Surge protection device-PT 2X1-VF-120AC-2859327
Technical data
Ambient conditions
Ambient temperature (operation) -40 °C ... 80 °C
Degree of protection IP20
General
Housing material PA 6.6
Inflammability class according to UL 94 V0
Color black
Standards for air and creepage distances IEC 60664-1
DIN VDE 0110-1
Surge voltage category III
Pollution degree 2
Mounting type DIN rail: 35 mm
Type DIN rail module, two-section, divisible
Number of positions 2
Direction of action Line-Line & Line-Earth Ground
Arrester can be tested with CHECKMASTER from software version: SW Version 2.13 or later
Protective circuit
IEC test classification C1
C2
C3
Nominal voltage UN120 V AC
Maximum continuous operating voltage UC175 V AC
Nominal current IN6 A
Operating effective current IC at UC≤ 2 µA
Residual current IPE ≤ 4 µA
Nominal discharge current In (8/20) µs 3 kA
Nominal discharge current In (8/20) µs (Core-Earth) 3 kA
Total surge current (8/20) µs 8 kA
Max. discharge current Imax (8/20) µs 8 kA
Nominal pulse current Ian (10/1000) µs (Core-Earth) 40 A
Impulse discharge current (10/350)˽µs, peak value limp 300 A
Output voltage limitation at 1 kV/µs (Core-Earth) static ≤ 800 V
Residual voltage at In, (conductor-ground) ≤ 600 V
Residual voltage with Ian (10/1000)µs (conductor-ground) ≤ 360 V
Energy absorption 85 J
Voltage protection level Up≤ 1 kV (C2 - 2 kA)
Voltage protection level UP (Core-Earth) ≤ 900 V (C1 - 500 A)