W8703A DAMPER INTERFACE MODULE
11 69-1344-1
• The first W8703 Damper Interface Module drives the
zone valves using its open contacts.
• The second W8703 Damper Interface Module,
addressed with the same DIP switch settings as the
first W8703 (Fig. 12-14) drives the AOBD damper.
• AOBD dampers open and close on a call for heat
and on a call for cool. An optional isolation relay can
be used to depower the common wire to the second
W8703 to prevent a call for heat from the operating
damper on a call for heat. Wire the coil to Y1 and C
on the W8635A.
NOTE: The transformer must be appropriately sized to
supply power to the total valve load (60 VA
maximum or 30 VA maximum valve load per
zone).
HYDRONIC ZONING WITH CIRCULATORS
Networked zoning can control a hydronic system zoned
with circulators. The damper module damper terminals
are wired to isolation relays that control the 120 Vac cir-
cuator. See Fig. 8.
If the system uses ducted air conditioning, wire using
Fig. 9.
PRIORITY ZONING
When an indirect water heater (IWH) is used, the
domestic water can be put on a priority zone. This
directs all the available heat from the boiler to the IWH,
if present, when a call for domestic hot water occurs.
Fig. 10 shows an isolation relay used to remove power
from the room-heating zones valves whenever the IWH
Aquastat calls for heat. In addition to powering the isola-
tion relay, the IWH Aquastat also powers the zone valve
for the IWH loop.
Fig. 11 shows a method of adding a time-out feature to
Fig. 10. This feature prevents the Aquastat from steal-
ing the heat for extended periods.
RELAY AND BOILER CONTROL PANELS
Networked zoning can control Honeywell zone valve or
circular panels. Wire similar to Fig. 7 but wire the nor-
mally open contacts on the circulator relays to zone
thermostat R or W contacts on the panel.
On Argo or Taco panels, connect the normally open
contacts to the TT terminals on the panel.
On Tekmar panels, connect the normally open contacts
where the end switches or thermostats are shown in the
Tekmar installation instructions.
SETTINGS
T8635 Thermostat Settings
The T8635 Thermostats must be configured using
Installer Setup. See Installer Setup 51 in Table 6 of the
T8635 Thermostat Installation Instructions.
Set Installer Setup 51 for the correct cycle rate. Use 6
cph for conventional forced air. Use 3 cph for high-effi-
ciency forced air or hydronic applications.
Set Installer Setup 5 to the number of stages of heat.
For example, set to 1 for a single-stage heat system.
Set Installer Setup 8 for the number of stages of cool-
ing. For example, for one stage of cooling, set it to 1.
For a heat only application, set it to 0.
W8703 DIP Switch Settings
Zones a, b, and c on the W8703 correspond with the
thermostat configuration zones 1, 2, and 3, respectively.
DIP switches are set in the factory as shown in Fig. 12.
Fig. 12. Zones 1-3 DIP switch settings.
When two W8703 are connected and the DIP switch is
configured on the second module as shown in Fig. 13,
zones a, b, and c on the W8703 correspond with the
thermostat configuration zones 4, 5, and 6, respectively
.
Fig. 13. Zones 4-6 DIP switch settings.
When three W8703 are connected and the DIP switch is
configured on the third module as shown in Fig. 14,
zones a, b, and c on the W8703 correspond with the
thermostat configuration zones 7,8 and 9, respectively.
Fig. 14. Zones 7-9 DIP switch settings.
M13428
1
0
ZONES 1-3
M20252
1
0
ZONES 4-6
M20253
1
0
ZONES 7-9