ACDC
Input
Input Voltage 90-264 VAC (130-370 VDC)
Input Frequency 47-63 Hz
Input Current 2.0/1.0 A max at 115/230 VAC (JPS130)
2.6/1.3 A max at 115/230 VAC (JPS130-M)
Inrush Current 30 A at 115 VAC, 60 A at 230 VAC,
cold start at 25 °C
Power Factor 0.9 typical
Earth Leakage Current 1.5 mA max at 264 VAC/60 Hz (JPS130)
260 µA max at 275 VAC/63 Hz (JPS130-M)
Input Protection JPS130 internal T3.15 A/250 VAC fused line,
JPS130-M fused line & neutral
Output
Output Voltage See table
Output Voltage Trim ±10% on single output models,
±5% on multi output models,
auxiliary outputs will track by the same
percentage
Initial Set Accuracy At 60% rated load ±1% single outputs,
±3% on V1 for multi outputs
Minimum Load Single output: no minimum load required
Multi-outputs: (see note 1)
Start Up Rise Time <20 ms
Hold Up Time 16 ms typical at 115 VAC & rated load (JPS130)
20 ms typical at 115 VAC & rated load (JPS130-M)
Drift <±0.2% after 20 mins warm up
Line Regulation ±0.5% Vmin to Vmax
Load Regulation ±1%, ±5% for auxiliary outputs,
20%-100% of rated load
Transient Response 4% max deviation, recovery to within
1% in 500 µs for a 25% load change
Ripple & Noise ±1% max pk-pk (see note 4)
Overvoltage Protection 110-140% Vnom on V1 only,
recycle input to reset
Overload Protection 110-150%, auto recovery
Short Circuit Protection Trip & restart (hiccup mode), auto recovery
Temperature 0.05%/°C
Coefficient
Remote Sense Single output models only, compensates for
up to 0.5 V drop
Fan Output 12 V, 450 mA multi-output models only
Specification
130 Watts
High Efficiency up to 90%
Medical Approval (JPS130M Versions)
3” x 5” Footprint
100 W Convectioncooled
130 W Forcedcooled
Single & Multi Outputs
3 Year Warranty
JPS Series
xppower.com
General
Efficiency Up to 90% nominal line, full load
Isolation 3000 VAC Input to Output (JPS130),
4000 VAC Input to Output (JPS130-M
2 x MOPP), 1500 VAC Input to Ground
(JPS130-M 1 x MOPP),
500 VAC Output to Ground
Switching Frequency 120 kHz, ±10% for both active PFC & PWM
Power Density 6.7 W/In3
MTBF 200 kHrs to MIL-HDBK-217F at 50 °C, GB
Environmental
Operating Temperature 0 °C to +70 °C, (see derating curves)
Cooling JPS130PS03 83 W convection-cooling,
100 W, with 18 CFM airflow.
All others, 100 W with convection
cooling,130 W with 18 CFM airflow
Operating Humidity 5-95% RH, non-condensing
Storage Temperature -40 °C to +85 °C (JPS130)
-20 °C to +85 °C (JPS130-M)
Operating Altitude 3000 m
EMC & Safety
Emissions EN55022, Class B conducted
FCC 20780, level B conducted
EN60601-1-2, (JPS130-M)
Harmonic Currents EN61000-3-2 Class A
Voltage Flicker EN61000-3-3
ESD Immunity EN61000-4-2, level 3 contact, level 3 air,
Perf Criteria A
Radiated Immunity EN61000-4-3, 10 V/m Perf Criteria A
EFT/Burst EN61000-4-4, level 3 Perf Criteria A
Surge EN61000-4-5, Installation Class 3
Perf Criteria A
Conducted Immunity EN61000-4-6, level 2, Perf Criteria A
Dips & Interruptions EN61000-4-11, 30% 10 ms, 60% 100 ms,
95% 5000 ms Perf Criteria A, B, B
Safety Approvals JPS130: EN60950-1, UL60950-1,
CSA C22.2 No. 60950-1,
CE Mark LVD.
JPS130-M: UL60601-1, EN60601-1,
CSA C22.2 No. 601.1
CE Mark LVD.
17-Sept-12
ACDC
TB2 TB2
TB3
TB1
1
2.55 (64.8)
[2.60 (66.2) -M]
0.22 (5.7) [0.2 (5.0) -M]
-M version
0.16 (4.0) Dia Mounting Hole (4 Places)
To Chassis Grounding x 2
Voltage Trim
4.55 (115.6) [4.60 (117.0) -M]
5.00 (127.0)
3.00 (76.2)
N
L
1
1
1.18 (30.0) (1)
0.10
(2.5)
JPS130
Mechanical Details
Models and Ratings
Notes
1. 20% minimum load required on V1 to maintain stated regulation for
auxiliary rails.
2. Load regulation of auxiliary rails is defined over the range of 20%-100%
of rated load.
3. Maximum power with 18 CFM of forced air.
4. Ripple and noise measured over 15 MHz bandwidth with a 47 µF
electrolytic capacitor and 0.47 µF ceramic capacitor.
