Data sheet
BLZP 5.08HC/18/180F SN OR BX Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
Germany
www.weidmueller.com
Technical data
Creation date December 21, 2020 1:26:04 PM CET
Catalogue status 08.12.2020 / We reserve the right to make technical changes. 3
Wire connection cross section AWG,
max.
AWG 12
Solid, min. H05(07) V-U 0.2 mm²
Solid, max. H05(07) V-U 4 mm²
Flexible, min. H05(07) V-K 0.2 mm²
Flexible, max. H05(07) V-K 4 mm²
w. plastic collar ferrule, DIN 46228 pt 4,
min.
0.2 mm²
w. plastic collar ferrule, DIN 46228 pt 4,
max.
2.5 mm²
w. wire end ferrule, DIN 46228 pt 1,
min.
0.2 mm²
w. wire end ferrule, DIN 46228 pt 1,
max.
4 mm²
Plug gauge in accordance with EN
60999 a x b; ø
2.8 mm x 2.4 mm
Clampable conductor Cross-section for conductor connection Type fine-wired
nominal 0.5 mm²
wire end ferrule Stripping length nominal 6 mm
Recommended wire-
end ferrule
H0,5/6
Cross-section for conductor connection Type fine-wired
nominal 1 mm²
wire end ferrule Stripping length nominal 6 mm
Recommended wire-
end ferrule
H1,0/6
Cross-section for conductor connection Type fine-wired
nominal 1.5 mm²
wire end ferrule Stripping length nominal 7 mm
Recommended wire-
end ferrule
H1,5/7
Cross-section for conductor connection Type fine-wired
nominal 2.5 mm²
wire end ferrule Stripping length nominal 7 mm
Recommended wire-
end ferrule
H2,5/7
Reference text The outside diameter of the plastic collar should not be larger than the pitch (P), Length of ferrules
is to be chosen depending on the product and the rated voltage.
Rated data acc. to IEC
tested acc. to standard
IEC 60664-1, IEC 61984
Rated current, min. number of poles
(Tu=20°C) 23 A
Rated current, max. number of poles
(Tu=20°C) 18 A
Rated current, min. number of poles
(Tu=40°C) 21 A
Rated current, max. number of poles
(Tu=40°C) 16 A
Rated voltage for surge voltage class /
pollution degree II/2 400 V
Rated voltage for surge voltage class /
pollution degree III/2 320 V
Rated voltage for surge voltage class /
pollution degree III/3 250 V
Rated impulse voltage for surge voltage
class/ pollution degree II/2 4 kV
Rated impulse voltage for surge voltage
class/ pollution degree III/2 4 kV
Rated impulse voltage for surge voltage
class/ contamination degree III/3 4 kV
Short-time withstand current resistance
3 x 1s with 120 A