Type MS 116
Standards: Major International IEC 60 947-4-1 / IEC 60 947-2
and European Standards EN 60 947-4-1 / EN 60 947-2
Approvals, Certificates UL, CSA
Rated insulation voltage UiV690 V AC/ 440 V DC
Acc. to IEC 158-1, IEC 60 947-4-1,
CSA, UL, NEMA
Impulse withstand voltage Uimp kV 6
Acc. to IEC 60 947-4-1
Rated operating voltage Ue 690 V AC/ 440 V DC
Rated frequency HZ 50/60
Short circuit capacity kA 10/16/30/50 (see table)
Rated current range Ie16 A
Tripping class IEC/EN 60947-4-1 10/10 A
Tripping factor 12 x In
Mechanical life time in operation switches 100.000
Permissible ambient temperature
-for storage °C -40 ... + 80
-in operation °C -25 ... + 55 (70)
Climatic resistance acc. to IEC 68-2-3, IEC 68-2-30
Mounting position Horizontal, other on request
Disconnecting feature IEC/EN 60947-1 yes
Phase failure sensitiveness IEC/EN 60947-1 yes
Permissible resistance to vibrations 10 ...100 Hz multiple of g 5
Permissible resistance to shocks 20
Resistance to shock Shock duration ms 20
Terminal types and connecting capacity
-Screw terminals (srew size) M3,5 +/- poz. 2
-Connection cross section
-single-core or stranded mm
2
2x1,0x4,0
-flexible with wire and ferrule mm
2
2x1,0x2,5
Protection degree to IEC/EN 60 947-1
All terminals are safe from finger-touch and touch by
the back of the hand in acc. with VDE 0106, Part 100
Switching frequency up to 15 ops./h or 60 ops./h with 40% on load
factor and the starting time not exceeding 1s
Required fuses for short circuit protection (back up) see Technical data II
Loads for accessories
Auxiliary contact for front mounting, HKF AC15 24 V, 3.0 A
230 V, 1.5 A
Auxiliary contact for front mounting, HKF DC13 24 V, 1.0 A
48/60 V, 0.7 A
110 V, 0.27 A
Auxiliary and Signal Contact, HK + SK AC15 24 V, 6 A
230 V, 4 A
400 V, 3.0 A
Auxiliary and Signal Contact, HK + SK DC13 24 V, 2.0 A
110 V, 0.5 A
220 V, 0.25 A
440 V, 0.1 A
Electromagnet trips
Response value set ex-works 9.6 ... 14.4 x In
Undervoltage release
Pick-up value % of U
C
• 85
Drop-out value % of U
C
35 ... 75
Power consumption Pick-up VA on request
Hold VA on request
Manual Motor Starter MS 116 up to 16 A
Technical Data
7
Caption
1 Open circuit shunt release
2 Undervoltage release
3 Undervoltage release with pre-mating
auxiliary switches 2 SV
4 Remote operating mechanism
6 Built-in auxiliary switches 1 NO + 1 NC, on MS 116
convertible from NC to NO and from NO to NC
7 Short-circuit pilot switch block 1 NO + 1 NC
8 Tripped pilot switch block (signal contact)
9 Auxiliary switches pluggable on front
10 Pilot switch for short-circuit and general tripping
Manual motor starter MS 116 with accessories
in accordance with the adjacent caption
MS 116 Dimension Drawings
MS 116 with auxiliary switch HKF 1 mounted on the front
Housing IP 65 for MS 116
8
Manual Motor Starter MS 116
Accessories
Dimension diagrams
Dimensions in mm
SST 006-00
177
85,6
45
75
HKF1-11
A9 ... A16
BEA16/116
159
85,6
45
47,5 47
52
BEA7/116
B6 / B7
HKF1-11
9918
90
81 85,6
SK1-...
HK1-...
UA1-...
HKF1-11
Manual motor starter MS 116
Manual motor starter MS 116 mounted with contactor A9...A16 Manual motor starter MS 116 mounted with mini contactor B6/7
Manual motor starter MS 116 mounted with UA1.../SK1.../HK1.../HKF1-11
9
SST11601
MS 116 with mini contactor B6
MS 116
Manual Motor Starter MS 116
Accessories
Ordering details
SST11602
Open design, enclosure IP 20, resistant to changeable climates. Quick fastening on mounting
rails DIN EN 50 022, 35 mm without auxiliary switch.
