1. Remove cover from starter.
2. Select and fit Overload (see ratings chart below).
3. Connect leads provided from - terminal 14 to Overload 95 and terminal A2 to Overload 96.
4. Check operating coil voltage and frequency.
5. Remove appropriate top/bottom knockouts. Attach conduit bushes to conduit.
6. Mount base and connect to bushes. If continuous grounding is required fit separate bonding strip
7. For on-site control circuit conversions see overleaf.
8. Connect cables and ensure that all terminations are tight.
9. When installed, set the Hand/Auto selector and adjust the current calibration to the desired value. (See below)
10. Replace cover and secure
11. Note: If an extra control device is required, see overleaf.
=
Ratings
=
Note: This product is not suitable for d.c. applications.
Terminal capacity
=
==
=
Main Auxiliary
Contactor 1 x 4mm2
or
2 x 2.5mm2
1 x 4mm2
or
2 x 2.5mm2
Overload 1 x 10mm2
or
2 x 6mm2
2 x 2.5mm2
Approximate motor rating
Order references
Coil Voltages (50Hz)
Overload
rating
Full load A 400V/3PH
AC3
230V/1PH
AC3
230V 400V
Requires
Overload
min. max. KW hp KW hp
Recommended
max. fuse size for
short circuit
protection A
TA25DU1.4
1SAZ211201R1023 1.0 1.4 0.37 0.55 0.07 0.09 4
TA25DU1.8
1SAZ211201R1025 1.3 1.8 0.55 0.75 0.1 0.125
TA25DU2.4
1SAZ211201R1028 1.7 2.4 0.75 1.0 0.18 0.25
TA25DU3.1
1SAZ211201R1031 2.2 3.1 1.1 1.5 0.25 0.33
10
TA25DU4.0
1SAZ211201R1033 2.8 4.0 1.5 2.0 0.37 0.5
TA25DU6.5
1SAZ211201R1038 4.5 6.5 2.2 3.0 0.55 0.75
20
TA25DU11
1SAZ211201R1043 7.5 11.0 4.0 5.5 1.1 1.5
122EXE0D-OL
1TVL300212E5099
124EXE0D-OL
1TVL300412E5099
TA25DU14
1SAZ211201R1045 10.0 14.0 5.5 7.5 1.5 2.0
182EXE0D-OL
1TVL300216E5099
184EXE0D-OL
1TVL300416E5099 TA25DU19
1SAZ211201R1047 13.0 19.0 7.5 10.0 2.2 3.0
35
DOL Starters Type EXE0D
Plastic Enclosure to IP66
Installation Instructions Issue 10
A direct-on-line motor starter with ingress protection to
IP66. Two-tone plastic enclosure with ABS lid and
base.
Trip class 10 requirements IEC 947-4-1
=
==
=
1.05 x FLC No tripping
1.2 x FLC Trip within 2 hours
1.5 x FLC Trip within 4 minutes
7.2 x FLC Trip between 4s and 10s
=
==
=
NOTE: FLC = Full load current
Summary
IEC947-4-1
ABB
06.012226.10E 0808