DC-DC CONVERTERS 30 W Wide Input DC-DC Converters 1
2 YEAR WARRANTY
BXA30 Series
Single and dual output
Designed to meet telecom power supply interface
standard ETS300-132-2
UL, VDE and CSA safety approvals
VDE0878 and EN55022 conducted emissions level A
EN61000-4-2, -3, -4, -5, -6 immunity compliant
Fixed frequency operation at 350 kHz
MTBF in excess of 7,005,000 hours (demonstrated)
Basic insulation system
Available RoHS compliant
The BXA30 series, comprising 9 different models, has been conceived as an applications-
specific range of dc-dc converters, specifically addressing telecommunications, industrial
electronics, test equipment, mobile telecommunications and distributed power applications.
The series offers three wide input voltage ranges, 9 Vdc to 18 Vdc and 36 Vdc to 75 Vdc,
and is available in single and dual output versions. Designed to meet ETSI telecoms
interface standards ETS300-132-2 and BTR2511, together with internal filtering to EN55022
level A, safety approval to EN60950 and UL1950, and isolation of 1500 Vdc, the 48 Vdc
models are ideal for telecommunications applications. The 12 V models are particularly
suited to industrial, mobile telecom and test equipment applications, featuring EN61000-4-2,
-3, -4, -5 and -6 immunity compliant. Other features include low output ripple, overvoltage
protection, continuous short circuit protection, remote enable and remote sense.
All specifications are typical at nominal input, full load at 25 °C unless otherwise stated
EMC CHARACTERISTICS
Conducted emissions EN55022, FCC part 15 (Note 4) Level A
EN55022, FCC part 15 (Note 5) Level B
VDE0878 (Note 4) (48 V) Level A
Radiated emissions EN55022, FCC part 15 Level A
ESD air EN61000-4-2, level 3 Perf. criteria 2
ESD contact EN61000-4-2, level 4 Perf. criteria 2
Surge EN61000-4-5, level 3 Perf. criteria 2
Fast transients EN61000-4-4, level 3 Perf. criteria 2
Radiated immunity EN61000-4-3, level 3 Perf. criteria 2
Conducted immunity EN61000-4-6, level 3 Perf. criteria 2
GENERAL SPECIFICATIONS
Efficiency See table
Isolation voltage Input/output 1500 Vdc
Basic insulation input/case, 48 V models 1500 Vdc
Switching frequency Fixed 350 kHz
Approvals and VDE0805, EN60950
standards IEC950, UL1950
(See Note 12) CSA C22.2 No. 950
Case material Aluminum substrate
with plastic case
Material flammability UL94V-0
Weight 120 g (4.24 oz)
MTBF (See Note 9)
Demonstrated @ 25 °C
7,005,000 hours
ENVIRONMENTAL SPECIFICATIONS
Thermal performance Baseplate operating -25 °C to +100 °C
temperature,
(See Notes 6, 8)
Non-operating -55 °C to +100 °C
Thermal impedance Free air convection, 6.5 °C/W
baseplate to air
With heatsink (See Note 8) 5.2 °C/W
SPECIFICATIONS
File Name: bxa30sd.pdf Rev (02): 08 Dec 2005
OUTPUT SPECIFICATIONS
Voltage adjustability Singles ±10%
Line regulation LL to HL (single/dual) ±0.2%/±0.4%
Load regulation FL to NL (single/dual) ±0.2%/±0.4%
Ripple and noise 3.3 V 60 mV pk-pk
(20 MHz bandwidth) 5.0 V 50 mV pk-pk
All others 100 mV pk-pk
All models 20 mV rms
Temperature coefficient ±0.02%/°C
Overvoltage protection Transient 135% Vout
Short circuit protection Singles Continuous
Duals (single short) (See BXA15/30
Design Note 100)
Duals (dual short) Continuous
Transient response 25% to 100% load 4.0%
Voltage accuracy ±1.5%
Load cross regulation Dual output 3.0%
30% to 100% output variation
INPUT SPECIFICATIONS
Input voltage range 12 Vin nominal 9-18 Vdc
48 Vin nominal 36-75 Vdc
Reverse voltage Yes
protection (See Note 7)
Max. input rise and 48 V 5 V/ms
fall time ETS300-132
Remote ON/OFF
Logic compatibility CMOS/TTL
ON Open circuit
OFF <1 Vdc
For the most current data and application support visit www.artesyn.com/powergroup/products.htm
NNootteess
1Nominal, at no load.
2Low line to high line.
3Full load to no-load. For duals, the value stated is for balanced loads.
4An optional internal filter is available, which will meet VDE0871 level A,
VDE0878 level A and EN55022 level A. Add the suffix ‘-F’ to the model
number, e.g. BXA30-48S12-FJ. See BXA15 and BXA30 Design Note 100.
5For conducted noise operation of the BXA30 to VDE0871, VDE0878 and
EN55022 level B, see BXA15 and BXA30 Design Note 100.
6For extended operating temperature, include the heatsink option, ‘-1’ in the
model number. Max. heatsink height is 12.5 mm, e.g. BXA30-48S15-1J
7Reverse voltage protection can be implemented by putting a slow blow
fuse on the negative input rail. Rate the fuse for 48 Vdc at 1.5 A and 12 Vdc
at 6 A.
