Low Voltage Products & Systems 17.A
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
Molded case
circuit breakers
17
17
Molded case circuit breakers
Index
Formula MCCBs ......................................................17.1 - 17.10
General information
Introduction ...................................................................................................................... 17.1
Circuit breakers for power distribution ..............................................................................17.2
Catalog number explanation .............................................................................................17.3
Ordering details
A1, 100A ..........................................................................................................................17.4
A2, 250A, 600Y/347V, 480V ∆ .........................................................................................17.5
Accessories .....................................................................................................................17.6 -17.9
Tmax MCCBs .........................................................17.11 - 17.10
General information
Introduction .................................................................................................................... 17.11
Ordering details guide ........................................................................................17.12 - 17.13
Catalog number explanation ...........................................................................................17.14
Ordering details
T1, 100A, 600Y/347V, 480V ∆ ...........................................................................17.15 - 17.16
T2, 100A, 480V ∆ ..............................................................................................17.17 - 17.19
T3, 225A, 600Y/347V, 480V ∆ ...........................................................................17.20 - 17.22
Ts3, 150A, 600V ∆, 225A, 480V ∆ .....................................................................17.23 - 17.26
T4, 250A, 600V ∆ ..............................................................................................17.27 - 17.32
T5, 400/600A, 600V ∆ .......................................................................................17.33 - 17.37
T6, 600A, 800A, 600V ∆ ....................................................................................17.38 - 17.40
T7 (Toggle), 1000A, 1200A, 600V ∆ ...............................................................................17.41
T7, 1000A, 1200A, 600V ∆ ................................................................................17.42 - 17.44
T7M (Stored energy) ...........................................................................................17.45 - 17.55
T8, 1600/2000/2500/3000A, 600VAC ∆ ............................................................17.56 - 17.66
Tmax UL489B Photovoltaic circuit breakers ........ 17.67 - 17.70
General information
Introduction .................................................................................................................... 17.67
Catalog number explanation ...........................................................................................17.68
Ordering details
Tmax UL489B MCCBs and switches .............................................................................17.69
Jumper kit accessories...................................................................................................17.70
Accessories, T1 - T7 .............................................. 17.71 - 17.83
Approximate dimensions, T1 - T7 .......................17.84 - 17.101
17 - Molded case circuit breakers
17.B Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Molded case
circuit breakers
17
17
Notes
FORMULA
MCCBs
Low Voltage Products & Systems 17.1
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
17
FORMULA
Molded case circuit breakers
FORMULA
Molded case circuit breakers
Introduction
ABB’s FORMULA molded case circuit breaker line offers simplicity and quality in some of
the smallest dimensions available. The A1 breaker frame size ranges in amperes from 15
through 100 and the A2 breaker frame size ranges from 125 through 250 amperes. All UL
FORMULA circuit breakers offer protection trip units that have xed thermal and magnetic
threshold values and are standard as a xed version with front terminals.
Standards
UL 489 & IEC 60947-2
Dimensions (W x D x H):
1 pole: 1.00 x 2.36 x 5.12
2 pole: 2.00 x 2.36 x 5.12
3 pole: 3.00 x 2.36 x 5.12
Weight:
1 pole: 0.54 lbs
2 pole: 1.04 lbs
3 pole: 1.54 lbs
Available accessories:
Shunt opening release (2p & 3p)
Undervoltage release (2p & 3p)
Auxiliary contacts (2p & 3p)
Termination kits (1p, 2p & 3p)
Padlocks (1p, 2p & 3p)
Direct and extended rotary handles (3p)
FORMULA
MCCBs
17.2 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
17
Circuit breakers for power distribution
Technical data
A1 A2
Frame size A100 250
Rated current, In A15...100 125...250
Poles [Nr] Nr 1, 2, 3 1, 2, 3
Rated service voltage, Ue (AC) 50-60 Hz V240 (1p, 2p, 3p) 240 (1p, 2p, 3p)
(DC) V125 (1p), 250 (2p,3p) 125 (1p), 250 (2p,3p)
Versions Fixed Fixed
Performance Level A N A N
Poles Nr 1 2, 3 12, 3 12, 3 12, 3
Rated ultimate short circuit breaking capacity, Icu
Interrupting rating @ 240 V 50-60 Hz (AC) kA 10 10 18 25 10 10 14 25
Interrupting rating @ 125 V (DC) 1 pole (in 2012) kA 5 - 10 - 5 - 10 -
Interrupting rating @ 250 V (DC) 2 poles in series (2p, 3p) (in 2012)
kA - 5 - 10 - 10 - 25
Reference Standard UL 489 UL 489
Isolation behavior Yes Yes
Fixing onto DIN rail DIN EN 50022 DIN EN 50022
Dimensions (Width x Depth x Height)
1 pole in 1.00 x 2.36 x 5.12 1.38 x 2.36 x 5.91
2 poles in 2.00 x 2.36 x 5.12 2.76 x 2.36 x 5.91
3 poles in 3.00 x 2.36 x 5.12 4.13 x 2.36 x 5.91
Weight
1 pole lbs 0.54 0.82
2 poles lbs 1.04 1.61
3 poles lbs 1.54 2.43
Trip Unit - Thermomagnetic TMF Ye s Yes
FORMULA
MCCBs
Low Voltage Products & Systems 17.3
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
17
Circuit breakers for power distribution
Catalog number explanation
A W
Number of Poles
-1= 1 pole (UL&IEC)
-2= 2 pole (UL&IEC)
None= 3 pole (UL&IEC)
-4= 4 pole (IEC)
Type Connectors
W=none
Trip Unit Function
T=thermalmagnetic (UL&IEC)
A=ELT - LI (IEC)
Current Rating
015=15A (UL&IEC); 016=16A (IEC)
020=20A (UL&IEC); 025=25A (UL&IEC)
030=30A (UL&IEC); 032=32A (IEC)
040=40A (UL&IEC); 050=50A (UL&IEC)
060=60A (UL&IEC); 063=63A (IEC)
070=70A (UL&IEC); 080=80A (UL&IEC)
090=90A (UL&IEC); 100=100A (UL&IEC)
125=125A (UL&IEC); 150=150A (UL&IEC)
160=160A (UL&IEC); 175=175A (UL&IEC)
200=200A (UL&IEC); 225=225A (UL&IEC)
250=250A (UL&IEC); 320=320A (IEC)
400=400A (IEC); 500=500A (IEC); 630=630A (IEC)
Interrupting Rating Class
A=adequate(UL&IEC); B=basic(IEC); C=common(IEC)
N=normal(UL&IEC); S=standard(IEC)
Frame Size:
1=100A, UL; 2=250A, UL
A=125A, IEC; B=250A, IEC; C=400A, IEC; D=630A, IEC
FORMULA
MCCBs
17.4 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
17
A1
100A
A1 - 100A Frame TMF, thermal magnetic fixed - fixed mount (F), front terminals (F)
Breaker IC at
240VAC
Rating
(A) Magnetic trip 1 pole
catalog number
2 pole
catalog number
3 pole
catalog number
A1A 10kA
15 400 A1A015TW-1 A1A015TW-2 A1A015TW
20 400 A1A020TW-1 A1A020TW-2 A1A020TW
25 400 A1A025TW-1 A1A025TW-2 A1A025TW
30 400 A1A030TW-1 A1A030TW-2 A1A030TW
40 400 A1A040TW-1 A1A040TW-2 A1A040TW
50 500 A1A050TW-1 A1A050TW-2 A1A050TW
60 600 A1A060TW-1 A1A060TW-2 A1A060TW
70 700 A1A070TW-1 A1A070TW-2 A1A070TW
80 800 A1A080TW-1 A1A080TW-2 A1A080TW
90 900 A1A090TW-1 A1A090TW-2 A1A090TW
100 1000 A1A100TW-1 A1A100TW-2 A1A100TW
A1N
1 pole
18kA
2-3 pole
25kA
15 400 A1N015TW-1 A1N015TW-2 A1A015TW
20 400 A1N020TW-1 A1N020TW-2 A1A020TW
25 400 A1N025TW-1 A1N025TW-2 A1A025TW
30 400 A1N030TW-1 A1N030TW-2 A1A030TW
40 400 A1N040TW-1 A1N040TW-2 A1A040TW
50 500 A1N050TW-1 A1N050TW-2 A1A050TW
60 600 A1N060TW-1 A1N060TW-2 A1A060TW
70 700 A1N070TW-1 A1N070TW-2 A1A070TW
80 800 A1N080TW-1 A1N080TW-2 A1A080TW
90 900 A1N090TW-1 A1N090TW-2 A1A090TW
100 1000 A1N100TW-1 A1N100TW-2 A1A100TW
1 Pole 2 Pole 3 Pole
FORMULA
MCCBs
Low Voltage Products & Systems 17.5
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
17
A2
250A, 600Y/347V, 480V ∆
Thermal-magnetic
1 Pole 2 Pole 3 Pole
A2 - 250A Frame TMF, thermal magnetic fixed - fixed mount (F), front terminals (F)
Breaker IC at
240VAC
Rating
(A) Magnetic trip 1 pole
catalog number
2 pole
catalog number
3 pole
catalog number
A2A 10kA
125 1250 A2A125TW-1 A2A125TW-2 A2A125TW
150 1500 A2A150TW-1 A2A150TW-2 A2A150TW
175 1750 A2A175TW-1 A2A175TW-2 A2A175TW
200 2000 A2A200TW-1 A2A200TW-2 A2A200TW
225 2250 A2A225TW-1 A2A225TW-2 A2A225TW
250 2500 A2A250TW-1 A2A250TW-2 A2A250TW
A1N
1 pole
18kA
2-3 pole
25kA
125 1250 A2N125TW-1 A2N125TW-2 A2N125TW
150 1500 A2N150TW-1 A2N150TW-2 A2N150TW
175 1750 A2N175TW-1 A2N175TW-2 A2N175TW
200 2000 A2N200TW-1 A2N200TW-2 A2N200TW
225 2250 A2N225TW-1 A2N225TW-2 A2N225TW
250 2500 A2N250TW-1 A2N250TW-2 A2N250TW
FORMULA
MCCBs
17.6 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
17
Accessories
Electrical
A1 - A2
1 Electrical/mechanical accessories cannot be installed on single pole breakers.
2 Rated 480Y/277 VAC for 15A.
3 When protected by a OCPD with appropriate ratings.
Cabled service release
SOR-C and UVR-C
Shunt opening release (SOR)
Frame size Voltage Catalog number
A1 - A2
12VDC KA2S9
24-30VAC/DC KA2S8
48-60VAC/DC KA2S7
110-127VAC KA2S4
220-240VAC KA2S2
The shunt opening release allows for opening of the circuit breaker by means of a non-permanent electrical control.
Operation of the release is guaranteed for a voltage between 70% and 110% of the power supply rated voltage value.
Undervoltage release (UVR)
Frame size Voltage Catalog number
A1 - A2
24-30VAC/DC KA2U8
48VAC/DC KA2U7
60VAC/DC KA2U5
110-127VAC KA2U4
220-240VAC KA2U2
The undervoltage release ensures opening of the circuit breaker for lack/lowering of the release power supply voltage.
Operation of the release is guaranteed for a voltage between 70% and 35% of the power supply rated voltage value.
After tripping, the circuit breaker can be closed again starting from a voltage higher than 85% of the power supply rated voltage
value.
Auxiliary contacts (AUX) & early auxiliary contacts (AUE)
Frame size Description 2 Pole
Catalog number
3 Pole
Catalog number
A1 - A2
AUX-C 1Q+1SY 250 VAC/DC KA2AS-2 KA2AS
AUX-C 2Q+1SY 250 VAC/DC KA2AS2-2 KA2AS2
AUX-C 1Q+1SY 24 VDC KA2ASAU-2 KA2ASAU
AUX-C 2Q+1SY 24 VDC KA2AS2AU-2 KA2AS2AU
AUX-C 250V 1 CONT. SPARE PART* KA2ASSP KA2ASSP
AUE 2 CONTACTS x RHx KA2RH-EM
The auxiliary contacts allow information about the state of the circuit breaker to be available through an electronic signal to another
apparatus. The early auxiliary contacts are normally open contacts which allow the undervoltage release to be supplied in advance
prior to the closing of the main contacts in direct and extended rotary handle operating mechanisms.
FORMULA
MCCBs
Low Voltage Products & Systems 17.7
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
17
Accessories
Mechanical
A1 - A2
Terminal F Terminal F with cable lug Terminal F with busbar
Front terminals - F
Frame size Description 1 piece catalog number 2 piece catalog number 3 piece catalog number 4 piece catalog number 6 piece catalog number
A1 KIT F A1 KA1F-1 KA1F-2 KA1F-3 KA1F-4 KA1F-6
A2 KIT F A2 KA2F-1 KA2F-2 KA2F-3 KA2F-4 KA2F-6
Front terminals are supplied as standard with all FORMULA circuit breakers.
