1
CSM_B7AP_DS_E_3_1
Power Couplers
B7AP
Transmits Input Device ON/OFF
Signals and Power.
The Key to Effortless Wiring for
Rotating and Moving Bodies.
Be sure to read Safety Precautions
on page 5.
Features
Transmit Multiple Switch Signals and Power
to without Contact
By connecting the B7AP Power Coupler between the B7A
Input Unit and B7A Output Unit, it is possible to transmit
multiple switch signals without contact from input devices to
controllers. When using the B7AP Power Coupler in this way,
it is possible to transmit power via electromagnetic coupling,
so a power supply for the Input Unit is not necessary.
Equipped with a Verification LED for Easy
Settings
The B7AP-M1 is equipped with an operation indicator that
lights the usable range during Coupler setup, allowing for
easy setup.
Total Transmission Distance Up to 100 m
The transmission distance between Power Couplers without
contact is 8±1.5 mm. The maximum transmission distance
between the B7A Input Unit and B7A Output Unit is 100 m
(when transmitting power or signals).
Transmission Also Possible When
Separated by a Non-metallic Object
Switch signals and power can be transmitted even when there
is plastic, glass, wooden, or other non-metallic objects
between the Couplers (B7AP-S1/-M1).
B7A Output Unit
B7AP-S1 B7AP-M1
B7A Input Unit
Switch, Sensor, etc.PLC or other controller
Signal
Power
B7AP-M1B7AP-S1
B7AP-S1
B7A Output Unit
B7AP-M1
B7A Input Unit
8±1.5 mm
Total length: 100 m
B7AP-M1B7AP-S1
B7AP
2
Usable in a Variety of Environments with
IP67 Environmental Resistance
The Couplers have IP67 degree of protection, which allows
them to be used in harsh environments that may expose them
to dust from glass, plastic or paper, or exposure to water. The
Couplers can be used in a wide range of applications.
Select Transmission Method Based on
Application Conditions
When transmitting power and transmission signals, a
maximum of 10 points can be input simultaneously to the B7A
Input Unit.
(B7A Input Unit: Input Current 3.8 mA × 10 points = 38 mA)
When transmitting only signals, a maximum of 16 points can
be input to the B7A Input Unit.
Applications
Ordering Information
* The B7AP-S1 Power Coupler has a gauge that is used to adjust the transmission distance between the B7AP Power Couplers.
B7A Output Unit
B7AP-S1 B7AP-M1
B7A Input Unit
Switch, Sensor, etc.PLC or other
controller
Power
Supply
B7A Output Unit
B7AP-S1 B7AP-M1
B7A Input Unit
Switch,
Sensor, etc.
PLC or other
controller
Power
Supply
Power
Supply
Turntable Transformation Robot Hand Pallet
Proximity Sensor
B7AP
Power Couplers To B 7 A
Output Unit
B7A
Input Unit
Proximity Sensor
To B 7 A
Output Unit
B7A
Input Unit
B7AP
Power Couplers
To B 7 A
Output Unit
B7A
Input Unit
Proximity
Sensor
B7AP
Power
Couplers
To B 7 A
Output Unit
B7A
Input Unit
B7AP
Power Couplers
Classification Appearance Transmission distance (couplers) I/O transmission
delay time Model
Stationary Unit
Typical: 19.2 ms
Max: 31 ms
B7AP-S1 *
Moving Unit B7AP-M1
M30
8±1.5 mm
Stationary Unit Moving Unit
M30
B7AP
3
Ratings and Specifications
Stationary Unit Transmission Specifications
*1. The value is for when a power supply is provided only for the B7AP-S1.
*2. Minimum Coupler interfacing time is the minimum time required for signal
and power transmission between the Power Couplers.
Engineering Data (Typical)
Transmission Range
Moving Unit Specifications
Note: Use the Moving Unit so that the total current consumption of all input
devices is 38 mA max.
Specifications
Connectable B7A Models (The 10-point and 16-point High-speed B7A Models cannot be connected.)
