LCM1000 Data Sheet
Environmental Specications
Operating temperature -40 °C to +70 °C, linear derating to 75% from 60 °C to 70 °C
Storage temperature -40 °C to +85 °C
Humidity 20 to 90%, non-condensing. Operating. Conformal coat option available
Fan noise <45 dBA, 100% load at 30C
Altitude Operating - 16,405 feet (3000m)
Storage - 30,000 feet
Shock MIL-STD-810F 516.5, Procedure I, VI. Storage
Vibration MIL-STD-810F 514.5, Cat. 4, 10. Storage
Electrical Specications
Output
Output rating See table 1 90 - 264 Vac
Set point ± 0.5% 90 - 264 Vac
Total regulation range Main output ± 2%
5 Vsb ± 1%
Combined line/load/transient when measured at output terminal
Rated load 1000 W maximum Derate linear to 50% from 50 °C to 70 °C
Minimum load Main output @ 0.0 A
5 Vsb @ 0.0 A
No loss of regulation
Output noise (PARD) 1% max p-p
50 mV max p-p
Main output
5 Vsb output
Measured with a 0.1 µF Ceramic and 10 µF Tantalum Capacitor on any output,
20 MHz
Output voltage overshoot No overshoot/undershoot outside the regulation band during on or off cycle
Transient response < 300 µSec 50% load step @ 1 A/µs
Step load valid between 10% to 100% of output rating
Recovery time to within 1% of set point at onset of transient
Max units in parallel Up to 10
Short circuit protection Protected, no damage to occur Bounce mode
Remote sense Compensation up to 500 mV
Output isolation Standard per safety requirements
Forced load sharing To within 10% of all shared outputs Analog sharing control
Overload protection (OCP) 105% to 125%
120% to 170%
Main output
5 Vsb output
Overvoltage protection (OVP) 125% to 145%
110% to 125%
12 V output
5 Vsb output
Overtemp protection 10 - 15 °C above safe operating area Both PFC and output converter monitored