PRODUCT SPECIFICATION 1 (3)
Prepared (also subject responsible if other) No.
EMINTAO 1/1301-BMR 630/7 Uen
Approved Checked Date Rev Reference
SEC/D (Julia You) 2009-2-25 D
Key Features
Industry standard Half-brick
61.00 x 57.90 x 12.70 mm (2.40 x 2.28 x 0.50 in.)
High efficiency, typ. 91.5 % at 30.2Vout half load
1500 Vdc input to output isolation
Meets isolation requirements equivalent to basic
insulation according to IEC/EN/UL 60950
3 million hours predicted MTBF
General Characteristics
Output over-voltage protection
Input under-voltage shutdown
Over temperature protection
Output short-circuit protection
Remote sense
Remote control
Output voltage adjust function
Highly automated manufacturing ensures quality
ISO 9001/14001 certified supplier
Safety Approvals Design for Environment
Meets requirements in high-
temperature lead-free soldering
processes.
Limited Internal
TABLE OF CONTENTS 1 (1)
Prepared (also subject responsible if other) No.
EMINTAO 001 52-EN/LZT 146 367 Uen
Approved Checked Date Rev Reference
SEC/D (Julia You) 2009-2-25 F
Contents
General Information ............................................................. 2
Safety Specification ............................................................. 3
Absolute Maximum Ratings ............................................................. 4
Product Program Ordering No.
28.2V,11A / 310W Electrical Specification PKJ 4316 PI ......................................... 5
28.2V/12.4A / 350W Electrical Specification PKJ 4316 API ...................................... 8
30.2V/8.3A / 250W Electrical Specification PKJ 4216N PI .................................... 11
28.2V/8.3A /230W Electrical Specification PKJ 4216 PI ........................................ 14
EMC Specification ........................................................... 18
Operating Information ........................................................... 19
Thermal Consideration ........................................................... 20
Connections ........................................................... 22
Mechanical Information ........................................................... 23
Soldering Information ........................................................... 24
Delivery Information ........................................................... 24
Product Qualification Specification ........................................................... 25
E
PKJ 4000 RFPA series Direct Converters
Input 36-75 V, Output up to 12.4 A / 350 W
EN/LZT 146 367 R3B September 2009
© Ericsson AB
Technical Specification
Ericsson Internal
PRODUCT SPECIFICATION 2 (3)
Prepared (also subject responsible if other) No.
EMINTAO 1/1301-BMR 630/7 Uen
Approved Checked Date Rev Reference
SEC/D (Julia You) 2009-2-25 D
General Information
Ordering Information
See Contents for individual product ordering numbers.
Option Suffix Ordering No.
Non-threaded standoff
Lead length 3.69 mm(0.145 in)
M
LA
PKJ 4316 PIM
PKJ 4316 PILA
Note: As an example a non-threaded standoff, short pin product would be
PKJ 4316 PIMLA.
Reliability
The Mean Time Between Failure (MTBF) is calculated at
full output power and an operating ambient temperature
(T
A
) of +40°C, which is a typical condition in Information
and Communication Technology (ICT) equipment. Different
methods could be used to calculate the predicted MTBF
and failure rate which may give different results. Ericsson
Power Modules currently uses Telcordia SR332.
Predicted MTBF for the series is:
- 3 million hours according to Telcordia SR332, issue 1,
Black box technique.
Telcordia SR332 is a commonly used standard method
intended for reliability calculations in ICT equipment. The
parts count procedure used in this method was originally
modelled on the methods from MIL-HDBK-217F, Reliability
Predictions of Electronic Equipment. It assumes that no
reliability data is available on the actual units and devices
for which the predictions are to be made, i.e. all predictions
are based on generic reliability parameters.
Compatibility with RoHS requirements
The products are compatible with the relevant clauses and
requirements of the RoHS directive 2002/95/EC and have a
maximum concentration value of 0.1% by weight in
homogeneous materials for lead, mercury, hexavalent
chromium, PBB and PBDE and of 0.01% by weight in
homogeneous materials for cadmium.
Exemptions in the RoHS directive utilized in Ericsson
Power Modules products include:
- Lead in high melting temperature type solder (used to
solder the die in semiconductor packages)
- Lead in glass of electronics components and in
electronic ceramic parts (e.g. fill material in chip
resistors)
- Lead as an alloying element in copper alloy containing
up to 4% lead by weight (used in connection pins made
of Brass)
Quality Statement
The products are designed and manufactured in an
industrial environment where quality systems and methods
like ISO 9000, 6σ (sigma), and SPC are intensively in use
to boost the continuous improvements strategy. Infant
mortality or early failures in the products are screened out
and they are subjected to an ATE-based final test.
Conservative design rules, design reviews and product
qualifications, plus the high competence of an engaged
work force, contribute to the high quality of our products.
Warranty
Warranty period and conditions are defined in Ericsson
Power Modules General Terms and Conditions of Sale.
Limitation of Liability
Ericsson Power Modules does not make any other
warranties, expressed or implied including any warranty of
merchantability or fitness for a particular purpose (including,
but not limited to, use in life support applications, where
malfunctions of product can cause injury to a person’s
health or life).
E
PKJ 4000 RFPA series Direct Converters
Input 36-75 V, Output up to 12.4 A / 350 W
EN/LZT 146 367 R3B September 2009
© Ericsson AB
Technical Specification
2
Ericsson Internal
PRODUCT SPECIFICATION 3 (3)
Prepared (also subject responsible if other) No.
EMINTAO 1/1301-BMR 630/7 Uen
Approved Checked Date Rev Reference
SEC/D (Julia You) 2009-2-25 D
Safety Specification
General information
Ericsson Power Modules DC/DC converters and DC/DC
regulators are designed in accordance with safety
standards IEC/EN/UL60950, Safety of Information
Technology Equipment.
IEC/EN/UL60950 contains requirements to prevent injury
or damage due to the following hazards:
Electrical shock
Energy hazards
Fire
Mechanical and heat hazards
Radiation hazards
Chemical hazards
On-board DC-DC converters are defined as component
power supplies. As components they cannot fully comply
with the provisions of any Safety requirements without
“Conditions of Acceptability”. It is the responsibility of the
installer to ensure that the final product housing these
components complies with the requirements of all
applicable Safety standards and Directives for the final
product.
Component power supplies for general use should comply
with the requirements in IEC60950, EN60950 and
UL60950 “Safety of information technology equipment”.
There are other more product related standards, e.g.
IEEE802.3af “Ethernet LAN/MAN Data terminal equipment
power”, and ETS300132-2 “Power supply interface at the
input to telecommunications equipment; part 2: DC”, but all
of these standards are based on IEC/EN/UL60950 with
regards to safety.
Ericsson Power Modules DC/DC converters and DC/DC
regulators are UL60950 recognized and certified in
accordance with EN60950.
The flammability rating for all construction parts of the
products meets requirements for V-0 class material
according to IEC 60695-11-10.
The products should be installed in the end-use equipment,
in accordance with the requirements of the ultimate
application. Normally the output of the DC/DC converter is
considered as SELV (Safety Extra Low Voltage) and the
input source must be isolated by minimum Double or
Reinforced Insulation from the primary circuit (AC mains) in
accordance with IEC/EN/UL60950.
Isolated DC/DC converters
It is recommended that a slow blow fuse with a rating twice
the maximum input current per selected product be used at
the input of each DC/DC converter. If an input filter is used
in the circuit the fuse should be placed in front of the input
filter.
In the rare event of a component problem in the input filter
or in the DC/DC converter that imposes a short circuit on
the input source, this fuse will provide the following
functions:
Isolate the faulty DC/DC converter from the input
power source so as not to affect the operation of
other parts of the system.
Protect the distribution wiring from excessive
current and power loss thus preventing hazardous
overheating.