Terminal FCCuAl Terminal FCCuAl with cable
Front terminals for copper aluminum cables - FCCuAL
Frame size Description 1 piece
catalog number
2 piece
catalog
number
3 piece
catalog
number
4 piece
catalog
number
6 piece
catalog
number
A1 KIT FC CuAl A1 80A KA1080-1 KA1080-2 KA1080-3 KA1080-4 KA1080-6
KIT FC CuAl A1 100A KA1100-1 KA1100-2 KA1100-3 KA1100-4 KA1100-6
A2 KIT FC CuAl A2 225A* KA2225-1 KA2225-2 KA2225-3 KA2225-4 KA2225-6
KIT FC CuAl A2 250A KA2250-1 KA2250-2 KA2250-3 KA2250-4 KA2250-6
* 250A Cu cables and 225A Al cables
Front extended terminals - EF (IEC only)
Frame size Description 1 piece
catalog number
2 piece
catalog
number
3 piece
catalog
number
4 piece
catalog
number
6 piece
catalog
number
A1 KIT EF A1 KA1EF-1 KA1EF-2 KA1EF-3 KA1EF-4 KA1EF-6
A2 KIT EF A2 KA2EF-1 KA2EF-2 KA2EF-3 KA2EF-4 KA2EF-6
Terminal EF Terminal EF with busbar
FORMULA
MCCBs
17.8 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
17
Accessories
Mechanical
A1 - A2
Terminal ES Terminal ES with cable lug Terminal ES with busbar
Front extended spread terminals - ES (IEC only)
Frame size Description 1 piece
catalog number
2 piece
catalog
number
3 piece
catalog
number
4 piece
catalog
number
6 piece
catalog
number
A1 KIT ES A1 KA1ES-2 KA1ES-3 KA1ES-4 KA1ES-6
A2 KIT ES A2 KA2ES-2 KA2ES-3 KA2ES-4 KA2ES-6
High terminal cover (HTC)
Low terminal cover (LTC)
Terminal covers - low profile (LTC) and high profile (HTC)
Frame size Description Catalog
number
A1 LTC 3p - 2pcs KA1LTC-3
HTC 3p - 2pcs KA1HTC-3
A2 LTC 3p - 2pcs KA2LTC-3
HTC 3p - 2pcs KA2HTC-3
A1 - A2 Sealable screws for terminal covers* KA2SSW-T
Sealable screws for front* KA2SSW-F
* IEC rated only
Phase barriers - low profile and high profile
Frame size Description
2-Piece
catalog
number
4-Piece
catalog
number
A1 PB 50mm KA1PBL-2 KA1PBL-3
A2 PB 80mm KA2PBL-2 KA2PBL-3
A1 - A2 PB 100mm KA2PBH-2 KA2PBH-3
Phase barriers
Direct handle (RHD)
Direct mount rotary handle (RHD)
Frame size Description Catalog
number
A1 - A2 RHD A1-A2 STANDARD DIRECT KA2RHD
RHD A1-A2 EMERGENCY DIRECT KA2RHDEM
FORMULA
MCCBs
Low Voltage Products & Systems 17.9
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
17
Accessories
Mechanical
A1 - A2
Extended handle (RHE)
Extended mount rotary handle (RHE)
Frame size Description Catalog
number
A1 - A2
RHE KIT A1-A2 STANDARD EXTENDED KA2RHE
RHE KIT A1-A2 EMERGENCY EXTENDED KA2RHEEM
RHE A1-A2 BASE KA2RHE-B
RHE A1-A2 SHAFT KA2RHE-S
RHE A1-A2 STANDARD HANDLE KA2RHE-H
RHE A1-A2 EMERGENCY HANDLE KA2RHE-HEM
Removable padlock in open
position (PLL)
Fixed padlock in open and
closed position (PLL)
Padlocks for lever operating mechanism (PLL)
Frame size Description Catalog
number
A1 - A2
PLL - removable in open position (1p, 2p, 3p) KA2LDOR
PLL - xed in open position (3p) KA2LDOR
PLL - xed in open and closed position (3p) KA2LD
Key lock on handle and front lever operating mechanism (RHL) (IEC only)
Frame size Description Catalog
number
A1 - A2
RHL-D open position, different keys KA2RHLO
RHL-S open position, type A key KA2RHLO-A
RHL-S open position, type B key KA2RHLO-B
RHL-S open position, type C key KA2RHLO-C
RHL-S open position, type D key KA2RHLO-D
RHL-D open and closed position, different keys
KA2RHL
Fixed padlock in open position
(PLL)
Key lock for direct handle
Bracket for fixing on DIN rail (IEC only)
Frame size Description Catalog
number
A1 - A2 Bracket for 1p, 2p, 3p KA2DIN
Bracket for DIN rail
FORMULA
MCCBs
17.10 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
17
Notes
Tmax
MCCBs
Low Voltage Products & Systems 17.11
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
17
Introduction
ABB is once again demonstrating its
commitment to new product development
and its superiority in product technology.
Never before has the industry seen such high
performance, versatility and standardization in a
range of molded case circuit breakers.
The ABB Tmax line of circuit breakers, with a
range up to 3000A, has several key features
that go along with its very small size:
Double insulation – this construction
characteristic allows for the UL Listed eld
installation of internal accessories without
exposure to energized parts.
Complete range of electrical and
mechanical accessories
Positive operation – breakers from ABB
ensure that the toggle indicates the precise
position of the moving contacts. This
guarantees safe and reliable signaling by
the device.
Installation – Tmax molded case circuit
breakers can be installed in panels and
switchboards in either the horizontal
or vertical planes while being fed from
either end without any derating of their
performance characteristics.
Interrupting ratings at 480VAC up to
150kAIC.
Compact size
All Tmax molded case circuit breakers
are UL Listed and IEC rated for global
application and acceptance.
All versions of the Tmax family are suitable
for reverse feed applications.
The ABB Tmax product line has the performance
and accessories to satisfy all industry
requirements in the 600VAC to 600VDC ranges.
Frame sizes — Nine basic sizes
The ABB Tmax series includes nine basic frame
sizes as well as the T1 single pole with the range
rated from 15A to 3000A at 480VAC. The various
versions carry the following interrupting capacities:
B Basic breaking capacity
N Normal breaking capacity
S Standard breaking capacity
H High breaking capacity
L Extra high breaking capacity
V Very high breaking capacity
Derived versions
Thermal magnetic
Electronic
Molded case switches
Motor circuit protectors (MCPs)
Direct current (DC) rated
ABB Tmax versions
Fixed: all models
Drawout or plug-in: T2, T3, Ts3, T4, T5, T6,
T7 & T7M
UL File #E93565 (breakers and MCPs)
#E116596 (Accessories)
#E116595 (Molded case switches)
Tmax
Molded case circuit breakers
Tmax
Molded case circuit breakers
Tmax
MCCBs
17.12 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
17
Selection Guide
Circuit breakers for power distribution
T1 – Ts3
1 In15A = 10kA@277VAC 10kA@347VAC
2 In15A = 35kA@240VAC 14kA@480Y/277 VAC
3 T5 600 with electronic trip units only and in three pole version
4 2p breakers: available only in N interrupting rating
5 In from 15A up to 30A=65kA@480V AC
T1 1P T1 T2 T3 Ts3
Type Tmax T1 1p Tmax T1 Tmax T2 Tmax T3 Tmax Ts3 Tmax Ts3
Frame size [A] 100 100 100 225 150 225
N u m b e r o f p o l e s [Nr] 1 3-4 3-4 3-4 2-3-4 2-3-4
R a t e d v o l t a g e AC (50-60Hz) [V] 347 600Y/347 480 600Y/347 600 480
DC [V] 500 500 600 500
Interrupting ratings B N S H N S N H L N H L
240V AC [kA rms] 50 265 150 50 65 65 100 150 65 100 150
277V AC [kA rms] 18 1
347V AC [kA rms] 14 1
480V AC [kA rms] 22 235 65 25 35 25 50 85 525 50 65
600Y/347V AC [kA rms] 10 10 10
600V AC [kA rms] 14 14 25
250V DC (2 poles in series) [kA rms] 25 25 35
500V DC (3 poles in series) [kA rms] 25 25 35
500V DC (2 poles in series) [kA rms] 35 50 65 20 35 50
600V DC (3 poles in series) [kA rms] 20 35 50
Trip units TMF
TMD/TMA
ELT
MA
Electronic
Dimensions H[in/mm] 5.12/130 5.12/130 5.12/130 5.9/150 6.7/170 6.7/170
W 3p [in/mm] 1/25.4 3/76 3.54/90 4.13/105 4.13/105 4.13/105
D [in/mm] 2.76/70 2.76/70 2.76/70 2.76/70 4.07/103.5 4.07/103.5
Mechanical life [No. operations] 25000 25000 25000 25000 25000 25000
Tmax
MCCBs
Low Voltage Products & Systems 17.13
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
17
Selection Guide
Circuit breakers for power distribution
T4 – T8
Type Tmax T4 Tmax T5 Tmax T6 Tmax T7/T7M Tmax T8
Frame size [A] 250 400-600 3800 1000-1200 1600, 2000,
2500 & 3000
N u m b e r o f p o l e s [Nr] 2-3-4 42-3-4 43-4 3-4 3-4
R a t e d v o l t a g e AC (50-60Hz) [V] 600 600 600 600 600
DC [V] 600 600 600
Interrupting ratings N S H L V N S H L V N S H L S H L V
240V AC [kA rms] 65 100 150 200 200 65 100 150 200 200 65 100 200 200 65 100 150 125
277V AC [kA rms]
347V AC [kA rms]
480V AC [kA rms] 25 35 65 100 150 25 35 65 100 150 35 50 65 100 50 65 100 125
600Y/347V AC [kA rms]
600V AC [kA rms] 18 25 35 65 100 18 25 35 65 100 20 25 35 42 25 50 65 100
250V DC (2 poles in series) [kA rms]
500V DC (3 poles in series) [kA rms]
500V DC (2 poles in series) [kA rms] 25 35 50 65 100 25 35 50 65 100 35 35 50 65
600V DC (3 poles in series) [kA rms] 16 25 35 50 65 16 25 35 50 65 20 20 35 50
Trip units TMF
TMD/TMA
ELT
MA
Electronic
Dimensions H[in/mm] 8.07/205 8.07/205 10.55/268 10.55/268 15 / 382
W 3p [in/mm] 4.13/105 5.51/140 8.26/210 8.26/210 16.8 / 427
D [in/mm] 4.07/103.5 4.07/103.5 4.07/103.5 6.06/154 (toggle)
7/178 (motor) 11.2 / 282
Mechanical life [No. operations] 20,000 20,000 20,000 10,000 15,000
1 In15A = 10kA@277 VAC 10kA@347 VAC
2 In15A = 35kA@240 VAC 14kA@480Y/277 VAC
3 T5 600 with electronic trip units only and in three pole version-
4 2p T4N250 and T5N400 available only in N interrupting capacity.
5 In from 15A up to 30A=65kA@480 VAC
6 Applies to MCS only.
T4 T5 T6 T7 T8
Tmax
MCCBs
17.14 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
17
T3 S 080 T W - 4 xxx
Interrupting rating class
B = Basic
N = Normal
S = Standard
H = High
L = Extra High
V = Very high
Q = 100% Rated
Current rating
015 = 15A
080 = 80A
100 = 100A
225 = 225A
250 = 250A
400 = 400A
600 = 600A
800 = 800A
1200 = 1200A
Trip unit function
B = LS/I (AC only)
D = Molded Case Switch (MCS)
T = Thermal-magnetic
M = Magnetic only (MCP)
E5 = Electronic MCP (AC only)
C = LSI (AC only)
E = LSIG (AC only)
CZ = LSI/PD 2
EZ = LSIG/PD 2
P = LI - LCD Display 3
R = LSI - LCD Display 3
S = LSIG - LCD Display 3
Type connectors
W = None
L = Lugs included
Number of poles
-1 =1 pole (T1 only)
-2 = 2 pole
-4 = 4 pole
None = 3 pole
Accessories (added in alpha-numeric order) 1
A = Auxiliary Switch
S_ = Shunt trip with voltage code
U_ = Undervoltage release with voltage code
Frame size
T1 = 100A
T2 = 100A
T3 = 225A
Ts3 = 225A
T4 = 250A
T5 = 400A, 600A
T6 = 600A, 800A
T7 = 1000A, 1200A (toggle)
1 Consult ABB for factory installed accessories.
2 Trip unit with communication module.
3 Available on T7 toggle version only.
General information
Catalog number explanation
Tmax
MCCBs
Low Voltage Products & Systems 17.15
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
17
T1
100A, 600Y/347V, 480V ∆
Thermal-magnetic
UL489 / CSA C22.2 Interrupting capacity (kA RMS)
Voltage Continuous rating B (1 pole) N
240VAC 15 – 100A 50 1
347VAC 15A
20 – 100A
10
14
480VAC ∆ 15A 2
20 – 100A
14
22
600Y/347VAC 15 – 100A 10
250VDC 2 pole series 15 – 100A 25
500VDC 3 pole series 15 – 100A 25
T1
General
The T1 breaker family ranges from 15 through 100 amperes. The T1 trip units are
non-interchangeable and use the very latest technology in electromagnetic relays for
overcurrent trip protection. Thermal overload protection is provided by heat sensitive
bimetals. Short circuit protection for the breaker is accomplished using a precise
magnetic coil. State of the art construction in contacts and arcing chambers aid in
limiting damaging fault currents through the protected circuits.
Standards
The UL489/CSA 22.2 version of T1 also carries an IEC-60947-2 rating.
