Visit our website at www.solahd.com or
contact Technical Services at (800) 377-4384 with any questions. 101
4
Power Supplies
The SDN-C DIN rail power supplies are the next generation
of the popular SDN series. These models combine high
efciency and compact size with new visual diagnostic
LEDs to offer the most performance available from SolaHD.
Essential industrial features such as Sag Immunity, Power
Factor Correction, and universal voltage input have been
retained in this series. Wide temperature operating range
and parallel operation capability make the new SDN-C units
suitable to a variety of industrial applications.
Features
Compact packaging to save space on the DIN rail
New visual diagnostic LEDs for input and output status
at a glance
High MTBF means high reliability and long life
Higher efciency saves energy and lowers amount of
heat generated in panel
PowerBoostTM overload capability to start high
inrush loads
Accepts Universal voltage 85-264 Vac, 50/60 Hz input
Single phase models meet SEMI F47 Sag Immunity
standard
Power Factor Correction (meets EN61000-3-2)
Class I, Div. 2 Hazardous Locations
ATEX approval (pending)
Single and three-phase input available
Patented DIN rail mounting clip
User Adjustable output voltage accessible via front face
Parallel capability standard
Industrial grade design
– -25oC to 60oC operation without derating
– Rugged metal case and DIN connector
User-friendly
– LEDs for status
– Large, rugged, accessible screw terminals
– Easy on/off DIN mounting
Fully tested and burned-in at factory
RoHS compliant
SDN-C Compact DIN Rail Series
Related Products
SDN-P series
SDPTM series
SFL series
SCP series
SDU UPS
Applications
Industrial Machine Control
Process Control
Conveying Equipment
Material Handling
Vending Machines
Packaging Equipment
Amusement Park Equipment
Semiconductor Fabrication Equipment
DeviceNetTM
Accessories
Chassis Mount Bracket (SDN-PMBRK2)
UL 508 Listed
IND. CONT. EQ.
E61379
UL 60950
E137632
CUL/CSA-C22.2
No. 234-M90
EMC and
Low Volt.
Directive
Visit our website at www.solahd.com or
contact Technical Services at (800) 377-4384 with any questions.
102
4Power Supplies
Rugged metal packaging
The SolaHD Difference
Large, IP20-rated, screw
terminals for #10 AWG/4 mm2,
for quick, easy installation
Multiple output connections for
ease of wiring multiple devices
Single or parallel use
selectable by user
Clearly labeled front panel
UL508 listing means no
derating in UL 508 systems
Automatically adjusts for global
Input voltages. No manual
intervention required.
New narrow width
saves panel space
Full CE compliance for
safety, emissions and
ingress protection
No internal fan, no extra cooling
required in any power level
Adjustable output voltage
DC OK Relay
New visual diagnostic LEDs
show input and output status
(see table below)
LED Light Status Conditions
Normal AC Power Loss AC Input Low No DC High Load Overload Hot Too Hot
Input Green - Yellow Green Green Green Green Green
Output Green - Green - Yellow Yellow Green -
Alarm - - - Red Yellow Red Yellow Yellow
Visit our website at www.solahd.com or
contact Technical Services at (800) 377-4384 with any questions. 103
4
Power Supplies
Description Catalog Number
SDN 5-24-100C SDN 10-24-100C SDN 20-24-100C
Input
Nominal Voltage 115/230 Vac
-AC Range 85 - 264 Vac
-DC Range190 - 375 Vdc
-Frequency 43-67 Hz
Nominal Current21.65 - 0.55 A 3.2 - 1.0 A 6A / 3A
-Inrush current max. Typ. < 15 A Typ.< 30 A < 40 A
Efficiency (Losses3)> 90% typ. (12 W) > 90% typ. (24 W) > 92% (38 W)
Power Factor Correction Active power factor correction to better than 0.92
Output
Nominal Voltage 24 V (23.5~28.5 Vdc Adj.)