*1. The maximum I/O points refers to the maximum I/O points handled simultaneously by the B7A Input and Output Units. Figures in
parentheses indicate the maximum I/O points handled simultaneously by the B7A Input and Output Units each connected with an
independent power supply. Refer to the Power Supplies page.
The B7AH requires two types of power supplies (24 VDC and 5 VDC), so a power supply is required for each Unit.
*2. The maximum I/O points are the same as the maximum input points of the B7A Input Unit connected to the B7AP-M1.
*3. PLCs and three-wire sensors can be connected only if the B7A Input and Output Units are each connected with independent power
supplies. Refer to the section on Power Supplies.
Item Model B7AP-S1
Transmission method Unidirectional, time-division multiplex
Transmis-
sion
distance
Between Couplers Between B7AP-S1 and -M1: 8±1.5 mm
Between Input Unit
and Output Unit
Between B7A Input and Output Units:
100 m max. *1
Transmission delay time Standard: 19.2 ms,
Maximum: 31 ms
Minimum Coupler interfacing time 0.3 s *2
Minimum distance between Pow-
er Couplers mounted in parallel 60 mm min.
Available zone
X
Y
B
12
10
8
6
4
2
0
6420246
Transmission distance X (mm)
Angle offset from center
B: 2° max.
Distance between axes Y (mm)
Item Model B7AP-M1
Power supply 12 VDC±10%, 38 mA
Item Model B7AP-S1 B7AP-M1
Power supply voltage
(operating voltage
range)
24 VDC ±10, ripple (p-p):
10% max ---
Current consumption 300 mA ---
Insulation resistance 100 M min. (at 500 VDC) between each lead wire
and external parts
Dielectric strength 1,000 VAC, 50/60 Hz for 1 min between each lead
wire and external parts
Noise immunity Noise level: ±1.5 kV, pulse width: 100 ns/1 µs
Ambient temperature
Operating: 10 to 55°C
Storage: 25 to 65°C
(with no icing or condensation)
Ambient humidity Operating/Storage: 35% to 95% (with no
condensation)
Vibration resistance
(destruction)
10 to 55 Hz, 1.5-mm double amplitude each in X,
Y, and Z directions
Shock resistance
(destruction) 500 m/s2 each in X, Y, and Z directions
Degree of protection IEC IP67
Nut tightening
strength 39 N·m
Connection method Pre-wired Models (Standard cable length: 2 m)
Cable tensile strength: 49 N
Weight (packed state) Approx. 300 g Approx. 230 g
Contact your OMRON sales representative for further
information.
B7AP Model Applicable B7A Link Terminal Max. I/O points (*1) Applicable input device (*3)
B7AP-S1
B7A-R6B31
(*2) ---
B7A-R6C31
B7A-R6F31
B7A-R6G31
B7A-R6A52
B7A-R6A33
B7A-R3A33
B7A-R3A33-M
B7AS-R6B31
B7AM-6BS
G70D-R6@@1-B7A
B7AH-R6D53
B7AP-M1
B7A-T6@1 10 (16) Two-wire sensor, contact
B7A-T6D2 10 (16)
Contact
B7A-T6E3 10 (16)
B7A-T3E3 10 (16)
B7A-T3E3-M 10 (16)
B7AS-T6B1 10 (16) Two-wire sensor, contact
B7AM-6BS 10 (16)
B7AH-T6D3 16 CMOS input is supported
B7AP
4
Connection
Power Supplies
Signal and Power Transmission (with Power Supplied to B7AP-S1)
Signal Transmission Only (with Power Supplied to B7AP-S1 and B7AP-M1)
Indicators
B7AP-S1
B7AP-M1
B7AP-M1B7AP-S1
B7A-R (Output Unit) B7A-T Input Unit
Brown
Black
Blue
Brown
Black
Blue
24 VDC±10%
SIG SIG
B7AP-M1
Transmission distance: 8±1.5 mm
B7AP-S1
Total length: 100 m max.
B7A-T
(Input Unit)
Brown
Black
Blue
Brown
Black
Blue
24 VDC±10%
B7A-R
(Output Unit)
SIG SIG
2m
(standard)
2 m
(standard)
Extension cable
(96 m max.)