Versions
The T1 frame is available in two versions:
T = Thermal-magnetic, xed
D = Molded case switch
Performance levels
The T1 breaker has two performance levels available:
B = Basic single pole
N = Normal three pole
Number of poles
The T1 molded case circuit breaker is available in single, three and four pole versions.
Estimate 4 pole pricing by adding 35% to the 3 pole price and contact your ABB sales
person for details.
Molded case switches
UL489 switches include no overcurrent protection except for a high instantaneous trip
mechanism for self protection.
1 In 15A 35kA @ 240VAC.
2 15A available in 480Y/277 VAC only.
3 Interrupting capacity for 16-20A is 16kA
Dimensions 3P Fixed Version 5.12H x 3.00W x 2.76D
Weight 2.34 (Ibs)
IEC 60947-2 Interrupting capacity (kA RMS)
Voltage Continuous rating B (1 pole) N
230VAC 15 – 100A 25 350
415VAC 15 – 100A 36
690VAC 15 – 100A 6
500VDC 3 pole series 15 – 100A 36
Tmax
MCCBs
17.16 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
17
T1
100A, 600Y/347V, 480V ∆
Thermal-magnetic/Molded Case Switch
1 Electrical/mechanical accessories cannot be installed on single pole breakers.
2 Rated 480Y/277 VAC for 15A.
3 When protected by a OCPD with appropriate ratings.
T1B TMF — Single pole thermal magnetic fixed 1
Breaker IC at
277VAC
Rating
(A)
Magnetic trip
(A)
1 pole, 277VAC
catalog number
T1B
10kA 15 1000 T1B015TL-1
18kA
20 1000 T1B020TL-1
25 1000 T1B025TL-1
30 1000 T1B030TL-1
40 1000 T1B040TL-1
50 1500 T1B050TL-1
60 1500 T1B060TL-1
70 1500 T1B070TL-1
80 1500 T1B080TL-1
90 1500 T1B090TL-1
100 1500 T1B100TL-1
T1N TMF — 3 pole thermal magnetic fixed
Breaker IC at
480VAC
Rating
(A)
Magnetic trip
(A)
3 pole,
600Y/347VAC/500VDC
catalog number
T1N
14kA 15 1000 T1N015TL 2
22kA
20 1000 T1N020TL
25 1000 T1N025TL
30 1000 T1N030TL
40 1000 T1N040TL
50 1500 T1N050TL
60 1500 T1N060TL
70 1500 T1N070TL
80 1500 T1N080TL
90 1500 T1N090TL
100 1500 T1N100TL
T1N-D — Molded case switch
Breaker Interrupting
capacity 3
Rating
(A)
Magnetic trip
(A)
480VAC/500VDC
catalog number
T1-D 240V,
50kA 100 1000 T1N100DL
T1N TMF — 100% Rated thermal-magnetic
Breaker IC at
480VAC
Rating
(A)
Magnetic trip
(A)
3 pole,
600Y/347VAC/500VDC
catalog number
T1N
14kA 15 1100 T1NQ015TL
22kA
20 1000 T1NQ020TL
25 1000 T1NQ025TL
30 1000 T1NQ030TL
40 1000 T1NQ040TL
50 1500 T1NQ050TL
60 1500 T1NQ060TL
70 1500 T1NQ070TL
80 1500 T1NQ080TL
90 1500 T1NQ090TL
100 1500 T1NQ100TL
Tmax
MCCBs
Low Voltage Products & Systems 17.17
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
17
T2
100A, 480V ∆
Thermal-magnetic/electronic/current limiting
T2
General
The T2 breaker family ranges from 15 through 100 amperes. The T2 trip units are
non-interchangeable and use the very latest technology in electromagnetic relays for
overcurrent trip protection as well as a version with microprocessor-based electronic
trip unit. Thermal overload protection is provided by heat sensitive bimetals. State of
the art construction in contacts and arcing chambers aid in limiting damaging fault
currents through the protected circuits.
Standards
The UL489/CSA 22.2 version of T2 also carries an IEC-60947-2 rating.
Versions
The T2 frame is available in four versions:
T = Thermal-magnetic, xed
B = Adjustable LS/I electronic
M = Magnetic only (MCP)
E5 = Electronic instantaneous only (MCP)
Trip functions
These tripping functions are available:
L = Long time
S = Short time
I - Instantaneous
Performance levels
The T2 breaker has two performance levels available:
S = Standard
H = High - UL Current Limiting
Number of poles
The T2 is available in three and four pole versions. Estimate 4 pole pricing by adding
35% to the 3 pole price and contact your ABB sales person for details.
UL489 / CSA C22.2 Interrupting capacity (kA RMS)
Voltage Continuous rating S H
240VAC 15 – 100A 65 150
480VAC ∆ 15 – 100A 35 65
Dimensions 3P Fixed Version 5.12H x 3.54W x 2.76D
Weight 2.84 (Ibs)
IEC 60947-2 Interrupting capacity (kA RMS)
Voltage Continuous rating S H
230VAC 15 – 100A 85 100
415VAC 15 – 100A 50 70
690VAC 15 – 100A 78
500VDC 3 pole series 15 – 100A 50 70
Tmax
MCCBs
17.18 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
17
T2
100A, 480V ∆
Thermal-magnetic/current limiting
T2 — 100A TMF thermal magnetic xed
Breaker IC at
480VAC
Rating
(A)
Magnetic trip
(A)
3 pole, 480VAC
Catalog number
T2S
15 500 T2S015TW
35kA
20 500 T2S020TW
25 500 T2S025TW
30 500 T2S030TW
40 500 T2S040TW
50 500 T2S050TW
60 600 T2S060TW
70 700 T2S070TW
80 800 T2S080TW
90 900 T2S090TW
100 1000 T2S100TW
T2H
UL
current
limiting
65kA
15 500 T2H015TW
20 500 T2H020TW
25 500 T2H025TW
30 500 T2H030TW
40 500 T2H040TW
50 500 T2H050TW
60 600 T2H060TW
70 700 T2H070TW
80 800 T2H080TW
90 900 T2H090TW
100 1000 T2H100TW
T2 – 100A TMF, 100% rated thermal magnetic xed
Breaker IC at
480VAC
Rating
(A)
Magnetic trip
(A)
3 pole, 480VAC
Catalog number
T2S
15 500 T2SQ015TW
35kA
20 500 T2SQ020TW
25 500 T2SQ025TW
30 500 T2SQ030TW
40 500 T2SQ040TW
50 500 T2SQ050TW
60 600 T2SQ060TW
70 700 T2SQ070TW
80 800 T2SQ080TW
90 900 T2SQ090TW
100 1000 T2SQ100TW
T2H
UL
current
limiting
65kA
15 500 T2HQ015TW
20 500 T2HQ020TW
25 500 T2HQ025TW
30 500 T2HQ030TW
40 500 T2HQ040TW
50 500 T2HQ050TW
60 600 T2HQ060TW
70 700 T2HQ070TW
80 800 T2HQ080TW
90 900 T2HQ090TW
100 1000 T2HQ100TW
Tmax
MCCBs
Low Voltage Products & Systems 17.19
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
17
T2 — 100A Frame, electronic trip unit (AC only)
Breaker IC at
480VAC Trip unit type CT rating 3 pole, 480VAC
catalog number
T2S 35kA PR221DS-LS/I
25A T2S025BW
60A T2S060BW
100A T2S100BW
T2H
UL Current
Limiting
65kA PR221DS-LS/I
25A T2H025BW
60A T2H060BW
100A T2H100BW
T2 — 100A Frame, instantaneous only (MCP)
Breaker IC at
480VAC Trip unit type Rating Adjustment
range
3 pole, 480VAC
Catalog number
T2S 35kA Mag only
20A 120 - 240 T2S020MW
50A 300 - 600 T2S050MW
100A 600 – 1200 T2S100MW
T2H 65kA Mag only
20A 120 - 240 T2H020MW
50A 300 - 600 T2H050MW
100A 600 – 1200 T2H100MW
T2 — 100A Frame, instantaneous only, electronic (MCP - AC only)
Breaker IC at
480VAC
Trip unit type Rating Adjustment
range
3 pole, 480VAC
Catalog number
T2S 35kA Instantaneous
only
25A 25 - 250 T2S025E5W
60A 60 - 600 T2S060E5W
100A 100 - 1000 T2S100E5W
T2H 65kA Instantaneous
only
25A 25 - 250 T2H025E5W
60A 60 - 600 T2H060E5W
100A 100 - 1000 T2H100E5W
T2
100A, 480V ∆, 100% rated
Electronic/Current limiting/MCP
T2 – 100A Frame 100% rated, electronic trip unit (AC only)
Breaker IC at
480VAC Trip unit type CT rating 3 pole, 480VAC
catalog number
T2S 35kA PR221DS-LS/I
25A T2SQ025BW
60A T2SQ060BW
100A T2SQ100BW
T2H
UL Current
Limiting
65kA PR221DS-LS/I
25A T2HQ025BW
60A T2HQ060BW
100A T2HQ100BW
Tmax
MCCBs
17.20 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
17
T3
225A, 600Y/347V, 480V ∆
Thermal-magnetic
T3
General
The T3 breaker family ranges from 60 through 225 amperes. The T3 trip units are
non-interchangeable and use the very latest technology in electromagnetic relays for
overcurrent trip protection. Thermal overload protection is provided by heat sensitive
bimetals. Short circuit protection begins at 10 times the thermal rating of the breaker
using a precise magnetic coil. State of the art construction in contacts and arcing
chambers aid in limiting damaging fault currents through the protected circuits.
Standards
The UL489/CSA 22.2 version of T3 also carries an IEC-60947-2 rating.
Versions
The T3 frame is available in three versions:
T = Thermal-magnetic, xed
M = Magnetic only (MCP)
D = Molded case switch
Performance levels
The T3 breaker has two performance levels available:
N = Normal
S = Standard
Number of poles
The T3 molded case circuit breaker is available in three and four pole versions.
Estimate 4 pole pricing by adding 35% to the 3 pole price and contact your ABB
sales person for details.
Molded case switches
UL489 switches include no overcurrent protection except for a high instantaneous
trip mechanism for self protection.
UL489 / CSA C22.2 Interrupting capacity (kA RMS)
Voltage Continuous rating N S
240VAC 60 – 225A 50 65
480VAC ∆ 60 – 225A 25 35
600Y/347VAC 60 – 225A 10 10
250VDC 2 pole series 60 – 225A 25 35
500VDC 3 pole series 60 – 225A 25 35
Dimensions 3P Fixed Version 5.9H x 4.13W x 2.76D
Weight 5.45 (Ibs)
IEC 60947-2 Interrupting capacity (kA RMS)
Voltage Continuous rating N S
230VAC 60 – 225A 50 85
415VAC 60 – 225A 36 50
690VAC 60 – 225A 5 8
750VDC 3 pole series 60 – 225A 36 50
Tmax
MCCBs
Low Voltage Products & Systems 17.21
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
17
T3
225A, 600Y/347V, 480V ∆
Thermal-magnetic
T3 — 225A Frame TMF, thermal magnetic xed
Breaker IC at
480VAC
Rating
(A)
Magnetic trip
(A)
3 pole, 480VAC/500VDC
Catalog number
T3N 25kA
60 600 T3N060TW
70 700 T3N070TW
80 800 T3N080TW
90 900 T3N090TW
100 1000 T3N100TW
125 1250 T3N125TW
150 1500 T3N150TW
175 1750 T3N175TW
200 2000 T3N200TW
225 2250 T3N225TW
T3S 35kA
60 600 T3S060TW
70 700 T3S070TW
80 800 T3S080TW
90 900 T3S090TW
100 1000 T3S100TW
125 1250 T3S125TW
150 1500 T3S150TW
175 1750 T3S175TW
200 2000 T3S200TW
225 2250 T3S225TW
T3 – 225A Frame TMF, 100% rated thermal magnetic xed
Breaker IC at
480VAC
Rating
(A)
Magnetic trip
(A)
3 pole, 600/347V
VAC/500VDC
Catalog number
T3N 25kA
60 600 T3NQ060TW
70 700 T3NQ070TW
80 800 T3NQ080TW
90 900 T3NQ090TW
100 1000 T3NQ100TW
125 1250 T3NQ125TW
150 1500 T3NQ150TW
175 1750 T3NQ175TW
200 2000 T3NQ200TW
225 2250 T3NQ225TW
T3S 35kA
60 600 T3SQ060TW
70 700 T3SQ070TW
80 800 T3SQ080TW
90 900 T3SQ090TW
100 1000 T3SQ100TW
125 1250 T3SQ125TW
150 1500 T3SQ150TW
175 1750 T3SQ175TW
200 2000 T3SQ200TW
225 2250 T3SQ225TW
Tmax
MCCBs
17.22 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
17
T3
225A, 600Y/347V, 480V ∆
MCP/Molded case switch
1 When protected by a OCPD with appropriate ratings.
T3 — 225A Frame instantaneous only, (MCP)
Breaker IC at
488-VAC
Trip unit
type
Rating Adjustment
range
3 pole, 480VAC
Catalog number
T3S 35kA Mag only
100A 600 – 1200 T3S100MW
125A 750 - 1500 T3S125MW
150A 900 - 1800 T3S150MW
200A 1200 - 2400 T3S200MW
T3S-D — Molded case switch
Breaker Interrupting
capacity 1
Rating
(A)
Magnetic trip
(A)
3 pole, 480VAC/500VDC
Catalog number
T3S-D 240V, 65kA 150 1500 T3S150DW
480V, 35kA 225 2250 T3S225DW
Tmax
MCCBs
Low Voltage Products & Systems 17.23
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
17
Ts3
150A, 600V ∆, 225A, 480V ∆
Thermal magnetic
General
The Ts3 breaker family ranges from 15 through 225 amperes. The Ts3 trip
mechanisms are non-interchangeable and use sensitive electromagnetic relays for
overcurrent trip protection. Heat sensitive bimetals are used for thermal overcurrent
protection. Short circuit current protection begins at 10 times the thermal rating of
the breaker and uses a magnetic coil principle.
Standards
The UL489/CSA 22.2 version of Ts3 also carries an IEC-60947-2 rating.
Versions
To meet all application needs, the Ts3 is available in various versions:
T =Thermal-magnetic
D = Molded case switch
M = Magnetic only (MCP)
Performance level
Each version is also available in different maximum fault interrupting levels
N = Normal
H = High
L = Extra high
Number of poles
The Ts3 is available in two, three and four pole versions. Estimate 4 pole pricing by
adding 35% to the 3 pole price and contact your ABB sales person for details.
Molded case switches
UL489 switches include no overcurrent protection except for a high instantaneous
trip mechanism for self protection.
1 15-30A are 65kA at 480VAC
Ts3
Dimensions 3P Fixed Version 6.7H x 4.13W x 4.07D
Weight 6.75 (Ibs)
UL/CSA Interrupting capacity (kA RMS)
UL489 / CSA C22.2
Voltage N H L
150AF, 15A-150A
240 VAC 65 100 150
480 VAC 25 50 85 1
600 VAC 14 14 25
500 VDC 35 50 65
600 VDC 20 35 50
225AF, 175A-225A
240 VAC 65 100 150
480 VAC 25 50 65
600 VAC
500 VDC 20 35 50
600 VDC
IEC-60947-2 Interrupting capacity (kA RMS)
230 VAC 65 100 170
415 VAC 35 65 85
690 VAC 14 18 20
750 VDC 220 35 50
Tmax
MCCBs
17.24 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
17
Ts3
150A, 600V ∆, 225A, 480V ∆
Thermal magnetic
Ts3
150A 600VAC/225A 480VAC
Thermal Magnetic Trip Units
Breaker IC at 480VAC kA Rating Magnetic
trip
2 pole,
600VAC/500VDC
catalog number
3 pole, 600VAC/DC
catalog number
Ts3N 25
15A 500A Ts3N015TW-2 Ts3N015TW
20A 500A Ts3N020TW-2 Ts3N020TW
25A 500A Ts3N025TW-2 Ts3N025TW
30A 500A Ts3N030TW-2 Ts3N030TW
35A 500A Ts3N035TW-2 Ts3N035TW
40A 500A Ts3N040TW-2 Ts3N040TW
50A 500A Ts3N050TW-2 Ts3N050TW
60A 600A Ts3N060TW-2 Ts3N060TW
70A 700A Ts3N070TW-2 Ts3N070TW
80A 800A Ts3N080TW-2 Ts3N080TW
90A 900A Ts3N090TW-2 Ts3N090TW
100A 1000A Ts3N100TW-2 Ts3N100TW
125A 1250A Ts3N125TW-2 Ts3N125TW
150A 1500A Ts3N150TW-2 Ts3N150TW
Breaker IC at 480VAC kA Rating Magnetic
trip
2 pole,
600VAC/500VDC
catalog number
3 pole, 600VAC/DC
catalog number
Ts3H 50
15A 500A Ts3H015TW-2 Ts3H015TW
20A 500A Ts3H020TW-2 Ts3H020TW
25A 500A Ts3H025TW-2 Ts3H025TW
30A 500A Ts3H030TW-2 Ts3H030TW
35A 500A Ts3H035TW-2 Ts3H035TW
40A 500A Ts3H040TW-2 Ts3H040TW
50A 500A Ts3H050TW-2 Ts3H050TW
60A 600A Ts3H060TW-2 Ts3H060TW
70A 700A Ts3H070TW-2 Ts3H070TW
80A 800A Ts3H080TW-2 Ts3H080TW
90A 900A Ts3H090TW-2 Ts3H090TW
100A 1000A Ts3H100TW-2 Ts3H100TW
125A 1250A Ts3H125TW-2 Ts3H125TW
150A 1500A Ts3H150TW-2 Ts3H150TW
Breaker IC at 480VAC kA Rating Magnetic
trip
2 pole,
600VAC/500VDC
catalog number
3 pole, 600VAC/DC
catalog number
Ts3L
65
15A 500A Ts3L015TW-2 Ts3L015TW
20A 500A Ts3L020TW-2 Ts3L020TW
25A 500A Ts3L025TW-2 Ts3L025TW
30A 500A Ts3L030TW-2 Ts3L030TW
85
35A 500A Ts3L035TW-2 Ts3L035TW
40A 500A Ts3L040TW-2 Ts3L040TW
50A 500A Ts3L050TW-2 Ts3L050TW
60A 600A Ts3L060TW-2 Ts3L060TW
70A 700A Ts3L070TW-2 Ts3L070TW
80A 800A Ts3L080TW-2 Ts3L080TW
90A 900A Ts3L090TW-2 Ts3L090TW
100A 1000A Ts3L100TW-2 Ts3L100TW
125A 1250A Ts3L125TW-2 Ts3L125TW
150A 1500A Ts3L150TW-2 Ts3L150TW
NOTE: See pages 17.71 - 17.83 for electrical/mechanical accessories.
Tmax
MCCBs
Low Voltage Products & Systems 17.25
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
17
Ts3
150A, 600V ∆, 225A, 480V ∆, 100% rated
Thermal magnetic
Ts3
150A 600VAC/225A 480VAC
Thermal Magnetic Trip Units 100% Rated
Breaker IC at
480VAC Rating Magnetic
trip
3 pole 600VAC/DC
catalog number
Ts3NQ 25
15A 500A Ts3NQ015TW
20A 500A Ts3NQ020TW
25A 500A Ts3NQ025TW
30A 500A Ts3NQ030TW
35A 500A Ts3NQ035TW
40A 500A Ts3NQ040TW
50A 500A Ts3NQ050TW
60A 600A Ts3NQ060TW
70A 700A Ts3NQ070TW
80A 800A Ts3NQ080TW
90A 900A Ts3NQ090TW
100A 1000A Ts3NQ100TW
125A 1250A Ts3NQ125TW
150A 1500A Ts3NQ150TW
Breaker IC at
480VAC Rating Magnetic
trip
3 pole
catalog number
Ts3HQ 50kA
15A 500A Ts3HQ015TW
20A 500A Ts3HQ020TW
25A 500A Ts3HQ025TW
30A 500A Ts3HQ030TW
35A 500A Ts3HQ035TW
40A 500A Ts3HQ040TW
50A 500A Ts3HQ050TW
60A 600A Ts3HQ060TW
70A 700A Ts3HQ070TW
80A 800A Ts3HQ080TW
90A 900A Ts3HQ090TW
100A 1000A Ts3HQ100TW
125A 1250A Ts3HQ125TW
150A 1500A Ts3HQ150TW
Breaker IC at
480VAC Rating Magnetic
trip
3 pole
catalog number
Ts3LQ
65kA
15A 500A Ts3LQ015TW
20A 500A Ts3LQ020TW
25A 500A Ts3LQ025TW
30A 500A Ts3LQ030TW
85kA
35A 500A Ts3LQ035TW
40A 500A Ts3LQ040TW
50A 500A Ts3LQ050TW
60A 600A Ts3LQ060TW
70A 700A Ts3LQ070TW
80A 800A Ts3LQ080TW
90A 900A Ts3LQ090TW
100A 1000A Ts3LQ100TW
125A 1250A Ts3LQ125TW
150A 1500A Ts3LQ150TW
NOTE: See pages 17.71-17.83 for electrical/mechanical accessories.
Tmax
MCCBs
17.26 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
17
1 When protected by a OCPD with appropriate ratings.
2 480 VAC maximum
Ts3
150/225A 600VAC
MCP/Molded case switch
Molded case switch 2
Type IC at 480V (2) Magnetic trip Amps 3 pole 600V
catalog number
Ts3H 50 1500 150 Ts3H150DW
50 2250 225 1Ts3H225DW
Magnetic only (MCP)
Breaker IC at 480VAC Trip unit type Rating Adjustment
range
3 pole 600VAC
Catalog number
Ts3L
25 Magnetic only 3 12-36 Ts3L003MW
25 Magnetic only 5 20-60 Ts3L005MW
25 Magnetic only 10 40-120 Ts3L010MW
25 Magnetic only 25 100-300 Ts3L025MW
85 Magnetic only 50 200-600 Ts3L050MW
Ts3L
85 Magnetic only 100 400-1200 Ts3L100MW
85 Magnetic only 125 500-1500 Ts3L125MW
85 Magnetic only 150 600-1500 Ts3L150MW
65 Magnetic only 175 1700-2100 Ts3L175MW
65 Magnetic only 200 1800-2400 Ts3L200MW
NOTE: See pages 17.71-17.83 for electrical/mechanical accessories.
Tmax
MCCBs
Low Voltage Products & Systems 17.27
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
17
T4
250A, 600V ∆
Electronic and thermal magnetic
T4
General
The T4 breaker is a 250 amp frame with either a microprocessor based over current
protective trip system or a thermal magnetic trip unit.
Standards
The UL489/CSA 22.2 version of T4 also carries an IEC-60947-2 rating.
Versions
To meet all application requirements, the T4 is available in the following versions:
T = Thermal-magnetic
B = Selectable & adjustable LI or LS
C = Adjustable LSI
E = Adjustable LSIG
D = Molded Case Switch
E5 = Electronic instantaneous only (MCP)
Trip functions
These trip functions are available:
L = Long time
S = Short time
I = Instantaneous
G = Ground fault
Performance levels
Each version is also available in different maximum fault interrupting levels:
N = Normal
S = Standard
H = High - UL Current Limiting
L = Extra high
V = Very high - UL Current Limiting
Number of poles 3
The T4 is available in two, three and four pole versions. Estimate 4 pole pricing by
adding 35% to the 3 pole price and contact your ABB sales person for details.
UL489 / CSA C22.2 Interrupting capacity (kA RMS)
Voltage N S H L V
240VAC 65 100 150 200 200
480VAC 25 35 65 100 150
600VAC 18 25 35 65 100
500VDC 1 25 35 50 65 100
600VDC 2 16 25 35 50 65
1 2 poles in series.
2 3 poles in series.
3 2 pole breakers available in N version only. 4 pole breakers available in N and H version only.
Dimensions 3P Fixed Version 8.07H x 4.13W x 4.07D
Weight 6.18 (Ibs)
IEC 60947-2 Interrupting capacity (kA RMS)
Voltage N S H L V
230VAC 70 85 100 200 200
415VAC 36 50 70 120 200
690VAC 20 25 40 70 80
750VDC 2 16 25 36 50 70
Tmax
MCCBs
17.28 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
17
T4
250A, 600V ∆
Adjustable thermal magnetic
20A - 250A Frame
Breaker IC at
480VAC Rating Magnetic
trip
2 pole, 600VAC/600VDC
catalog number
3 pole, 600VAC/600VDC
catalog number
T4N 25
125A 625-1250 T4N125TW-2 T4N125TW
150A 750-1500 T4N150TW-2 T4N150TW
200A 1000-2000 T4N200TW-2 T4N200TW
250A 1250-2500 T4N250TW-2 T4N250TW
T4S 35
125A 625-1250 T4S125TW
150A 750-1500 T4S150TW
200A 1000-2000 T4S200TW
250A 1250-2500 T4S250TW
T4H
UL Current
Limiting
65
125A 625-1250 T4H125TW
150A 750-1500 T4H150TW
200A 1000-2000 T4H200TW
250A 1250-2500 T4H250TW
T4L 100
125A 625-1250 T4L125TW
150A 750-1500 T4L150TW
200A 1000-2000 T4L200TW
250A 1250-2500 T4L250TW
T4V
UL Current
Limiting
150
125A 625-1250 T4V125TW
150A 750-1500 T4V150TW
200A 1000-2000 T4V200TW
250A 1250-2500 T4V250TW
NOTE: See pages 17.71-17.83 for electrical/mechanical accessories.
Tmax
MCCBs
Low Voltage Products & Systems 17.29
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
17
30A - 250A Frame 100% rated
Breaker
IC at 480 VAC
kA Rating
Magnetic
trip
3 pole,
600VAC/600VDC
Catalog number
T4N 25
125A 625-1250 T4NQ125TW
150A 750-1500 T4NQ150TW
200A 1000-2000 T4NQ200TW
250A 1250-2500 T4NQ250TW
T4S 35
125A 625-1250 T4SQ125TW
150A 750-1500 T4SQ150TW
200A 1000-2000 T4SQ200TW
250A 1250-2500 T4SQ250TW
T4H
UL Current
Limiting
65
125A 625-1250 T4HQ125TW
150A 750-1500 T4HQ150TW
200A 1000-2000 T4HQ200TW
250A 1250-2500 T4HQ250TW
T4L 100
125A 625-1250 T4LQ125TW
150A 750-1500 T4LQ150TW
200A 1000-2000 T4LQ200TW
250A 1250-2500 T4LQ250TW
T4V
UL Current
Limiting
150
125A 625-1250 T4VQ125TW
150A 750-1500 T4VQ150TW
200A 1000-2000 T4VQ200TW
250A 1250-2500 T4VQ250TW
NOTE: See pages 17.71-17.83 for electrical/mechanical accessories.
