Product data sheet
Characteristics
ATS22D17S6U
soft starter-ATS22-control110V-power
208V(3hp)/230V(5hp)/460V(10hp)/575V(15hp)
Product availability : Stock - Normally stocked in distribution facility
Price* : 613.00 USD
Main
Range of product Altistart 22
Product or component type Soft starter
Product destination Asynchronous motors
Product specific application Pumps and fans
Component name ATS22
Phase 3 phases
[Us] rated supply voltage 208...600 V - 15...10 %
Motor power hp 10 hp 460 V
15 hp 575 V
3 hp 208 V
5 hp 230 V
Factory setting current 14 A
Power dissipation in W 39 W for standard applications
Utilisation category AC-53A
Type of start Start with torque control (current limited to 3.5 In)
IcL starter rating 17 A connection in the motor supply line for standard applications
IP degree of protection IP20
Complementary
Assembly style With heat sink
Function available Internal bypass
Supply voltage limits 177...660 V
Supply frequency 50...60 Hz - 10...10 %
Network frequency 45...66 Hz
Device connection In the motor supply line
[Uc] control circuit voltage 110 V -15...10 % 50/60 Hz
Control circuit consumption 20 W
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Jul 13, 2019
1
Discrete output number 2
Discrete output type Relay outputs R1 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O
Relay outputs R2 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O
Minimum switching current 100 mA 12 V DC relay outputs
Maximum switching current 5 A 250 V AC resistive 1 relay outputs
5 A 30 V DC resistive 1 relay outputs
2 A 250 V AC inductive 0.4 20 ms relay outputs
2 A 30 V DC inductive 7 ms relay outputs
Discrete input number 3
Discrete input type Logic LI1, LI2, LI3 5 mA 20 kOhm
Discrete input voltage 110 V <= 121 V
Discrete input logic Positive logic LI1, LI2, LI3 < 20 V and <= 15 mA > 79 V <= 2 mA
Output current 0.4...1 Icl adjustable
PTC probe input 750 Ohm
Communication port protocol Modbus
Connector type 1 RJ45
Communication data link Serial
Physical interface RS485 multidrop
Transmission rate 4800, 9600 or 19200 bps
Installed device 31
Protection type Phase failure line
Thermal protection starter
Thermal protection motor
Marking CE
Type of cooling Forced convection
Operating position Vertical +/- 10 degree
Height 10.43 in (265 mm)
Width 5.12 in (130 mm)
Depth 6.65 in (169 mm)
Product weight 15.43 lb(US) (7 kg)
Environment
Electromagnetic compatibility Conducted and radiated emissions level A IEC 60947-4-2
Damped oscillating waves level 3 IEC 61000-4-12
Electrostatic discharge level 3 IEC 61000-4-2
Immunity to electrical transients level 4 IEC 61000-4-4
Immunity to radiated radio-electrical interference level 3 IEC 61000-4-3
Voltage/current impulse level 3 IEC 61000-4-5
Standards EN/IEC 60947-4-2
Product certifications UL
CCC
C-Tick
GOST
CSA
Vibration resistance 1.5 mm 2...13 Hz EN/IEC 60068-2-6
1 gn 13...200 Hz EN/IEC 60068-2-6
Shock resistance 15 gn 11 ms EN/IEC 60068-2-27
Noise level 45 dB
Pollution degree Level 2 IEC 60664-1
Relative humidity 0...95 % without condensation or dripping water EN/IEC 60068-2-3
Ambient air temperature for operation 14...104 °F (-10...40 °C) without derating
> 104...< 140 °F (> 40...< 60 °C) with current derating 2.2 % per °C
Ambient air temperature for storage -13...158 °F (-25...70 °C)
Operating altitude <= 3280.84 ft (1000 m) without derating
> 3280.84...< 6561.68 ft (> 1000...< 2000 m) with current derating of 2.2 % per additional 100 m
2
Ordering and shipping details
Category 22576 - ATS22 ALTISTART
Discount Schedule CP1G
GTIN 00785901687238
Nbr. of units in pkg. 1
Package weight(Lbs) 12.76
Returnability Y
Country of origin ID
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 0939 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Available
California proposition 65 WARNING: This product can expose you to chemicals including:
- - - - - - - Substance 1 Lead and lead compounds, which is known to the State of California to cause cancer and birth
defects or other reproductive harm.
