FL SWITCH MM HS Order No.: 2832328
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2832328
PHOENIX CONTACT Deutschland GmbH Page 2 / 6
http://www.phoenixcontact.de Feb 4, 2011
Type of connection Via interface modules
Transmission physics Multimode glass fiber
Transmission speed 100 MBit/s (full duplex)
Transmission length Up to 10000 m (depending on the fiber used)
1300 nm
Interface Serial (V.24 (RS-232))
Type of connection V.24 (RS-232-C), 6-pos. MINI-DIN female connector (PS/2)
Function
Basic functions Store and forward switch complies with IEEE 802.3 2 priority
classes in acc. with IEEE 802.1 P TCP/IP protocol, BootP-
capable, port-mirroring, integrated web server function, multicast
filtering, IGMP snooping, VLAN, Rapid Spanning Tree (RSTP),
port security, PROFINET-IO-device, DHCP option 82 relay agent
Management Integrated Management Agent, SNMP protocol (private MIB,
MIB-2, RMON MIB, Bridge MIB), integrated Web server function
Supported browsers Internet Explorer 5.5 or higher
Redundancy Spanning Tree 802.1d, Rapid Spanning Tree 802.1w, Fast Ring
Detection, Media Redundancy Protocol (MRP) as per IEC62439
Status and diagnostic indicators Per Ethernet 2 status LEDs: LINK and switch-over Status Activity,
100, full duplex, supply voltage US1 und US2 (redundant supply
voltage) and FAIL, two-digit 7-segment display
Network expansion parameters
Cascading depth Network, linear, and star structure: any
Maximum conductor length ((twisted pair) 100 m
Supply voltage
Supply voltage 24 V DC
Residual ripple 3.6 VPP (within the permitted voltage range)
Supply voltage range 18.5 V DC ... 30.2 V DC
Typical current consumption 350 mA (Up to 3500 mA, depending on the configuration)
Max. current consumption 3.5 A
Mechanical tests
Type of test Shock test in acc. with IEC 60068-2-27
Test result Operation: 25 g, 11 ms duration, semi-sinusoidal shock impulse
Type of test Shock test in acc. with IEC 60068-2-27
Test result Storage/Transport: 50 g, 11 ms duration, semi-sinusoidal shock
impulse
Type of test Vibration resistance in acc. with IEC 60068-2-6