-Tolerance < ±2 % overall (combination Line, load, time and temperature related changes)
Initial Voltage Setting 24.5V ± 1%
-Ripple4< 50 mVpp <100mVpp
PARD PARD (Periodic and Random Deviation) = 100 mV peak-peak max
Overvoltage Protection > 30.5 but < 33 Vdc, auto recovery
Power Back Immunity < 35V
Nominal Current 5 A (120 W) 10 A (240 W) 20 A (480W)
-Peak Current51.5 × Nominal Current for 2 seconds minimum while holding voltage > 20 Vdc
-Short Circuit Current 1.5 x Nominal Current at near zero volts at short circuit condition
-Current Limit PowerBoost™
Parallel Operation Switch selectable single unit or parallel unit operation. Units will not be damaged by parallel operation (regardless of switch position setting).
Holdup Time >20 ms (Full load, 100 Vac Input @ Tamb=+25°C) to 95% output voltage
Voltage Fall Time <150 mS from 95% to 10% rated voltage @ full load (Tamb=+25°C)
Line and Load Regulation < 0.5%
General
EMC:
-Emissions EN61000-6-2:2001, EN61000-6-3:2001, Class B EN55011, EN55022 Radiated and Conducted including Annex. A, EN61000-3-2
-Immunity EN61000-6-1:2001, EN61000-6-2:2001, EN61000-4-2 Level 4, EN61000-4-3 Level 3, EN61000-4-6 Level 3, EN61000-4-4 Level 4 input
and level 3 output. EN61000-4-5 Isolation class 4, EN61000-4-11, IEC 61000-4-34 voltage dip immunity standard
Approvals UL508 Listed, cULus; UL 60950-1, cURus; IEC60950-1; Class I, Div. 2, Hazadous location approval; CE (LVD 73/23 & 2004/108/EC),
(EMC 89/336 & 93/68/EEC); EN61000-3-2
Temperature7Storage: -40oC to + 85oC, Operation -25oC to +60oC full power, with linear derating to half power from 60 to 70oC (Convection cooling,
no forced air required). Operation up to 50% load permissible with sideways or front side up mounting orientation.
MTBF 6 > 550,000 hrs > 450,000 hrs
Warranty 5 Years
General Protection/Safety Protected against continuous short -circuit, continuous overload, continuous open circuit.
Protection Class 1 (IEC536), degree of protection IP20 (IEC60529) Safe low voltage: SELV (acc. IEC60950-1)
Status Indicators Visual: 3 status LEDs (Input, Output, Alarm)
Relay: N.O. contact rated 200ma/50 Vdc
Installation
Fusing
-Input Internally fused
-Output Outputs are capable of providing high currents for short periods of time for inductive load startup or switching. Fusing may be required for
wire/loads if 2x Nominal O/P current rating cannot be tolerated. Continuous current overload allows for reliable fuse tripping.
Mounting Simple snap-on to DIN TS35/7.5 or TS35/15 rail system.
Connections Input: Screw terminals, connector size range: 16-10 AWG (1.5-6 mm2) for solid conductors.
Output: Two terminals per output, connector size range: 16-10 AWG (1.5-6 mm2) for solid conductors.
Case Fully enclosed metal housing with ne ventilation grid to keep out small parts.
-Free Space 15 mm in front, 25 ~ 40 mm above and below, 10 mm left and right.
H x W x D (inches/mm) 4.88 × 1.97 × 4.55 (124 × 50 × 116) 4.88 × 2.36 × 4.55 (124 × 60 × 116) 4.88 x 3.42 x 4.98 (124 x 87 x 126.6)
Weight (lbs/kg) 1.65 (0.75) 1.98 (0.9) 2.6 (1.2)
SDN-C Specifications (Single Phase)
1. Not UL listed for DC input.
2. Input current ratings are conservatively specied with low input, worst case
efciency and power factor.
3. Losses are heat dissipation in watts at full load, nominal input line.
4. Ripple/noise is stated as typical values when measured with a 20 MHz, bandwidth
scope and 50 Ohm resistor.
5. Peak current is calculated at 24 Volt levels.
6. Demonstrated through extended life test.
7. Contact tech support for operation at -25oC.
Visit our website at www.solahd.com or
contact Technical Services at (800) 377-4384 with any questions.