The galvanic isolation is verified in an electric strength test.
The test voltage (V
iso
) between input and output is
1500 Vdc or 2250 Vdc for 60 seconds (refer to product
specification).
Leakage current is less than 1 µA at nominal input voltage.
24 V DC systems
The input voltage to the DC/DC converter is SELV (Safety
Extra Low Voltage) and the output remains SELV under
normal and abnormal operating conditions.
48 and 60 V DC systems
If the input voltage to Ericsson Power Modules DC/DC
converter is 75 Vdc or less, then the output remains SELV
(Safety Extra Low Voltage) under normal and abnormal
operating conditions.
Single fault testing in the input power supply circuit should
be performed with the DC/DC converter connected to
demonstrate that the input voltage does not exceed
75 Vdc.
If the input power source circuit is a DC power system, the
source may be treated as a TNV2 circuit and testing has
demonstrated compliance with SELV limits and isolation
requirements equivalent to Basic Insulation in accordance
with IEC/EN/UL60950.
Non-isolated DC/DC regulators
The input voltage to the DC/DC regulator is SELV (Safety
Extra Low Voltage) and the output remains SELV under
normal and abnormal operating conditions.
E
PKJ 4000 RFPA series Direct Converters
Input 36-75 V, Output up to 12.4 A / 350 W
EN/LZT 146 367 R3B September 2009
© Ericsson AB
Technical Specification
3
Ericsson Internal
PRODUCT SPECIFICATION 1 (6)
Prepared (also subject responsible if other) No.
EGLANDY 2/1301-BMR 630 01/7 Uen
Approved Checked Date Rev Reference
SEC/D (Betty Wu) EQUENXU 2009-02-12 E
Absolute Maximum Ratings
Characteristics min typ max Unit
T
ref
Operating Temperature (see Thermal Consideration section) -40 +120 °C
T
S
Storage temperature -55 +125 °C
V
I
Input voltage -0.5 +80 V
V
iso
Isolation voltage (input to output test voltage) 1500 Vdc
V
tr
Input voltage transient (t
p
100 ms) 100 V
Positive logic option -0.5 20 V
V
RC
Remote Control pin voltage
(see Operating Information section) Negative logic option 20 V
V
adj
Adjust pin voltage (see Operating Information section) -0.5 28 V
Stress in excess of Absolute Maximum Ratings may cause permanent damage. Absolute Maximum Ratings, sometimes referred to as no destruction limits, are
normally tested with one parameter at a time exceeding the limits of Output data or Electrical Characteristics. If exposed to stress above these limits, function and
performance may degrade in an unspecified manner.
Fundamental Circuit Diagram
+In
-In
RC
-Out
+Out
Vadj
-Sense
+Sense
Primary Secondary
Control
Isolated
Feedback
E
PKJ 4000 RFPA series Direct Converters
Input 36-75 V, Output up to 12.4 A / 350 W
EN/LZT 146 367 R3B September 2009
© Ericsson AB
Technical Specification
4
Ericsson Internal
PRODUCT SPECIFICATION 2 (6)
Prepared (also subject responsible if other) No.
EGLANDY 2/1301-BMR 630 01/7 Uen
Approved Checked Date Rev Reference
SEC/D (Betty Wu) EQUENXU 2009-02-12 E
28.2 V/11 A Electrical Specification PKJ 4316 PI
T
ref
= -40 to +90ºC, V
I
= 35 to 75 V, unless otherwise specified under Conditions.
Typical values given at: T
ref
= +25°C, V
I
= 53 V, max I
O
, unless otherwise specified under Conditions.
Characteristics
Conditions
min
typ
max
Unit
V
I
Input voltage range 35 75 V
V
Ioff
Turn-off input voltage Decreasing input voltage 30 33.5 35 V
V
Ion
Turn-on input voltage Increasing input voltage 32 34.5 36 V
C
I
Internal input capacitance 10
µ
F
P
O
Output power Output voltage initial setting 0 310 W
SVR Supply voltage rejection (ac) f = 100 Hz sinewave, 1 Vp-p 40 dB
50 % of max I
O
91.0
max I
O
,
T
ref
= +25°C 88.8 89
50 % of max I
O
, V
I
= 48 V 91.0
η Efficiency
max I
O
, V
I
= 48 V,
T
ref
= +25°C 88.8 89
%
P
d
Power Dissipation max I
O
,
T
ref
= +25°C 38.3 39.4 W
P
li
Input idling power I
O
= 0, V
I
= 53 V 3 W
P
RC
Input standby power V
I
= 53 V (turned off with RC) 150 mW
f
s
Switching frequency 0 -100% of max I
O
190 210 230 kHz
Output voltage initial setting and
accuracy T
ref
= +25°C, V
I
= 53 V, I
O
= 12.4 A 27.93 28.2 28.47 V
V
Oi
Output adjust range See operation information& see
Note 1 19.74 30.17 V
Output voltage tolerance band 10-100% of max I
O
27.85 28.55 V
Idling voltage I
O
= 0 27.92 28.48 V
Line regulation max I
O
80 mV
V
O
Load regulation V
I
= 53 V, 1-100% of max I
O
80 mV
V
tr
Load transient
voltage deviation ±1000 mV
t
tr
Load transient recovery time
V
I
= 53 V, Load step 25-75-25 % of
max I
O
, di/dt = 0.2 A/
µ
s,
40 µs
t
r
Ramp-up time
(from 1090 % of V
Oi
)
8 ms
t
s
Start-up time
(from V
I
connection to 90% of V
Oi
)
10-100% of max I
O
12 ms
I
O
Output current 0 11 A
I
lim
Current limit threshold T
ref
< max T
ref
11.8 16 A
I
sc
Short circuit current T
ref
= 25ºC 18 A
V
Oac
Output ripple & noise See ripple & noise section,
max I
O
, V
Oi
70 250 mVp-p
OVP Over Voltage Protection T
ref
= +25°C, V
I
= 53 V, I
O
= 0-100%
of max I
O
34.7 39.5 V
Note 1:The module can be trimmed down 30% and trimmed up 7% at all temperature condition.
The module can be trimmed down 40% at 25°C and minimum reference temperature. At least 10% of normal output current is suggested when it is
trimmed down 40% at maximum reference temperature. The module can be trimmed up 10% at 25°C and minimum reference temperature. When input
voltage below 48V, at most 65% of normal output current is suggested in case it is trimmed up 10% at maximum reference temperature.
Note 2:
V
O
=<0.5 V
E
PKJ 4000 RFPA series Direct Converters
Input 36-75 V, Output up to 12.4 A / 350 W
EN/LZT 146 367 R3B September 2009
© Ericsson AB
Technical Specification
5
Ericsson Internal
PRODUCT SPECIFICATION 3 (6)
Prepared (also subject responsible if other) No.
EGLANDY 2/1301-BMR 630 01/7 Uen
Approved Checked Date Rev Reference
SEC/D (Betty Wu) EQUENXU 2009-02-12 E
28.2 V/11 A Typical Characteristics
PKJ 4316 PI
Efficiency Power Dissipation
70
75
80
85
90
95
024681012[A]
[%]
36 V
48 V
53 V
75 V
0
10
20
30
40
50
024681012[A]
[W]
36 V
48 V
53 V
75 V
Efficiency vs. load current and input voltage at T
ref
= +25°C Dissipated power vs. load current and input voltage at
T
ref
= +25°C
Output Characteristics Current Limit Characteristics
28.00
28.10
28.20
28.30
28.40
28.50
024681012[A]
[V]
36 V
48 V
53 V
75 V
0.00
6.00
12.00
18.00
24.00
30.00
6 8 10 12 14 16 [A]
[V]
36 V
48 V
53 V
75 V
O
utput voltage vs. load current at T
ref
= +25°C
O
utput voltage vs. load current at I
O
> max I
O
, T
ref
= +25°C
E
PKJ 4000 RFPA series Direct Converters
Input 36-75 V, Output up to 12.4 A / 350 W
EN/LZT 146 367 R3B September 2009
© Ericsson AB
Technical Specification
6
Ericsson Internal
PRODUCT SPECIFICATION 4 (6)
Prepared (also subject responsible if other) No.