Type Setting range Order code Weight/ Packing Price
piece Unit
A...A kg piece
MS 116 with thermal and electromagnetic trips, short-circuit-proof up to 50 kA
MS 116 - 0.16 0.10 ... 0.16 1SAM 250 000 R 1001 0.268 1
MS 116 - 0.25 0.16 ... 0.25 1SAM 250 000 R 1002 0.268 1
MS 116 - 0.4 0.25 ... 0.40 1SAM 250 000 R 1003 0.268 1
MS 116 - 0.63 0.40 ... 0.63 1SAM 250 000 R 1004 0.268 1
MS 116 - 1.0 0.63 ... 1.00 1SAM 250 000 R 1005 0.268 1
MS 116 - 1.6 1.00 ... 1.60 1SAM 250 000 R 1006 0.268 1
MS 116 - 2.5 1.60 ... 2.50 1SAM 250 000 R 1007 0.268 1
MS 116 - 4 2.50 ... 4.00 1SAM 250 000 R 1008 0.268 1
MS 116 - 6.3 4.00 ... 6.30 1SAM 250 000 R 1009 0.268 1
MS 116 - 10.0 6.30 ... 10.00 1SAM 250 000 R 1010 0.268 1
MS 116 - 16.0 10.00 ... 16.00 1SAM 250 000 R 1011 0.268 1
Accessories
Type Order code Packing Price
Unit
piece
Auxillary switches, for front-panel installation
HKF1-11 1 NO + 1 NC 1SAM 201 901 R 1001 10
Auxiliary switches, lateral attechment at right
HK1-11 1 NO + 1 NC 1SAM 201 902 R 1001 10
HK1-20 2 NO 1SAM 201 902 R 1002 10
HK1-02 2 NC 1SAM 201 902 R 1003 10
Signal contakt for general “tripped” signal, lateral attachment at right
SK1-11 1 NO + 1 NC 1SAM 201 903 R 1001 10
SK1-20 2 NO 1SAM 201 903 R 1002 10
SK1-02 2 NC 1SAM 201 903 R 1003 10
Undervoltage release, lateral attachment at left
UA1-24 24 V AC 1SAM 201 904 R 1001 10
UA1-48 48 V AC 1SAM 201 904 R 1002 10
UA1-60 60 V AC 1SAM 201 904 R 1003 10
UA1-120 120 V AC 1SAM 201 904 R 1004 10
UA1-230 230 V AC 1SAM 201 904 R 1005 10
UA1-400 400 V AC 1SAM 201 904 R 1006 10
UA1-415 415 V AC 1SAM 201 904 R 1007 10
Undervoltage release with pre-mating auxiliary switch 2S, lateral attachment at left
UA1-HK-24 24 V AC 1SAM 201 905 R 1001 10
UA1-HK-48 48 V AC 1SAM 201 905 R 1002 10
UA1-HK-60 60 V AC 1SAM 201 905 R 1003 10
UA1-HK-120 120 V AC 1SAM 201 905 R 1004 10
UA1-HK-230 230 V AC 1SAM 201 905 R 1005 10
UA1-HK-400 400 V AC 1SAM 201 905 R 1006 10
UA1-HK-415 415 V AC 1SAM 201 905 R 1007 10
Locking device (see also MS 225 / MS 325, Page 9)
SA1 lock adapter GJF1 101 903 R 0001 10
SA3 locking device GJF1 101 903 R 0003 1
assy.
Direct adapter, for mounting of contactors
BEA7/116 mini contactors B6/B7 1SBN 080 906 R 1000 1
BEA16/116 contactors A9/A12/A16 1SBN 081 406 R 1000 1
BEA26/116 contactors A26 1SBN 082 406 R 1000 1
Not suitable for panel mounting
HKF 1-11
MS 116 with A-contactor
MS 116 with reversing contactor
10
Manual Motor Starter MS 116
Accessories
Ordering details
OTPA 116
enclosure IP 64
Switch cubicle mounting kit
62-00
Power infeed
block S1-M1
Power infeed
block S1-M2
Accessories
Type Order code Packing Price
Unit/piece
Phase buses for cross wiring MS 116, 63 A, 690 V
PS1-2-0,
for 2 devices without auxiliary switches
1SAM 201 906 R 1002 10
PS1-3-0,
for 3 devices without auxiliary switches
1SAM 201 906 R 1003 10
PS1-4-0,
for 4 devices without auxiliary switches
1SAM 201 906 R 1004 10
PS1-5-0,
for 5 devices without auxiliary switches
1SAM 201 906 R 1005 10
PS1-2-1,
for 2 devices with 1 auxiliary switch
1SAM 201 906 R 1012 10
PS1-3-1,
for 3 devices with 1 auxiliary switch
1SAM 201 906 R 1013 10
PS1-4-1,
for 4 devices with 1 auxiliary switch
1SAM 201 906 R 1014 10
PS1-5-1,
for 5 devices with 1 auxiliary switch
1SAM 201 906 R 1015 10
PS1-2-2,
for 2 devices with 2 auxiliary switches
1SAM 201 906 R 1022 10
PS1-3-2,
