Powerex, Inc., 200 E. Hillis Street, Youngwood, Pennsylvania 15697-1800 (724) 925-7272
MIG400Q2CMB1X
Compact IPM Series Dual Module
400 Amperes/1200 Volts
3Rev. 8/05
Electrical and Mechanical Characteristics, Tj = 25°C unless otherwise specified
Characteristics Symbol Test Conditions Min. Typ. Max. Units
IGBT Inverter Sector
Collector Cut-off Current ICEX VCE = 1200V, Tj = 25°C — — 1 mA
VCE = 1200V, Tj = 125°C — — 10 mA
Collector-Emitter VCE(sat) VD = 15V, IC = 400A, VIN = 15V to 0V, Tj = 25°C — 2.4 2.8 Volts
Saturation Voltage VD = 15V, IC = 400A, VIN = 15V to 0V, Tj = 125°C — 2.8 — Volts
Forward Voltage VF IF = 400A, Tj = 25°C — 2.4 2.8 Volts
ton — 2.0 3.0 µs
Switching tc(on) VCC = 600V, IC = 400A, — 0.5 — µs
Time trr VD = 15V, VIN = 15V ↔ 0V, — 0.3 — µs
toff Tj = 25°C, Inductive Load — 1.6 2.5 µs
tc(off) — 0.3 — µs
Control Sector
Control Circuit Current ID(H) High Side, VD = 15V — 13 17 mA
ID(L) Low Side, VD = 15V — 13 17 mA
Input-ON Signal Voltage VIN(on) VD = 15V 1.4 1.6 1.8 Volts
Input-OFF Signal Voltage VIN(off) VD = 15V 2.2 2.5 2.8 Volts
Fault Output Current IFO(on) Protection Current, VD = 15V 8 10 12 mA
IFO(off) Normal Current, VD = 15V — — 0.1 mA
Over-Current Protection Trip Level OC VD = 15V, Tj ≤ 125°C 640 — — Amperes
Short-Circuit Current SC VD = 15V, Tj ≤ 125°C 640 — — Amperes
Protection Trip Level
Over-Current Cut-off Time toff(OC) — — 5 — µs
Over-Temperature OT Trip Level Case Temperature 110 118 125 °C
Protection OTr Reset Level Case Temperature — 98 — °C
Control Supply Under UV Trip Level 11.0 12.0 12.5 Volts
Voltage Protection UVr Reset Level 12.0 12.5 13.0 Volts
Fault Output Pulse Width td(FO) VD = 15V 1 2 3 ms