- - - - - - - Substance 2 Bisphenol A (BPA), which is known to the State of California to cause birth defects or other
reproductive harm.
- - - - - - - More information For more information go to www.p65warnings.ca.gov
Contractual warranty
Warranty period 18 months
3
Product data sheet
Dimensions Drawings
ATS22D17S6U
Frame Size A
Dimensions
4
Product data sheet
Mounting and Clearance
ATS22D17S6U
Precautions
Standards
The Altistart 22 soft starter is compliant with pollution Degree 2 as defined in NEMA ICS1-1 or IEC 60664-1.
For environment pollution degree 3, install the Altistart 22 soft starter inside a cabinet type 12 or IP54.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
ATS22 soft starters are open devices and must be mounted in a suitable enclosure.
Failure to follow these instructions will result in death or serious injury.
Air Circulation
Leave sufficient free space to help the air required for cooling purposes to circulate from the bottom to the top of the unit.
Overheating
To avoid the soft starter to overheat, respect the following recommendations:
Mount the Altistart 22 Soft Starter within ± 10° of vertical.
Do not locate the Altistart 22 Soft Starter near heat radiating elements.
Electrical current through the Altistart 22 Soft Starter will result in heat losses that must be dissipated into the ambient air immediately surrounding the soft starter. To help prevent a thermal fault, provide sufficient enclosure cooling and/or ventilation to limit the ambient temperature around the soft starter.
If several soft starters are installed in a control panel, arrange them in a row. Do not stack soft starters. Heat generated from the bottom soft starter can adversely affect the ambient temperature around the top soft starter.
5
Product data sheet
Mounting and Clearance
ATS22D17S6U
Mounting
Connection Between the Fan and the Altistart 22 Soft Starter
1 Altistart 22 Soft Starter
2 Fan
6
Product data sheet
Mounting and Clearance
ATS22D17S6U
Wall mounted or Floor-standing Enclosure with IP 23 Degree of protection
Introduction
To help proper air circulation in the soft starter, grilles and forced ventilation can be installed.
Ventilation Grilles
Forced Ventilation Unit
7
Product data sheet
Connections and Schema
ATS22D17S6U
Power Terminal
Cage Style
1 Ground connection
Power connections, minimum and maximum wiring capabilities, tightening torque
IEC cable UL cable
min 2.5 mm 12 AWGSize/gauge
max 16 mm 4 AWG
min 3 N.m 26.25 lb.inTightening torque
max 3 N.m 26.25 lb.in
Power supply and output to motor
Strip length 10 mm 0.4 in.
Power connections, minimum required wiring section
IEC cable
mm² (Cu 70°C/158°F) (1)
UL cable
AWG (Cu 75°C/167°F) (1)
2.5 10
8
Product data sheet
Connections and Schema
ATS22D17S6U
110 Vac control, Logic Inputs (LI) 110 Vac, 3-wire control
9
Product data sheet
Connections and Schema
ATS22D17S6U
110 Vac control, Logic Inputs (LI) 110 Vac, 2-wire control, freewheelstop
10
Product data sheet
Performance Curves
ATS22D17S6U
Motor Thermal Protection - Cold Curves
Curves
A Class 10
B Class 20
C Class 30
Trip time for a Standard Application (Class 10)
3.5 ln
32 s
Trip time for a Severe Application (Class 20)
3.5 ln
63 s
11
Trip time for a Severe Application (Class 30)
3.5 ln
95 s
12
Product data sheet
Performance Curves
ATS22D17S6U
Motor Thermal Protection - Warm Curves
Curves
A Class 10
B Class 20
C Class 30
Trip time for a Standard Application (Class 10)
3.5 ln
16 s
Trip time for a Severe Application (Class 20)
3.5 ln
32 s
13
Trip time for a Severe Application (Class 30)
3.5 ln
48 s
14