104
4Power Supplies
Description Catalog Number
SDN 20-24-480CC SDN 40-24-480C
Input
Nominal Voltage 380 - 480 Vac
Two-phase input Yes 1
-AC Range Continuous 2320 - 540 Vac
-DC Range Continuous 450 - 760 Vdc TBD
-DC Range Short Term 3420 - 780 Vdc TBD
-Frequency 50 - 60 Hz
Nominal Current 43 x 0.9 A or 2 x 1.3 A 3 x 1.6 A
-Inrush Current Max. Negligible Negligible
Efficiency (Losses 5)93% (42 W) 94% (78 W)
Power Factor Correction Active Power Factor Correction
Output
Turn on Time Typ. 1s
Voltage Rise Time < 100mS full resistance load (Tamb=+25°C)
Power Back Immunity < 35V
Overvoltage Protection > 30.5 but < 33 Vdc, auto recovery
Nominal Voltage 24V (24-28Vdc Adjustable)
Voltage Regulation < ± 2% overall
Initial Voltage Setting 24.5V ± 1%
-Ripple 6< 100mVpp
PARD PARD (Periodic and Random Deviation) = 200mV peak-peak max
Nominal Current 20 A (480 W) (constant power, not constant) 40 A (960 W)
-Peak Current 71.5 × Nominal Current for 4 seconds minimum while holding voltage > 20 Vdc
-Current Limit PowerBoost™
Derating (T amb=60-70 °C) typ. 24W/°C typ. 48 W/°C
Holdup Time >20 ms >15 ms
Voltage Fall Time <50 mS from 95% to 10% rated voltage @ full load (Tamb=+25°C)
Parallel Operation 8Single or parallel operation selectable via front switch. For redundant
operation, use of external diode module is preferred SDN 40 uses active paralleling
General
Case Fully enclosed metal housing with ne ventilation grid to keep out small parts.
Min. Required Free Space 70mm above and below, 10mm left and right (same as manual) 70mm above and below, 15mm in front, 25mm left & right
Max. Dimensions HxWxD (in/mm) 4.85 x 2.56 x 4.68 (123.3 x 85 x 118.8) 4.85 x 7.09 x 4.85 (123.3 x 180 x 123.17)
Weight (lbs/g) 2.8 lb (1300 g) 5.3 lb (2400 g)
EMC: -Emissions EN61000-6-3:2001, Class B EN55011, EN55022 Radiated and Conducted including Annex. A, EN61000-3-2
-Immunity EN61000-6-1:2001, EN61000-6-2:2001, EN61000-4-2 Level 4, EN61000-4-3 Level 3, EN61000-4-6 Level 3, EN61000-4-4 Level 4 input and
level 3 output. EN61000-4-5 Isolation class 4, EN61000-4-11, Semi F47 sag immunity
Approvals UL508 Listed, cULus; UL60950-1, cURus; IEC60950-1; ISA 12.12.01 Class 1 Div 2,
CE (LVD 73/23 & 2004/108/EC), (EMC 89/336 & 93/68/EEC); EN61000-3-2,EN 60079-15 (Class 1, Zone 2)
Temperature Storage: -40°C to + 85°C, Operation -25°C to +60°C full power, with linear derating to half power from 60°C to 70°C (Convection
cooling, no forced air required). Operation up to 50% load permissible with sideways or front side up mounting orientation.
Humidity < 90% RH, noncondensing; IEC 60068-2-2, 68-2-3
Altitude 0 to 3000 meters (0 to 10,000 feet)
Vibration 2.5(g) RMS, 10-2000 Hz (random); three axes for 20 minutes each - IEC 60068-2-6
Shock 3(g) peak, three axes, 11mseconds for each axis - IEC 60068-2-27
Warranty 5 Years
MTBF > 550,000 hrs MTBF (Nominal voltage, full load, T ambient = 25°C
General Protection/Safety Protected against short -circuit, overload, open circuit. Protection class 1 (IEC536),
degree of protection IP20 (IEC 529), Safe low voltage: SELV (acc. EN60950)
Over-Temperature Protection LED Alarm, Output shutdown with automatic restart
Status Indicators Visual: 3 status LEDs (Input, Output, Alarm); Relay: SSR or dry relay contact, signal active when Vout = 18.5Vdc = +/-5%
Installation
Fusing: -Input Externally fused
-Output Not fused. Output is capable of providing high currents (PowerBoost) for motor load startup.