8The maximum operating ambient temperature, without derating depends
on internal power dissipation and hence efficiency and cooling method.
BXA15 and BXA30 Design Note 100 provides detailed thermal calculations
and design-in details.
9Test results to-date are 1,590,000 hours @ 46 ˚C. The MTBF figure shown
includes a calculated acceleration factor of 4.1 based on an activation
energy of -0.55 eV.
10 Visit the Artesyn website to download a copy of Design Note 100.
11 This model has the same electrical pin-out and pin pitch spacings as the
drawing on the following page. Dimensions are 76.2 x 76.2 x 14.2 mm,
±0.3 mm.
12 This product is only for inclusion by professional installers within other
equipment and must not be operated as a stand alone product.
13 If remote sense is not used, connect +sense to +vout and -sense to -vout.
14 The ‘J’ suffix indicates that these parts are Pb-free (RoHS 6/6) compliant.
TSE RoHS 5/6 (non Pb-free) compliant versions may be available on
special request, please contact your local sales representative for details.
15 NOTICE: Some models do not support all options. Please contact your
local Artesyn representative or use the on-line model number search tool at
http://www.artesyn.com/powergroup/products.htm to find a suitable
alternative
BXA30 Series
Single and dual output
DC-DC CONVERTERS 30 W Wide Input DC-DC Converters 2
File Name: bxa30sd.pdf Rev (02): 08 Dec 2005
INPUT OUTPUT OUTPUT INPUT TYPICAL REGULATION MODEL
VOLTAGE VOLTAGE CURRENT (MAX.) CURRENT (1) EFFICIENCY LINE (2) LOAD (3) NUMBER (4,6,14,15)
9-18 Vdc 5.0 V 5.0 A 100 mA 80% ±0.2% ±0.2% BXA30-12S05J
36-75 Vdc 3.3 V 6.0 A 30 mA 75% ±0.2% ±0.2% BXA30-48S3V3J
36-75 Vdc 3.3 V 8.0 A 30 mA 81% ±0.2% ±0.2% BXA30-48S3V3/8J (11)
36-75 Vdc 5.0 V 5.0 A 30 mA 80% ±0.4% ±1.0% BXA30-48S05J
36-75 Vdc 12.0 V 2.5 A 30 mA 85% ±0.2% ±0.2% BXA30-48S12J
36-75 Vdc 15.0 V 2.0 A 30 mA 87% ±0.2% ±0.2% BXA30-48S15J
36-75 Vdc ±5.0 V ±2.5 A 30 mA 80% ±0.4% ±0.4% BXA30-48D05J
36-75 Vdc ±12.0 V ±1.25 A 30 mA 84% ±0.4% ±0.4% BXA30-48D12J
36-75 Vdc ±15.0 V ±1.0 A 30 mA 86% ±0.4% ±0.4% BXA30-48D15J
International Safety Standard Approvals
VDE0805/EN60950/IEC950 File No. 14501-3336-7006
Licence No. 6231
UL1950 File No. E174104
CSA C22.2 No. 950 File No. LR41062C
10K
TRIMPOT
TRIM
UP
TRIM
DOWN
5
4
3
5
4
3
Datasheet © Artesyn Technologies
®
2005
The information and specifications contained in this datasheet are believed to be correct at time of publication. However, Artesyn Technologies accepts no responsibility for consequences arising
from printing errors or inaccuracies. Specifications are subject to change without notice. No rights under any patent accompany the sale of any such product(s) or information contained herein.
For the most current data and application support visit www.artesyn.com/powergroup/products.htm
BXA30 Series
Single and dual output
DC-DC CONVERTERS 30 W Wide Input DC-DC Converters 3
Please consult our website for the following items: Design Note www.artesyn.com
File Name: bxa30sd.pdf Rev (02): 08 Dec 2005
0.52
(13.30±0.30)
0.76
(19.20±0.30)
SIDE VIEW
4
5
6
7
1
8
2.50
(63.5)
0.20
(5.08)
3.02
(76.30 ± 0.30)
1.15
(29.21)
0.302
(7.67±0.30)
Case/Metal Inserts M3.0
(Typ. 4 Places)
BOTTOM
VIEW
2
3
0.95
(24.13)
2.00
(50.80)
0.6 (15.24)
0.4 (10.16)
0.30 (7.62)
1.30
(33.02)
0.70 (17.78)
0.50 (12.70)
0.80 (20.32)
0.20 (5.08)
2.41
(61.10
±0.30
)
Ø 1.000
8 Places
ALL DIMENSIONS IN INCHES (mm)
Tolerance .XX ±0.02
.XXX ±0.005
PIN CONNECTIONS
PIN NUMBER SINGLE OUTPUT DUAL OUTPUT
1 + Vin + Vin
2 – Vin – Vin
3 + Sense (13) + Vout
4 Trim Common
5 – Sense – Vout
6 + Vout No Pin
7 – Vout No Pin
8
Remote ON/OFF Remote ON/OFF
EXTERNAL OUTPUT TRIMMING
Single output models can be
externally trimmed by ±10%
using either method shown.