EGLANDY 2/1301-BMR 630 01/7 Uen
Approved Checked Date Rev Reference
SEC/D (Betty Wu) EQUENXU 2009-02-12 E
28.2 V/11 A Typical Characteristics PKJ 4316 PI
Start-up Shut-down
Start-up enabled by connecting V
I
at:
T
ref
= +25°C, V
I
= 53 V,
I
O
= 11 A resistive load.
Top trace: output voltage (10 V/div.).
Bottom trace: input voltage (20 V/div.).
Time scale: (10 ms/div.).
Shut-down enabled by disconnecting V
I
at:
T
ref
= +25°C, V
I
= 53 V,
I
O
= 11 A resistive load.
Top trace: output voltage (10 V/div.).
Bottom trace: input voltage (20 V/div.).
Time scale: (2 ms/div.).
Output Ripple & Noise Output Load Transient Response
Output voltage ripple at:
T
ref
= +25°C, V
I
= 53 V,
I
O
= 11 A resistive load.
Trace: output voltage (20 mV/div.).
Time scale: (2 µs/div.).
Output voltage response to load current step-
change (2.75-8.25-2.75 A) at:
T
ref
=+25°C, V
I
= 53 V.
Top trace: output voltage (500 mV/div.).
Bottom trace: load current (10 A/div.).
Time scale: (0.1 ms/div.).
Output Voltage Adjust (see operating information)
Passive adjust
The resistor value for an adjusted output voltage is calculated by
using the following equations:
Output Voltage Adjust Upwards, Increase:
(
)
×+
×
+
=%
%2100
%5.2
%100
10 o
V
adj
R
k
Output Voltage Adjust Downwards, Decrease:
(
)
2
%
100
10
=
adj
R
k
Example: Increase 4% =>V
out
= 29.33 Vdc
(
)
×+
×
+
4
42100
45.2
4100
2.2810
k
= 2663 k
Example: Decrease 2% =>V
out
= 27.64 Vdc
(
)
2
2
100
10
k
=480 k
E
PKJ 4000 RFPA series Direct Converters
Input 36-75 V, Output up to 12.4 A / 350 W
EN/LZT 146 367 R3B September 2009
© Ericsson AB
Technical Specification
7
Ericsson Internal
PRODUCT SPECIFICATION 5 (6)
Prepared (also subject responsible if other) No.
EGLANDY 2/1301-BMR 630 01/7 Uen
Approved Checked Date Rev Reference
SEC/D (Betty Wu) EQUENXU 2009-02-12 E
28.2 V/11 A Typical Characteristics PKJ 4316 PI
Output Current Derating – Base Plate Thermal Resistance – Base Plate
0
3
6
9
12
0 20 40 60 80 100 [°C]
[A]
3.0 m/s
2.5 m/s
2.0 m/s
1.5 m/s
1.0 m/s
Nat. Conv.
0
1
2
3
4
0.0 0.5 1.0 1.5 2.0 2.5 3.0 [m/s]
[°C/W]
Available load current vs. ambient air temperature and airflow at
V
I
= 53 V. See Thermal Consideration section.
Thermal resistance vs. airspeed measured at the converter. Tested in wind
tunnel with airflow and test conditions as per
the Thermal consideration section. V
I
= 53 V.
Output Current Derating – Cold wall sealed box
0
3
6
9
12
0 20 40 60 80 100 [°C]
[A]
Tamb 85 C
Tamb 35 C
Available load current vs. base plate temperature.
V
I
= 53 V. See Thermal Consideration section.
E
PKJ 4000 RFPA series Direct Converters
Input 36-75 V, Output up to 12.4 A / 350 W
EN/LZT 146 367 R3B September 2009
© Ericsson AB
Technical Specification
8
Ericsson Internal
PRODUCT SPECIFICATION 2 (6)
Prepared (also subject responsible if other) No.
EGLANDY 2/1301-BMR 630 03/7 Uen
Approved Checked Date Rev Reference
SEC/D (Betty Wu) ESECZHW 2009-09-07 F
28.2 V/12.4 A Electrical Specification PKJ 4316 API
Tref = -40 to +90ºC, VI = 35 to 75 V, unless otherwise specified under Conditions.
Typical values given at: Tref = +25°C, VI= 53 V, max IO , unless otherwise specified under Conditions.
Characteristics Conditions min typ max Unit
VI Input voltage range 35 75 V
VIoff Turn-off input voltage Decreasing input voltage 31 32.2 33 V
VIon Turn-on input voltage Increasing input voltage 32.5 34 35 V
CI Internal input capacitance 10 µF
PO Output power Output voltage initial setting 0 350 W
SVR Supply voltage rejection (ac) f = 100 Hz sinewave, 1 Vp-p 40 dB
50 % of max IO 91.0
max IO 88 89
50 % of max IO , VI = 48 V 91.0
η Efficiency
max IO, VI = 48 V 88 89
%
Pd Power Dissipation max IO, Tref = +25°C 41.0 44.1 W
Pli Input idling power IO= 0, VI = 53 V 3 W
PRC Input standby power VI = 53 V (turned off with RC) 150 mW
fs Switching frequency 0 -100% of max IO 190 210 230 kHz
Output voltage initial setting and
accuracy Tref = +25°C, VI = 53 V, IO = 12.4 A 27.93 28.2 28.47 V
VOi
Output adjust range See operation information & see
Note 1 19.74 30.17 V
Output voltage tolerance band 10-100% of max IO 27.85 28.55 V
Idling voltage IO = 0 27.92 28.48 V
Line regulation max IO 80 mV
VO
Load regulation VI = 53 V, 0-100% of max IO 80 mV
Vtr Load transient
voltage deviation ±1000 mV
ttr Load transient recovery time
VI = 53 V, Load step 25-75-25 % of
max IO, di/dt = 0.2 A/µs,
40 µs
tr Ramp-up time
(from 1090 % of VOi) 10 ms
ts
Start-up time
(from VI connection to 90% of
VOi)
10-100% of max IO
13 ms
IO Output current 0 12.4 A
Ilim Current limit threshold Tref < max Tref 13 19.5 A
Isc Short circuit current Tref = 25ºC, see Note 2 20.5 A
VOac Output ripple & noise See ripple & noise section,
max IO, VOi 70 250 mVp-p
OVP Over Voltage Protection Tref = +25°C, VI = 53 V, IO = 0-100%
of max IO 34.7 39.5 V
Note 1:The module can be trimmed down 30% and trimmed up 7% at all temperature condition.
The module can be trimmed down 40% at 25°C and minimum reference temperature. At least 10% of normal output current is suggested when it is
trimmed down 40% at maximum reference temperature. The module can be trimmed up 10% at 25°C and minimum reference temperature. When input
voltage below 48V, at most 65% of normal output current is suggested in case it is trimmed up 10% at maximum reference temperature.
Note 2: VO =<0.5 V
E
PKJ 4000 RFPA series Direct Converters
Input 36-75 V, Output up to 12.4 A / 350 W
EN/LZT 146 367 R3B September 2009
© Ericsson AB
Technical Specification
9
Ericsson Internal
PRODUCT SPECIFICATION 3 (6)
Prepared (also subject responsible if other) No.
