https://www.phoenixcontact.com/us/products/2800983
09/10/2014Page1/5
Surge protection device-PT-IQ-4X1+F-24DC-UT-2800983
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Surge protection, consisting of protective plug and base element, with integrated multi-stage status indicator on
the module for four signal wires with common reference potential. Indirect grounding via gas-filled surge arrester.
The figure shows the PT-
IQ-2x2-24DC-UT version
Product Features
Surge protection system
Multi-level state monitoring
Collective message about supply and remote module
System supplied via DIN rail bus
Up to 28 protection modules per supply module
Maximum ease of maintenance thanks to the two-piece design
Codable plug
Impedance-neutral disconnection of plug for maintenance purposes
Base element remains an integral part of the installation
Key commercial data
Packing unit 1 pc
Weight per Piece (excluding packing) 160.0 GRM
Custom tariff number 85363010
Country of origin Germany
Technical data
Dimensions
Height 91.1 mm
Width 17.7 mm
https://www.phoenixcontact.com/us/products/2800983
09/10/2014Page2/5
Surge protection device-PT-IQ-4X1+F-24DC-UT-2800983
Technical data
Dimensions
Depth 77.5 mm
Horizontal pitch 1 Div.
Ambient conditions
Ambient temperature (operation) -40 °C ... 70 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Degree of protection IP20
General
Housing material PA 6.6
Inflammability class according to UL 94 V0
Color black
Mounting type DIN rail mounting
Type DIN rail module, two-section, divisible
Direction of action Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-
Earth Ground
Protective circuit
IEC test classification C1
C2
C3
D1
Nominal voltage UN24 V
Maximum continuous operating voltage UC30 V DC
21 V AC
Nominal current IN700 mA (Up to 45°C)
Operating effective current IC at UC≤ 1 mA (per path)
Residual current IPE ≤ 1 µA
Nominal discharge current In (8/20) µs (Core-Earth) 10 kA
Impulse discharge current (10/350)˽µs, peak value limp 2.5 kA
Voltage protection level UP (Core-Earth) ≤ 800 V (C1 - 1 kV/500 A)
≤ 950 V (C2 - 10 kV / 5 kA)
≤ 180 V (C2 - 10 kA)
≤ 780 V (C3 - 25 A)
≤ 950 V (C3 - 50 A)
Voltage protection level UP (Core-GND) ≤ 75 V (C1 - 1 kV/500 A)
≤ 135 V (C2 - 10 kV / 5 kA)
≤ 55 V (C3 - 25 A)
≤ 60 V (C3 - 50 A)
https://www.phoenixcontact.com/us/products/2800983
09/10/2014Page3/5
Surge protection device-PT-IQ-4X1+F-24DC-UT-2800983
Technical data
Protective circuit
Response time tA (Core-Earth) ≤ 1 ns
≤ 100 ns
Input attenuation aE, asym. typ. 0.3 dB (≤ 300 kHz)
Cut-off frequency fg (3 dB), asym. (GND) in 150 Ohm system typ. 1.1 MHz
Capacity (Core-Earth) 2 nF
Resistance in series 1.2 Ω ±5 %
Surge protection fault message Optical, multi-stage
Max. required back-up fuse 0.8 A (FF)
Surge carrying capacity in acc. with IEC 61643-21 (Core-Earth) C1 (1 kV / 500 A)
C2 (10 kV / 5 kA)
C2 (10 kA)
C3 (25 A)
C3 (50 A)
D1 - 2,5 kA
Surge carrying capacity in acc. with IEC 61643-21 (Core-GND) C1 (1 kV/500 A)
C2 (10 kV/5 kA)
C2 (10 kA)
C3 (25 A)
C3 (50 A)
Pulse reset time tr in acc. with IEC 61643-21 (Core-Earth) ≤ 30 ms
Pulse reset time tr in acc. with IEC 61643-21 (Core-GND) ≤ 350 ms
Overload failure mode as per IEC 61643-21 (plug) Mode 2
Overload failure mode as per IEC 61643-21 (GND-Ground base element) Mode 2
Connection data
Connection method Screw connection
Connection type IN Screw terminal blocks
Connection type OUT Screw terminal blocks
Tightening torque 0.5 Nm
Stripping length 8 mm
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 4 mm²
Conductor cross section AWG/kcmil min. 24
Conductor cross section AWG/kcmil max 12
Connection, equipotential bonding
Connection method NS 35 DIN rail or connection terminal block
https://www.phoenixcontact.com/us/products/2800983
09/10/2014Page4/5
Surge protection device-PT-IQ-4X1+F-24DC-UT-2800983
Classifications
eCl@ss
eCl@ss 4.0 27140201
eCl@ss 4.1 27130801
eCl@ss 5.0 27130801
eCl@ss 5.1 27130801
eCl@ss 6.0 27130807
eCl@ss 7.0 27130807
eCl@ss 8.0 27130807
ETIM
ETIM 3.0 EC000943
ETIM 4.0 EC000943
ETIM 5.0 EC000943
UNSPSC
UNSPSC 6.01 30212010
UNSPSC 7.0901 39121610
UNSPSC 11 39121610
UNSPSC 12.01 39121610
UNSPSC 13.2 39121620
Approvals
Approvals
Approvals
UL Listed
Ex Approvals
Approvals submitted
Approval details
UL Listed
https://www.phoenixcontact.com/us/products/2800983
09/10/2014Page5/5
Surge protection device-PT-IQ-4X1+F-24DC-UT-2800983
Drawings
Diagram
30 35 40 45 50 55 60 65 70 75
I [mA]
T [°C]
400
200
0
600
800
Dimensioned drawing
91,1
45
51,6
77,5
7,8
17,7
Circuit diagram
1 2
5 6
7 8
11 12
9 10
3 4
Phoenix Contact 2014 © - all rights reserved