SPECIFICATION
HRP-300-3.3 HRP-300-5 HRP-300-7.5 HRP-300-12 HRP-300-15 HRP-300-24 HRP-300-36 HRP-300-48
MODEL
DCVOLTAGE
RATEDCURRENT
CURRENTRANGE
RATEDPOWER
RIPPLE&NOISE(max.) Note.2
OUTPUT VOLTAGE ADJ.RANGE
VOLTAGETOLERANCE Note.3
LINEREGULATION
LOADREGULATION
SETUP,RISETIME
HOLDUP TIME (Typ.)
VOLTAGERANGE Note.5
FREQUENCY RANGE
POWERFACTOR (Typ.)
EFFICIENCY (Typ.)
INPUT
ENVIRONMENT
INRUSHCURRENT (Typ.)
LEAKAGECURRENT
OVERTEMPERATURE
SAFETY STANDARDS
HARMONICCURRENT
EMICONDUCTION&RADIATION
SAFETY &
EMSIMMUNITY
EMC
(Note4)
WITHSTANDVOLTAGE
ISOLATIONRESISTANCE
WORKINGTEMP.
WORKINGHUMIDITY
STORAGETEMP.,HUMIDITY
TEMP.COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVERVOLTAGE
PROTECTION
ACCURRENT (Typ.)
3.3V 5V 7.5V 12V 15V 24V 36V 48V
60A 60A 40A 27A 22A 14A 9A 7A
0~60A 0~60A 0~40A 0~27A 0~22A 0~14A 0~9A 0~7A
198W 300W 300W 324W 330W 336W 324W 336W
80mVp-p 90mVp-p 100mVp-p 120mVp-p 150mVp-p 150mVp-p 250mVp-p 250mVp-p
2.8~3.8V 4.3~5.8V 6.8~9V 10.2~13.8V 13.5~18V 21.6~28.8V 28.8~39.6V 40.8~55.2V
2.5% 2.0% 2.0% 1.0% 1.0% 1.0% 1.0% 1.0%
0.5% 0.5% 0.5% 0.3% 0.3% 0.2% 0.2% 0.2%
1.0% 1.0% 1.0% 0.5% 0.5% 0.5% 0.5% 0.5%
1000ms,50ms/230VAC2500ms,50ms/115VACatfullload
16ms/230VAC16ms/115VACatfullload
85~264VAC120~370VDC
47~63Hz
PF>0.95/230VACPF>0.99/115VACatfullload
6~7V 9.4~10.9V 14.4~16.8V 18.8~21.8V 30~34.8V 41.4~48.6V 57.6~67.2V
5A/115VAC2.5A/230VAC
35A/115VAC70A/230VAC
<1.2mA /240VAC
105~135%ratedoutputpower
3.96~4.62V
Protectiontype: Constantcurrentlimiting,recoversautomaticallyafterfaultconditionisremoved
Protectiontype:Shutdowno/pvoltage,re-powerontorecover
Protectiontype:Shutdowno/pvoltage,recoversautomaticallyaftertemperaturegoesdown
UL60950-1, TUVEN60950-1approved
CompliancetoEN55022(CISPR22)ClassB
Complianceto EN61000-3-2,-3
CompliancetoEN61000-4-2,3,4,5,6,8,11,ENV50204,EN55024,EN61000-6-2, heavyindustrylevel,criteria A
I/P-O/P:3KVACI/P-FG:1.5KVACO/P-FG:0.5KVAC
I/P-O/P,I/P-FG,O/P-FG:100MOhms/500VDC/25 /70%RH
-40~+70 (Refertooutputloadderatingcurve)
20~90%RHnon-condensing
-40~+85 ,10~95%RH
0.03%/ (0~50 )
10~500Hz,5G10min./1cycle,60min.eachalongX, Y,Zaxes
176Khrsmin.MIL-HDBK-217F(25 )
199*105*41mm(L*W*H)
FileName:HRP-300-SPEC2010-11-29
Features :
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Derating may be needed under low input voltages. Please check the derating curve for more details.
For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies.
(as available on http://www.meanwell.com)
HRP-300 series
300WSingleOutputwithPFCFunction
0.95Kg;15pcs/15.3Kg/0.69CUFT
80% 82% 86% 88% 88% 87% 88% 89%
DCOKSIGNAL
PSUturnson:3.3~5.6V;PSUturnsoff:0~1V
FUNCTION
100 5 for3.3V,5V,7.5V;95 5 forothers(TSW2: powerdioddetectonheatsinkof e)
90 5 (TSW1: detectonheatsinkofpowertransistor)
FANCONTROL (Typ.)
Load35 15%orRTH2 50 Fanon
http://store.iiic.cc/
AMBIENTTEMPERATURE( )
LOAD(%)
-40 0 10 20 30 40 50 60 70 (HORIZONTAL)
MechanicalSpecification CaseNo.980A Unit:mm
300WSingleOutputwithPFCFunction
FileName:HRP-300-SPEC2010-11-29
DeratingCurve OutputDeratingVSInputVoltage
INPUTVOLTAGE(V)60Hz
Ta=25
85 100 125 135 155 264
100
90
80
70
60
50
40
LOAD(%)
BlockDiagram fosc:70KHz
O.L.P.
O.T.P.
EMI INRUSH
ACTIVE
FILTER CURRENT
LIMITING
RECTIFIERS
&
PFC
I/P
FG
PWMPFC
CIRCUIT
DETECTION
POWER
SWITCHING FILTER
&
RECTIFIERS +V
+S
CONTROLCONTROL O.V.P.
-V
-S
DCOK
HR P -3 00 se r i e s
20
40
50
60
80
100
TerminalPinNo. Assignment
PinNo. PinNo.
1
2
4,5
3
6,7
Assignment Assignment
DCOUTPUT -V
DCOUTPUT +V
FG
AC/L
AC/N
HRSDF11-08DP-2DSorequivalent
ConnectorPinNo. (CN100):Assignment
PinNo.
7
8
5
3
1,2,4,6
Assignment
NC
MatingHousing
HRSDF11-8DS
orequivalent
Terminal
HRSDF11-**SC
orequivalent
+S
-S
DC-OK
GND
41
18
12.5
1
2
7
8
CN100
18 12.5
11
9.2
127.4
105
75
15
Airflow
direction
17max.
167.5
168.5
199
4-M4L=5
FAN
120
LED
SVR
12.25
168.5
12.25
12.25
4-M4L=6
12.25
167.5
4-M4L=6
42.5