EGLANDY 2/1301-BMR 630 03/7 Uen
Approved Checked Date Rev Reference
SEC/D (Betty Wu) ESECZHW 2009-09-07 F
28.2 V/12.4 A Typical Characteristics PKJ 4316 API
Efficiency Power Dissipation
70
75
80
85
90
95
03691215[A]
[%]
36 V
48 V
53 V
75 V
0
10
20
30
40
50
0 3 6 9 12 15 [A]
[W]
36 V
48 V
53 V
75 V
Efficiency vs. load current and input voltage at Tref = +25°C Dissipated power vs. load current and input voltage at
Tref = +25°C
Output Characteristics Current Limit Characteristics
28.10
28.15
28.20
28.25
28.30
03691215[A]
[V]
36 V
48 V
53 V
75 V
0.00
6.00
12.00
18.00
24.00
30.00
6 8 10 12 14 16 18 [A]
[V]
36 V
48 V
53 V
75 V
Output voltage vs. load current at Tref = +25°C Output voltage vs. load current at IO > max IO , Tref = +25°C
E
PKJ 4000 RFPA series Direct Converters
Input 36-75 V, Output up to 12.4 A / 350 W
EN/LZT 146 367 R3B September 2009
© Ericsson AB
Technical Specification
10
Ericsson Internal
PRODUCT SPECIFICATION 4 (6)
Prepared (also subject responsible if other) No.
EGLANDY 2/1301-BMR 630 03/7 Uen
Approved Checked Date Rev Reference
SEC/D (Betty Wu) ESECZHW 2009-09-07 F
28.2 V/12.4 A Typical Characteristics PKJ 4316 API
Start-up Shut-down
Start-up enabled by connecting VI at:
Tref = +25°C, VI = 53 V,
IO = 12.4 A resistive load.
Top trace: output voltage (10 V/div.).
Bottom trace: input voltage (50 V/div.).
Time scale: (5 ms/div.).
Shut-down enabled by disconnecting VI at:
Tref = +25°C, VI = 53 V,
IO = 12.4 A resistive load.
Top trace: output voltage (10 V/div.).
Bottom trace: input voltage (50 V/div.).
Time scale: (5 ms/div.).
Output Ripple & Noise Output Load Transient Response
Output voltage ripple at:
Tref = +25°C, VI = 53 V,
IO = 12.4 A resistive load.
Trace: output voltage (20 mV/div.).
Time scale: (2 µs/div.).
Output voltage response to load current step-
change (3.1-9.3-3.1 A) at:
Tref =+25°C, VI = 53 V.
Top trace: output voltage (1 V/div.).
Bottom trace: load current (5 A/div.).
Time scale: (0.1 ms/div.).
Output Voltage Adjust (see operating information)
Passive adjust
The resistor value for an adjusted output voltage is calculated by
using the following equations:
Output Voltage Adjust Upwards, Increase:
(
)
×+
×
+
=%%2100
%5.2 %100
10 o
V
adj
R k
Output Voltage Adjust Downwards, Decrease:
(
)
2
%
100
10
=
adj
R k
Example: Increase 4% =>Vout = 29.33 Vdc
(
)
×+
×
+
442100
45.2 4100
2.2810 k =2663 k
Example: Decrease 2% =>Vout = 27.64 Vdc
(
)
2
2
100
10 k=480 k
Active adjust
The output voltage may be adjusted using a voltage applied to the
Vadj pin. This voltage is calculated by using the following equations:
×+= o
Vo
VVdesired
Vadj 55.2 V
Example: Upwards => 29.33V
×+ 2.28 2.2833.29
55.2 =2.7V
Example: Downwards => 27.07V
×+ 2.28 2.2807.27
55.2 =2.3V
E
PKJ 4000 RFPA series Direct Converters
Input 36-75 V, Output up to 12.4 A / 350 W
EN/LZT 146 367 R3B September 2009
© Ericsson AB
Technical Specification
11
Ericsson Internal
PRODUCT SPECIFICATION 5 (6)
Prepared (also subject responsible if other) No.
EGLANDY 2/1301-BMR 630 03/7 Uen
Approved Checked Date Rev Reference
SEC/D (Betty Wu) ESECZHW 2009-09-07 F
28.2 V/12.4 A Typical Characteristics PKJ 4316 API
Output Current Derating – Base Plate Thermal Resistance – B ase Plate
0
3
6
9
12
15
0 20 40 60 80 100 C]
[A]
3.0 m/s
2.5 m/s
2.0 m/s
1.5 m/s
1.0 m/s
Nat. Conv.
0
1
2
3
4
0.00.51.01.52.02.53.0[m/s]
[°C/W]
Available load current vs. ambient air temperature and airflow at
VI = 53 V. See Thermal Consideration section.
Thermal resistance vs. airspeed measured at the converter. Tested in
wind tunnel with airflow and test conditions as per
the Thermal consideration section. VI = 53 V.
Output Current Derating – Cold w all sealed box
0
3
6
9
12
15
0 20 40 60 80 100 [°C]
[A]
Tamb 85 C
Tamb 35 C
Available load current vs. base plate temperature.
VI = 53 V. See Thermal Consideration section.
E
PKJ 4000 RFPA series Direct Converters
Input 36-75 V, Output up to 12.4 A / 350 W
EN/LZT 146 367 R3B September 2009
© Ericsson AB
Technical Specification
12
Ericsson Internal
PRODUCT SPECIFICATION 2 (6)
Prepared (also subject responsible if other) No.
EGLANDY 2/1301-BMR 630 04/7 Uen
Approved Checked Date Rev Reference
SEC/D (Betty Wu) EQUENXU 2009-02-12 D
30.2 V/8.3 A Electrical Specification PKJ 4216N PI
T
ref
= -40 to +90ºC, V
I
= 35 to 75 V, unless otherwise specified under Conditions.
Typical values given at: T
ref
= +25°C, V
I
= 53 V, max I
O
, unless otherwise specified under Conditions.
Characteristics
Conditions
min
typ
max
Unit
V
I
Input voltage range 35 75 V
V
Ioff
Turn-off input voltage Decreasing input voltage 30 33.5 35 V
V
Ion
Turn-on input voltage Increasing input voltage 32 34.5 36 V
C
I
Internal input capacitance 10 µF
P
O
Output power Output voltage initial setting 0 250 W
SVR Supply voltage rejection (ac) f = 100 Hz sinewave, 1 Vp-p 40 dB
50 % of max I
O
91.5
max I
O
90.5 91.0
50 % of max I
O
, V
I
= 48 V 91.5
η Efficiency
max I
O
, V
I
= 48 V 90.5 91.0
%
P
d
Power Dissipation max I
O
,
T
ref
= +25°C 24.7 26.2 W
P
li
Input idling power I
O
= 0, V
I
= 53 V 3 W
P
RC
Input standby power V
I
= 53 V (turned off with RC) 150 mW
f
s
Switching frequency 0 -100% of max I
O
190 210 230 kHz
Output voltage initial setting and
accuracy T
ref
= +25°C, V
I
= 53 V, I
O
= 8.3 A 29.95 30.2 30.45 V
V
Oi
Output adjust range See operation information & see
Note 1 21.14 30.95 V
Output voltage tolerance band 10-100% of max I
O
29.90 30.50 V
Idling voltage I
O
= 0 29.90 30.50 V
Line regulation max I
O
100 mV
V
O
Load regulation V
I
= 53 V, 1-100% of max I
O
100 mV
V
tr
Load transient
voltage deviation ±1000 mV
t
tr
Load transient recovery time
V
I
= 53 V, Load step 25-75-25 % of
max I
O
, di/dt = 1 A/µs,
40 µs
t
r
Ramp-up time
(from 1090 % of V
Oi
) 8 ms
t
s
Start-up time
(from V
I
connection to 90% of
V
Oi
)
10-100% of max I
O
12 ms
I
O
Output current 0 8.3 A
I
lim
Current limit threshold T
ref
< max T
ref
8.7 14.2 A
I
sc
Short circuit current T
ref
= 25ºC, see Note 2 15.8 A
V
Oac
Output ripple & noise See ripple & noise section,
max I
O
, V
Oi
200 250 mVp-p
OVP Over Voltage Protection T
ref
= +25°C, V
I
= 53 V, I
O
= 0-100%
of max I
O
34 40 V
Note 1:The module can be trimmed down 30% and trimmed up 2.5% at all temperature condition.
