EMD-FL-3V-690 Order No.: 2885249
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2885249
PHOENIX CONTACT Inc., USA Page 2 / 5
http://www.phoenixcon.com Feb 3, 2011
The operating states are indicated using colored LEDs, errors that may occur can be sent to a control system via a
floating contact or can shut down a part of the system. Some device versions are equipped with startup and response
delays in order to briefly tolerate measured values outside the set monitoring range.
Technical data
Input data
Nominal input voltage UN3 ~ 690 V
Maximum temperature coefficient < 0.1 %/K
Function Undervoltage, window, asymmetry, phase sequence, phase
failure
Min. setting range -30 % ... 20 % (From UN)
Max. setting range -20 % ... 30 % (From UN)
Min setting range of the voltage threshold value 483 V AC ... 828 V AC
Max. setting range of the voltage threshold value 552 V AC ... 897 V AC
Setting range for response delay 0.1 s ... 10 s
Basic accuracy ± 5 % (of scale end value)
Setting accuracy ≤ 5 % (of scale end value)
Repeat accuracy ≤ 2 %
Asymmetry 5% ... 25% / OFF
Recovery time 500 ms
Contact side
Contact type 2 floating PDT contacts
Maximum switching voltage 250 V AC (in acc. with IEC 60664-1)
Interrupting rating (ohmic load) max. 750 VA (3 A/250 V AC, module aligned, ≤ 5 mm spacing)
1250 VA (5 A/250 V AC, module not aligned, ≥ 5 mm spacing)
Output fuse 5 A (fast-blow)
Power supply
Supply voltage range 110 V AC ... 500 V AC (see Power modules)
General data
Width 45 mm
Height 90 mm
Depth 113 mm
Mechanical service life Approx. 2 x 107 cycles
Operating mode 100% operating factor