INPUT SPECIFICATIONS IAC5 IAC15 IAC24 IAC5A IAC15A IAC24A
(S)MIAC5 (S)MIAC15 (S)MIAC24 (S)MIAC5A (S)MIAC15A (S)MIAC24A
X4IAC5 X4IAC15 X4IAC24 X4IAC5A X4IAC15A X4IAC24A
Nominal input voltage [Vrms/Vdc] 120 120 120 240 240 240
Minimum Input Voltage [Vrms/Vdc] 90 90 90 180 180 180
Maximum Input Voltage [Vrms/Vdc] 140 140 140 280 280 280
Maximum Input Current [mA rms] 10 10 10 8 8 8
Drop Out Current [mA rms] 2.5 2.5 2.5 1.5 1.5 1.5
Allowable Off-state Current [mA rms] 3.0 3.0 3.0 2.0 2.0 2.0
Allowable Off-state Voltage [Vrms/Vdc] 50.0 50.0 50.0 120 120 120
OUTPUT SPECIFICATIONS
Nominal Logic Voltage [Vdc] 5 15 24 5 15 24
Minimum Logic Voltage [Vdc] (X4 Series) 1.5 (3) 8.5 (10) 16.5 (18) 1.5 (3) 8.5 (10) 16.5 (18)
Maximum Logic Voltage [Vdc] (X4 Series) 6.0 (7) 18.5 (20) 30.5 (32) 6.0 (7) 18.5 (20) 30.5 (32)
Typical Logic Supply Current [mAdc] 10 10 10 10 10 10
Max. Logic Supply Current [mAdc] 18.5 16 14 18.5 16 14
Max. Logic Sup. Leak. Current [µAdc] 10 10 10 10 10 10
Maximum Output Voltage [Vdc] 30 30 30 30 30 30
Maximum Output Current [mAdc] 50 50 50 50 50 50
Max. Output Leakage Current [µAdc] 10 10 10 10 10 10
Max. Output Voltage Drop [mVdc
]
200 200 200 200 200
Maximum Turn-on Time [msec] 20 20 20 20 20 20
Maximum Turn-off Time [msec] 30 30 30 30 30 30
Solid state I/O switching modules deliv-
er an electrically clean, photo-isolated,
noise-free "output" interface from
logic level control systems to external
loads such as motors, valves, solenoids,
etc. -- or an "input" interface from the
load or sensors to microprocessor or
computer-based logic level systems.
Designed for long, reliable service in
demanding industrial environments.
Status Indicating LED on
X4 Series
UL, CSA, and CE
SERIES IAC.
Rev. 060305
PAGE 1 OF 2
© 2003 CRYDOM CORP Specifications subject to change without notice.
For recommended applications and more information contact:
USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540
Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
Email: sales@crydom.com WEB SITE: http://www.crydom.com
UK: +44 (0)1202 365070 • FAX +44 (0)1202 365090 Crydom International Ltd., 7 Cobham
Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE, Email: intsales@crydom.com.
GERMANY: +49 (0)180 3000 506
Series IAC,
AC Input Modules
(S)MIAC, X4IAC
IAC Module for 24 Vac Input
Available (E suffix)
200
GENERAL SPECIFICATIONS
Operating temperatue ranger -30 to +80°C
Storage temperature range -40 to +100°C
Isolation 4,000 V rms
Capacitance input to output 8 pF
Line frequency range 47 to 63 Hz
Package Color Yellow
SERIES IAC.
Rev. 060305
PAGE 2 OF 2
© 2003 CRYDOM CORP Specifications subject to change without notice.
WIRING & MECHANICAL DIAGRAMS
All dimensions are in inches (millimeters)
1.25
(31.7)
.25
(6.3)
.040 (1.0) DIA.
(5 PLACES)
.70
(17.8)
1.20
(30.5)
1.40
(35.5)
1.60
(40.6)
1.70
(43.1)
.30
(7.6)
.100
(2.5)
.30
(7.6) .60
(15.2)
1.00
(25.4)
.030
(0.8)
CAPTIVE
#4-40. PHILLIPS
HEAD HOLD
DOWN SCREW
12345
BOTTOM VIEW
X4 Series, X4IAC
Standard Series, IAC
1.78
(45.2)
0.35
(8.9)
1.82
(46.2)
1.70
(43.1)
1.3
(33.0)
0.81
(20.6)
0.55
(13.9)
0.20
(5.1)
0.48
(12.2)
0.20
(5.1)
CAPTIVE
#4-40. PHILLIPS
HEAD HOLD
DOWN SCREW
0.15
(3.8)
.040 (1.0) DIA.
(5 PLACES)
LOGIC
GND
Vac/dc
OUT
1
2
3
4
5
+
-
Schmitt
Trigger
LOGIC
GND
Vac/dc
OUT
1
2
3
4
5
+
-
Schmitt
Trigger
Standard and Mini Pack X4 Series
1.00
(25.4)
.25
(6.35)
.040(1.0) DIA
(5 PLACES)
.30
(7.6)
.200
(5.1)
.700
(17.8)
1.100
(27.9)
1.30
(43.1)
.100
(2.5)
.40
(10.2)
123+5
BOTTOM VIEW
1.70
(43.1)
4
1.70
(43.1)
1.00
(25.4)
CAPTIVE
#4-40.PHILLIPS
HEAD HOLD
DOWN SCREW
MINI-PACK Series, (S)MIAC
1.00
(25.4)
.25
(6.35)
.040 (1.0) DIA.
(5 PLACES)
.30
(7.6)
.200
(5.1)
.700
(17.8)
1.100
(27.9)
1.30
(43.1)
.100
(2.5)
.40
(10.2)
123+5
BOTTOM VIEW
1.70
(43.1)
4
1.70
(43.1)
SM Prefix M Prefix
APPLICATION NOTES
¥Do not install or remove modules
in live (electrically hot) circuits.
High voltage may be present.
¥An externally located
commutating diode must be
installed across inductive loads
¥ I/O module boards also available
For recommended applications and more information contact:
USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540
Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
Email: sales@crydom.com WEB SITE: http://www.crydom.com
UK: +44 (0)1202 365070 • FAX +44 (0)1202 365090 Crydom International Ltd., 7 Cobham
Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE, Email: intsales@crydom.com.
GERMANY: +49 (0)180 3000 506
Series IAC,
AC Input Modules