quality phenolic
Duty cycle Rated for continuous duty operation at 25% overvoltage
Shock 15 g’s 11±1 ms (non-operating test, no mechanical damage)
Vibration 0.1” DA or 10 g’s, 10 to 55 Hz (operating test, no contact chatter)
Life expectancy Electrical at
rated load
100,000 operations
Mechanical 10,000,000 operations
Dielectric strength Greater than 750 VAC, RMS 60 Hz across open contacts
Greater than 2,500 VAC, RMS 60 Hz all other mutually insulated elements
Terminals Quick Connect
Weight 64 g (2.3 oz) open relay
54 g (3.0 oz) enclosed relay