Visit our website at www.solahd.com or
contact Technical Services at (800) 377-4384 with any questions.
104
4Power Supplies
Description Catalog Number
SDN 20-24-480CC SDN 40-24-480C
Input
Nominal Voltage 380 - 480 Vac
Two-phase input Yes 1
-AC Range Continuous 2320 - 540 Vac
-DC Range Continuous 450 - 760 Vdc TBD
-DC Range Short Term 3420 - 780 Vdc TBD
-Frequency 50 - 60 Hz
Nominal Current 43 x 0.9 A or 2 x 1.3 A 3 x 1.6 A
-Inrush Current Max. Negligible Negligible
Efficiency (Losses 5)93% (42 W) 94% (78 W)
Power Factor Correction Active Power Factor Correction
Output
Turn on Time Typ. 1s
Voltage Rise Time < 100mS full resistance load (Tamb=+25°C)
Power Back Immunity < 35V
Overvoltage Protection > 30.5 but < 33 Vdc, auto recovery
Nominal Voltage 24V (24-28Vdc Adjustable)
Voltage Regulation < ± 2% overall
Initial Voltage Setting 24.5V ± 1%
-Ripple 6< 100mVpp
PARD PARD (Periodic and Random Deviation) = 200mV peak-peak max
Nominal Current 20 A (480 W) (constant power, not constant) 40 A (960 W)
-Peak Current 71.5 × Nominal Current for 4 seconds minimum while holding voltage > 20 Vdc
-Current Limit PowerBoost™
Derating (T amb=60-70 °C) typ. 24W/°C typ. 48 W/°C
Holdup Time >20 ms >15 ms
Voltage Fall Time <50 mS from 95% to 10% rated voltage @ full load (Tamb=+25°C)
Parallel Operation 8Single or parallel operation selectable via front switch. For redundant
operation, use of external diode module is preferred SDN 40 uses active paralleling
General
Case Fully enclosed metal housing with ne ventilation grid to keep out small parts.
Min. Required Free Space 70mm above and below, 10mm left and right (same as manual) 70mm above and below, 15mm in front, 25mm left & right
Max. Dimensions HxWxD (in/mm) 4.85 x 2.56 x 4.68 (123.3 x 85 x 118.8) 4.85 x 7.09 x 4.85 (123.3 x 180 x 123.17)
Weight (lbs/g) 2.8 lb (1300 g) 5.3 lb (2400 g)
EMC: -Emissions EN61000-6-3:2001, Class B EN55011, EN55022 Radiated and Conducted including Annex. A, EN61000-3-2
-Immunity EN61000-6-1:2001, EN61000-6-2:2001, EN61000-4-2 Level 4, EN61000-4-3 Level 3, EN61000-4-6 Level 3, EN61000-4-4 Level 4 input and
level 3 output. EN61000-4-5 Isolation class 4, EN61000-4-11, Semi F47 sag immunity
Approvals UL508 Listed, cULus; UL60950-1, cURus; IEC60950-1; ISA 12.12.01 Class 1 Div 2,
CE (LVD 73/23 & 2004/108/EC), (EMC 89/336 & 93/68/EEC); EN61000-3-2,EN 60079-15 (Class 1, Zone 2)
Temperature Storage: -40°C to + 85°C, Operation -25°C to +60°C full power, with linear derating to half power from 60°C to 70°C (Convection
cooling, no forced air required). Operation up to 50% load permissible with sideways or front side up mounting orientation.
Humidity < 90% RH, noncondensing; IEC 60068-2-2, 68-2-3
Altitude 0 to 3000 meters (0 to 10,000 feet)
Vibration 2.5(g) RMS, 10-2000 Hz (random); three axes for 20 minutes each - IEC 60068-2-6
Shock 3(g) peak, three axes, 11mseconds for each axis - IEC 60068-2-27
Warranty 5 Years
MTBF > 550,000 hrs MTBF (Nominal voltage, full load, T ambient = 25°C
General Protection/Safety Protected against short -circuit, overload, open circuit. Protection class 1 (IEC536),
degree of protection IP20 (IEC 529), Safe low voltage: SELV (acc. EN60950)
Over-Temperature Protection LED Alarm, Output shutdown with automatic restart
Status Indicators Visual: 3 status LEDs (Input, Output, Alarm); Relay: SSR or dry relay contact, signal active when Vout = 18.5Vdc = +/-5%
Installation
Fusing: -Input Externally fused
-Output Not fused. Output is capable of providing high currents (PowerBoost) for motor load startup.
Mounting Simple snap-on to DIN TS35/7.5 or TS35/15 rail system.
Unit should handle normal shock and vibration of industrial use and transportation without falling off the rail.
Connections 9
Input: screw terminals, Wiring for the connector will be ground on the left (when looking at the front of the unit), connector size range:
16-10AWG (1.5-6mm2) for solid conductors. Output: connector size range, wire gauge 6-7 AWG for SDN40;
all other models: 16-10AWG (1.5-6mm2) for solid conductors. The connector color will be gray or off-white.
SDN-C Specifications (Three Phase)
1. SDN20 will operate at 75% load and SDN40 will operate at 50% load under loss of
1 phase. Units will shut down if thermal threshold is exceeded under this condition.
2. Unit passed input voltage overstress test at 600 Vac maximum without failure.
3. DC operation will require the user to provide the proper input circuit protection.
4. Input current ratings are specied with low input, line conditions, worst case
efciency values and power factor spikes. Input current at nominal input settings will
be typically half these values.
5. Losses are heat dissipation in watts at full load, nominal line.
6. Ripple/noise is stated as typical values when measured with a 20 MHZ, bandwidth
scope and 50 Ohm resister.
7. SDN 20 and SDN 40 unit will go to HICCUP mode. SDN 5 and SDN 10 will maintain
min 4 secs to deliver 150% load then drops to almost zero V out. The output voltage
will immediately drop to almost zero when load rises above 150%.
8. All models except the 40amp unit are capable of parallel operation by use of a jumper
pin, accessible by the end user. 40amp has current sharing signal.
9. SDN40-24-480 only = Output signaling terminal block features (Shut down, Power
Good, Current Monitor, Current Balance, signal GND).