Bussmann®
7
For complete specification data, call Bussmann Information Fax ~ 636.527.1450
Electrical - Power Fuses
BIF document: (LPN-RK) 1003 (0-60) & 1004 (70-600) BIF document: (LPS-RK) 1001 (0-60) & 1002 (70-600)
Low-Peak®Dual-Element, Time-Delay, Class RK1 Fuses
LPN-RK_SP (250V)
LPS-RK_SP (600V)
Dual-Element, Time-Delay – 10 seconds (minimum) at
500% rated current (8 seconds for 0-30A sizes)
Ampere Ratings: ⁄Ω¡º-600 Amps.
Voltage Rating: LPN-RK: 250 Volts AC (or less),
125 Volts DC (⁄Ω¡º-60 A); 250 VDC (70-600 A)
LPS-RK: 600 Volts AC (or less), 300 Volts DC
Current Limiting RK1 Fuse
Interrupting Rating: 300,000A RMS Sym.
(50,000A @ 300V DC)
Agency Approvals:
UL Listed – Special Purpose**, Guide JFHR, File E56412
CSA Certified (200,000 AIR), Class RK1 per CSA C22.2,
No. 248.12, Class 1422-02, File 53787
Dimensions: See pages 2-3 for Class RK1 dimensional data.
Catalog Numbers (250V AC/125V DC)
LPN-RK-⁄Ω¡ºSP LPN-RK-3⁄Ω™SP LPN-RK-60SP
LPN-RK-⁄fiΩ¡ººSP LPN-RK-4SP LPN-RK-70SP
LPN-RK-¤Ω¡ºSP LPN-RK-4⁄Ω™SP LPN-RK-80SP
LPN-RK-‹Ω¡ºSP LPN-RK-5SP LPN-RK-90SP
LPN-RK-›Ω¡ºSP LPN-RK-5flΩ¡ºSP LPN-RK-100SP
LPN-RK-⁄Ω™SP LPN-RK-6SP LPN-RK-110SP
LPN-RK-flΩ¡ºSP LPN-RK-6⁄Ω¢SP LPN-RK-125SP
LPN-RK-°Ω¡ºSP LPN-RK-8SP LPN-RK-150SP
LPN-RK-1SP LPN-RK-9SP LPN-RK-175SP
LPN-RK-1⁄Ω•SP LPN-RK-10SP LPN-RK-200SP
LPN-RK-1⁄Ω¢SP LPN-RK-12SP LPN-RK-225SP
LPN-RK-1›Ω¡ºSP LPN-RK-15SP LPN-RK-250SP
LPN-RK-1flΩ¡ºSP LPN-RK-17⁄Ω™SP LPN-RK-300SP
LPN-RK-1°Ω¡ºSP LPN-RK-20SP LPN-RK-350SP
LPN-RK-2SP LPN-RK-25SP LPN-RK-400SP
LPN-RK-2⁄Ω¢SP LPN-RK-30SP LPN-RK-450SP
LPN-RK-2⁄Ω™SP LPN-RK-35SP LPN-RK-500SP
LPN-RK-2°Ω¡ºSP LPN-RK-40SP LPN-RK-600SP
LPN-RK-3SP LPN-RK-45SP
LPN-RK-3¤Ω¡ºSP LPN-RK-50SP
**Meets all performance requirements of UL Standard 248-12 for Class RK1 fuses.
0-60 Amp fuses available with Albaloy plate option.
70-600 Amp fuses available with Tin plate option.
•Current limitation for maximum short-circuit protection.
High speed of response is highly sensitive to fault currents, but
insensitive to starting current and transient surges.
•Provides long time-delay for temporary motor start-up.
•Time-delay permits 125% FLA sizing for back-up, motor running
protection.
Catalog Numbers (600V AC/300V DC)
LPS-RK-⁄Ω¡ºSP LPS-RK-2⁄Ω™SP LPS-RK-12SP LPS-RK-110SP
LPS-RK-¤Ω¡ºSP LPS-RK-2°Ω¡ºSP LPS-RK-15SP LPS-RK-125SP
LPS-RK-‹Ω¡ºSP LPS-RK-3SP LPS-RK-17⁄Ω™SP LPS-RK-150SP
LPS-RK-›Ω¡ºSP LPS-RK-3¤Ω¡ºSP LPS-RK-20SP LPS-RK-175SP
LPS-RK-⁄Ω™SP LPS-RK-3⁄Ω™SP LPS-RK-25SP LPS-RK-200SP
LPS-RK-flꭧSP LPS-RK-4SP LPS-RK-30SP LPS-RK-225SP
LPS-RK-°Ω¡ºSP LPS-RK-4⁄Ω™SP LPS-RK-35SP LPS-RK-250SP
LPS-RK-1SP LPS-RK-5SP LPS-RK-40SP LPS-RK-300SP
LPS-RK-1⁄Ω•SP LPS-RK-5flΩ¡ºSP LPS-RK-45SP LPS-RK-350SP
LPS-RK-1⁄Ω¢SP LPS-RK-6SP LPS-RK-50SP LPS-RK-400SP
LPS-RK-1›Ω¡ºSP LPS-RK-6⁄Ω¢SP LPS-RK-60SP LPS-RK-450SP
LPS-RK-1⁄Ω™SP LPS-RK-7SP LPS-RK-70SP LPS-RK-500SP
LPS-RK-1flꭧSP LPS-RK-8SP LPS-RK-80SP LPS-RK-600SP
LPS-RK-1°Ω¡ºSP LPS-RK-9SP LPS-RK-90SP
LPS-RK-2⁄Ω¢SP LPS-RK-10SP LPS-RK-100SP
**Meets all performance requirements of UL Standard 248-12 for Class RK1 fuses.
Carton Quantity and Weight
LPN-RK (250 Volts AC) LPS-RK (600 Volts AC)
Ampere Carton Weight* Carton Weight*
Ratings Qty. Lbs. Kg Qty. Lbs. Kg
0-30 10 0.5 0.227 10 1.6 0.725
35-60 10 1.2 0.544 10 2.6 1.178
70-100 5 1.5 0.680 5 4.0 1.814
110-200 1 0.69 0.313 1 2.0 0.906
225-400 1 1.75 0.793 1 4.6 2.086
450-600 1 3.25 1.474 1 5.6 2.540
*Weight per carton.
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000V AC, 75-1500V DC). Refer to BIF document #8002 or contact
Bussmann Application Engineering at 636-527-1270 for more information.