http://www.tracopower.com Page 3 of 6
Industrial Power Supplies
TSP-3P Series 240–960 Watt
General Specifications
Electromagnetic compatibility (EMC), Emissions EN 61000-6-3
– Conducted RI suppression on input EN 55011 class B, EN 55022 class B,
– Radiated RI suppression EN 55011 class B, EN 55022 class B,
Electromagnetic compatibility (EMC), Immunity EN 61000-6-2
– Electrostatic discharge (ESD) IEC/EN 61000-4-2 8 kV / 15 kV criteria tba
– Radiated RF field immunity IEC/EN 61000-4-3 10 V/m criteria tba
– Electrical fast transient burst immunity input IEC/EN 61000-4-4 4 kV criteria tba
burst immunity output IEC/EN 61000-4-4 2 kV criteria tba
– Surge immunity L – L IEC/EN 61000-4-5 2 kV criteria tba
L – PE IEC/EN 61000-4-5 4 kV criteria tba
+ Output – - Output IEC/EN 61000-4-5 0.5 kV criteria tba
+ Output – PE IEC/EN 61000-4-5 0.5 kV criteria tba
– Output – PE IEC/EN 61000-4-5 0.5 kV criteria tba
– Immunity to conducted RF disturbances IEC/EN 61000-4-6 10 V criteria tba
– Mains voltage dips and interruptions IEC/EN 61000-4-11
Safety standards – Information technology equipment
IEC/EN 60950-1, UL 60950-1
– Industrial control equipment UL 508 listed, CSA C22.2 No. 107.1
– Equipment for use in explosive atmospheres ATEX 94/9/EC
– Electrical equipment for machines EN 60204
– Electronic equipment for power installations EN 50178
– Safety of power transformers EN 61558-2-16
Safety approvals and – CB report for IEC 60950-1 www.tracopower.com/products/tsp3p-cb.pdf
– SIQ certificate for EN 60950-1 www.tracopower.com/products/tsp3p-siq.pdf
– II3G Ex nA nC llC T3 www.tracopower.com/products/tsp3p-atex.pdf
– UL approvals for UL 508 listed www.tracopower.com/products/tsp3p-ul508.pdf
– Curtis-Straus certificate for UL 60950-1 (2nd) www.tracopower.com/products/tsp3p-ul.pdf
– Bureau Veritas for other standards www.tracopower.com/products/tsp3p-bv.pdf
Environmental compliance – Reach www.tracopower.com/products/tsp3p-reach.pdf
– RoHS RoHS directive 2002/95/EC
Environment – Vibration acc. IEC 60068-2-6; 0.075 mm / 10 – 55 Hz,
– Shock acc. IEC 60068-2-27 11ms / 15 g
Status signals – DC-OK relay contact DC OK = contact closed at >20...22 VDC
rated: 30 VDC/1.0 A for 24 VDC models
– DC-OK indication green LED at >20...22 VDC
– Phase error indication red blinking LED if one or two phases are missing
(function only if earth is connected)
– Overload / Overtemperature red LED on at >100% nominal load (5 sec. count down
for boost power is activated)
red blinking LED at temperature shut down (manual
restart required - mains disconnect for 5 sec.)
– Automatic restart indication red blinking LED during overload recovery periode
Enclosure material aluminium (chassis) / stainless steel (cover)
Mounting – DIN-rail mounting for DIN-rails as per EN 50022-35x15/7.5
(snap-on with self-locking spring)
– Wall mounting (option) with wall mounting bracket - see page 6
Connection screw terminals
Installation instructions www.tracopower.com/products/tsp3p-inst.pdf
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.