The module can be trimmed down 40% at 25°C and minimum reference temperature. At least 10% of normal output current is suggested when it is
trimmed down 40% at maximum reference temperature. At most 10% of normal output current is suggested when it is trimmed up 10% at all
temperature condition.
Note 2:
V
O
=<0.5 V
E
PKJ 4000 RFPA series Direct Converters
Input 36-75 V, Output up to 12.4 A / 350 W
EN/LZT 146 367 R3B September 2009
© Ericsson AB
Technical Specification
13
Ericsson Internal
PRODUCT SPECIFICATION 3 (6)
Prepared (also subject responsible if other) No.
EGLANDY 2/1301-BMR 630 04/7 Uen
Approved Checked Date Rev Reference
SEC/D (Betty Wu) EQUENXU 2009-02-12 D
30.2 V/8.3 A Typical Characteristics
PKJ 4216N PI
Efficiency Power Dissipation
70
75
80
85
90
95
0246810[A]
[%]
36 V
48 V
53 V
75 V
0
5
10
15
20
25
30
0246810[A]
[W]
36 V
48 V
53 V
75 V
Efficiency vs. load current and input voltage at T
ref
= +25°C Dissipated power vs. load current and input voltage at
T
ref
= +25°C
Output Characteristics
Current Limit Characteristics
30.00
30.10
30.20
30.30
30.40
30.50
0246810[A]
[V]
36 V
48 V
53 V
75 V
0.00
8.00
16.00
24.00
32.00
4 6 8 10121416[A]
[V]
36 V
48 V
53 V
75 V
Output voltage vs. load current at T
ref
= +25°C Output voltage vs. load current at I
O
> max I
O
, T
ref
= +25°C
E
PKJ 4000 RFPA series Direct Converters
Input 36-75 V, Output up to 12.4 A / 350 W
EN/LZT 146 367 R3B September 2009
© Ericsson AB
Technical Specification
14
Ericsson Internal
PRODUCT SPECIFICATION 4 (6)
Prepared (also subject responsible if other) No.
EGLANDY 2/1301-BMR 630 04/7 Uen
Approved Checked Date Rev Reference
SEC/D (Betty Wu) EQUENXU 2009-02-12 D
30.2 V/8.3 A Typical Characteristics PKJ 4216N PI
Start-up Shut-down
Start-up enabled by connecting V
I
at:
T
ref
= +25°C, V
I
= 53 V,
I
O
= 8.3 A resistive load.
Top trace: output voltage (10 V/div.).
Bottom trace: input voltage (20 V/div.).
Time scale: (10 ms/div.).
Shut-down enabled by disconnecting V
I
at:
T
ref
= +25°C, V
I
= 53 V,
I
O
= 8.3 A resistive load.
Top trace: output voltage (10 V/div.).
Bottom trace: input voltage (20 V/div.).
Time scale: (2 ms/div.).
Output Ripple & Noise Output Load Transient Response
Output voltage ripple at:
T
ref
= +25°C, V
I
= 53 V,
I
O
= 8.3 A resistive load.
Trace: output voltage (50 mV/div.).
Time scale: (2 µs/div.).
Output voltage response to load current step-
change (3-6-3 A) at:
T
ref
=+25°C, V
I
= 53 V.
Top trace: output voltage (500 mV/div.).
Bottom trace: load current (5 A/div.).
Time scale: (0.1 ms/div.).
Output Voltage Adjust (see operating information)
Passive adjust
The resistor value for an adjusted output voltage is calculated by
using the following equations:
Output Voltage Adjust Upwards, Increase:
()
×+
×
+
=%
%2100
%5.2
%100
10 o
V
adj
R
k
Output Voltage Adjust Downwards, Decrease:
(
)
2
%
100
10
=
adj
R
k
Example: Increase 4% =>V
out
= 31.41 Vdc
()
×+
×
+
4
42100
45.2
4100
2.3010
k
= 2871 k
Example: Decrease 2% =>V
out
= 29.60 Vdc
(
)
2
2
100
10
k
=480 k
E
PKJ 4000 RFPA series Direct Converters
Input 36-75 V, Output up to 12.4 A / 350 W
EN/LZT 146 367 R3B September 2009
© Ericsson AB
Technical Specification
15
Ericsson Internal
PRODUCT SPECIFICATION 5 (6)
Prepared (also subject responsible if other) No.
EGLANDY 2/1301-BMR 630 04/7 Uen
Approved Checked Date Rev Reference
SEC/D (Betty Wu) EQUENXU 2009-02-12 D
30.2 V/8.3 A Typical Characteristics
PKJ 4216N PI
Output Current Derating – Base Plate Thermal Resistance – Base Plate
0
2
4
6
8
10
0 20 40 60 80 100 [°C]
[A]
3.0 m/s
2.5 m/s
2.0 m/s
1.5 m/s
1.0 m/s
Nat. Conv.
0
1
2
3
4
0.0 0.5 1.0 1.5 2.0 2.5 3.0 [m/s]
[°C/W]
Available load current vs. ambient air temperature and airflow at
V
I
= 53 V. See Thermal Consideration section.
Thermal resistance vs. airspeed measured at the converter. Tested in
wind tunnel with airflow and test conditions as per
the Thermal consideration section. V
I
= 53 V.
Output Current Derating – Cold wall sealed box
0
2
4
6
8
10
0 20 40 60 80 100 [°C]
[A]
Tamb 85 C
Tamb 35 C
Available load current vs. base plate temperature.
V
I
= 53 V. See Thermal Consideration section.
E
PKJ 4000 RFPA series Direct Converters
Input 36-75 V, Output up to 12.4 A / 350 W
EN/LZT 146 367 R3B September 2009
© Ericsson AB
Technical Specification
16
Ericsson Internal
PRODUCT SPECIFICATION 2 (6)
Prepared (also subject responsible if other) No.
EGLANDY 2/1301- BMR 630 05/7 Uen
Approved Checked Date Rev Reference
SEC/D (Betty Wu) EQUENXU 2009-02-12 D
28.2 V,8.3 A/234W Electrical Specification PKJ 4216 PI
T
ref
= -40 to +90ºC, V
I
= 35 to 75 V, sense pins connected to output pins unless otherwise specified under Conditions.
Typical values given at: T
ref
= +25°C, V
I
= 53 V
I
max I
O
, unless otherwise specified under Conditions.
