Data sheet
Pro-H
CP T SNT 70W 12V 6A
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Creation date November 9, 2020 1:09:15 PM CET
Catalogue status 23.10.2020 / We reserve the right to make technical changes. 3
EMC / shock / vibration
Limiting of mains voltage harmonic
currents
According to EN
61000-3-2
Noise emission in accordance with
EN55032 Class B
Vibration resistance IEC 60068-2-6
3 axes, sinus, 10…55 Hz, 1
g, 1 oct/min.
Interference immunity test acc. to EN 61000-4-2 (ESD)|
EN 61000-4-3 and EN
61000-4-8 (fields)|EN
61000-4-4 (burst)|EN
61000-4-5 (surge)|EN
61000-4-6 (conducted)|
EN 61000-4-11 (dips)
Shock resistance IEC 60068-2-27 3 axes, half sinus, 15 g, 11
ms
Insulation coordination
Insulation voltage 4 kV (input / output) Pollution severity 2
Protection class I, with PE connection
Electrical safety (applied standards)
Electrical machine equipment
Acc. to EN60204
For use with electronic equipment Acc. to EN50178 /
VDE0160
Safety extra-low voltage SELV according to EN
60950
Safety transformers for switch-mode
power supplies
According to EN
61558-2-4
Connection data (input)
Conductor cross-section, AWG/kcmil ,
max. 12
Conductor cross-section, AWG/kcmil ,
min. 24
Conductor cross-section, flexible , min. 0.5 mm² Conductor cross-section, rigid , max. 2.5 mm²
Conductor cross-section, rigid , min. 0.5 mm² Connection system Screw connection
Number of terminals 3 for L/N/PE Tightening torque, max. 0.6 Nm
Tightening torque, min.
0.5 Nm
Wire connection cross section, flexible
(input), max. 2.5 mm²
Connection data (output)
Conductor cross-section, AWG/kcmil ,
max. 12
Conductor cross-section, AWG/kcmil ,
min. 18
Conductor cross-section, flexible , max. 2.5 mm² Conductor cross-section, flexible , min. 1 mm²
Conductor cross-section, rigid , max. 2.5 mm² Conductor cross-section, rigid , min. 1 mm²
Number of terminals 2 (+ / -) Tightening torque, max. 0.6 Nm
Tightening torque, min. 0.5 Nm
Connection data (signal)
Number of terminals
3
Wire connection method Pluggable screw
connection
Wire cross-section, AWG/kcmil , max. 12 Wire cross-section, AWG/kcmil , min. 32
Wire cross-section, solid , max. 2.5 mm² Wire cross-section, solid , min. 0.2 mm²
Signalling
Active output signal 11 V DC ± 1 V DC / max.
20 mA
Power Good Signal
Trigger point 9…11 V DC