106
G5V-2G5V-2
High Sensitivity Models
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with a tolerance of ±10%.
2. Operating characteristics are measured at a coil temperature of 23°C.
3. The maximum voltage is the highest voltage that can be imposed on the relay coil.
■Contact Ratings
Note: P level: λ60 = 0.1 x 10–6/operation
This value was measured at a switching frequency of 120 operations/min and the criterion of contact resistance is 50 Ω. This value
may vary depending on the switching frequency and operating environment. Always double-check relay suitability under actual op-
erating conditions.
■Characteristics
Note: The above values are initial values.
Note: 1. The contact resistance was measured with 10 mA at 1 VDC with a voltage drop method.
2. The insulation resistance was measured with a 500-VDC megohmmeter applied to the same parts as those used for checking
the dielectric strength.
Rated voltage 3 VDC 5 VDC 6 VDC 9 VDC 12 VDC 24 VDC 48 VDC
Rated current 50 mA 30 mA 25 mA 16.7 mA 12.5 mA 8.33 mA 6.25 mA
Coil resistance 60 Ω166.7 Ω240 Ω540 Ω960 Ω2,880 Ω7,680 Ω
Coil inductance
(H) (ref. value)
Armature ON 0.18 0.46 0.70 1.67 2.90 6.72 20.1
Armature OFF 0.57 0.71 0.97 2.33 3.99 9.27 26.7
Must operate voltage 75% max. of rated voltage
Must release voltage 5% min. of rated voltage
Max. voltage 180% of rated voltage at 23°C 150% of rated
voltage at
23°C
Power consumption Approx. 150 mW Approx.
200 mW Approx.
300 mW
Item Standard models High sensitivity models
Load Resistive load (cosφ = 1)
Rated load 0.5 A at 125 VAC; 2 A at 30 VDC 0.5 A at 125 VAC; 1 A at 24 VDC
Contact material Ag + Au-clad
Rated carry current 2 A
Max. switching voltage 125 VAC, 125 VDC
Max. switching current 2 A 1 A
Max. switching power 62.5 VA, 60 W 62.5 VA, 24 W
Failure rate (reference value)
(See note.) 0.01 mA at 10 mVDC
Item Standard models High sensitivity models
Contact resistance (See note 1.) 50 mΩ max. 100 mΩ max.
Operate time 7 ms max.
Release time 3 ms max.
Max. operating frequency Mechanical: 36,000 operations/hr
Electrical: 1,800 operations/hr (under rated load)
Insulation resistance (See note 2.) 1,000 MΩ min. (at 500 VDC)
Dielectric strength 1,000 VAC, 50/60 Hz for 1 min between coil
and contacts
1,000 VAC, 50/60 Hz for 1 min between con-
tacts of different polarity
750 VAC, 50/60 Hz for 1 min between contacts
of same polarity
1,000 VAC, 50/60 Hz for 1 min between coil
and contacts
1,000 VAC, 50/60 Hz for 1 min between con-
tacts of different polarity
500 VAC, 50/60 Hz for 1 min between contacts
of same polarity
Impulse withstand voltage 1,500 V (10 x 160 µs) between coil and contacts (conforms to FCC Part 68)
Vibration resistance Destruction: 10 to 55 to 10 Hz, 0.75-mm single amplitude (1.5-mm double amplitude)
Malfunction: 10 to 55 to 10 Hz, 0.75-mm single amplitude (1.5-mm double amplitude)
Shock resistance Destruction: 1,000 m/s2 (approx. 100G)
Malfunction: 200 m/s2 (approx. 20G)
Destruction: 1,000 m/s2 (approx. 100G)
Malfunction: 100 m/s2 (approx. 10G)
Endurance Mechanical: 15,000,000 operations min. (at 36,000 operations/hr)
Electrical: 100,000 operations min. (at 1,800 operations/hr)
Ambient temperature Operating: −25°C to 65°C (with no icing) Operating: −25°C to 70°C (with no icing)
Ambient humidity Operating: 5% to 85%
Weight Approx. 5 g