General Purpose Relays
Industrial Relays
KCP Series Plug-in Relay
08-2011, Rev. 0811
www.te.com
© 2011 Tyco Electronics Corporation,
a TE Connectivity Ltd. company
Datasheets and product specification
according to IEC 61810-1 and to be used
only together with the ‘Definitions’ section.
Datasheets and product data is subject to the
terms of the disclaimer and all chapters of
the ‘Definitions’ section, available at
http://relays.te.com/definitions
Datasheets, product data, ‘Definitions’ sec-
tion, application notes and all specifications
are subject to change.
1
Potter & Brumfield
Insulation Data
Initial dielectric strength
between open contacts 500Vrms
between contact and coil 500Vrms
between adjacent contacts 500Vrms
Initial insulation resistance
between insulated elements 1,000MΩ
Other Data
Material compliance: EU RoHS/ELV, China RoHS, REACH, Halogen content
refer to the Product Compliance Support Center at
www.te.com/customersupport/rohssupportcenter
Ambient temperature
DC coil -45ºC to 70ºC
AC coil -45ºC to 70ºC
Category of environmental protection
IEC 61810 RTI - dust protected
Terminal type 8- or 11-pin octal-style plug
Weight 82.2g
Packaging/unit tray/25 pcs., box/200pcs.
Accessories
For details see datasheet Sockets and Accessories, KRP Relays
Product Code Description
27E891 8-pin DIN socket (use 20C318 clip)
27E892 11-pin DIN socket (use 20C318 clip)
27E122 8-pin track mount socket (use 20C318 clip)
27E123 11-pin track mount socket (use 20C318 clip)
n Enclosed dust cover
n DC current sensitive relay
n 1, 2, and 3 Form C (CO) contact arrangement
n 8 and 11 pin octal style plugs
n Operates on 125mW per movable arm
Contact Data
Contact arrangement 1 form C (CO), 2 form C (CO), 3 form C (CO)
Rated voltage 120VAC
Rated current 2A
Contact material Ag
Min. recommended contact load 100mA, 12VDC
Initial contact resistance 100mΩ
Frequency of operation 360 ops./hour
Operate/release time max. 20/10ms
Contact ratings
Type Load Cycles
1, 2 and 3 pole, Ag
2A, 120VAC 100x103 ops.
Mechanical endurance 15x106 ops.
Coil Data
Coil current range 3.6mA to 12.3mA (DC only)
Coil versions, DC Coil
Coil Operate Coil Rated coil
code current resistance power
mADC Ω±10% mW
Coil versions, 1 pole
2,500 7.2 2,500 125
5,000 5 5,000 125
10,000 3.6 10,000 125
Coil versions, 2 pole
2,500 10 2,500 250
5,000 7.2 5,000 250
10,000 5 10,000 250
Coil versions, 3 pole
2,500 12.3 2,500 375
5,000 8.7 5,000 375
10,000 6.1 10,000 375
All figures are given for coil without preenergization, at ambient temperature +23°C.