Characteristics Conditions min typ max Unit
V
I
Input voltage range 35 75 V
V
Ioff
Turn-off input voltage Decreasing input voltage 30 32.5 35 V
V
Ion
Turn-on input voltage Increasing input voltage 32 34.5 36 V
C
I
Internal input capacitance 10
µ
F
P
O
Output power Output voltage initial setting 0 234 W
50 % of max I
O
91.4
max I
O
90.8
50 % of max I
O
, V
I
= 48 V 91.5
η Efficiency
max I
O
, V
I
= 48 V 90.8
%
P
d
Power Dissipation max I
O
23.7 27.5 W
P
li
Input idling power I
O
= 0 A, V
I
= 53 V 2 W
P
RC
Input standby power V
I
= 53 V (turned off with RC) 0.20 W
f
s
Switching frequency 0-100 % of max I
O
190 210 230 kHz
V
Oi
Output voltage initial setting and
accuracy T
ref
= +25°C, V
I
= 53 V, I
O
= 8.3 A 27.92 28.20 28.48 V
Output adjust range See operating information 19.74 31.02 V
Output voltage tolerance band 10-100 % of max I
O
27.64 28.76 V
Idling voltage I
O
= 0 A 27.64 28.76 V
Line regulation max I
O
10 50 mV
V
O
Load regulation V
I
= 53 V, 0-100 % of max I
O
10 50 mV
V
tr
Load transient
voltage deviation ±1200 ±1800 mV
t
tr
Load transient recovery time
V
I
= 53 V, Load step 25-75-25 % of
max I
O
, di/dt = 0.2 A/
µ
s 40 100 µs
t
r
Ramp-up time
(from 1090 % of V
Oi
)
3 8 15 ms
t
s
Start-up time
(from V
I
connection to 90 % of V
Oi
)
10-100 % of max I
O
6 12 20 ms
max I
O
0.1 0.2 0.4
m
s
t
f
V
I
shut-down fall time
(from V
I
off to 10 % of V
O
)
I
O
= 0 A 0.2 0.4 0.8 s
RC start-up time max I
O
13 ms
max I
O
0.4 ms
t
RC
RC shut-down fall time
(from RC
off to 10 % of V
O
)
I
O
= 0 A 0.4 s
I
O
Output current 0 8.3 A
I
lim
Current limit threshold T
ref
< max T
ref
9.5 12 16 A
I
sc
Short circuit current T
ref
= 25ºC, see Note 1 13 17 A
V
Oac
Output ripple & noise See ripple & noise section,
max I
O
, V
Oi
50 250 mVp-p
OVP Over voltage protection T
ref
= +25°C, V
I
= 53 V, 0-100 % of
max I
O
35 37 39 V
Note 1:The module can be trimmed down 30% and trimmed up 10% at all temperature condition.
The module can be trimmed down 40% at 25°C and minimum reference temperature. At least 10% of normal output current is suggested when it is
trimmed down 40% at maximum reference temperature.
Note 2:
V
O
=<0.5 V
E
PKJ 4000 RFPA series Direct Converters
Input 36-75 V, Output up to 12.4 A / 350 W
EN/LZT 146 367 R3B September 2009
© Ericsson AB
Technical Specification
17
Ericsson Internal
PRODUCT SPECIFICATION 3 (6)
Prepared (also subject responsible if other) No.
EGLANDY 2/1301- BMR 630 05/7 Uen
Approved Checked Date Rev Reference
SEC/D (Betty Wu) EQUENXU 2009-02-12 D
28.2 V,8.3 A/234W Typical Characteristics PKJ 4216 PI
Efficiency Power Dissipation
70
75
80
85
90
95
02468[A]
[%]
36 V
48 V
53 V
75 V
0
5
10
15
20
25
30
02468[A]
[W]
36 V
48 V
53 V
75 V
Efficiency vs. load current and input voltage at T
ref
= +25°C Dissipated power vs. load current and input voltage at
T
ref
= +25°C
Output Characteristics Current Limit Characteristics
28.10
28.15
28.20
28.25
28.30
28.35
02468[A]
[V]
36 V
48 V
53 V
75 V
0.00
8.00
16.00
24.00
32.00
4 6 8 10121416[A]
[V]
36 V
48 V
53 V
75 V
O
utput voltage vs. load current at T
ref
= +25°C
O
utput voltage vs. load current at I
O
> max I
O
, T
ref
= +25°C
E
PKJ 4000 RFPA series Direct Converters
Input 36-75 V, Output up to 12.4 A / 350 W
EN/LZT 146 367 R3B September 2009
© Ericsson AB
Technical Specification
18
Ericsson Internal
PRODUCT SPECIFICATION 4 (6)
Prepared (also subject responsible if other) No.
EGLANDY 2/1301- BMR 630 05/7 Uen
Approved Checked Date Rev Reference
SEC/D (Betty Wu) EQUENXU 2009-02-12 D
28.2 V,8.3 A/234W Typical Characteristics PKJ 4216 PI
Start-up Shut-down
Start-up enabled by connecting V
I
at:
T
ref
= +25°C, V
I
= 53 V,
I
O
= 8.3 A resistive load.
Top trace: output voltage (10 V/div.).
Bottom trace: input voltage (20 V/div.).
Time scale: (5 ms/div.).
Shut-down enabled by disconnecting V
I
at:
T
ref
= +25°C, V
I
= 53 V,
I
O
= 8.3 A resistive load.
Top trace: output voltage (10V/div.).
Bottom trace: input voltage (20 V/div.).
Time scale: (0.1 ms/div.).
Output Ripple & Noise Output Load Transient Response
Output voltage ripple at:
T
ref
= +25°C, V
I
= 53 V,
I
O
= 8.3 A resistive load.
Trace: output voltage (20 mV/div.).
Time scale: (2 µs/div.).
Output voltage response to load current step-
change (2.1-6.2-2.1 A) at:
T
ref
=+25°C, V
I
= 53 V.
Top trace: output voltage (1.0 V/div.).
Bottom trace: load current (5 A/div.).
Time scale: (0.1 ms/div.).
Output Voltage Adjust (see operating information)
Passive adjust
The resistor value for an adjusted output voltage is calculated by
using the following equations:
Output Voltage Adjust Upwards, Increase:
(
)
×+
×
+
=%
%2100
%5.2
%100
10 o
V
adj
R
k
Output Voltage Adjust Downwards, Decrease:
2
%
100
10
=
adj
R
k
Example: Increase 4% =>V
out
= 29.33 Vdc
()
×+
×
+
4
42100
45.2
4100
2.2810 k = 2663 k
Example: Decrease 2% =>V
out
= 27.64 Vdc
(
)
2
2
100
10 k=480 k
E
PKJ 4000 RFPA series Direct Converters
Input 36-75 V, Output up to 12.4 A / 350 W
EN/LZT 146 367 R3B September 2009
© Ericsson AB
Technical Specification
19
Ericsson Internal
PRODUCT SPECIFICATION 5 (6)
Prepared (also subject responsible if other) No.
EGLANDY 2/1301- BMR 630 05/7 Uen
Approved Checked Date Rev Reference
SEC/D (Betty Wu) EQUENXU 2009-02-12 D
28.2 V,8.3 A/234W Typical Characteristics PKJ 4216 PI
Output Current Derating – Base Plate Thermal Resistance – Base Plate
0
2
4
6
8
10
0 20 40 60 80 100 C]
[A]
3.0 m/s
2.5 m/s
2.0 m/s
1.5 m/s
1.0 m/s
Nat. Conv.
0
1
2
3
4
5
0.00.51.01.52.02.53.0
[m/s]
[°C/W]
Available load current vs. ambient air temperature and airflow at
V
I
= 53 V. See Thermal Consideration section.
Thermal resistance vs. airspeed measured at the converter. Tested in
wind tunnel with airflow and test conditions as per
the Thermal consideration section. V
I
= 53 V.
Output Current Derating – Cold wall sealed box
0
2
4
6
8
10
0 20 40 60 80 100 [°C]
[A]
Tamb 85 C
Tamb 35 C
Available load current vs. base plate temperature.
V
I
= 53 V. See Thermal Consideration section.
E
PKJ 4000 RFPA series Direct Converters
Input 36-75 V, Output up to 12.4 A / 350 W
EN/LZT 146 367 R3B September 2009
© Ericsson AB
Technical Specification
20
Ericsson Internal
PRODUCT SPECIFICATION 1 (6)
Prepared (also subject responsible if other) No.
