Control of 3-phase network
As soon as the phase sequence (L1 L2 L3) and phase amplitude symmetry (D < 30 %) are considered correct, the contact of the output relay closes and, subject to the result of the temperature
check, LED''R2''lights up.
In case of total failure or a drop in the amplitude of a phase (absence of phase with regeneration) or inversion of the phase sequence, the contact of the output relay opens and LED "R2" is
extinguished.
Temperature control without latching
As soon as it is verified that the resistance of the thermal detector is between 15 and 3,100
Ω
, the contact of the output relay closes and, subject to the result of the phase control check,
LED''R1''lights up.
If the resistance of the thermal detector circuit exceeds 3,100
Ω
, the output relay opens and LED "R1" is extinguished. After an overheating fault, the resistance must fall below 1,650
Ω
for the
output relay contact to reclose and, subject to the result of the phase check, LED "R1" to light up.
If the resistance falls below 15
Ω
(short-circuit), the output relay opens and LED "R1" is extinguished. As soon as it returns to between 15 and 3,100
Ω
, the contact of the output relay closes again
and, subject to the result of the phase control check, LED''R1''lights up.
Control of 3-phase network
As soon as the phase sequence (L1 L2 L3) and phase amplitude symmetry (D < 30 %) are considered correct, the contact of the output relay closes and, subject to the result of the temperature
check, LED''R2''lights up.
In case of total failure or a drop in the amplitude of a phase (absence of phase with regeneration) or inversion of the phase sequence, the contact of the output relay opens and LED "R2" is
extinguished.
Temperature control without latching
As soon as it is verified that the resistance of the thermal detector is between 15 and 3,100
Ω
, the contact of the output relay closes and, subject to the result of the phase control check,
LED''R1''lights up.
If the resistance of the thermal detector circuit exceeds 3,100
Ω
, the output relay opens and LED "R1" is extinguished. After an overheating fault, the resistance must fall below 1,650
Ω
for the
output relay contact to reclose and, subject to the result of the phase check, LED "R1" to light up.
If the resistance falls below 15
Ω
(short-circuit), the output relay opens and LED "R1" is extinguished. As soon as it returns to between 15 and 3,100
Ω
, the contact of the output relay closes again
and, subject to the result of the phase control check, LED''R1''lights up.
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected