Modular timers 1 - 6 - 8 - 16 A Building automation 80 SRIES Elevators and lifts Automation for blinds, grilles and shutters Hoists and cranes Panels for electrical distribution Door and gate openers FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products. 80 SERIES Modular timers 16 A 80 SERIES 80.01 Multi-function and mono-function timer range 80.11 80.01 - Multi-function & multi-voltage 80.11 - On-delay, multi-voltage * 17.5 mm wide * Six time scales from 0.1 s to 24 h * High input/output isolation * 35 mm rail (EN 60715) mount * "Blade + cross" - both flat blade and cross head * screw drivers can be used to adjust the range and function selectors, the timing trimmer, and to disengage the rail mounting clip New multi-voltage versions with "PWM clever" technology 80.01 / 80.11 Screw terminal * Multi-voltage * Multi-function * Multi-voltage * Mono-function AI: On-delay DI: Interval SW: Symmetrical flasher (starting pulse on) BE: Off-delay with control signal CE: On- and off-delay with control signal DE: Interval with control signal on AI: On-delay For UL ratings see: "General technical information" page V Wiring diagram (without control signal) For outline drawing see page 9 Wiring diagram (with control signal) Wiring diagram (without control signal) Contact specification Contact configuration Rated current/Maximum peak current Rated voltage/ Maximum switching voltage A V AC Rated load AC1 VA 1 CO (SPDT) 1 CO (SPDT) 16/30 16/30 250/400 250/400 4000 4000 Rated load AC15 (230 V AC) VA 750 750 Single phase motor rating (230 V AC) kW 0.55 0.55 A 16/0.3/0.12 16/0.3/0.12 mW (V/mA) 500 (10/5) 500 (10/5) AgNi AgNi 12...240 24...240 Breaking capacity DC1: 30/110/220 V Minimum switching load Standard contact material H Supply specification Nominal voltage (UN) Rated power AC/DC Operating range V AC (50/60 Hz) V DC 12...240 24...240 VA (50 Hz)/W < 1.8/< 1 < 1.8/< 1 V AC 10.8...265 16.8...265 V DC 10.8...265 16.8...265 Technical data V-2019, www.findernet.com Specified time range (0.1...2)s, (1...20)s, (0.1...2)min, (1...20)min, (0.1...2)h, (1...24)h Repeatability% 1 1 Recovery time ms 100 100 Minimum control impulse ms 50 -- Setting accuracy-full range % 5 5 50 * 103 50 * 103 -10...+50 -10...+50 IP 20 IP 20 Electrical life at rated load in AC1 Ambient temperature range Protection category cycles C Approvals (according to type) 3 80 SERIES 80 SERIES Modular timers 16 A 80.21 Mono-function timer range 80.41 80.91 80.21 - Interval, multi-voltage 80.41 - Off-delay with control signal, multi-voltage 80.91 - Asymmetrical flasher, multi-voltage * 17.5 mm wide * Six time scales from 0.1 s to 24 h * High input/output isolation * 35 mm rail (EN 60715) mount * "Blade + cross" - both flat blade and cross head * screw drivers can be used to adjust the range and function selectors, the timing trimmer, and to disengage the rail mounting clip New multi-voltage versions with "PWM clever" technology * Multi-voltage * Mono-function * Multi-voltage * Mono-function * Multi-voltage * Mono-function DI: Interval BE: Off-delay with control signal LI:Asymmetrical flasher (starting pulse on) LE:Asymmetrical flasher (starting pulse on) with control signal 80.21 / 80.41 / 80.91 Screw terminal For UL ratings see: "General technical information" page V For outline drawing see page 9 Wiring diagram (without control signal) Wiring diagram (with control signal) Wiring diagram (without control signal) Wiring diagram (with control signal) 1 CO (SPDT) 1 CO (SPDT) 1 CO (SPDT) 16/30 16/30 16/30 250/400 250/400 250/400 4000 