BURNDY
EHV
H-11
WELDED TERMINAL
CONNECTOR
SWAC-A-N
Weld type
Application: Bus to Two or Four
Hole Pad (center
formed)
EHV RATED: UP TO 550 kV
when used with
Shielding Caps
Material: Cast 356 Aluminum Alloy
NOTES:
1. Dimensions in brackets [ ] are in millimeters.
2. Conductor smaller than 3 inch bus size not recommended
for 550 kV.
3. DOES NOT INCLUDE SHIELDING CAPS. For EHV
applications, shielding caps are required. Order separately
(Type STS) shown on page 32 or ADD SUFFIX “STS” to
Catalog Number (example: SWAC22A44NSTS), includes
two shielding caps.
4. Pad surface finished on both sides of tongue.
5. For six hole NEMA pad contact factory.
CATALOG NUMBER CONDUCTOR FIG. DIMENSIONS IN / [mm]
IPS (SCH40) EHPS (SCH80) IPS A NO. B L T
1.25 5.80 .50
SWAC18A-2N SWAC58A-2N 1[32] [147] [13]
2.38 1.25 5.80 .50
SWAC18A-34N SWAC58A-34N 2[60] 2[32] [147] [13]
1.25 6.86 .50
SWAC18A-44N SWAC58A-44N 3[32] [174] [13]
1.50 6.23 .56
SWAC19A-2N SWAC59A-2N 1[38] [158] [14]
2.88 1.50 6.23 .56
SWAC19A-34N SWAC59A-34N 2-1/2[73] 2[38] [158] [14]
1.50 7.29 .56
SWAC19A-44N SWAC59A-44N 3[38] [185] [14]
1.75 6.30 .62
SWAC20A-2N SWAC90A-2N 1[44] [160] [16]
3.50 1.75 6.30 .62
SWAC20A-34N SWAC90A-34N 3[89] 2[44] [160] [16]
1.75 7.36 .62
SWAC20A-44N SWAC90A-44N 3[44] [187] [16]
1.75 6.30 .62
SWAC21A-34N SWAC91A-34N 4.00 2[44] [160] [16]
3-1/2[102] 1.75 7.36 .62
SWAC21A-44N SWAC91A-44N 3[44] [187] [16]
2.00 6.40 .75
SWAC22A-34N SWAC92A-34N 4.50 2[51] [163] [14]
4[114] 2.00 7.40 .75
SWAC22A-44N SWAC92A-44N 3[51] [188] [19]
5.00 2.00 6.23 .56
SWAC23A-34N SWAC93A-34N 4-1/2[127] 2[51] [158] [19]
2.00 6.68 .75
SWAC24A-34N SWAC94A-34N 5.56 2[51] [170] [19]
5[141] 2.00 7.72 .75
SWAC24A-44N SWAC94A-44N 3[51] [196] [19]
6.62 2.50 7.75 1.00
SWAC86A-44N SWAC96A-44N 6[168] 3[64] [197] [25]