Note 1. The thickness of the extension cable for
the B7AP-S1 Power Coupler must be
0.75 mm2 min.
2. No extension cable can be connected to
the B7AP-M1 Power Coupler. Use the
original 2-m cable connected to the
B7AP-M1 Power Coupler.
3. Refer to page 3, B7A Models for the
maximum input points of the B7A Input
Unit.
4. No PLC or three-wire sensor can be
connected to the B7A Input Unit.
B7AP-M1
Transmission distance: 8±1.5 mm
B7AP-S1
Total length: 500 m max.
B7A-T
(Input Unit)
Brown
Open (no connection)
Black
Blue
Brown
Black
Blue
12 to
24 VDC
±10%
B7A-R
(Output Unit)
SIG SIG
2 m
(standard)
2 m
(standard)
Extension cable
(96 m max.) Extension
cable
(400 m max.)
24 VDC±10%
Note 1. The thickness of the extension cable for
the B7AP-S1 or B7AP-M1 Power Coupler
must be 0.75 mm2 min.
2. For transmitting signals only, the brown
lead wire of the B7AP-M1 Power Coupler
must not be used. Insulate the brown
lead wire with insulation tape so that the
brown wire will not come in contact with
any lead wire.
3. The maximum input points of the B7A
Input Unit are available.
4. PLCs and three-wire sensors can be
connected to the B7A Input Unit.
Indicators Function
Power
indicator
Lit green when power is supplied to the
Power Coupler.
Not lit when power is not supplied to the
Power Coupler.
Operation
indicator
Lit green when the Power Couplers are
properly set for power transmission at a
transmission distance of 8±1.5 mm.
Not lit when the Power Couplers are not
properly set for power transmission, or
the Power Coupler has excessive loads.
Operation indicator
Operation indicator
B7AP
5
Safety Precautions
This product is not designed or rated for
ensuring safety of persons.
Do not use it for such purposes.
Be careful when touching the B7AP-S1 (Stationary Unit)
Power Coupler during operation because the surface
temperature of the B7AP-S1 Power Coupler will rise
approximately 20°C after the B7AP-S1 Power Coupler starts
power transmission. The surface temperature varies with the
load of the sensing device connected to the B7AP-M1
(Moving Unit) Power Coupler and the transmission distance.
Do not use this product under ambient conditions that exceed
the ratings.
Handling
1. Use the B7AP-S1 and B7AP-M1 Power Couplers with the
available B7A Link Terminals shown in Connectable B7A
Models on page 3.
The M7E-12@@ Display Unit, M7E-20@@ Display Unit,
B7A-T10M2, B7AC-T10A1, and 16-point High-speed
model cannot be connected to the Power Controller.
2. Use the LOAD-OFF model for the B7A Output Unit to be
connected to the B7AP-S1 Stationary Unit. The LOAD-OFF
model turns OFF all outputs when there is no transmission
between the B7AP Power Couplers.
3. The B7AP Power Couplers must be separated by at least
30 mm to prevent transmission.
4. Do not supply power to the B7AP-S1 or B7AP-M1 Power
Coupler while connecting the Power Couplers to the B7A
Link Terminals. Connect the Power Couplers to the B7A
Link Terminals correctly, otherwise the internal circuits of
the Power Couplers may be damaged.
5. The SIG terminal must not contact with the power supply
terminals, otherwise the internal element may be damaged
and normal transmission may not be possible.
6. Wire the cables of the B7AP-S1and B7AP-M1 Power
Couplers through independent metal conduits to prevent
the Power Couplers from being influenced by noise if there
are power or high-tension lines nearby. Test the Power
Couplers and make sure that the Power Couplers operate
normally before they are put in actual operation.
7. Do not subject the head of the B7AP-S1 or B7AP-M1
Power Coupler to excessive shock with hard objects.
8. Do not use the B7AP-S1 or B7AP-M1 Power Coupler
outdoors unless it is properly protected.
