3
Environment
Standards EN/IEC 61131-2
EN/IEC 61010-2-201
Product certifications CSA
CULus
IACS E10
RCM
Resistance to electrostatic discharge 4 kV on contact conforming to EN/IEC 61000-4-2
8 kV in air conforming to EN/IEC 61000-4-2
Resistance to electromagnetic fields 1 V/m ( 2 GHz...3 GHz) conforming to EN/IEC 61000-4-3
3 V/m ( 1.4 GHz...2 GHz) conforming to EN/IEC 61000-4-3
10 V/m ( 80 MHz...1 GHz) conforming to EN/IEC 61000-4-3
Resistance to magnetic fields 30 A/m at 50...60 Hz conforming to EN/IEC 61000-4-8
Resistance to fast transients 1 kV for serial link conforming to EN/IEC 61000-4-4
1 kV for Ethernet line conforming to EN/IEC 61000-4-4
1 kV for I/O conforming to EN/IEC 61000-4-4
2 kV for relay output conforming to EN/IEC 61000-4-4
2 kV for power lines conforming to EN/IEC 61000-4-4
Surge withstand 1 kV for relay output in differential mode conforming to EN/IEC 61000-4-5
1 kV for power lines (AC) in differential mode conforming to EN/IEC 61000-4-5
0.5 kV for power lines (DC) in differential mode conforming to EN/IEC 61000-4-5
1 kV for shielded cable in common mode conforming to EN/IEC 61000-4-5
1 kV for I/O in common mode conforming to EN/IEC 61000-4-5
2 kV for relay output in common mode conforming to EN/IEC 61000-4-5
2 kV for power lines (AC) in common mode conforming to EN/IEC 61000-4-5
1 kV for power lines (DC) in common mode conforming to EN/IEC 61000-4-5
Resistance to conducted disturbances, induced by
radio frequency fields
10 Vrms (spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz)) con-
forming to Marine specification (LR, ABS, DNV, GL)
3 Vrms (0.1...80 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
10 Vrms (0.15...80 MHz) conforming to EN/IEC 61000-4-6
Electromagnetic emission Radiated emissions conforming to EN/IEC 55011 class A 10 m, 230 MHz...1
GHz : 47 dBμV/m QP
Radiated emissions conforming to EN/IEC 55011 class A 10 m, 30...230 MHz :
40 dBμV/m QP
Conducted emissions conforming to EN/IEC 55011 power lines, 1.5...30 MHz : 63
dBμV/m QP
Conducted emissions conforming to EN/IEC 55011 power lines, 150 kHz...1.5
MHz : 79...63 dBμV/m QP
Conducted emissions conforming to EN/IEC 55011 power lines, 10...150 kHz :
120...69 dBµV/m QP
Conducted emissions conforming to EN/IEC 55011 power lines (AC), 0.5...300
MHz : 73 dBμV/m QP/60 dBμV/m AV
Conducted emissions conforming to EN/IEC 55011 power lines (AC), 0.15...0.5
MHz : 79 dBμV/m QP/66 dBμV/m AV
Immunity to microbreaks 10 ms
Ambient air temperature for operation -10...35 °C for vertical installation
-10...55 °C for horizontal installation
Ambient air temperature for storage -25...70 °C
Relative humidity 10...95 % without condensation in storage
10...95 % without condensation in operation
IP degree of protection IP20 with protective cover in place
Pollution degree <= 2
Operating altitude 0...2000 m
Storage altitude 0...3000 m
Vibration resistance 3 gn (vibration frequency: 8.4...150 Hz) on panel mounting
3.5 mm (vibration frequency: 5...8.4 Hz) on panel mounting
3 gn (vibration frequency: 8.4...150 Hz) on symmetrical rail
3.5 mm (vibration frequency: 5...8.4 Hz) on symmetrical rail
Shock resistance 15 gn (test wave duration:11 ms)