EGLANDY 3/1301-BMR 630 03/7 Uen
Approved Checked Date Rev Reference
SEC/D (Betty Wu) EQUENXU 2009-02-16 C
EMC Specification
Conducted EMI measured according to EN55022, CISPR 22
and FCC part 15J (see test set-up). See Design Note 009 for
further information. The fundamental switching frequency is
210 kHz for PKJ 4316 API @ VI = 53 V, max IO.
Conducted EMI Input terminal value (typ)
EMI without filter
External filter (class B)
Required external input filter in order to meet class B in
EN 55022, CISPR 22 and FCC part 15J.
Filter components:
C1=120pF
C2,3,4 = 2 μF
C5 = 33 μF
C6,7 = 2.2 nF
L1 = 1 μH
L2,3 = 0.809 μH
Common mode
inductor
EMI with filter
Test set-up
Layout recommendations
The radiated EMI performance of the Product will depend on
the PCB layout and ground layer design. It is also important to
consider the stand-off of the product. If a ground layer is used,
it should be connected to the output of the product and the
equipment ground or chassis.
A ground layer will increase the stray capacitance in the PCB
and improve the high frequency EMC performance.
Output ripple and noise
Output ripple and noise measured according to figure below.
See Design Note 022 for detailed information.
Output ripple and noise test setup
E
PKJ 4000 RFPA series Direct Converters
Input 36-75 V, Output up to 12.4 A / 350 W
EN/LZT 146 367 R3B September 2009
© Ericsson AB
Technical Specification
21
Ericsson Internal
PRODUCT SPECIFICATION 2 (6)
Prepared (also subject responsible if other) No.
EGLANDY 3/1301-BMR 630 03/7 Uen
Approved Checked Date Rev Reference
SEC/D (Betty Wu) EQUENXU 2009-02-16 C
Operating information
Input Voltage
The input voltage range 35 to 75Vdc meets the requirements
of the European Telecom Standard ETS 300 132-2 for normal
input voltage range in –48 and –60 Vdc systems, -40.5 to -
57.0 V and –50.0 to -72 V respectively.
At input voltages exceeding 75 V, the power loss will be higher
than at normal input voltage and Tref must be limited to
absolute max +120°C. The absolute maximum continuous
input voltage is 80 Vdc.
Turn-off Input Voltage
The DC/DC converters monitor the input voltage and will turn
on and turn off at predetermined levels.
The minimum hysteresis between turn on and turn off input
voltage is 1V.
Remote Control (RC)
The products are fitted with a
remote control function referenced
to the primary negative input
connection (- In), with negative and
positive logic options available. The
RC function allows the product to
be turned on/off by an external
device like a semiconductor or
mechanical switch. The RC pin has
an internal pull up resistor to + In.
The maximum required sink current is 1 mA. When the RC pin
is left open, the voltage generated on the RC pin is
3.5 – 6.0 V. The standard product is provided with “negative
logic” remote control and will be off until the RC pin is
connected to the -In. To turn on the product the voltage
between RC pin and -In should be less than 1V. To turn off the
converter the RC pin should be left open, or connected to a
voltage higher than 4 V referenced to -In. In situations where it
is desired to have the product to power up automatically
without the need for control signals or a switch, the RC pin can
be wired directly to -In.
See Design Note 021 for detailed information.
Input and Output Impedance
The impedance of both the input source and the load will
interact with the impedance of the product. It is important that
the input source has low characteristic impedance. The
products are designed for stable operation without external
capacitors connected to the input or output. The performance
in some applications can be enhanced by addition of external
capacitance as described under External Decoupling
Capacitors.
If the input voltage source contains significant inductance, the
addition of a 22 - 100 µF capacitor across the input of the
product will ensure stable operation. The capacitor is not
required when powering the product from an input source with
an inductance below 10 µH. The minimum required
capacitance value depends on the output power and the input
voltage. The higher output power the higher input capacitance
is needed. Approximately doubled capacitance value is
required for a 24 V input voltage source compared to a 48V
input voltage source.
External Decoupling Capacitors
When powering loads with significant dynamic current
requirements, the voltage regulation at the point of load can
be improved by addition of decoupling capacitors at the load.
The most effective technique is to locate low ESR ceramic and
electrolytic capacitors as close to the load as possible, using
several parallel capacitors to lower the effective ESR. The
ceramic capacitors will handle high-frequency dynamic load
changes while the electrolytic capacitors are used to handle
low frequency dynamic load changes. It is equally important to
use low resistance and low inductance PCB layouts and
cabling.
External decoupling capacitors will become part of the control
loop of the DC/DC converter and may affect the stability
margins. As a “rule of thumb”, 100 µF/A of output current can
be added without any additional analysis. The ESR of the
capacitors is a very important parameter. Power Modules
guarantee stable operation with a verified ESR value of >10
m across the output connections.
For further information please contact your local Ericsson
Power Modules representative.
Output Voltage Adjust (Vadj)
The products have an Output Voltage Adjust pin (Vadj). This
pin can be used to adjust the output voltage above or below
Output voltage initial setting.
When increasing the output voltage, the voltage at the output
pins (including any remote sense compensation ) must be
kept below the threshold of the over voltage protection, (OVP)
to prevent the converter from shutting down. At increased
output voltages the maximum power rating of the converter
remains the same, and the max output current must be
decreased correspondingly.
To increase the voltage the resistor should be connected
between the Vadj pin and +Sense pin. The resistor value of the
Output voltage adjust function is according to information
given under the Output section for the respective product.
To decrease the output voltage, the resistor should be
connected between the Vadj pin and –Sense pin.
E
PKJ 4000 RFPA series Direct Converters
Input 36-75 V, Output up to 12.4 A / 350 W
EN/LZT 146 367 R3B September 2009
© Ericsson AB
Technical Specification
22
Ericsson Internal
PRODUCT SPECIFICATION 3 (6)
Prepared (also subject responsible if other) No.
EGLANDY 3/1301-BMR 630 03/7 Uen
Approved Checked Date Rev Reference
SEC/D (Betty Wu) EQUENXU 2009-02-16 C
Operating information continued
Parallel Operation
Two converters may be paralleled for redundancy if the total
power is equal or less than PO max. It is not recommended to
parallel the converters without using external current sharing
circuits.
See Design Note 006 for detailed information.
Remote Sense
The DC/DC converters have remote sense that can be used to
compensate for voltage drops between the output and the
point of load. The sense traces should be located close to the
PCB ground layer to reduce noise susceptibility. The remote
sense circuitry will compensate for up to 10% voltage drop
between output pins and the point of load.
If the remote sense is not needed +Sense should be
connected to +Out and -Sense should be connected to -Out.
Over Temperature Protection (OTP)
The converters are protected from thermal overload by an
internal over temperature shutdown circuit.
When the baseplate temperature (center of baseplate)
exceeds 140°C the converter will shut down(latching). The
DC/DC converter can be restarted by cycling the input voltage
or using the remote control function.
Over Voltage Protection (OVP)
The converters have latching output overvoltage protection. In
the event of an overvoltage condition, the converter will
shutdown immediately. The converter can be restarted by
cycling the input voltage or using the remote control function.
Over Current Protection (OCP)
The converters include current limiting circuitry for protection
at continuous overload.
The output voltage will decrease towards zero for output
currents in excess of max output current (max Io). The
converter will resume normal operation after removal of the
overload. The load distribution should be designed for the
maximum output short circuit current specified.
Thermal Consideration
General
The products are designed to operate in different thermal
environments and sufficient cooling must be provided to
ensure reliable operation.
For products mounted on a PCB without a heat sink attached,
cooling is achieved mainly by conduction, from the pins to the
host board, and convection, which is dependant on the airflow
across the product. Increased airflow enhances the cooling of
the product. The Output Current Derating graph found in the
Output section for each model provides the available output
current vs. ambient air temperature and air velocity at
VI = 53 V.