T4
250A, 600V ∆ 100% rated
Adjustable thermal magnetic
Tmax
MCCBs
17.30 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
17
T4
250A, 600V ∆
Electronic (AC only)
100A Frame, electronic trip unit (AC only)
Breaker IC at 480VAC
kA
Trip
Unit
2 pole, 600V
catalog number
3 pole, 600V
catalog number
PR221 LS/I T4N100BW-2 T4N100BW
T4N 25 PR222 LSI T4N100CW-2 T4N100CW
PR222 LSIG T4N100EW-2 T4N100EW
PR221 LS/I - T4S100BW
T4S 35 PR222 LSI - T4S100CW
PR222 LSIG - T4S100EW
T4H
UL Current
Limiting
PR221 LS/I - T4H100BW
65 PR222 LSI - T4H100CW
PR222 LSIG - T4H100EW
PR221 LS/I - T4L100BW
T4L 100 PR222 LSI - T4L100CW
PR222 LSIG - T4L100EW
T4V
UL Current
Limiting
PR221 LS/I - T4V100BW
150 PR222 LSI - T4V100CW
PR222 LSIG - T4V100EW
150A Frame, electronic trip unit (AC only)
Breaker IC at 480VAC
kA
Trip
Unit
2 pole, 600V
catalog number
3 pole, 600V
catalog number
PR221 LS/I T4N150BW-2 T4N150BW
T4N 25 PR222 LSI T4N150CW-2 T4N150CW
PR222 LSIG T4N150EW-2 T4N150EW
PR221 LS/I - T4S150BW
T4S 35 PR222 LSI - T4S150CW
PR222 LSIG - T4S150EW
T4H
UL Current
Limiting
PR221 LS/I - T4H150BW
65 PR222 LSI - T4H150CW
PR222 LSIG - T4H150EW
PR221 LS/I - T4L150BW
T4L 100 PR222 LSI - T4L150CW
PR222 LSIG - T4L150EW
T4V
UL Current
Limiting
PR221 LS/I - T4V150BW
150 PR222 LSI - T4V150CW
PR222 LSIG - T4V150EW
250A Frame, electronic trip unit (AC only)
Breaker IC at 480VAC
kA
Trip
Unit
2 pole, 600V
catalog number
3 pole, 600V
catalog number
PR221 LS/I T4N250BW-2 T4N250BW
T4N 25 PR222 LSI T4N250CW-2 T4N250CW
PR222 LSIG T4N250EW-2 T4N250EW
PR221 LS/I - T4S250BW
T4S 35 PR222 LSI - T4S250CW
PR222 LSIG - T4S250EW
T4H
UL Current
Limiting
PR221 LS/I - T4H250BW
65 PR222 LSI - T4H250CW
PR222 LSIG - T4H250EW
PR221 LS/I - T4L250BW
T4L 100 PR222 LSI - T4L250CW
PR222 LSIG - T4L250EW
T4V
UL Current
Limiting
PR221 LS/I - T4V250BW
150 PR222 LSI - T4V250CW
PR222 LSIG - T4V250EW
NOTE: See pages 17.71-17.83 for electrical/mechanical accessories.
Tmax
MCCBs
Low Voltage Products & Systems 17.31
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
17
T4
250A, 600V ∆, 100% Rated
Electronic (AC only)
100A Frame - 100% rated, electronic trip unit (AC only)
Breaker IC at 480VAC
kA
Trip
Unit
3 pole, 600V
catalog number
PR221 LS/I T4NQ100BW
T4N 25 PR222 LSI T4NQ100CW
PR222 LSIG T4NQ100EW
PR221 LS/I T4SQ100BW
T4S 35 PR222 LSI T4SQ100CW
PR222 LSIG T4SQ100EW
T4H
UL Current
Limiting
PR221 LS/I T4HQ100BW
65 PR222 LSI T4HQ100CW
PR222 LSIG T4HQ100EW
PR221 LS/I T4LQ100BW
T4L 100 PR222 LSI T4LQ100CW
PR222 LSIG T4LQ100EW
T4V
UL Current
Limiting
PR221 LS/I T4VQ100BW
150 PR222 LSI T4VQ100CW
PR222 LSIG T4VQ100EW
150A Frame - 100% rated, electronic trip unit (AC only)
Breaker IC at 480VAC
kA
Trip
Unit
3 pole, 600V
catalog number
PR221 LS/I T4NQ150BW
T4N 25 PR222 LSI T4NQ150CW
PR222 LSIG T4NQ150EW
PR221 LS/I T4SQ150BW
T4S 35 PR222 LSI T4SQ150CW
PR222 LSIG T4SQ150EW
T4H
UL Current
Limiting
PR221 LS/I T4HQ150BW
65 PR222 LSI T4HQ150CW
PR222 LSIG T4HQ150EW
PR221 LS/I T4LQ150BW
T4L 100 PR222 LSI T4LQ150CW
PR222 LSIG T4LQ150EW
T4V
UL Current
Limiting
PR221 LS/I T4VQ150BW
150 PR222 LSI T4VQ150CW
PR222 LSIG T4VQ150EW
250A Frame - 100% rated, electronic trip unit (AC only)
Breaker IC at 480VAC
kA
Trip
Unit
3 pole, 600V
catalog number
PR221 LS/I T4NQ250BW
T4N 25 PR222 LSI T4NQ250CW
PR222 LSIG T4NQ250EW
PR221 LS/I T4SQ250BW
T4S 35 PR222 LSI T4SQ250CW
PR222 LSIG T4SQ250EW
T4H
UL Current
Limiting
PR221 LS/I T4HQ250BW
65 PR222 LSI T4HQ250CW
PR222 LSIG T4HQ250EW
PR221 LS/I T4LQ250BW
T4L 100 PR222 LSI T4LQ250CW
PR222 LSIG T4LQ250EW
T4V
UL Current
Limiting
PR221 LS/I T4VQ250BW
150 PR222 LSI T4VQ250CW
PR222 LSIG T4VQ250EW
NOTE: See pages 17.71-17.83 for electrical/mechanical accessories.
Tmax
MCCBs
17.32 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
17
1 When protected by a OCPD with appropriate ratings.
T4
250A, 600V ∆
Instantaneous only, MCP/Molded case switch
Instantaneous only MCPs
T4 - 250A Frame magnetic only (MCP - AC only)
Breaker IC at 480VAC Trip unit type Rating Adjustment range 3 pole, 600VAC
Catalog number
T4N 25kA Instantaneous
only
100A 100-1000 T4N100E5W
150A 150-1500 T4N150E5W
250A 250-2500 T4N250E5W
T4S 35kA Instantaneous
only
100A 100-1000 T4S100E5W
150A 150-1500 T4S150E5W
250A 250-2500 T4S250E5W
T4H 65kA Instantaneous
only
100A 100-1000 T4H100E5W
150A 150-1500 T4H150E5W
250A 250-2500 T4H250E5W
T4L 100kA Instantaneous
only
100A 100-1000 T4L100E5W
150A 150-1500 T4L150E5W
250A 250-2500 T4L250E5W
Molded case switch 1
Type IC at 480VAC Amps Magnetic
trip
3 pole 600V
catalog number
T4N-D 25kA 250 3000 T4N250DW
T4S-D 35kA 250 3000 T4S250DW
T4H-D 65kA 250 3000 T4H250DW
T4L-D 100kA 250 3000 T4L250DW
T4V-D 150kA 250 3000 T4V250DW
NOTE: See pages 17.71-17.83 for electrical/mechanical accessories.
Tmax
MCCBs
Low Voltage Products & Systems 17.33
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
17
T5
400/600A, 600V ∆
Electronic and thermal magnetic
T5
General
The T5 breaker is a 400/600 amp frame with either a microprocessor based over
current protective trip system or a thermal magnetic trip unit. 3
Standards
The UL489/CSA 22.2 version of T5 also carries an IEC-60947-2 rating.
Versions
To meet all application requirements, the T5 is available in the following versions:
T = Thermal-magnetic
B = Selectable & adjustable LI or LS
C = Adjustable LSI
E = Adjustable LSIG
D = Molded Case Switch
E5 = Electronic instantaneous only (MCP)
Trip functions
These trip functions are available:
L = Long time
S = Short time
I = Instantaneous
G = Ground fault
Performance levels
Each version is also available in different maximum fault interrupting levels:
N = Normal
S = Standard
H = High - UL Current Limiting
L = Extra high
V = Very high - UL Current Limiting
Number of poles 4
The T5 is available in two, three and four pole versions. Estimate 4 pole pricing by
adding 35% to the 3 pole price and contact your ABB sales person for details.
UL489 / CSA C22.2 Interrupting capacity (kA RMS)
Voltage N S H L V
240VAC 65 100 150 200 200
480VAC 25 35 65 100 150
600VAC 18 25 35 65 100
500VDC 1 25 35 50 65 100
600VDC 2 16 25 35 50 65
1 2 poles in series.
2 3 poles in series.
3 T5 600A not available with thermal magnetic trip unit.
4 2 pole available in N version only. 4 pole available in N and H version only.
Dimensions 3P Fixed Version 8.07H x 5.51W x 4.07D
Weight 8.55 (Ibs)
IEC 60947-2 Interrupting capacity (kA RMS)
Voltage N S H L V
230VAC 70 85 100 200 200
415VAC 36 50 70 120 200
690VAC 20 25 40 70 80
750VDC 2 16 25 36 50 70
Tmax
MCCBs
17.34 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
17
T5
400/600A, 600V ∆
Thermal magnetic 1
300A - 400A Frames - thermal-magnetic trip units
Breaker IC at 480VAC
kA Rating Magnetic
trip
2 pole, 600VAC/500VDC
catalog number
3 pole, 600VAC/600VDC
catalog number
T5N 25 300A 1500-3000 T5N300TW-2 T5N300TW
400A 2000-4000 T5N400TW-2 T5N400TW
T5S 35 300A 1500-3000 T5S300TW
400A 2000-4000 T5S400TW
T5H
UL Current Limiting 65 300A 1500-3000 T5H300TW
400A 2000-4000 T5H400TW
T5L 100 300A 1500-3000 T5L300TW
400A 2000-4000 T5L400TW
T5V
UL Current Limiting 150 300A 1500-3000 T5V300TW
400A 2000-4000 T5V400TW
1 T5 600A not available with Thermal Magnetic trip unit.
300A - 400A Frames - 100% rated, thermal-magnetic
Breaker IC at 480VAC Rating Magnetic
trip
3 pole, 600VAC/600VDC
Catalog number
T5N 25 300A 1500-3000 T5NQ300TW
400A 2000-4000 T5NQ400TW
T5S 35 300A 1500-3000 T5SQ300TW
400A 2000-4000 T5SQ400TW
T5H
UL Current Limiting 65 300A 1500-3000 T5HQ300TW
400A 2000-4000 T5HQ400TW
T5L 100 300A 1500-3000 T5LQ300TW
400A 2000-4000 T5LQ400TW
T5V
UL Current Limiting 150 300A 1500-3000 T5VQ300TW
400A 2000-4000 T5VQ400TW
NOTE: See pages 17.71-17.83 for electrical/mechanical accessories.
Tmax
MCCBs
Low Voltage Products & Systems 17.35
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
17
1 T5 600A not available in 2 pole version.
T5
400/600A, 600V ∆
Electronic (AC only)
300A Frame, electronic trip unit (AC only)
Breaker IC at 480VAC
kA
Trip
Unit
2 pole, 600V
catalog number
3 pole, 600V
catalog number
PR221 LS/I T5N300BW-2 T5N300BW
T5N 25 PR222 LSI T5N300CW-2 T5N300CW
PR222 LSIG T5N300EW-2 T5N300EW
PR221 LS/I - T5S300BW
T5S 35 PR222 LSI - T5S300CW
PR222 LSIG - T5S300EW
T5H
UL Current
Limiting
PR221 LS/I - T5H300BW
65 PR222 LSI - T5H300CW
PR222 LSIG - T5H300EW
PR221 LS/I - T5L300BW
T5L 100 PR222 LSI - T5L300CW
PR222 LSIG - T5L300EW
T5V
UL Current
Limiting
PR221 LS/I - T5V300BW
150 PR222 LSI - T5V300CW
PR222 LSIG - T5V300EW
400A Frame, electronic trip unit (AC only)
Breaker IC at 480VAC
kA
Trip
Unit
2 pole, 600V
catalog number
3 pole, 600V
catalog number
PR221 LS/I T5N400BW-2 T5N400BW
T5N 25 PR222 LSI T5N400CW-2 T5N400CW
PR222 LSIG T5N400EW-2 T5N400EW
PR221 LS/I - T5S400BW
T5S 35 PR222 LSI - T5S400CW
PR222 LSIG - T5S400EW
T5H
UL Current
Limiting
PR221 LS/I - T5H400BW
65 PR222 LSI - T5H400CW
PR222 LSIG - T5H400EW
PR221 LS/I - T5L400BW
T5L 100 PR222 LSI - T5L400CW
PR222 LSIG - T5L400EW
T5V
UL Current
Limiting
PR221 LS/I - T5V400BW
150 PR222 LSI - T5V400CW
PR222 LSIG - T5V400EW
600A Frame, electronic trip unit (AC only) 1
Breaker IC at 480VAC
kA
Trip
Unit
3 pole, 600V
catalog number
PR221 LS/I T5N600BW
T5N 25 PR222 LSI T5N600CW
PR222 LSIG T5N600EW
PR221 LS/I T5S600BW
T5S 35 PR222 LSI T5S600CW
PR222 LSIG T5S600EW
PR221 LS/I T5H600BW
T5H 65 PR222 LSI T5H600CW
PR222 LSIG T5H600EW
PR221 LS/I T5L600BW
T5L 100 PR222 LSI T5L600CW
PR222 LSIG T5L600EW
PR221 LS/I T5V600BW
T5V 150 PR222 LSI T5V600CW
PR222 LSIG T5V600EW
NOTE: See pages 17.71-17.83 for electrical/mechanical accessories.