5. Covers available, order part number ‘JPS130-M COVER’ or add suffix ‘-
C’ to receive the unit with cover fitted. Overall dimensions 89.5 x 143.0 x
40.0 mm. For industrial units order part number ‘JPS130 COVER’ or add
suffix ‘-C’ to receive the unit with cover fitted. Overall dimensions 90.6 x
142.9 x 39.8 mm. Fixing screws M3, maximum penetration depth 3mm
from cover outer surface.
6. Connector kits and cable harnesses available. Consult sales for options.
All dimensions are in inches (mm).
Tolerance: 0.02 (0.4) max.
Weight: 0.5 lbs (240 g) approx.
1. Single output industrial model shown, add extra 0.08” (2.0 mm) to overall
height for multi-output models. Dimensions followed by ‘-M’ apply for
medical units (note output connector orientation).
2. AC input connector (TB1): Molex 5277-02A or equivalent. Mates with
5196-N housings/5194/5225 crimps.
3. DC output connector (TB2): Molex 5273 or equivalent, mates with 5195-N
housing/5194/5225 crimps and 5239-N housing/5167/5168/2478/2578
crimps. Except JPS130PS03 which has a 6-position terminal screw
block: Dinkle part number EHK508V Series accepts 24-12 AWG wire.
Terminal screw tightening torque 4 lbs-in (0.45 Nm) maximum.
4. TB3: Molex 5045-02A or equivalent. Mates with KK 51191
housings/50802 crimps and KK 5051 housings/2759/5159 crimps. Single
output units - TB3 is remote sense. Multi-output units - TB3 is 12 V,
450 mA fan output.
TB3 PIN CONNECTIONS
Pin Single Multi
1 - Sense 0 V
2 + Sense +12 V Fan
Output
Power(3)
Output
Voltage
Output Current Ripple & Noise
Pk-Pk(4)
Standard Model
Number
Medical Model
Number
Convection-cooled 18 CFM
100 W 3.3 V 25.0 A 30.0 A 50 mV JPS130PS03
130 W
5.0 V 20.0 A 26.0 A 50 mV JPS130PS05 JPS130PS05-M
12.0 V 9.0 A 10.8 A 120 mV JPS130PS12 JPS130PS12-M
15.0 V 7.0 A 8.7 A 120 mV JPS130PS15 JPS130PS15-M
24.0 V 4.5 A 5.4 A 200 mV JPS130PS24 JPS130PS24-M
28.0 V 3.8 A 4.6 A 200 mV JPS130PS28-M
48.0 V 2.1 A 2.7 A 200 mV JPS130PS48 JPS130PS48-M
130 W
+5.0 V(1) 11.5 A 15.0 A 50 mV
JPS130PT31+12.0 V(2) 3.0 A 5.0 A 100 mV
-12.0 V(2) 0.5 A 0.5 A 100 mV
130 W
+3.3 V(1) 10.0 A 15.0 A 50 mV
JPS130PT30+5.0 V(2) 8.0 A 15.0 A 50 mV
+12.0 V(2) 0.5 A 0.5 A 100 mV
130 W
+5.0 V(1) 10.0 A 15.0 A 50 mV
JPS130PT31-M+12.0 V(2) 3.0 A 4.1 A 120 mV
-12.0 V(2) 0.8 A 1.1 A 120 mV
130 W
+5.0 V(1) 10.0 A 15.0 A 50 mV
JPS130PT32-M+15.0 V(2) 2.5 A 4.1 A 150 mV
-15.0 V(2) 0.8 A 1.1 A 150 mV
130 W
+5.0 V(1) 2.5 A 4.0 A 50 mV
JPS130PT34-M+24.0 V(2) 2.8 A 4.0 A 240 mV
+12.0 V(2) 0.7 A 1.0 A 120 mV
JPS130-M PIN CONNECTIONS
TB2 PS05 PS 12 - 48 PT31 PT32 PT34
1 Return Return -12 V -15 V +12 V
2 Return Return +12 V +15 V +24 V
3 Return Return Return Return Return
4 Return +V Return Return Return
5 +V +V Return Return Return
6 +V +V Return Return Return
7 +V +5 V +5 V +5 V
8 +V +5 V +5 V +5 V
9 +5 V +5 V +5 V
Type *5273-08A *5273-06A *5273-09A
JPS130 PIN CONNECTIONS
TB2 PS05 PS03, 12 - 48 PT31 PT30
1 +V +V +5 V +3.3 V
2 +V +V +5 V +3.3 V
3 +V +V +5 V Return
4 +V Return Return Return
5 Return Return Return Return
6 Return Return Return Return
7 Return Return Return
8 Return +12 V +5 V
9 -12 V +5 V
10 +12 V
Type *5273-08A *5273-06A *5273-09A *5273-10A
-10 0 10 20 30 40 50 60 70
20
40
60
80
100
130
0
Ambient Temp (˚C)
A
B
C
D
Load (W)
AJPS130 and ‘-M’ with 18 CFM fan
(except JPS130PS03).
JPS130PS05, PT30, PT31, PT32 and
PT34 and ‘-M’ with convection cooling.
JPS130PS03 with convection cooling.
JPS130PS12, PS15, PS24 and PS48
and ‘-M’ with convection cooling.
JPS130PS03 with 18 CFM fan.
B
C
D
Notes
Derating Curves
* Note: MOLEX connector type