Web: www.crompton-instruments.com • Email: crompton.info@tycoelectronics.com 2002
Shunts
DIN 43703 Shunts
860 Series
Designed and manufactured to
comply with the requirements of
DIN43 703 this range of shunts
provides an accurate D.C. millivolt
signal, exactly proportional to the
system current, to drive ammeter
indicators, overload protection and
control devices.
Features
Ratings 1A up to 15000A
Shock and vibration tested
Low temperature
coefficient
Long term stability Specification
The 860 series complies with DIN43 703 for dimensions and DIN43 780 for performance.
When specified they conform to IEC51 (BS89).
Model N°: Ratings
Model 860-92 1, 1.5, 2.5, 4, 6, 10, 15,
60mV & 150mV 20 & 25A
Model 861-92 30, 40, 50, 60 75, 80, 100
60mV & 150A
Model 863-92 200, 250, 400, 500 &
60mV 600A
Model 864-92 750, 800, 1000, 1200,
60mV 1500, 2000 & 2500A
Model 868-92 4000, 5000, 6000, 8000,
10000 & 12000A
Accuracy class: 0.5
0.2 available on request
Outputs: Standard outputs are 60mV
and 150mV
Overload 1.2 x rated current
withstand: continuously
5 second 1A-500A = 10 x rated
withstand: current
501A-2000A = 5 x rated
current
2001-15000A = 2 x rated
current
Temperature 0.002% per °C overall
Coefficient:
Ambient Calibrated for 20°C the
temperature: working range is -20°C to
+60°C
Maximum load: for maximum accuracy the
load should not exceed 0.1%
of the shunt current rating
Construction
Highest quality materials, rugged design and
advanced manufacturing techniques are used
throughout. The substantial solid brass end
blocks have conservatively rated contact
surface areas and fixing hole dimensions to
DIN 43703: For maximum long term stability
and strength, copper manganese resistance
elements are both rivetted and soldered into
slots in the end blocks.
Installation
For maximum heat dissipation, mount shunts
in the horizontal plane, with the blade facing
vertical. Utilise the full end block surface
area. Ample ventilation should be provided.
Busbars should be adequately rated, clean
and level, with a thin coat of silicone grease
applied to the contact surface area. Shunts
are supplied with bolts, nuts and washers.
These must be tightened fully. Ample
ventilation should be provided.
Potential Leads
The length/resistance of leads should be
allowed for up to 25A, end blocks are
mounted on an insulated base which provides
support and protection against damage to the
resistance elements. An element cover is
fitted on ratings up to 10A.
Warning
Shunts are uninsulated and protection
against accidental contact may be necessary
in order to comply with Health & Safety
regulations.
Web: www.crompton-instruments.com • Email: crompton.info@tycoelectronics.com 2002
Shunts
DIN 43703 Shunts
860 Series
60mV Models
Form A1 Form A2 Form B Form C
1A 26A 151A 251A 601A 1001A 1501A 2501A 4001A 6001A 10001A
Rated to to to to to to to to to to to
25A 150A 250A 600A 1000A 1500A 2500A 4000A 6000A 10000A 12000A
Model N° 860 861 863 863 864 864 864 867 868 869 869
Dim
a1 90 100 145 145 165 165 165 165 175 185 185
a2 28 33 55 55 65 65 65 65 70 75 75
b1 20 20 30 40 60 90 120 120 154 206 310
b2 - - 15 20 30 21 30 30 25 25 25
b3 -----486060525252
c1 8 8 10 10 10 10 10 15 25 30 30
c2 - - 10 10 10 10 10 10 15 20 20
e 78 80 105 105 115 115 115 115 125 135 135
h - -303030303060130170170
Form A1 Form B Form C
Model N° 860 862 865 865 866 867 867 868 868 869 869
Dim
a1 90 225 270 270 290 290 290 300 300 310 310
a2 28 33 55 55 65 65 65 70 70 75 75
b1 20 25 30 40 70 90 120 120 154 206 310
b2 - - 15 20 35 21 30 30 25 25 25
b3 -----486060525252
c1 8 8 10 10 10 15 15 25 25 30 30
c2 - - 10 10 10 10 10 15 15 20 20
e 78 205 230 230 240 240 240 250 250 260 260
h - - 50 50 60 60 60 130 130 170 170
End block
bolt holes 2 x 1 2 x 1 2 x 1 2 x 1 2 x 1 2 x 2 2 x 2 2 x 2 2 x 3 2 x 4 2 x 6
Bolt size
60mV M5 x 12 M8 x 15 M12 x 40 M16 x 45 M20 x 50 M16 x 45 M20 x 50 M20 x 60 M20 x 75 M20 x 85 M20 x 85
150mV M5 x 12 M8 x 15 M12 x 40 M16 x 45 M20 x 50 M16 x 60 M20 x 60 M20 x 75 M20 x 75 M20 x 85 M20 x 85
Dimensions comply with DIN 43 703
150mV Models
Form A1
(Form A2 is without insulated base)
Insulated base model 860
Form B Form C
All voltage terminals have M5 x 8 screws and flat washers
Use flat
and lock
washers