Tmax
MCCBs
17.36 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
17
T5
400/600A, 600V ∆, 100% Rated 1
Electronic (AC only)
400A Frame – 100% rated, electronic trip units (AC only)
Breaker IC at 480VAC
kA
Trip
Unit
3 pole, 600V
catalog number
PR221 LS/I T5NQ400BW
T5N 25 PR222 LSI T5NQ400CW
PR222 LSIG T5NQ400EW
PR221 LS/I T5SQ400BW
T5S 35 PR222 LSI T5SQ400CW
PR222 LSIG T5SQ400EW
T5H
UL Current
limiting
PR221 LS/I T5HQ400BW
65 PR222 LSI T5HQ400CW
PR222 LSIG T5HQ400EW
PR221 LS/I T5LQ400BW
T5L 100 PR222 LSI T5LQ400CW
PR222 LSIG T5LQ400EW
T5V
UL Current
limiting
PR221 LS/I T5VQ400BW
150 PR222 LSI T5VQ400CW
PR222 LSIG T5VQ400EW
NOTE: See pages 17.71-17.83 for electrical/mechanical accessories.
300A Frame – 100% rated, electronic trip units (AC only)
Breaker IC at 480VAC
kA
Trip
Unit
3 pole, 600V
catalog number
PR221 LS/I T5NQ300BW
T5N 25 PR222 LSI T5NQ300CW
PR222 LSIG T5NQ300EW
PR221 LS/I T5SQ300BW
T5S 35 PR222 LSI T5SQ300CW
PR222 LSIG T5SQ300EW
T5H
UL Current
limiting
PR221 LS/I T5HQ300BW
65 PR222 LSI T5HQ300CW
PR222 LSIG T5HQ300EW
PR221 LS/I T5LQ300BW
T5L 100 PR222 LSI T5LQ300CW
PR222 LSIG T5LQ300EW
T5V
UL Current
limiting
PR221 LS/I T5VQ300BW
150 PR222 LSI T5VQ300CW
PR222 LSIG T5VQ300EW
1 T5 600A not available in 100% rated frame.
Tmax
MCCBs
Low Voltage Products & Systems 17.37
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
17
T5
400/600A, 600V ∆
Instantaneous only, MCP/Molded case switch
T5 - 400A Frame, magnetic only (MCP - AC only)
Breaker IC at 480VAC Trip unit type Rating Adjustment
range
3 pole, 600VAC
Catalog number
T5N 25kA Instantaneous
only
300A 300-3000 T5N300E5W
400A 400-4000 T5N400E5W
T5S 35kA Instantaneous
only
300A 300-3000 T5S300E5W
400A 400-4000 T5S400E5W
T5H 65kA Instantaneous
only
300A 300-3000 T5H300E5W
400A 400-4000 T5H400E5W
T5L 100kA Instantaneous
only
300A 300-3000 T5L300E5W
400A 400-4000 T5L400E5W
T5 - 600A Frame, magnetic only (MCP - AC only)
Breaker IC at 480VAC Trip unit type Rating Adjustment
range
3 pole, 600VAC
Catalog number
T5N 25kA Instantaneous
only 600A 600-6000 T5N600E5W
T5S 35kA Instantaneous
only 600A 600-6000 T5S600E5W
T5H 65kA Instantaneous
only 600A 600-6000 T5H600E5W
T5L 100kA Instantaneous
only 600A 600-6000 T5L600E5W
Molded case switch 1
Type IC at 480VAC Amps Magnetic
trip
3 pole 600V
catalog number
T5N-D 25kA 400 5000 T5N400DW
T5S-D 35kA 400 5000 T5S400DW
T5H-D 65kA 400 5000 T5H400DW
T5L-D 100kA 400 5000 T5L400DW
T5V-D 150kA 400 5000 T5V400DW
T5N-D 25kA 600 6000 T5N600DW
T5S-D 35kA 600 6000 T5S600DW
T5H-D 65kA 600 6000 T5H600DW
T5L-D 100kA 600 6000 T5L600DW
T5V-D 150kA 600 6000 T5V600DW
NOTE: See pages 17.71-17.83 for electrical/mechanical accessories.
1 When protected by a OCPD with appropriate ratings.
Tmax
MCCBs
17.38 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
17
T6
600A, 800A, 600V ∆
Thermal magnetic and electronic
T6
General
The T6 breaker is an 800 amp frame with either a microprocessor based over current
protective trip system or a thermal magnetic trip unit. The T6 is available as a 600 or
800A frame.
Standards
The UL489/CSA 22.2 version of T6 also carries an IEC-60947-2 rating.
Versions
To meet all application requirements, the T6 is available in the following versions:
T = Thermal-magnetic, xed
B = Selectable & adjustable LI or LS
C = Adjustable LSI
E = Adjustable LSIG
D = Molded Case Switch
E5 = Electronic instantaneous only (MCP)
Trip functions
These trip functions are available:
L = Long time
S = Short time
I = Instantaneous
G = Ground fault
Performance levels
Each version is also available in different maximum fault interrupting levels:
N = Normal
S = Standard
H = High
L = Extra high
Number of poles 3
The T6 is available as a three and four pole breaker. Estimate 4 pole pricing by
adding 35% to the 3 pole price and contact your ABB sales person for details.
Dimensions 3P Fixed Version 10.55H x 8.26W x 4.07D
Weight 20.9 (Ibs)
UL489 / CSA C22.2 Interrupting capacity (kA RMS)
Voltage N S H L
240VAC 65 100 200 200
480VAC 35 50 65 100
600VAC 20 25 35 42
500VDC 135 35 50 65
600VDC 220 20 35 50
1 2 poles in series.
2 3 poles in series.
3 4 pole available N and H version only.
IEC 60947-2 Interrupting capacity (kA RMS)
Voltage N S H L
230VAC 70 85 100 200
415VAC 36 50 70 100
690VAC 20 22 25 30
750VDC 216 20 36 50
Tmax
MCCBs
Low Voltage Products & Systems 17.39
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
17
T6
800A, 600V
Electronic Trip Units
Breaker IC at
480VAC Trip type Adjustment 3 pole, 600VAC catalog
number
T6N 35
PR221 LS/I T6N800BW
PR222 LSI T6N800CW
PR222 LSIG T6N800EW
T6S 50
PR221 LS/I T6S800BW
PR222 LSI T6S800CW
PR222 LSIG T6S800EW
T6H 65
PR221 LS/I T6H800BW
PR222 LSI T6H800CW
PR222 LSIG T6H800EW
T6L 100
PR221 LS/I T6L800BW
PR222 LSI T6L800CW
PR222 LSIG T6L800EW
NOTE: See pages 17.71-17.83 for electrical/mechanical accessories.
T6
600A, 800A, 600V
Thermal Magnetic Trip Units 100% rated
Breaker IC at 480
VAC kA Rating Magnetic trip 3 pole, 600VAC/600VDC
catalog number
T6N 35 600A 3000 - 6000A T6NQ600TW
800A 4000 - 8000A T6NQ800TW
T6S 50 600A 3000 - 6000A T6SQ600TW
800A 4000 - 8000A T6SQ800TW
T6H 65 600A 3000 - 6000A T6HQ600TW
800A 4000 - 8000A T6HQ800TW
T6L 100 600A 3000 - 6000A T6LQ600TW
800A 4000 - 8000A T6LQ800TW
T6
600A, 800A, 600V
Thermal Magnetic Trip Units
Breaker IC at 480
VAC kA Rating Magnetic trip 3 pole, 600VAC/600VDC
catalog number
T6N 35 600A 3000 - 6000A T6N600TW
800A 4000 - 8000A T6N800TW
T6S 50 600A 3000 - 6000A T6S600TW
800A 4000 - 8000A T6S800TW
T6H 65 600A 3000 - 6000A T6H600TW
800A 4000 - 8000A T6H800TW
T6L 100 600A 3000 - 6000A T6L600TW
800A 4000 - 8000A T6L800TW
T6
600A, 800A, 600V ∆
Thermal magnetic and electronic
T6
600A, 600V
Electronic Trip Units
Breaker IC at
480VAC Trip type Adjustment 3 pole, 600VAC catalog
number
T6N 35
PR221 LS/I T6N600BW
PR222 LSI T6N600CW
PR222 LSIG T6N600EW
T6S 50
PR221 LS/I T6S600BW
PR222 LSI T6S600CW
PR222 LSIG T6S600EW
T6H 65
PR221 LS/I T6H600BW
PR222 LSI T6H600CW
PR222 LSIG T6H600EW
T6L 100
PR221 LS/I T6L600BW
PR222 LSI T6L600CW
PR222 LSIG T6L600EW
Tmax
MCCBs
17.40 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
17
T6
600A, 800A, 600V ∆
Thermal magnetic and electronic
T6
600A, 600V ∆
Electronic Trip Units 100% Rated
Breaker IC at 480VAC Trip type Adjustment 3 pole, 600VAC
catalog number
PR221 LS/I T6NQ600BW
T6N 35 PR222 LSI T6NQ600CW
PR222 LSIG T6NQ600EW
PR221 LS/I T6SQ600BW
T6S 50 PR222 LSI T6SQ600CW
PR222 LSIG T6SQ600EW
PR221 LS/I T6HQ600BW
T6H 65 PR222 LSI T6HQ600CW
PR222 LSIG T6HQ600EW
PR221 LS/I T6LQ600BW
T6L 100 PR222 LSI T6LQ600CW
PR222 LSIG T6LQ600EW
T6
800A, 600V
Electronic Trip Units 100% Rated
Breaker IC at 480VAC Trip type Adjustment 3 pole, 600VAC
catalog number
PR221 LS/I T6NQ800BW
T6N 35 PR222 LSI T6NQ800CW
PR222 LSIG T6NQ800EW
PR221 LS/I T6SQ800BW
T6S 50 PR222 LSI T6SQ800CW
PR222 LSIG T6SQ800EW
PR221 LS/I T6HQ800BW
T6H 65 PR222 LSI T6HQ800CW
PR222 LSIG T6HQ800EW
PR221 LS/I T6LQ800BW
T6L 100 PR222 LSI T6LQ800CW
PR222 LSIG T6LQ800EW
T6
600A, 600V ∆
Electronic Trip Units Instantaneous Only
Breaker IC at 480VAC kA Trip type Adjustment
Range
3 pole, 600VAC
catalog number
T6N 35 PR221 600-6000 T6N600E5W
T6S 50 PR221 600-6000 T6S600E5W
T6H 65 PR221 600-6000 T6H600E5W
T6L 100 PR221 600-6000 T6L600E5W
T6
800A, 600V
Electronic Trip Units Instantaneous Only
Breaker IC at 480VAC kA Trip type Adjustment
Range
3 pole, 600VAC
catalog number
T6N 35 PR221 800-8000 T6N800E5W
T6S 50 PR221 800-8000 T6S800E5W
T6H 65 PR221 800-8000 T6H800E5W
T6L 100 PR221 800-8000 T6L800E5W
T6
800A, 600V
Molded Case Switch
Breaker IC at 480VAC 1Amp Magnetic Trip 3 pole, 600VAC
catalog number
T6H 65 800 10,000 T6H800DW
1 When protected by a OCPD with appropriate ratings.
Tmax
MCCBs
Low Voltage Products & Systems 17.41
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
17
T7 (Toggle)
1000A, 1200A, 600V ∆
Electronic
T7
General
The T7 breaker is a 1200 amp frame with a microprocessor based over current
protective trip system.
Standards
The UL489/CSA 22.2 version of T7 also carries an IEC-60947-2 rating.
Versions
To meet all application requirements, the T7 is available in the following versions:
B = Selectable & adjustable LI or LS — Dip switch settings
C = Adjustable LSI — Dip switch settings
E = Adjustable LSIG — Dip switch settings
D = Molded Case Switch
P = LI — LCD display
R = LSI — LCD display
S = LSIG — LCD display
Trip functions
These trip functions are available:
L = Long time
S = Short time
I = Instantaneous
G = Ground fault
Performance levels
Each version is also available in different maximum fault interrupting levels:
S = Standard
H = High
L = Extra high
Number of poles 1
The T7 is available as a 3 and 4 pole breaker. Estimate 4 pole pricing by adding 35%
to the 3 pole price and contact your ABB sales person for details.
