Du line
®
Fieldbus Installationbus
Specifications are subject to change without notice (28.09.99) 1
Dupline®is a registered trademark. A product of the CARLO GAVAZZI Group
Supply Ordering no.
8 channels
2 x 10 V/10 mA
24 VAC D 1230 5111 024
120 VAC D 1230 5111 120
220 VAC D 1230 5111 220
12 VDC D 1230 5111 712
Code Module: No code module required. D 1230 5111
automatically uses the highest available channel group of the
Dupline®installation.
Ordering KeyProduct Description
Dupline®receiver with demul-
tiplex output (8:1) for multi-
plex transmission on Dupline®
channels. Applicable for trans-
mitters with frequency input
(type FFD 1680, SPEC 918).
Increases the transmission
capacity of a Dupline®system
to max. 3825 x 8-bit measu-
red values.
8-channel receiver
8 : 1 demultiplex function
2 NPN transistor outputs
Enable and disable output operation
D-housing
Plug-in type module
LED-indications for supply and output
AC or DC power supply
Type: Dupline®
D-housing
Receiver
No. of channels
Output type
Supply
Type Selection
Output Specifications
Outputs 1 NPN 1 NPN
transistor transistor
(enable) (disable)
Output voltage VBB 10 VDC 10 VDC
Reverse polarity
protection Yes Yes
Current per output 2.5 mA 2.5 mA
Total load capability 100% 100%
Short-circuit protection None None
Built-in protective diodes None None
Off-state leakage current 100 µA 100 µA
Output voltage drop 1.2 V 1.2 V
Cable length 3 m 3 m
Dielectric voltage
Output - Dupline®2 kVAC (rms) None
Response time < 1 pulse train < 1 pulse train
Supply Specifications
Power supply AC types
Overvoltage cat. III (IEC 60664)
Rated operational voltage
through pins A1 & A2 220
230 VAC +6%, -15% (IEC 60038)
120 120 VAC ± 10% (IEC 60038)
024 24 VAC ± 10%
Frequency 45 to 65 Hz
Voltage interruption 40 ms
Rated operational power Typ. 2.5 VA
Rated impulse withstand
voltage 220 4 kV
120 2.5 kV
024 800 V
Dielectric voltage
Supply - Dupline®2 kVAC (rms)
Supply - Outputs 2 kVAC (rms)
Alternative DC supply (VDD in)
through pins 3 & 9 12 VDC ± 10%
Reverse polarity protection Yes
Rate operational current 20 mA
Inrush current 1 A
Rated impulse withstand
voltage 800 V
Dielectric voltage
Supply - Dupline®None
Supply - Enable output 2 kVAC (rms)
Supply - Disable output None
AC types as supply source
Source voltage (VDD out)
through pins 3 & 9 12 VDC
Source current 40 mA
Fan out 4 modules .... .... 700
Cable length 3 m
Receiver with Demultiplex Output
Type D 1230 5111
D 1230 5111 024
Du line
®
Fieldbus Installationbus
2Specifications are subject to change without notice (28.09.99)
Dupline®is a registered trademark. A product of the CARLO GAVAZZI Group
D 1230 5111
General Specifications
Output OFF delay
upon loss of Dupline®carrier Undefined
Power ON delay Undefined, 1 s
Indication for
Supply ON LED, green
Output ON (enable) LED, red
Environment
Degree of protection IP 40
Pollution degree 3 (IEC 60664)
Operating temperature -2 to +50°C (-4° to +122°F)
Storage temperature
-50° to +85°C (-58° to +185°F)
Humidity (non-condensing) 20 to 80%
Mechanical resistance
Shock 15 G (11 ms)
Vibration 2 G (6 to 55 Hz)
Dimensions
Material
(see "Technical Information") D - Housing
Weight
AC types 200 g
DC types 125 g
In the example given below
the Dupline®installation uses
32 channels (FMK 32 of the
channel generator). There-
fore, the address setup of the
D 1230 5111 is compared with
the status of channel group
D. As soon as the status of
channel group D (provided by
the transmitter GGD 1550) is
equal to the address setup,
the disable output of the D
1230 5111 turns off. This
causes the FFD 1680 to trans-
mit the counter value on
channel groups A-B for dis-
play on the D6369 6475
(coded for channel groups A-
B).
Note: If DC-supplied D 1230
5111 receivers are used, the
length of the supply bus must
not exceed 3 m in order to
avoid disturbance unbalanc-
ing the Dupline®.
Mode of Operation
8-channel receiver with de-
multiplexed outputs for ena-
ble and disable functions.
The receiver continuously re-
ceives the status of 8 chan-
nels on the highest channel
group of a Dupline®installa-
tion (e.g. channel group P if
128 channels are selected on
the channel generator). The
status of these 8 channels is
compared with the address
selected by the DIP switch
selector inside the D 1230
5111. As soon as the trans-
mitted channel status is equal
to the selected address, the
two outputs change state (en-
able output turns on and dis-
able output turns off).
This module used in connec-
tion with transmitters for ana-
logue signals (type FFD 15..)
allows the transmission of 255
individual analogue values on
one channel group. The D
1230 5111 can be used for all
Dupline
®
transmitters that have
enable or disable inputs, e.g.
FFD 15.., FFD 16.. or SPEC 918.
Example
S: signal wire.
Du line
®
Fieldbus Installationbus
Specifications are subject to change without notice (28.09.99) 3
Dupline®is a registered trademark. A product of the CARLO GAVAZZI Group
D 1230 5111
Wiring Diagrams
S: signal wire AC supply
VDD in/out
Disable VBB1
Enable VBB2
D 1230 5111 024/120/220
AC supply (DC supply VDD)
Address Selection
Most Significant bit
=channel 1
Least Significant bit
=channel 8
ON
OFF
Accessories
SocketD 411
Socket cover BB 5
Hold down springHF
Front mounting bezel FRS 2
DIN-rail for D 411 FMD 411
For further information refer to "Accessories".
VDD in/out
Disable VBB1
Enable VBB2
D 1230 5111 712
DC supply
MSB LSB
S: signal wire