Mounting Simple snap-on to DIN TS35/7.5 or TS35/15 rail system.
Unit should handle normal shock and vibration of industrial use and transportation without falling off the rail.
Connections 9
Input: screw terminals, Wiring for the connector will be ground on the left (when looking at the front of the unit), connector size range:
16-10AWG (1.5-6mm2) for solid conductors. Output: connector size range, wire gauge 6-7 AWG for SDN40;
all other models: 16-10AWG (1.5-6mm2) for solid conductors. The connector color will be gray or off-white.
SDN-C Specifications (Three Phase)
1. SDN20 will operate at 75% load and SDN40 will operate at 50% load under loss of
1 phase. Units will shut down if thermal threshold is exceeded under this condition.
2. Unit passed input voltage overstress test at 600 Vac maximum without failure.
3. DC operation will require the user to provide the proper input circuit protection.
4. Input current ratings are specied with low input, line conditions, worst case
efciency values and power factor spikes. Input current at nominal input settings will
be typically half these values.
5. Losses are heat dissipation in watts at full load, nominal line.
6. Ripple/noise is stated as typical values when measured with a 20 MHZ, bandwidth
scope and 50 Ohm resister.
7. SDN 20 and SDN 40 unit will go to HICCUP mode. SDN 5 and SDN 10 will maintain
min 4 secs to deliver 150% load then drops to almost zero V out. The output voltage
will immediately drop to almost zero when load rises above 150%.
8. All models except the 40amp unit are capable of parallel operation by use of a jumper
pin, accessible by the end user. 40amp has current sharing signal.
9. SDN40-24-480 only = Output signaling terminal block features (Shut down, Power
Good, Current Monitor, Current Balance, signal GND).
Visit our website at www.solahd.com or
contact Technical Services at (800) 377-4384 with any questions. 105
4
Power Supplies
24-28 V
115/230 VAC 1.3-0.7 A 50/60 HZ
  
US LISTED
Power Supply
SDN 2.5-24-100P
S O L A
Parallel
Single
C

L
U
L
N
24 VDC / 2.5 A
++
NEC Class 2
Power Supply
OK
--
OK
SDN-C Series Dimensions
W
D
H
Catalog
Number
Dimensions - inches (mm)
H W D
SDN 5-24-100C 4.88 (124) 1.97 (50) 4.55 (116)
SDN 10-24-100C 4.88 (124) 2.36 (60) 4.55 (116)
SDN 20-24-100C 4.88 (124) 3.42 (87) 4.98 (126.6)
SDN 20-24-480CC 4.85 (123) 2.56 (85) 4.68 (118.8)
Catalog
Number
Dimensions - inches (mm)
H W D
SDN 40-24-480C 4.85 (123) 7.09 (180) 4.85 (123)
H
WD
S O L A
SDN 20-24-480C
Power Supply
Electronically protected
24 VDC / 20 A
Output:
L1 L2 +
L3 +--
24-
28V
OK
Overload
FuseMode
Continuo
usMode
3PH 380/500 VAC
1.7/1.5A/Phase 50/60 Hz
Input:
SingleUse
ParallelUse
Res
etfusemode
  
US LISTED

U
CL
SDN5-24-100C
Visit our website at www.solahd.com or
contact Technical Services at (800) 377-4384 with any questions.
106
4Power Supplies
SDN-C Series Mounting
SDN-C Series Mounting (cont.)
DIN Rail Mounting
Snap on the DIN Rail:
1. Tilt unit slightly backwards
2. Put it onto the DIN Rail
3. Push downwards until stopped
4. Push at the lower front edge to lock
5. Shake the unit slightly to ensure that the retainer
has locked
Alternative Panel Mount: Using the optional SDN-PMBRK2
accessory, the unit can be screw mounted to a panel.
Chassis Mounting
Instead of snapping a Sola SDN™ unit on the DIN Rail,
you can also attach it using the screw mounting set
SDN-PMBRK2.
This set consists of two metal brackets, which replace the
existing two aluminum proles.
Dimensions
Detachment from DIN Rail: