www.osram-americas.com/OPTOTRONIC OPTOTRONIC(R) LED Power Supply OTi 30W Programmable - Technical Specifications GENERAL INFORMATION Item Number 79630, 79397, 79466, 79515 Type Constant Current, Class 2 Output Power Programming Tool Software 30W (Max.) 51645 & 51647/51648 Download Output current Dimming level Dim-to-off, Soft start Programmable Features LED thermal protection Auxiliary output voltage Constant lumen output End-of-life indicator ELECTRICAL SPECIFICATIONS Input Input Voltage (VAC) Frequency Range (Hz) Input Current (A) THD @ Full Load Power Factor @ Full Load 120V-277V (+/- 10%) 50 - 60 Hz (+/- 10%) 120V 277V 0.31 0.15 <10% <20% >0.9 >0.9 Efficiency @ Full Load (%) Inrush Current (Apk) Output >85% 0.86 >85% 1.35 DIMMING SPECIFICATIONS Dimming Control 0 - 10V (Isolated) Dimming Range2 10-100%, 1-100% Dimming Type Analog , PWM2 (1kHz) Output Current (mA) 150-1050mA1 ( 1% model) 350-1050mA (10% model) Dimming Input Isolation 2.5kV Output Voltage (VDC) 10-55VDC Source/Sink Current 0.2mA max Output Ripple Current <20% @ 1050mA Dim-to-Off Threshold 0.8V Max. Output Power (W) 30W Stand-by Power (max) 1.4W(120V); 1.7W(277V) LED Power Up Time <1sec Load Regulation <5% Line Regulation <5% Over Voltage Protection Yes, non-latching Over Load Protection Yes, non-latching Output Short-Circuit Yes, non-latching Protection Over Temperature Foldback at 110C Protection Auxiliary Output (Models: 79397 & 79466 only) Output Voltage (VDC) 12/20/24V1 (configurable) Output Current (mA) 40 Voltage Regulation 10% LED thermal protection (NTC) NTC Value Active Range 25k Output Level Minimum User defined ESC287 6/20 ENVIRONMENTAL SPECIFICATIONS Ambient Operating -30C to 50C Temperature 75C (50kHrs)3 Case Temperature (Tc) 90C (20kHrs) Max. Storage Temp. 70C Max. Relative Humidity (%) 85% non-condensing NEMA SSL1 - 2010 Transient Protection Non-Roadway 2.5KV UL Rating Dry & Damp UL File Number E320395 // Class TL EMI Compliance FCC Part 15 Class A Sound Rating Class A 1- Default for Gen 1.5 is 12V 2- The output is in PWM mode under 350mA. Set current under 350mA is limited to 10% DIM. The lowest output current is 10mA and the minimum percentage of dimming is dependent on the programmed output current of the driver 3- Warranty applicable only at 75C 1 WIRING DIAGRAM Note 1: The Vaux Out (YELLOW) and LED- (BLUE) will provide the DC Auxiliary output. Yellow is "+ve" polarity and blue is "-ve" polarity. Note 2: Maximum suggested remote mounting distance is 16 feet. For additional information on further distances and EMI compliance reference OPTOTRONIC Technical Guide LED258 MECHANICAL DIAGRAM MECHANICAL SPECIFICATIONS Length 11.02" (280mm) Width 1.15" (29.4mm) Height 1.0" (25.4mm) Mounting Length ESC287 6/20 10.63" (270mm) 2 OPERATING RANGE 60 Outpu Voltage (V) 50 40 30 20 10 0 100 300 500 700 900 Output Current (mA) 1100 1% Dimming models 10% Dimming models DIMMING CURVE 100 % of Output Current 80 60 40 20 0 0 1 2 3 4 5 6 7 8 9 10 Dimming Voltage (V) 10% Dimming 1% Dimming ESC287 6/20 3 THD VS INPUT VOLTAGE (FULL LOAD) 16 14 12 THD (%) 10 8 6 4 2 0 100 150 200 250 300 Input Voltage (VAC) POWER FACTOR VS INPUT VOLTAGE (FULL LOAD) 1.00 0.99 0.98 Power Factor 0.97 0.96 0.95 0.94 0.93 0.92 0.91 0.90 100 150 200 250 300 Input Voltage (VAC) ESC287 6/20 4 EFFICIENCY VS OUTPUT VOLTAGE Efficiency @ 120V 90 88 86 Efficiency (%) 84 82 80 1050mA 78 700mA 350mA 76 74 72 70 5 15 25 35 45 55 65 Output Voltage (V) Efficiency @ 277V 90 88 86 Efficiency (%) 84 82 80 1050mA 78 700mA 350mA 76 74 72 70 5 15 25 35 45 55 65 Output Voltage (V) ESC287 6/20 5 POWER FACTOR VS LOAD Power Factor vs Output Power (120V) 1.00 0.99 0.98 Power Factor 0.97 0.96 0.95 1050mA 0.94 700mA 0.93 350mA 0.92 0.91 0.90 0 5 10 15 20 25 30 35 Output Power (W) Power Factor vs Output Power (277V) 1.00 0.99 0.98 Power Factor 0.97 0.96 0.95 1050mA 0.94 700mA 0.93 350mA 0.92 0.91 0.90 0 5 10 15 20 25 30 35 Output Power (W) ESC287 6/20 6 THD VS LOAD THD vs Output Power (120V) 20.0 18.0 16.0 THD (%) 14.0 12.0 10.0 1050mA 8.0 700mA 6.0 350mA 4.0 2.0 0.0 0 5 10 15 20 25 30 35 Output Power (W) THD vs Output Power (277V) 20.0 18.0 16.0 THD (%) 14.0 12.0 10.0 1050mA 8.0 700mA 6.0 350mA 4.0 2.0 0.0 0 5 10 15 20 25 30 35 Output Power (W) ESC287 6/20 7 LED THERMAL PROTECTION (NTC) CHARACTERISTIC The LED thermal protection feature of the OTi 30W helps reduce the temperature of the LED module by reducing the output current in case of abnormal temperature conditions. To use this feature, a third party NTC thermistor should be connected to the LED power supply as shown in the wiring diagram below. In the end application, care must be taken to place the NTC thermistor close to the hottest spot on the LED module. If LED thermal protection is not required the NTC port on the LED power supply connector can be left open. Vishay, EPCOS, Murata, Panasonic are some of the manufacturers of NTC thermistor. EPCOS part number for reference only B57164K153J (15k @ 25C). Murata part number for reference only - NCP03XH223J05RL (22k @ 25C) Note 3: Graphs for reference. The derating limits can be programmed using the OT Linear Handheld Programmer Derating start = 6.3k; Derating end = 4.3k; Min output level = 10% % Of Output Current 100 80 60 40 20 0 6.5 6 5.5 5 4.5 4 RNTC in k CONSTANT LUMEN MAINTENANCE The Constant Lumen Maintenance feature of the OTi 30W helps to maintain the required lumen output of the fixture at a constant level throughout its lifetime. In general, LED's lumen output will depreciate over time and in order to maintain sufficient light level towards the end of lifetime, the LEDs are driven at high current initially and will result in more energy consumption. The constant lumen maintenance will give the flexibility to drive the LEDs at optimal driving current throughout its lifetime. This helps in energy savings, constant light output and enhanced reliability of the system. Note 4: A detailed step-by-step instructions are outlined in the OT Programmer User Manual V2.4 ESC287 6/20 8 END-OF-LIFE INDICATOR The End-of-Life indicator helps the end user to receive a signal from the fixture indicating that it has reached its programmed life-time. After the LED driver reaches the programmed life-time, whenever it is turned ON, it stays at `Dim' level (10%) for 10 minutes and reaches its appropriate level. INRUSH CHARACTERISTICS Vin (V) Ipeak (A) T (@ 50% of Ipeak) 120 0.86 50s 277 1.35 60s DIMMER COMPATIBILITY Manufacturer Part no OSRAM ZBHA-CLM DIM (NAED: 45678) EN-LCM-1R10V-GB2-BK EN-LCM-1R10V-GB2-BK/DR EN-ALC-1R10V-GB2-BK EN-ALC-1R10V-GB2-BK-DR 45561 - LC-SL3W-TVWBX/UNV IP710-DLX DVTV-XX ADF-120277 ISD BC FD-301 Encelium EMS OSRAM Leviton Lutron Wattstopper Synergy lighting Controls Wattstopper Note 5: The absence of a dimmer from this chart does not necessarily imply incompatibility. Please reference the dimmer manufacturer's instructions for installation. UL CONDITIONS OF ACCEPTABILITY (E320395) Conditions of Acceptability - When installed in the end-product, consideration shall be given to the following: The LED driver was evaluated using an electronic LED load resulting in an output rated current and rated power as indicated in the electrical ratings. The unit employs a Class B isolation transformer (T1) on the main PWB. The need to repeat the Temperature Test shall be determined in end-use product. Tc point case temperatures in the end-use shall not exceed 90C. The unit was tested on a 20A branch circuit. If used on a branch circuit greater than this, additional testing may be necessary. The PWB spacing for use in Damp locations have been evaluated to UL 8750. The unit is completely potted on the bottom and partially potted on the top. Areas that are potted meet spacing requirements are out of Table 7.4 Parts Potted or subsequently coated. Other areas meet applicable requirements in Table 7.4. The Leakage current test was conducted between the ground terminal, exposed conductive surface and the grounded pole of the supply circuit. These products are intended for use in Dry and Damp locations. The use in other environmental locations shall be considered in the end product. ESC287 6/20 9 For models with rated output voltage above 30V rms (42.4V peak) suitability shall be determined in the cUL end-use application based on accessibility to the user. These models were tested in a 40C ambient. For Tref values see Table below. Determination to repeat the temperature test shall be made in end-use product. During the normal temperature test of the end product, the temperature at any point on the case is to be monitored and shall not exceed 90C. When provided the Tc in a circle can be considered a reference hot spot on the case. Product Tref Max Tref - measured @ 40C OTi 30/120-277/1A0 DIM L * 90C 66C *Applies to DIM or DIM-1 and may be followed by AUX WARRANTY OPTOTRONIC(R) products are covered by our LED Module, OPTOTRONIC Power Supply or Control Warranty. For additional details, refer to the latest version of the warranty (LED395) available at www.osramamericas.com/optotronic. (c) 2016 OSRAM SYLVANIA Inc. ESC287 6/20 OSRAM and OPTOTRONIC are registered trademarks of OSRAM GmbH. Specifications subject to change without notice. 10