Dimensions 3P Fixed Version 10.55H x 8.26W x 6.06D
Weight 21.4 (Ibs)
UL489 / CSA C22.2 Interrupting capacity (kA RMS)
Voltage S H L
240VAC 65 100 150
480VAC 50 65 100
600VAC 25 50 65
IEC 60947-2 Interrupting capacity (kA RMS)
Voltage S H L
230VAC 85 100 200
415VAC 50 70 120
690VAC 30 42 50
1 4 Pole available S, H and L version.
Tmax
MCCBs
17.42 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
17
T7
1000A, 1200A, 600V ∆
Electronic
T7S, 1000A, 600V
Electronic
Breaker
IC at
480VAC
kA
Trip type Adjustment 3 pole, 600VAC catalog
number
T7S 50
PR231/P LS/I T7S1000BW
PR232/P LSI T7S1000CW
PR331/P LSIG T7S1000EW
PR332/P LI T7S1000PW
PR332/P LSI T7S1000RW
PR332/P LSIG T7S1000SW
T7S, 1200A, 600V
Electronic
Breaker IC at
480VAC kA Trip type Adjustment 3 pole, 600VAC catalog
number
T7S 50
PR231/P LS/I T7S1200BW
PR232/P LSI T7S1200CW
PR331/P LSIG T7S1200EW
PR332/P LI T7S1200PW
PR332/P LSI T7S1200RW
PR332/P LSIG T7S1200SW
T7H, 1000A, 600V
Electronic
Breaker IC at
480VAC kA Trip type Adjustment 3 pole, 600VAC catalog
number
T7H 65
PR231/P LS/I T7H1000BW
PR232/P LSI T7H1000CW
PR331/P LSIG T7H1000EW
PR332/P LI T7H1000PW
PR332/P LSI T7H1000RW
PR332/P LSIG T7H1000SW
T7H, 1200A, 600V
Electronic
Breaker IC at
480VAC kA Trip type Adjustment 3 pole, 600VAC catalog
number
T7H 65
PR231/P LS/I T7H1200BW
PR232/P LSI T7H1200CW
PR331/P LSIG T7H1200EW
PR332/P LI T7H1200PW
PR332/P LSI T7H1200RW
PR332/P LSIG T7H1200SW
T7L, 1000A, 600V
Electronic
Breaker
IC at
480VAC
kA
Trip type Adjustment 3 pole, 600VAC catalog
number
T7L 100
PR231/P LS/I T7L1000BW
PR232/P LSI T7L1000CW
PR331/P LSIG T7L1000EW
PR332/P LI T7L1000PW
PR332/P LSI T7L1000RW
PR332/P LSIG T7L1000SW
T7L, 1200A, 600V
Electronic
Breaker
IC at
480VAC kA
Trip type Adjustment 3 pole, 600VAC catalog
number
T7L 100
PR231/P LS/I T7L1200BW
PR232/P LSI T7L1200CW
PR331/P LSIG T7L1200EW
PR332/P LI T7L1200PW
PR332/P LSI T7L1200RW
PR332/P LSIG T7L1200SW
NOTE: See pages 17.71-17.83 for electrical/mechanical accessories.
Tmax
MCCBs
Low Voltage Products & Systems 17.43
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
17
T7
1000A, 1200A, 600V ∆
Electronic, 100% rated
T7S, 1000A, 600V
Electronic, 100% rated
Breaker IC at 480VAC
kA Trip type Adjustment 3 pole, 600VAC Catalog
number
T7S 50
PR231/P LS/I T7SQ1000BW
PR232/P LSI T7SQ1000CW
PR331/P LSIG T7SQ1000EW
PR332/P LI T7SQ1000PW
PR332/P LSI T7SQ1000RW
PR332/P LSIG T7SQ1000SW
T7S, 1200A, 600V
Electronic, 100% rated
Breaker IC at 480VAC
kA Trip type Adjustment 3 pole, 600VAC Catalog
number
T7S 50
PR231/P LS/I T7SQ1200BW
PR232/P LSI T7SQ1200CW
PR331/P LSIG T7SQ1200EW
PR332/P LI T7SQ1200PW
PR332/P LSI T7SQ1200RW
PR332/P LSIG T7SQ1200SW
T7H, 1000A, 600V
Electronic, 100% rated
Breaker IC at 480VAC
kA Trip type Adjustment 3 pole, 600VAC Catalog
number
T7H 65
PR231/P LS/I T7HQ1000BW
PR232/P LSI T7HQ1000CW
PR331/P LSIG T7HQ1000EW
PR332/P LI T7HQ1000PW
PR332/P LSI T7HQ1000RW
PR332/P LSIG T7HQ1000SW
T7H, 1200A, 600V
Electronic, 100% rated
Breaker IC at 480VAC
kA Trip type Adjustment 3 pole, 600VAC Catalog
number
T7H 65
PR231/P LS/I T7HQ1200BW
PR232/P LSI T7HQ1200CW
PR331/P LSIG T7HQ1200EW
PR332/P LI T7HQ1200PW
PR332/P LSI T7HQ1200RW
PR332/P LSIG T7HQ1200SW
T7L, 1000A, 600V
Electronic, 100% rated
Breaker IC at 480VAC
kA Trip type Adjustment 3 pole, 600VAC Catalog
number
T7L 100
PR231/P LS/I T7LQ1000BW
PR232/P LSI T7LQ1000CW
PR331/P LSIG T7LQ1000EW
PR332/P LI T7LQ1000PW
PR332/P LSI T7LQ1000RW
PR332/P LSIG T7LQ1000SW
T7L, 1200A, 600V
Electronic, 100% rated
Breaker IC at 480VAC
kA Trip type Adjustment 3 pole, 600VAC Catalog
number
T7L 100
PR231/P LS/I T7LQ1200BW
PR232/P LSI T7LQ1200CW
PR331/P LSIG T7LQ1200EW
PR332/P LI T7LQ1200PW
PR332/P LSI T7LQ1200RW
PR332/P LSIG T7LQ1200SW
NOTE: See pages 17.71 - 17.83 for electrical/mechanical accessories.
Tmax
MCCBs
17.44 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
17
T7
1200A, 600V ∆
Electronic/Molded case switch
T7
1200A, 600V
Molded case switch
Breaker IC at
480VAC kA 1Amp Magnetic
trip
3 pole, 600VAC
Catalog number
T7H - 1200 20,000 T7H1200DW
NOTE: See pages 17.67 - 17.79 for electrical/mechanical accessories.
1 When protected by a OCPD with appropriate ratings.
T7
1000 - 1200A, 600V
Motor circuit protection
Electronic trip, instantaneous only
Breaker IC at 480VAC kA 1Amp Catalog number
T7S 50 1000 T7S1000E5W
T7H 65 1000 T7H1000E5W
T7L 100 1000 T7L1000E5W
T7S 50 1200 T7S1200E5W
T7H 65 1200 T7H1200E5W
T7L 100 1200 T7L1200E5W
NOTE: See pages 17.71 - 17.83 for electrical/mechanical accessories.
Tmax
MCCBs
Low Voltage Products & Systems 17.45
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
17
T7M (Stored energy)
1000A, 1200A, 600V ∆
Electronic
General
The T7M breaker is a stored energy 1200A frame with a microprocessor based
overcurrent protective trip system.
Standards
The UL489/CSA 22.2 version of T7M also carries an IEC-60947-2 rating.
Versions
To meet all application requirements, the T7M is available in the following versions:
B = Selectable & adjustable LI or LS — Dip switch setting
C = Adjustable LSI — Dip switch setting
E = Adjustable LSIG — Dip switch setting
D = Molded Case Switch
P = LI — LCD display
R = LSI — LCD display
S = LSIG — LCD display
Trip functions
These trip functions are available:
L = Long time
S = Short time
I = Instantaneous
G = Ground fault
Performance levels
Each version is also available in different maximum fault interrupting levels:
S = Standard
H = High
L = Extra high
Number of poles
The T7M is available as a three and four pole breaker.
Dimensions 3P Fixed Version 10.55H x 8.26W x 7D
Weight 24.25 (Ibs)
UL489 / CSA C22.2 Interrupting capacity (kA RMS)
Voltage S H L
240VAC 65 100 150
480VAC 50 65 100
600VAC 25 50 65
IEC 60947-2 Interrupting capacity (kA RMS)
Voltage S H L
230VAC 85 100 200
415VAC 50 70 120
690VAC 30 42 50
T7M
Tmax
MCCBs
17.46 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
17
T7M
1000A, 1200A, 600V ∆
Electronic
T 7 M
Accessories:
X = None
A = Mechanical counter
B = Trip signal
C = Trip signal and reset 24-30 VAC/DC
D = Trip signal and reset 110-130 VAC/DC
E = Trip signal and reset 200-240 VAC/DC
F = A+C; G=A+D; H=A+E
Locking provisions:
X = None
A = Keylock; B = Button guard
C = Padlock provision (open)
F = A+B
Undervoltage:
0 = None; A = 24 VAC/DC; B = 30 VAC/DC;
C = 48 VAC/DC; D = 60 VAC/DC; E = 110...120 VAC/DC
F = 120...127 VAC/DC; G = 220...240 VAC/DC;
H = 240…250 VAC/DC; J = 380…400 VAC; K = 415…440 VAC
Shunt trip:
0 = None; A = 24 VAC/DC; B = 30 VAC/DC;
C = 48 VAC/DC; D = 60 VAC/DC; E = 110…120 VAC/DC
F = 120…127 VAC/DC; G = 220…240 VAC/DC; H = 240…250 VAC/DC
J = 380…400 VAC; K = 415…440 VAC
Spring Charging Motor:
0 = None; A = 24…30 VAC/DC;
B = 48…60 VAC/DC; C = 100...130 VAC/DC; D = 220…250 VAC/DC
E = 380…415 VAC; F = Springs charged 24 VDC; G = Springs charged 250 VAC/DC;
H=A+F; J=B+F; K=C+F; L=D+F; M=E+F; N=A+G; P=B+G; Q=C+G; R=D+G; S=E+G
Auxilary Contacts:
0 = None A = 2 Form C (400 VAC); B = 2 Form C (24 VDC); C=Ready to close 24 VDC;
D = Ready to close 250 VAC/DC
Closing Coil:
0 = None; A = 24 VAC/DC; B = 30 VAC/DC; C = 48 VAC/DC;
D = 60 VAC/DC; E = 110…120 VAC/DC; F = 120…127 VAC/DC;
G = 220…240 VAC/DC; H = 240…250 VAC/DC; J = 380…400 VAC;
K = 415…440 VAC
Trip Unit Accessories:
0 = None; A = PR330V; B = PR330/D-M; C = A + B (PR332/P only)
Trip Unit:
A = PR231/P-I (MCP); B = PR231/P-LS/I; C = PR232/P-LSI; D = Non-Automatic (MCS);
E = PR331/P-LSIG; P = PR332/P-LI; R = PR332/P-LSI; S = PR332P-/LSIG
Rating Plug:
0 = None; Non –Automatic (MCS) A = 400A; B = 600/630A; C = 800A; D = 1000A; E = 1200/1250A F = 1600A (IEC only)
Frame Ampere rating:
A3 = 800 A (3P) IEC only; P3 = 1000 A (3P); B3 = 1200/1250 A (3P); C3 1600 A (3P IEC only)
A4 = 800 A (4P) IEC only; P4 = 1000 A (4P); B4 = 1200/1250 A (4P); C4 1600 A (4P IEC only)
Version:
0 = Fixed non-automatic (MCS); B = UL xed; Q = UL xed 100% rated; F = IEC xed
Breaking Capacity:
S, H, L, V = IEC, T7 800, 1000, 1250A only); D = MCS (IEC) Call factory for IEC breaker pricing
Tmax
MCCBs
Low Voltage Products & Systems 17.47
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
17
T7M-S, 1000A, 600V
Electronic
Breaker IC at 480VAC kA Trip unit 3 pole, 600V
Catalog number
T7M-S 50
PR231/P-LS/I T7MSBP3DB000000XX
PR232/P-LSI T7MSBP3DC000000XX
PR331/P-LSIG T7MSBP3DE000000XX
PR332/P-LI T7MSBP3DP000000XX
PR332/P-LSI T7MSBP3DR000000XX
PR332/P-LSIG T7MSBP3DS000000XX
