ACDC
Input
Input Voltage • 90-264 VAC (130-370 VDC)
Input Frequency • 47-63 Hz
Input Current • 2.0/1.0 A max at 115/230 VAC (JPS130)
2.6/1.3 A max at 115/230 VAC (JPS130-M)
Inrush Current • 30 A at 115 VAC, 60 A at 230 VAC,
cold start at 25 °C
Power Factor • 0.9 typical
Earth Leakage Current • 1.5 mA max at 264 VAC/60 Hz (JPS130)
260 µA max at 275 VAC/63 Hz (JPS130-M)
Input Protection • JPS130 internal T3.15 A/250 VAC fused line,
JPS130-M fused line & neutral
Output
Output Voltage • See table
Output Voltage Trim • ±10% on single output models,
±5% on multi output models,
auxiliary outputs will track by the same
percentage
Initial Set Accuracy • At 60% rated load ±1% single outputs,
±3% on V1 for multi outputs
Minimum Load • Single output: no minimum load required
Multi-outputs: (see note 1)
Start Up Rise Time • <20 ms
Hold Up Time • 16 ms typical at 115 VAC & rated load (JPS130)
20 ms typical at 115 VAC & rated load (JPS130-M)
Drift • <±0.2% after 20 mins warm up
Line Regulation • ±0.5% Vmin to Vmax
Load Regulation • ±1%, ±5% for auxiliary outputs,
20%-100% of rated load
Transient Response • 4% max deviation, recovery to within
1% in 500 µs for a 25% load change
Ripple & Noise • ±1% max pk-pk (see note 4)
Overvoltage Protection • 110-140% Vnom on V1 only,
recycle input to reset
Overload Protection • 110-150%, auto recovery
Short Circuit Protection • Trip & restart (hiccup mode), auto recovery
Temperature • 0.05%/°C
Coefficient
Remote Sense • Single output models only, compensates for
up to 0.5 V drop
Fan Output • 12 V, 450 mA multi-output models only
Specification
130 Watts
•High Efficiency up to 90%
•Medical Approval (JPS130M Versions)
•3” x 5” Footprint
•100 W Convectioncooled
•130 W Forcedcooled
•Single & Multi Outputs
•3 Year Warranty
JPS Series
xppower.com
General
Efficiency • Up to 90% nominal line, full load
Isolation • 3000 VAC Input to Output (JPS130),
4000 VAC Input to Output (JPS130-M
2 x MOPP), 1500 VAC Input to Ground
(JPS130-M 1 x MOPP),
500 VAC Output to Ground
Switching Frequency • 120 kHz, ±10% for both active PFC & PWM
Power Density • 6.7 W/In3
MTBF • 200 kHrs to MIL-HDBK-217F at 50 °C, GB
Environmental
Operating Temperature • 0 °C to +70 °C, (see derating curves)
Cooling • JPS130PS03 83 W convection-cooling,
100 W, with 18 CFM airflow.
All others, 100 W with convection
cooling,130 W with 18 CFM airflow
Operating Humidity • 5-95% RH, non-condensing
Storage Temperature • -40 °C to +85 °C (JPS130)
-20 °C to +85 °C (JPS130-M)
Operating Altitude • 3000 m
EMC & Safety
Emissions • EN55022, Class B conducted
FCC 20780, level B conducted
EN60601-1-2, (JPS130-M)
Harmonic Currents • EN61000-3-2 Class A
Voltage Flicker • EN61000-3-3
ESD Immunity • EN61000-4-2, level 3 contact, level 3 air,
Perf Criteria A
Radiated Immunity • EN61000-4-3, 10 V/m Perf Criteria A
EFT/Burst • EN61000-4-4, level 3 Perf Criteria A
Surge • EN61000-4-5, Installation Class 3
Perf Criteria A
Conducted Immunity • EN61000-4-6, level 2, Perf Criteria A
Dips & Interruptions • EN61000-4-11, 30% 10 ms, 60% 100 ms,
95% 5000 ms Perf Criteria A, B, B
Safety Approvals • JPS130: EN60950-1, UL60950-1,
CSA C22.2 No. 60950-1,
CE Mark LVD.
JPS130-M: UL60601-1, EN60601-1,
CSA C22.2 No. 601.1
CE Mark LVD.