The product is tested on a 254 x 254 mm, 35 µm (1 oz),
16-layer test board mounted vertically in a wind tunnel with a
cross-section of 608 x 203 mm.
For products with base plate used in a sealed box/cold wall
application, cooling is achieved mainly by conduction
throughthe cold wall. The Output Current Derating graphs are
found in the Output section for each model. The product is
tested in a sealed box test set up with ambient temperatures
85, 55 and 35°C. See Design Note 028 for further details.
E
PKJ 4000 RFPA series Direct Converters
Input 36-75 V, Output up to 12.4 A / 350 W
EN/LZT 146 367 R3B September 2009
© Ericsson AB
Technical Specification
23
Ericsson Internal
PRODUCT SPECIFICATION 4 (6)
Prepared (also subject responsible if other) No.
EGLANDY 3/1301-BMR 630 03/7 Uen
Approved Checked Date Rev Reference
SEC/D (Betty Wu) EQUENXU 2009-02-16 C
Proper cooling of the product can be verified by measuring the
temperature at positions P1, P2. The temperature at these
positions should not exceed the max values provided in the
table below. The number of points may vary with different
thermal design and topology.
See Design Note 019 for further information.
Position Description Temp. limit
P1 Reference Point, Baseplate 120º C
P2 PCB 110º C
Base plate
Definition of reference temperature TP1
The reference temperature is used to monitor the temperature
limits of the product. Temperatures above maximum TP1,
meassured at the reference point P1 are not allowed and may
cause degradation or permanent damage to the product. TP1 is
also used to define the temperature range for normal operating
conditions. TP1 is defined by the design and used to guarantee
safety margins, proper operation and high reliability to the
product.
Ambient Temperature Calculation
For products with base plate the maximum allowed ambient
temperature can be calculated by using the thermal resistance.
1. The power loss is calculated by using the formula
((1/η) - 1) × output power = power losses (Pd).
η = efficiency of product. E.g. 89.5% = 0.895
2. Find the thermal resistance (Rth) in the Thermal Resistance
graph found in the Output section for each model. Note that
the thermal resistance can b e significantly reduced if a
heat sink is mounted on the top of the base plate.
Calculate the temperature increase (ΔT).
ΔT = Rth x Pd
3. Max allowed ambient temperature is:
Max TP1 - ΔT.
E.g PKJ 4316 API at 2m/s:
1. (( ) - 1) × 350 W = 52.3 W
2. 52.3 W × 1.8°C/W = 94.1°C
3. 120 °C –94.1°C = max ambient temperature is 25.9°C.
The actual temperature will be dependent on several factors
such as the PCB size, number of layers and direction of
airflow.
1
0.87
E
PKJ 4000 RFPA series Direct Converters
Input 36-75 V, Output up to 12.4 A / 350 W
EN/LZT 146 367 R3B September 2009
© Ericsson AB
Technical Specification
24
Ericsson Internal
PRODUCT SPECIFICATION 5 (6)
Prepared (also subject responsible if other) No.
EGLANDY 3/1301-BMR 630 03/7 Uen
Approved Checked Date Rev Reference
SEC/D (Betty Wu) EQUENXU 2009-02-16 C
Connections
Pin Designation Function
1 +In Positive input
2 RC Remote control
3 Case Connected to base plate
4 -In Negative input
5 -Out Negative output
6 -Sen Negative sense
7 Vadj Output voltage adjust
8 +Sen Positive sense
9 +Out Positive output
E
PKJ 4000 RFPA series Direct Converters
Input 36-75 V, Output up to 12.4 A / 350 W
EN/LZT 146 367 R3B September 2009
© Ericsson AB
Technical Specification
25
Ericsson Internal
PRODUCT SPEC. MECHANICAL 1 (2)
Prepared (also subject responsible if other) No.
EXXUYNG 4/1301-BMR 630/7 Uen
Approved Checked Date Rev Reference
SEC/D (Betty Wu) 2009-2-11 D
Mechanical Information
E
PKJ 4000 RFPA series Direct Converters
Input 36-75 V, Output up to 12.4 A / 350 W
EN/LZT 146 367 R3B September 2009
© Ericsson AB
Technical Specification
26
Ericsson Internal
PRODUCT. SPEC. MECH. 1 (3)
Prepared (also subject responsible if other) No.
EXXUYNG 5/1301-BMR 630 Uen
Approved Checked Date Rev Reference
SEC/D (Betty Wu) See §1 2009-02-11 D
Soldering Information
The product is intended for manual or wave soldering. When
wave soldering is used, the temperature on the pins is
specified to maximum 270 °C for maximum 10 seconds.
A maximum preheat rate of 4°C/s and a temperature of max of
+150°C is suggested. When soldering by hand, care should
be taken to avoid direct contact between the hot soldering iron
tip and the pins for more than a few seconds in order to
prevent overheating.
A no-clean flux is recommended to avoid entrapment of
cleaning fluids in cavities inside the product or between the
product and the host board. The cleaning residues may affect
long time reliability and isolation voltage.
Delivery Package Information
The products are delivered in antistatic clamshell trays.
Clamshell Specifications
Material Conductive/dissipative PET
Surface resistance 10
5
< Ohm/square < 10
12
Bake ability The clamshells are not bake able.
Clamshell capacity 10 products/clamshell
Clamshell
thickness 25 mm [0.984 inch]
Box capacity 50 products (5 full clamshells/box)
Clamshell weight 150 g empty, typical 1050 g one full
clamshell
E
PKJ 4000 RFPA series Direct Converters
Input 36-75 V, Output up to 12.4 A / 350 W
EN/LZT 146 367 R3B September 2009
© Ericsson AB
Technical Specification
27
Ericsson Internal
PRODUCT. SPEC. MECH. 2 (3)
Prepared (also subject responsible if other) No.
EXXUYNG 5/1301-BMR 630 Uen
Approved Checked Date Rev Reference
SEC/D (Betty Wu) See §1 2009-02-11 D
Product Qualification Specification
Characteristics
External visual inspection IPC-A-610
Dry heat IEC 60068-2-2 Bd Temperature
Duration
+125 °C
1000 h
Cold (in operation) IEC 60068-2-1 Ad Temperature T
A
Duration
-45°C
72 h
Damp heat IEC 60068-2-67 Cy Temperature
Humidity
Duration
+85 °C
85 % RH
1000 hours
Operational life test MIL-STD-202G method 108A Duration 1000 h
Change of temperature
(Temperature cycling)
IEC 60068-2-14 Na Temperature range
Number of cycles
Dwell/transfer time
-40 to +100 °C
1000
15 min/0-1 min
Vibration, broad band random IEC 60068-2-64 Fh, method 1 Frequency
Spectral density
Duration
10 to 500 Hz
0.07 g
2
/Hz
10 min in each 3 perpendicular
directions
Mechanical shock IEC 60068-2-27 Ea Peak acceleration
Duration
Pulse shape
Directions
Number of pulses
100 g
6 ms
Half sine
6
18 (3 + 3 in each perpendicular
direction)
Robustness of terminations
IEC 60068-2-21 Test Ua1
Plated through hole mount
products
All leads
Resistance to soldering heat IEC 60068-2-20 Tb Method 1A Solder temperature
Duration
270° C
10-13 s
Solderability
IEC 60068-2-20 test Ta
Preconditioning
Temperature, SnPb Eutectic
Temperature, Pb-free
Steam ageing
235° C
260° C
Immersion in cleaning solvents IEC 60068-2-45 XA
Method 2
Water
Glycol ether
Isopropanol
+55° C
+35° C
+35° C
E
PKJ 4000 RFPA series Direct Converters
Input 36-75 V, Output up to 12.4 A / 350 W
EN/LZT 146 367 R3B September 2009
© Ericsson AB
Technical Specification
28