HIGH EFFICIENCY, AC/DC INSTRUMENTATION POWER SUPPLIES DMS-PS-CM Series
3
DATEL, Inc., Mansfi eld, MA 02048 (USA) • Tel: (508)339-3000, (800)233-2765 Fax: (508)339-6356 • E–mail: sales@datel.com • Internet: www.datel.com
Tehnical Notes
Ordering Information and Selection Guide
DATEL Part No. Rated Power Effi ciency ➀ V1 Output V2 Output V3 Output
DMS-PS1-CM 5 Watts 75% 5Vdc/1A — —
DMS-PS2-CM 5 Watts 73% 5Vdc/0.65A 4.85Vdc/0.2A —
DMS-PS3-CM 5 Watts 71% 5Vdc/0.35A 4.85Vdc/0.2A 4.85Vdc/0.2A
DMS-PS4-CM 10 Watts 80% 24Vdc/0.45A — —
DMS-PS5-CM 10 Watts 75% 24Vdc/0.35A 4.85Vdc/0.2A —
DMS-PS6-CM 10 Watts 73% 24Vdc/0.30A 4.85Vdc/0.2A 4.85Vdc/0.2A
DMS-PS7-CM 16 Watts 82% 24Vdc/0.70A — —
DMS-PS8-CM 16 Watts 76% 24Vdc/0.60A 4.85Vdc/0.2A —
DMS-PS9-CM 16 Watts 74% 24Vdc/0.55A 4.85Vdc/0.2A 4.85Vdc/0.2A
DMS-PS10-CM 16 Watts 82% 12Vdc/1.35A — —
1. Shock Hazard: DMS-PS-CM Series power supplies feature touch-
proof terminals blocks and fully-isolated plastic construction, thereby
greatly reducing the risk of electrical shock. However, these are mains-
powered devices whose operation is derived from hazardous and
potentially lethal voltages.
All service and installation must be performed by qualifi ed personnel,
with the ac supply voltage de-energized. Before making connections to
any of the unit’s terminal blocks, use a digital voltmeter to verify that the
ac supply is de-energized (off).
2. AC Supply Fuse (F1): All DMS-PS-CM Series power supplies are
equipped with a built-in 1A/250V time-lag fuse. Replacement fuses
must be of the same type and rating; please refer to the Functional
Specifi cations section of this datasheet for more information. F1 is
conservatively rated in order to reduce nuisance tripping which might
occur during power-up or output overload conditions. However, F1 is
primarily intended to provide protection in the event of catastrophic
failure in the DMS-PS-CM’s ac/dc converter.
IMPORTANT! To ensure safe and reliable operation, DMS-PS-CM
power supplies must be installed and serviced by qualifi ed per-
sonnel. Contact DATEL if there is any doubt regarding their instal-
lation and/or operation. Please read all of the following technical
and application notes BEFORE installing or making connections
to DMS-PS-CM power supplies.
3. Fuse Replacement: If any dc-output drops to zero volts, and no fault
conditions exist within the external load circuitry or the ac mains, F1
may have failed. F1 is located on the circuit (etch) side of the pc-board.
Fuse replacement is performed by fi rst de-energizing and then discon-
necting the ac mains from TB4. Next, disconnect all load wiring from
TB1, TB2, and TB3. Lastly, remove the four screws that secure the
pc-board to the plastic case. After making sure that the new fuse is
securely attached to its mounting clips, re-assemble the unit using all
four screws. Reconnect all input and output wiring and re-apply ac
power.
If the unit still does not operate properly, and the ac supply at TB4 is
measured to be within its specifi ed operating range, the power supply
is defective and must be replaced. Except for F1, DMS-PS-CM supplies
contain no other user-serviceable components.
4. Wire Gauges and Fusing: All wiring connected to the DMS-PS-CM’s
terminal blocks must meet the requirements specifi ed in the Functional
Specifi cations section. All ac supply and load wiring must be rated
for the voltages and currents they will conduct and must comply with
any code or application-mandated requirements pertaining to the user’s
specifi c installation. Applications subject to vibration should include
adequate strain reliefs on both input and output wiring. Install the strain
reliefs within 2-3 inches (5-7.5cm) of the terminal blocks.
It is recommended that all wiring be rated for 600V and 105°C opera-
tion (UL1015 type, for example). Also, wire insulation must be stripped
to within ±10% of the dimensions shown in Figure 2. All wires must
be inserted into their respective terminal blocks such that the screw
terminal does not pinch their insulation. No more than two wires
should be connected to any single terminal on TB1 through TB4.
If two wires are attached to a single terminal, be sure to use only two
20AWG (0.5mm2) wires on TB1, TB2, and TB3, and only two 18 or
20AWG (0.75 or 0.5mm2) wires on TB4.
Dangerous, potentially lethal voltages are present during
normal operation. Disconnect ac mains before servicing.
Reference document: IEC 417, No. 5036.
Caution, refer to accompanying documents for more information.
Reference document: ISO 3864, No. B.3.1.
Caution, unit may become hot in normal operation, thereby creat-
ing a potential burn hazard. Disconnect ac mains and then allow
unit to cool before servicing.
Reference document: IEC 417, No. 5041.
Figure 2. Insulation Strip Length
0.25"
(6.4mm)
Warnings (Marking)
➀ Effi ciency typical @120V/60Hz