3PCB Relay G2RL
JAPPROVED STANDARDS
UL508 (File No. E41643)/CSA C22.2 (No.14) (File No. LR31928)
Part number Contact form Coil ratings Contact ratings
G2RL-1A SPST-NO 3to48VDC 12 A at 250 VAC (General use), 100k ops.
G2RL-1 SPDT 12
at 24
DC (Resistive), 50k ops.
1/3 hp, 120 VAC, 30k ops., 60_C
G2RL-1A-E SPST-NO (High capacity) 16 A at 250 VAC (General use), 100k ops.
16 A at 24 VDC (Resistive), 50k ops.
_
G2RL-1-E SPDT (High capacity) 20
at 240
C (General use), 85_C
15 A at 240 VAC (General use), 105_C
1/2 hp, 120 VAC, 100k ops., 70_C(NO)
G2RL-2A DPST-NO 8 A at 277 VAC (General use), 100k ops.
G2RL-2 DPDT
8 A at 30 VDC (Resistive), 100k ops.
VDE (VDE0435)
Part number Contact form Coil ratings Contact ratings
G2RL 1 pole 5, 12, 18, 22, 24, 48 VDC 12 A at 250 VAC (cosφ=1)
12 A at 24 VDC (L/R=0 ms)
AC15: 3 A at 240 VAC
DC13: 2.5 A at 24 VDC, 50 ms
1 pole (High capacity) 16 A at 250 VAC (cosφ=1)
16 A at 24 VDC (L/R=0 ms)
AC15: 3 A at 240 VAC (NO)
1.5 A at 240 VAC (NC)
DC13: 2.5 A at 24 VDC (NO), 50 ms
2 poles 8 A at 250 VAC (cosφ=1)
8 A at 24 VDC (L/R=0 ms)
AC15: 1.5 A at 240 VAC
DC13: 2 A at 30 VDC, 50 ms
Note: To achieve approved life cycles on sealed models, the relay should be vented by removing “knock off vent nib” on top of relay case
after the soldering/washing process.
Electrical Life Data
Part number Contact rating Minimum operations
G2RL-1-E 16 A at 250 VAC (cosφ=1) 100,000 operations min. (1 sec. ON / 9 sec. OFF)
16 A at 24 VDC 30,000 operations min.
8 A at 250 VAC (cosφ=0.4) 200,000 operations min. (N.O. side operation)
8 A at 30 VDC (L/R=7 ms) 10,000 operations min.
G2RL-1 12 A at 250 VAC (cosφ=1) 100,000 operations min. (1 sec. ON / 9 sec. OFF)
12 A at 24 VDC 30,000 operations min.
5 A at 250 VAC (cosφ=0.4) 150,000 operations min.
5 A at 30 VDC (L/R=7 ms) 20,000 operations min.
G2RL-2 8 A at 250 VAC (cosφ=1) 100,000 operations min. (1 sec. ON / 9 sec. OFF)
8 A at 30 VDC 30,000 operations min.
G2RL-1A-E Pilot duty (A300), 250 VAC 250,000 operations min. (1 sec. ON / 9 sec OFF)
Pilot duty (A300), 125 VAC 150,000 operations min. (1 sec. ON / 9 sec OFF)
Note: 1. The results shown reflect minimum cycles using a very severe duty cycle of 1 sec ON/1 sec OFF (unless otherwise specified
above).
2. In order to obtain the full rated life cycles on the fully sealed models, the relay should be properly vented by removing the
“knock off vent nib” on top of the relay case after the soldering / washing process of the P.C.B.
Contact Omron for applications where venting of the sealed relay is not possible.