Surge protection device-C-UFB-24DC-2797861
Technical data
General
Housing material Aluminum
Color black
Standards for air and creepage distances VDE 0110-1
IEC 60664-1
Mounting type Connection-specific intermediate plugging
Type Attachment plug
Direction of action Line-Shield/Earth Ground
Protective circuit
IEC test classification C2
C3
D1
Maximum continuous operating voltage UC30 V DC
Maximum continuous voltage UC (wire-ground) 30 V DC
Nominal current IN185 mA (25 °C)
Operating effective current IC at UC≤ 10 µA
Residual current IPE ≤ 10 µA
Nominal discharge current In (8/20) µs (Core-Earth) 10 kA
Nominal discharge current In (8/20) µs (Core-Shield) 10 kA
Total surge current (8/20) µs 10 kA
Max. discharge current Imax (8/20) µs maximum (Core-Earth) 10 kA
Output voltage limitation at 1 kV/µs (Core-Earth) spike ≤ 65 V
Output voltage limitation at 1 kV/µs (Core-Shield) spike ≤ 65 V
Output voltage limitation at 1 kV/µs (Core-Earth) static ≤ 45 V
Output voltage limitation at 1 kV/µs (Core-Shield) static ≤ 45 V
Residual voltage at In, (conductor-ground) ≤ 45 V
Residual voltage at In, (conductor-shield) ≤ 45 V
Voltage protection level UP (Core-Earth) ≤ 120 V (C2 - 10 kV / 5 kA)
≤ 85 V (C1 - 1 kV/500 A)
≤ 60 V (C3 - 10 A)
Voltage protection level UP (Core-Shield) ≤ 120 V (C2 - 10 kV / 5 kA)
≤ 60 V (C3 - 10 A)
≤ 85 V (C1 - 1 kV/500 A)
Voltage protection level UP static (core-ground) ≤ 50 V (C1 - 1 kV/500 A)
≤ 70 V (C2 - 10 kV / 5 kA)
Response time tA (Core-Earth) ≤ 500 ns
Response time tA (Core-GND) ≤ 500 ns