for 3 devices with 2 auxiliary switches
1SAM 201 906 R 1023 10
PS1-4-2,
for 4 devices with 2 auxiliary switches
1SAM 201 906 R 1024 10
PS1-5-2,
for 5 devices with 2 auxiliary switches
1SAM 201 906 R 1025 10
Power infeed blocks, 63 A, 690 V, stranded 25 mm2, flexible 16 mm2
S1-M1, flat 1SAM 201 907 R 1001 10
S1-M2, high 1SAM 201 907 R 1002 10
Cover for phase busses
BS1-3 1SAM 201 908 R 1001 50
Insulating enclosure light grey IP 64, with rotary handle, triple lockable in Off position,
with N- und PE-terminal, for Manual Motor Starter
OTPA 116 L2 M1, grey/black shrouded handle 1SCA 022 615 R 3860 1
OTPA 116 A2 M1, yellow/red shrouded handle 1SCA 022 615 R 3510 1
Insulating enclosure, light grey IP 55 with cover, including DIN rail
for manual motor starter or line protection devices
QES 4/3 N, for 4 modules, 72 mm GHL 111 2304 R 0013
QES 6/3 N, for 6 modules, 108 mm GHL 111 2306 R 0013
QES 10/3 N, for 10 modules, 180 mm GHL 111 2310 R 0013
Set of neutral and earth terminals
SMO 4, for QES 4/3 N GHL 430 1910 R 0004
SMO 6, for QES 6/3 N GHL 430 1910 R 0006
SMO 10, for QES 10/3 N GHL 430 1910 R 0010
Plastic enclosure, light grey, IP40 in panel design, including DIN rail
PCD 4 N, for 4 modules, 72 mm GHS 270 1921 R 0004
PCD 6 N, for 6 modules, 108 mm GHS 270 1921 R 0006
PCD 8 N, for 8 modules, 144 mm GHS 270 1921 R 0008
Set of terminals
KL-PCD 4/6, for 4/6 module enclosure GHS 270 1912 R 0004
KL-PCD 8, for 10 module enclosure GHS 270 1912 R 0008
Cover for empty module places, grey
SZ-BP 2, for 1 module, 18 mm GHL 530 1904 R 0001
SZ-BP 1, for 12 modules, GHS 270 1913 R 0002
Switch cubicle mounting kit IP 65, with axial extension
triple lockable in Off position, locked in On position
OHB2AJM, Twist knob black 1SCA 022 384 R 6940 1
OHY2AJM, Twist knob red/yellow 1SCA 022 384 R 7080 1
OXS5X 85, axis 85 mm 1SCA 022 347 R 3570 1
OXS5X105, axis 105 mm 1SCA 022 347 R 3650 1
OXS5X130, axis 130 mm 1SCA 022 353 R 4540 1
OXS5X180, axis 180 mm 1SCA 022 353 R 4620 1
MSMN, driver 1SAM 101 923 R 0001 1
MSOX, driver spindle 32 mm 1SAM 101 924 R 0001 1
For accommodating spindle and attachment to manual motor starter
Is srewed directly onto the manual motor starter
Insulating enclosure
IP 55
Plastic enclosure IP 40
11
Phase buses PS1-4-1
Phase buses PS1-2-1
ABB STOTZ-KONTAKT GmbH
P. O. Box 10 16 80
D-69006 Heidelberg
Telephone ++49 62 21 / 7 01-0
Telefax ++49 62 21 / 7 01-11 15
Internet: http://www.abb.de/stotz-kontakt
e-mail: desst.info@de.abb.com
Approvals Ships’ classification societies
CSA
Canada
USA PTB GL
Germany
LRS
Great Britain
BV
France
DNV
Norway
Test mark
Abbreviation
Validity
On your side – products and services
The MS 116 is only the smallest within a large
range of manual motor starters made by ABB.
ABB’s full motor starter line in the low voltage
range can switch and protect motors up to
100 A. Also various other components for the
increased performance of your drives and
applications are available through ABB world-
wide. E. g. various industrial relays like the ther-
mistor machine protection device Custorapid
can usefully enhance the safety of your motor.
Your local representative will be pleased to
answer all your questions on how ABB’s low
voltage products can help you in your special
case. Talk to us.
Brochure No. 1SAC 103500 D0201 Printed in the Federal Republic of Germany (07.01 · 3 · DAD)