4000 4000 Contact specification Contact configuration Rated current/Maximum peak current Rated voltage/ Maximum switching voltage A V AC Rated load AC1 VA Rated load AC15 (230 V AC) VA 750 750 750 Single phase motor rating (230 V AC) kW 0.55 0.55 0.55 A 16/0.3/0.12 16/0.3/0.12 16/0.3/0.12 mW (V/mA) 500 (10/5) 500 (10/5) 500 (10/5) AgNi AgNi AgNi 24...240 24...240 12...240 Breaking capacity DC1: 30/110/220 V Minimum switching load Standard contact material Supply specification Nominal voltage (UN) Rated power AC/DC Operating range V AC (50/60 Hz) V DC 24...240 24...240 12...240 VA (50 Hz)/W < 1.8/< 1 < 1.8/< 1 < 1.8/< 1 V AC 16.8...265 16.8...265 10.8...265 V DC 16.8...265 16.8...265 10.8...265 Technical data Specified time range (0.1...2)s, (1...20)s, (0.1...2)min, (1...20)min, (0.1...2)h, (1...24)h Repeatability% 1 1 1 Recovery time ms 100 100 100 Minimum control impulse ms -- 50 50 Setting accuracy-full range % 5 5 5 50 * 103 50 * 103 50 * 103 -10...+50 -10...+50 -10...+50 IP 20 IP 20 IP 20 Electrical life at rated load in AC1 Ambient temperature range Protection category Approvals (according to type) 4 cycles C V-2019, www.findernet.com H 80 SERIES Modular Solid State timer (SST) 1 A 80 SERIES 80.71 Multi-function and multi-voltage solid-state output timer * 17.5 mm wide * Six time scales from 0.1 s to 24 h * High input/output isolation * 35 mm rail (EN 60715) mount * Multi-voltage output (24...240 V AC/DC), independent from the input voltage * "Blade + cross" - both flat blade and cross head * screw drivers can be used to adjust the range and function selectors, the timing trimmer, and to disengage the rail mounting clip Multi-voltage input with "PWM clever" technology 80.71 Screw terminal * Multi-voltage * Multi-function AI: DI: SW: BE: CE: DE: On-delay Interval Symmetrical flasher (starting pulse on) Off-delay with control signal On- and off-delay with control signal Interval with control signal on Wiring diagram (without control signal) For outline drawing see page 9 Wiring diagram (with control signal) Output circuit Contact configuration 1 NO (SPST-NO) Rated current A Rated voltage V AC/DC 24...240 Switching voltage range V AC/DC 19...265 Rated load AC15 A 1 Rated load DC1 A 1 Minimum switching current mA 0.5 Max. "OFF-state" leakage current mA 0.05 V 2.8 Max. "ON-state" voltage drop H 1 Input circuit Nominal voltage (UN) Rated power Operating range V AC (50/60 Hz) 24...240 V DC 24...240 VA (50 Hz)/W 1.3/1.3 V AC 19...265 V DC 19...265 Technical data V-2019, www.findernet.com Specified time range (0.1...2)s, (1...20)s, (0.1...2)min, (1...20)min, (0.1...2)h, (1...24)h Repeatability% 1 Recovery time ms 100 Minimum control impulse ms 50 Setting accuracy-full range % 5 Electrical life Ambient temperature range Protection category cycles C 100 * 106 -20...+50 IP 20 Approvals (according to type) 5 80 SERIES 80 SERIES Modular timers 6 - 8 A 80.61 Mono-function timer range 80.82 80.61 - Power off-delay (True off-delay), multi-voltage 80.82 - Star-delta, multi-voltage * 17.5 mm wide * Rotary range selector, and timing trimmer * Four time scales from 0.05s to 180 s (type 80.61) * Six time scales from 0.1 s to 20min (type 80.82) * High input/output isolation * 35 mm rail (EN 60715) mount 80.61 / 80.82 Screw terminal * Multi-voltage * Mono-function * Multi-voltage * Mono-function * Transfer time can be regulated (0.05...1)s BI: Power off-delay (True off-delay) SD: Star-delta For UL ratings see: "General technical information" page V For outline drawing see page 9 Wiring diagram (without control signal) Wiring diagram (without control signal) 1 CO (SPDT) 2 NO (DPST-NO) 8/15 6/10 Contact specification Contact configuration Rated current/Maximum peak current Rated voltage/ Maximum switching voltage A 250/400 250/400 Rated load AC1 VA 2000 1500 Rated load AC15 (230 V AC) VA 400 300 Single phase motor rating (230 V AC) kW 0.3 -- Breaking capacity DC1: 30/110/220 V A 8/0.3/0.12 6/0.2/0.12 mW (V/mA) 300 (5/5) 500 (12/10) AgNi AgNi V AC (50/60 Hz) 24...240 24...240 V DC 24...220 24...240 VA (50 Hz)/W < 0.6/< 0.6 < 1.3/< 0.8 V AC 16.8...265 16.8...265 V DC 16.8...242 16.8...265 Minimum switching load V AC Standard contact material Supply specification Nominal voltage (UN) Rated power AC/DC Operating range Technical data (0.05...2)s, (1...16)s, (8...70)s, (50...180)s (0.1...2)s, (1...20)s, (0.1...2)min, (1...20)min Repeatability% Specified time range 1 1 Recovery time ms -- 100 Minimum control impulse ms 500 (A1-A2) -- Setting accuracy-full range % 5 5 100 * 103 60 * 103 -10...+50 -10...+50 IP 20 IP 20 Electrical life at rated load in AC1 Ambient temperature range Protection category Approvals (according to type) 6 cycles C V-2019, www.findernet.com H 80 SERIES Modular timers 8 A 80 SERIES 80.51 Multi-function and multi-voltage * 17.5 mm wide * Six time scales from 0.1 s to 24 h * High input/output isolation * 35 mm rail (EN 60715) mount * "Blade + cross" - both flat blade and cross head * screw drivers can be used to adjust the range and function selectors, the timing trimmer, and to disengage the rail mounting clip New multi-voltage versions with "PWM clever" technology 80.51.0.240.0000 Screw terminal 80.51.0.240.P000 Push-in terminal * Multi-voltage (24...240) V AC/DC * Multi-function AI: On-delay DI: Interval SW: Symmetrical flasher (starting pulse on) BE: Off-delay with control signal CE: On- and off-delay with control signal DE: Interval with control signal on For UL ratings see: "General technical information" page V Wiring diagram (without control signal) For outline drawing see page 9 Wiring diagram (with control signal) Contact specification Contact configuration 1 CO (SPDT) Rated current/Maximum peak current Rated voltage/ Maximum switching voltage A V AC Rated load AC1 8/16 VA 2000 Rated load AC15 (230 V AC) VA 400 Single phase motor rating (230 V AC) kW 0.3 Breaking capacity DC1: 30/110/220 V Minimum switching load A 8/0.3/0.12 mW (V/mA) 500 (10/5) Standard contact material H 250/400 AgNi Supply specification Nominal voltage (UN) Rated power AC/DC Operating range V AC (50/60 Hz) 24...240 V DC 24...240 VA (50 Hz)/W < 1.8/< 1 V AC 17...265 V DC 17...265 Technical data V-2019, www.findernet.com Specified time range (0.1...2)s, (1...20)s, (0.1...2)min, (1...20)min, (0.1...2)h, (1...24)h Repeatability% 1 Recovery time ms 50 Minimum control impulse ms 50 Setting accuracy-full range % 5 Electrical life at rated load in AC1 Ambient temperature range Protection category cycles C 100 * 103 -10...+50 IP 20 Approvals (according to type) 7 80 SERIES Modular timers 1 - 6 - 8 - 16 A 80 SERIES Ordering information Example: 80 series, modular timers, 1 CO (SPDT) - 16 A, supply rated at (12...240)V AC/DC. 8 0 . 0 1 . 0 . 2 4 0 . 0 Series 0 0 0 Versions 0 = Standard P = Push-in (only for 80.51) Type 0 = Multi-function (AI, DI, SW, BE, CE, DE) 1 = On-delay (AI) 2 = Interval (DI) 4 = Off-delay with control signal (BE) 5 = Multi-function (AI, DI, SW, BE, CE, DE) 6 = Power off-delay (True off-delay) (BI) 7 = Multi-function with solid state output (AI, DI, SW, BE, CE, DE) 8 = Star-delta (SD) 9 = Asymmetrical flasher (LI, LE) Supply voltage 240 = (12...240)V AC/DC (80.01, 80.91) 240 = (24...240)V AC/DC (80.11, 80.21, 80.41, 80.51, 80.71, 80.82) 240 = (24...240)V AC, (24...220)V DC (80.61) Supply version 0 = AC (50/60 Hz)/DC No. of poles 1 = 1 CO (SPDT) 1 = 1 NO (SPST-NO), type 80.71 only 2 = 2 NO (DPST-NO), type 80.82 only Technical data H between input and output circuit V AC between open contacts V AC Insulation (1.2/50 s) between input and output kV EMC specifications Type of test Electrostatic discharge contact discharge air discharge Radio-frequency electromagnetic field (80 / 1000 MHz) Fast transients (burst) (5-50 ns, 5 kHz) on Supply terminals Surges (1.2/50 s) on Supply terminals common mode differential mode on start terminal (B1) common mode differential mode Radio-frequency common mode (0.15 / 80 MHz) on Supply terminals Radiated and conducted emission Other data Current absorption on signal control (B1) Power lost to the environment without contact current W with rated current W Terminals Wire strip length mm Screw torque Reference standard EN 61000-4-2 EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-5 EN 61000-4-5 EN 61000-4-5 EN 61000-4-6 EN 55022 < 1 mA 1.4 3.2 Screw terminals 10 Nm 0.8 Min. wire size mm2 AWG Max. wire size mm2 AWG Min. wire size mm2 AWG Max. wire size mm2 AWG 8 80.01/11/21/41/51/82/91 4000 1000 6 solid cable 0.5 20 solid cable 1x6/2x4 1 x 10 / 2 x 12 stranded cable 0.5 20 stranded cable 1 x 4 / 2 x 2.5 1 x 12 / 2 x 14 80.61 2500 1000 4 80.01/11/21/41/61/71/91 4 kV 8 kV 10 V/m 4 kV 4 kV 4 kV 4 kV 4 kV 10 V class B 80.71 2500 -- 4 80.51/82 4 kV 8 kV 10 V/m 4 kV 4 kV 4 kV 4 kV 4 kV 10 V class A Push-in terminals 10 -- solid cable 0.75 18 solid cable 1 x 1.5 / 2 x 1.5 1 x 16 / 2 x 16 stranded cable 0.75 18 stranded cable 1 x 2.5 / 2 x 2.5 1 x 14 / 2 x 14 V-2019, www.findernet.com Insulation Dielectric strength 80 SERIES Modular timers 1 - 6 - 8 - 16 A 80 SERIES Outline drawings Type 80.51 Push-in terminal 86 56.5 45 4.3 30.5 89.8 17.5 33.8 Types 80.01/80.51 Screw terminal Types 80.11/80.21/80.61 Screw terminal Type 80.41 Screw terminal Type 80.91 Screw terminal Type 80.71 Screw terminal H V-2019, www.findernet.com Type 80.82 Screw terminal 9 80 SERIES 80 SERIES Modular timers 1 - 6 - 8 - 16 A Functions U = Supply voltage LED* S = Signal switch Contacts Supply voltage NO output contact Open Closed OFF Open 15 - 18 15 - 16 ON Open 15 - 18 15 - 16 ON Open (Timing in Progress) 15 - 18 15 - 16 ON Closed 15 - 16 15 - 18 = Output contact * The LED on type 80.61 is illuminated only when the supply voltage is applied to the timer; during the timing period the LED is not illuminated. Without control signal = Start via contact in supply line (A1). With control signal = Start via contact into control terminal (B1). Wiring diagram Without control signal Type 80.01 80.51 80.71 (AI) On-delay. Apply power to timer. Output contacts transfer after preset time has elapsed. Reset occurs when power is removed. (DI) Interval. Apply power to timer. Output contacts transfer immediately. After the preset time has elapsed, contacts reset. 80.01 80.51 (SW) Symmetrical flasher (starting pulse on). Apply power to timer. Output contacts transfer immediately and cycle between ON and OFF for as long as power is applied. The ratio is 1:1 (time on = time off ). 80.71 With control signal H 80.01 80.51 80.71 80.01 80.51 (BE) Off-delay with control signal. Power is permanently applied to the timer. The output contacts transfer immediately on closure of the Signal Switch (S). Opening the Signal Switch initiates the preset delay, after which time the output contacts reset. (CE) On- and off-delay with control signal. Power is permanently applied to the timer. Closing the Signal Switch (S) initiates the preset delay, after which time the output contacts transfer. Opening the Signal switch initiates the same preset delay, after which time the output contacts reset. (DE) Interval with control signal on. Power is permanently applied to the timer. On momentary or maintained closure of Signal Switch (S), the output contacts transfer, and remain so for the duration of the preset delay, after which they reset. 80.71 NOTE: The function must be set before energising the timer. * Possible to control an external load, such as another relay coil or timer, connected to the control signal terminal B1. **A voltage other than the supply voltage can be applied to the command Start (B1), example: A1 - A2 = 230 V AC B1 - A2 = 12 V DC 10 V-2019, www.findernet.com * With DC supply, positive polarity has to be connected to B1 terminal (according to EN 60204-1). 80 SERIES Modular timers 6 - 8 - 16 A 80 SERIES Functions Wiring diagram Without control signal Type 80.11 (AI) On-delay. Apply power to timer. Output contacts transfer after preset time has elapsed. Reset occurs when power is removed. 80.21 (DI) Interval. Apply power to timer. Output contacts transfer immediately. After the preset time has elapsed, contacts reset. 80.61 (BI) Power off-delay (True off-delay). Apply power to timer (minimum 500 ms). Output contacts transfer immediately. Removal of power initiates the preset delay, after which time the output contacts reset. 80.82 (SD) Star-delta. Apply power to timer. The star contact ( ) closes immediately. After preset delay has elapsed the star contact ( ) resets. After a further transfer time variable from (0.05...1)s the delta contact ( ) closes and remains in that position, until reset on power off. 80.41 (BE) Off-delay with control signal. Power is permanently applied to the timer. The output contacts transfer immediately on closure of the Signal Switch (S). Opening the Signal Switch initiates the preset delay, after which time the output contacts reset. 80.91 (LI) Asymmetrical flasher (starting pulse on). Apply power to timer. Output contacts transfer immediately and cycle between ON and OFF for as long as power is applied. The ON (T1) and OFF (T2) times are independently adjustable. 80.11/21/61 80.82 With control signal 80.41 Without control signal 80.91 With control signal (LE) Asymmetrical flasher (starting pulse on) with control signal Power is permanently applied to the timer. Closing Signal Switch (S) causes the output contacts to transfer immediately and cycle between ON (T1) and OFF (T2), until opened. 80.91 * Possible to control an external load, such as another relay coil or timer, connected to the control signal terminal B1. V-2019, www.findernet.com * With DC supply, positive polarity has to be connected to B1 terminal (according to EN 60204-1). ** A voltage other than the supply voltage can be applied to the command Start (B1), example: A1 - A2 = 230 V AC B1 - A2 = 12 V DC 11 H 80 SERIES Modular timers 1 - 6 - 8 - 16 A 80 SERIES Times scales Rotary switch position series 80 (0.1...2)s (1...20)s (0.1...2)min (1...20)min (0.1...2)h (1...24)h Accessories Sheet of marker tags (CEMBRE Thermal transfer printers) for relays types 80.01/11/21/41/51/61/71 (48 tags), 6 x 12 mm 060.48 060.48 V-2019, www.findernet.com H 12 Please see general technical information