9. Degree of Protection
The B7AP-S1 and B7AP-M1 Power Couplers are products
meeting the requirements of IP67. (They are not fully
sealed water-tight models.) The B7AP-S1 or B7AP-M1
Power Coupler cannot be, however, used in water or oil.
10. Keep the heads of the B7AP-S1 and B7AP-M1 Power
Couplers free from dust, otherwise improper signal or
power transmission may result between the Power
Couplers.
11. When complying with UL standards, install a device
between the external power supply and the B7AP-S1 that
limits the current to 5 A.
Mounting
Use nuts and serrated toothed washers and tighten the nuts.
The torque is 39 N·m maximum. The mounting position will
change and improper signal or power transmission may result
between the Power Couplers if the nuts are not tightened
properly.
WARNING
Precautions for Safe Use
Precautions for Correct Use
B7AP-M1B7AP-S1
30 mm min.
B7A
Brown (+)
Black (SIG)
Blue ()
Black (+)
Brown (SIG)
Blue ()
Brown (+)
Black (SIG)
Blue ()
SIG
B7A
SIG
Contact
B7A
SIG
Correct
Incorrect
Incorrect
Metal conduit
Power or high-tension line
Correct Incorrect
39 N·m max.
B7AP
6
Transmission Distance for Stable Signal and Power
Transmission
Use the gauge to adjust the transmission distance to 8 mm,
make sure that the green operation indicator of the B7AP-M1
Power Coupler is lit, and the B7A Output Unit has no error
output before operating the Power Couplers.
Monitoring Transmission Status
Judge from the power supply/error indicator and error output
of the B7A Output Unit whether the B7AP-S1 and B7AP-M1
Power Couplers are facing each other properly. (Use the B7A
Output Unit power and error indicator, and error terminal.)
The error output of the B7A Output Unit will be ON when the
B7AP-S1 and B7AP-M1 Power Couplers are not facing each
other properly.
Minimum Distance between Power Couplers Mounted in
Parallel
When mounting the B7AP-S1 and B7AP-M1 Power Couplers
in parallel, refer to the following table. Keep at least the
specified minimum distance between adjacent Power
Couplers for proper heat radiation by considering the
temperature rise (approximately 20°C) of the B7AP-S1 Power
Couplers in operation.
(Unit: mm)
Effects of Surrounding Metal
The B7AP Power Coupler may malfunction when affected by
surrounding metal. When mounting the B7AP within a metal
panel, ensure that the clearances given in the following table
are maintained. Be sure to check in advance that the B7AP
operates properly.
(Unit: mm)
Maintenance
As with other control devices, regularly check the following to
ensure the long-term stable operation of the B7AP-S1 and
B7AP-M1 Power Couplers.
1. The mounting positions, misalignment, tightening of the
mounting nuts, and warping.
2. The tightening, contacts, and breaking of the lead wires.
3. Dust accumulation on the heads.
4. The ambient operating temperature and other operating
conditions.
5. The transmission distance.
Dimensions Model B7AP-S1 B7AP-M1
L6060
B7AP-M1B7AP-S1
Operation indicator
Gauge
8 mm
L
Dimensions Model B7AP-S1 B7AP-M1
L2020
d 60 dia. 60 dia.
D2020
n6060
d dia.
L
n
D
B7AP
7
(Unit: mm)
Dimensions Unless otherwise specified, the tolerance class IT16 is used for dimensions in this data sheet.
B7AP-S1
B7AP-M1
M30 × 1.5
5
98
85.3
80
13 10
27.3 dia.
36
42 dia.
Two,
clamping nuts
Toothed washer
Power indicator
6-dia. round vinyl-insulated cable
(0.5 mm2)
Standard length: 2 m
30.5+0.5
0 dia.
Mounting Holes
M30 × 1.5
5
61
48.3
43
13
27.3 dia.
36
42 dia.
30.5+0.5
0 dia.
Operation indicator
Toothed washer
Two,
clamping nuts
6-dia. round vinyl-insulated cable
(0.5 mm2)
Standard length: 2 m
Mounting Holes
In the interest of product improvement, specifications are subject to change without notice.
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
2011.7
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/