Climatic proofing
Damp heat, constant, to IEC
60068−2−78
Damp heat, cyclic, to IEC
60068−2−30
Ambient temperature
Open °C −25/70
Mounting position As required
Mechanical shock resistance to
IEC 60068−2−27Shock duration
11 ms, half−sinusoidal g > 30
Terminal capacities
Solid mm20.75 – 2.5
Stranded mm20.5 – 2.5
Contacts
Rated impulse withstand voltage Uimp V AC 6000
Rated insulation voltage UiV 500
Overvoltage category/pollution
degree III3
Control circuit reliability
at 24 V DC/5 mA HFFault
probability < 10−7, < 1 fault in 107
operations
at 5 V DC/1 mA HFFault
probability < 5 × 10−6, < 1 fault in 5 ×
106 operations
Max. short−circuit protective
device
Fuseless Type PKZM0–10/FAZ−B6/1
Fuse gG/gL A 10
Switching capacity
Rated operational current
AC–15
115 V IeA 6
230 V IeA 6
400 V IeA 4
500 V IeA 2
DV−13
24 V IeA 3
42 V IeA 1,7
60 V IeA 1,2
110 V IeA 0,8
220 V IeA 0,3
Lifespan, electrical
2