T7M-H, 1000A, 600V
Electronic
Breaker IC at 480VAC kA Trip unit 3 pole, 600V
Catalog number
T7M-H 65
PR231/P-LS/I T7MHBP3DB000000XX
PR232/P-LSI T7MHBP3DC000000XX
PR331/P-LSIG T7MHBP3DE000000XX
PR332/P-LI T7MHBP3DP000000XX
PR332/P-LSI T7MHBP3DR000000XX
PR332/P-LSIG T7MHBP3DS000000XX
T7M-L, 1000A, 600V
Electronic
Breaker IC at 480VAC kA Trip unit 3 pole, 600V
Catalog number
T7M-L 100
PR231/P-LS/I T7MLBP3DB000000XX
PR232/P-LSI T7MLBP3DC000000XX
PR331/P-LSIG T7MLBP3DE000000XX
PR332/P-LI T7MLBP3DP000000XX
PR332/P-LSI T7MLBP3DR000000XX
PR332/P-LSIG T7MLBP3DS000000XX
T7M-S, 1200A, 600V
Electronic
Breaker IC at 480VAC kA Trip unit 3 pole, 600V Catalog number
T7M-S 50
PR231/P-LS/I T7MSBB3EB000000XX
PR232/P-LSI T7MSBB3EC000000XX
PR331/P-LSIG T7MSBB3EE000000XX
PR332/P-LI T7MSBB3EP000000XX
PR332/P-LSI T7MSBB3ER000000XX
PR332/P-LSIG T7MSBB3ES000000XX
T7M-H, 1200A, 600V
Electronic
Breaker IC at 480VAC kA Trip unit 3 pole, 600V Catalog number
T7M-H 65
PR231/P-LS/I T7MHBB3EB000000XX
PR232/P-LSI T7MHBB3EC000000XX
PR331/P-LSIG T7MHBB3EE000000XX
PR332/P-LI T7MHBB3EP000000XX
PR332/P-LSI T7MHBB3ER000000XX
PR332/P-LSIG T7MHBB3ES000000XX
T7M-L, 1200A, 600V
Electronic
Breaker IC at 480VAC kA Trip unit 3 pole, 600V
Catalog number
T7M-L 100
PR231/P-LS/I T7MLBB3EB000000XX
PR232/P-LSI T7MLBB3EC000000XX
PR331/P-LSIG T7MLBB3EE000000XX
PR332/P-LI T7MLBB3EP000000XX
PR332/P-LSI T7MLBB3ER000000XX
PR332/P-LSIG T7MLBB3ES000000XX
T7M
1000A, 1200A, 600V ∆ - Three Pole
Electronic
Undervoltage:
0 = None; A = 24 VAC/DC; B = 30 VAC/DC;
C = 48 VAC/DC; D = 60 VAC/DC; E = 110...120 VAC/DC
F = 120...127 VAC/DC; G = 220...240 VAC/DC;
H = 240…250 VAC/DC; J = 380…400 VAC; K = 415…440 VAC
Tmax
MCCBs
17.48 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
17
T7M
1000A, 1200A, 600V ∆ - Three Pole
Electronic 100% Rated
T7M-S, 1000A, 600V
Electronic
Breaker IC at 480VAC kA Trip unit 3 pole, 600V
Catalog number
T7M-S 50
PR231/P-LS/I T7MSQP3DB000000XX
PR232/P-LSI T7MSQP3DC000000XX
PR331/P-LSIG T7MSQP3DE000000XX
PR332/P-LI T7MSQP3DP000000XX
PR332/P-LSI T7MSQP3DR000000XX
PR332/P-LSIG T7MSQP3DS000000XX
T7M-H, 1000A, 600V
Electronic
Breaker IC at 480VAC kA Trip unit 3 pole, 600V
Catalog number
T7M-H 65
PR231/P-LS/I T7MHQP3DB000000XX
PR232/P-LSI T7MHQP3DC000000XX
PR331/P-LSIG T7MHQP3DE000000XX
PR332/P-LI T7MHQP3DP000000XX
PR332/P-LSI T7MHQP3DR000000XX
PR332/P-LSIG T7MHQP3DS000000XX
T7M-L, 1000A, 600V
Electronic
Breaker IC at 480VAC kA Trip unit 3 pole, 600V
Catalog number
T7M-L 100
PR231/P-LS/I T7MLQP3DB000000XX
PR232/P-LSI T7MLQP3DC000000XX
PR331/P-LSIG T7MLQP3DE000000XX
PR332/P-LI T7MLQP3DP000000XX
PR332/P-LSI T7MLQP3DR000000XX
PR332/P-LSIG T7MLQP3DS000000XX
T7M-S, 1200A, 600V
Electronic
Breaker IC at 480VAC
kA Trip unit 3 pole, 600V
Catalog number
T7M-S 50
PR231/P-LS/I T7MSQB3EB000000XX
PR232/P-LSI T7MSQB3EC000000XX
PR331/P-LSIG T7MSQB3EE000000XX
PR332/P-LI T7MSQB3EP000000XX
PR332/P-LSI T7MSQB3ER000000XX
PR332/P-LSIG T7MSQB3ES000000XX
T7M-H, 1200A, 600V
Electronic
Breaker IC at 480VAC
kA Trip unit 3 pole, 600V
Catalog number
T7M-H 65
PR231/P-LS/I T7MHQB3EB000000XX
PR232/P-LSI T7MHQB3EC000000XX
PR331/P-LSIG T7MHQB3EE000000XX
PR332/P-LI T7MHQB3EP000000XX
PR332/P-LSI T7MHQB3ER000000XX
PR332/P-LSIG T7MHQB3ES000000XX
T7M-L, 1200A, 600V
Electronic
Breaker IC at 480VAC
kA Trip unit 3 pole, 600V
Catalog number
T7M-L 100
PR231/P-LS/I T7MLQB3EB000000XX
PR232/P-LSI T7MLQB3EC000000XX
PR331/P-LSIG T7MLQB3EE000000XX
PR332/P-LI T7MLQB3EP000000XX
PR332/P-LSI T7MLQB3ER000000XX
PR332/P-LSIG T7MLQB3ES000000XX
Tmax
MCCBs
Low Voltage Products & Systems 17.49
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
17
T7M
1000A, 1200A, 600V ∆ - Four Pole
Electronic
T7M-S, 1000A, 600V
Electronic
Breaker IC at 480VAC kA Trip unit 4 pole, 600V
Catalog number
T7M-S 50
PR231/P-LS/I T7MSBP4DB000000XX
PR232/P-LSI T7MSBP4DC000000XX
PR331/P-LSIG T7MSBP4DE000000XX
PR332/P-LI T7MSBP4DP000000XX
PR332/P-LSI T7MSBP4DR000000XX
PR332/P-LSIG T7MSBP4DS000000XX
T7M-H, 1000A, 600V
Electronic
Breaker IC at 480VAC kA Trip unit 4 pole, 600V
Catalog number
T7M-H 65
PR231/P-LS/I T7MHBP4DB000000XX
PR232/P-LSI T7MHBP4DC000000XX
PR331/P-LSIG T7MHBP4DE000000XX
PR332/P-LI T7MHBP4DP000000XX
PR332/P-LSI T7MHBP4DR000000XX
PR332/P-LSIG T7MHBP4DS000000XX
T7M-L, 1000A, 600V
Electronic
Breaker IC at 480VAC kA Trip unit 4 pole, 600V Catalog number
T7M-L 100
PR231/P-LS/I T7MLBP4DB000000XX
PR232/P-LSI T7MLBP4DC000000XX
PR331/P-LSIG T7MLBP4DE000000XX
PR332/P-LI T7MLBP4DP000000XX
PR332/P-LSI T7MLBP4DR000000XX
PR332/P-LSIG T7MLBP4DS000000XX
T7M-S, 1200A, 600V
Electronic
Breaker IC at
480VAC kA Trip unit 4 pole, 600V
Catalog number
T7M-S 50
PR231/P-LS/I T7MSBB4EB000000XX
PR232/P-LSI T7MSBB4EC000000XX
PR331/P-LSIG T7MSBB4EE000000XX
PR332/P-LI T7MSBB4EP000000XX
PR332/P-LSI T7MSBB4ER000000XX
PR332/P-LSIG T7MSBB4ES000000XX
T7M-H, 1200A, 600V
Electronic
Breaker IC at 480VAC
kA Trip unit 4 pole, 600V
Catalog number
T7M-H 65
PR231/P-LS/I T7MHBB4EB000000XX
PR232/P-LSI T7MHBB4EC000000XX
PR331/P-LSIG T7MHBB4EE000000XX
PR332/P-LI T7MHBB4EP000000XX
PR332/P-LSI T7MHBB4ER000000XX
PR332/P-LSIG T7MHBB4ES000000XX
T7M-L, 1200A, 600V
Electronic
Breaker IC at 480VAC
kA Trip unit 4 pole, 600V
Catalog number
T7M-L 100
PR231/P-LS/I T7MLBB4EB000000XX
PR232/P-LSI T7MLBB4EC000000XX
PR331/P-LSIG T7MLBB4EE000000XX
PR332/P-LI T7MLBB4EP000000XX
PR332/P-LSI T7MLBB4ER000000XX
PR332/P-LSIG T7MLBB4ES000000XX
Tmax
MCCBs
17.50 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
17
T7M
1000A, 1200A, 600V ∆ - Four Pole
Electronic 100% Rated
T7M-S, 1000A, 600V
Electronic
Breaker IC at 480VAC kA Trip unit 4 pole, 600V
Catalog number
T7M-S 50
PR231/P-LS/I T7MSQP4DB000000XX
PR232/P-LSI T7MSQP4DC000000XX
PR331/P-LSIG T7MSQP4DE000000XX
PR332/P-LI T7MSQP4DP000000XX
PR332/P-LSI T7MSQP4DR000000XX
PR332/P-LSIG T7MSQP4DS000000XX
T7M-H, 1000A, 600V
Electronic
Breaker IC at 480VAC kA Trip unit 4 pole, 600V
Catalog number
T7M-H 65
PR231/P-LS/I T7MHQP4DB000000XX
PR232/P-LSI T7MHQP4DC000000XX
PR331/P-LSIG T7MHQP4DE000000XX
PR332/P-LI T7MHQP4DP000000XX
PR332/P-LSI T7MHQP4DR000000XX
PR332/P-LSIG T7MHQP4DS000000XX
T7M-L, 1000A, 600V
Electronic
Breaker IC at 480VAC kA Trip unit 4 pole, 600V
Catalog number
T7M-L 100
PR231/P-LS/I T7MLQP4DB000000XX
PR232/P-LSI T7MLQP4DC000000XX
PR331/P-LSIG T7MLQP4DE000000XX
PR332/P-LI T7MLQP4DP000000XX
PR332/P-LSI T7MLQP4DR000000XX
PR332/P-LSIG T7MLQP4DS000000XX
T7M-S, 1200A, 600V
Electronic
Breaker IC at 480VAC kA Trip unit 4 pole, 600V
Catalog number
T7M-S 50
PR231/P-LS/I T7MSQB4EB000000XX
PR232/P-LSI T7MSQB4EC000000XX
PR331/P-LSIG T7MSQB4EE000000XX
PR332/P-LI T7MSQB4EP000000XX
PR332/P-LSI T7MSQB4ER000000XX
PR332/P-LSIG T7MSQB4ES000000XX
T7M-H, 1200A, 600V
Electronic
Breaker IC at 480VAC kA Trip unit 4 pole, 600V
Catalog number
T7M-H 65
PR231/P-LS/I T7MHQB4EB000000XX
PR232/P-LSI T7MHQB4EC000000XX
PR331/P-LSIG T7MHQB4EE000000XX
PR332/P-LI T7MHQB4EP000000XX
PR332/P-LSI T7MHQB4ER000000XX
PR332/P-LSIG T7MHQB4ES000000XX
T7M-L, 1200A, 600V
Electronic
Breaker IC at 480VAC kA Trip unit 4 pole, 600V
Catalog number
T7M-L 100
PR231/P-LS/I T7MLQB4EB000000XX
PR232/P-LSI T7MLQB4EC000000XX
PR331/P-LSIG T7MLQB4EE000000XX
PR332/P-LI T7MLQB4EP000000XX
PR332/P-LSI T7MLQB4ER000000XX
PR332/P-LSIG T7MLQB4ES000000XX
Tmax
MCCBs
Low Voltage Products & Systems 17.51
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
17
T7M
1200A, 600V
Molded case switch
Breaker IC at
480VAC kA Amp Magnetic
override
3 pole, 600VAC Catalog
number
T7M-H - 1200 20,000 T7MH0B30D000000XX
T7M
1200A, 600V ∆ - Molded Case Swich
T7M
1000 - 1200A, 600V
Motor circuit protection
Electronic trip, instantaneous only
Breaker IC at 480VAC kA Amp Catalog number
T7M-S 50 1000 T7MSBP3DA000000XX
T7M-H 65 1000 T7MHBP3DA000000XX
T7M-L 100 1000 T7MLBP3DA000000XX
T7M-S 50 1200 T7MSBB3EA000000XX
T7M-H 65 1200 T7MHBB3EA000000XX
T7M-L 100 1200 T7MLBB3EA000000XX
Tmax
MCCBs
17.52 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
17
KT7MXM*
KT7XU*
1 Not Suitable for T7 toggle version.
2 Always supplied with PR332/P trip units
Closing coils 1Field installation
Catalog number
T7M
415…440 VAC KT7MXC1
380…400 VAC KT7MXC2
240…250 VAC/DC KT7MXC3
220…240 VAC/DC KT7MXC4
120…127 VAC/DC KT7MXC5
110…120 VAC/VDC KT7MXC6
60 VAC/DC KT7MXC7
48 VAC/DC KT7MXC8
30 VAC/DC KT7MXC9
24 VAC/DC KT7MXC0
Shunt trip Field installation
Catalog number
T7/T7M
415…440 VAC KT7XS1
380…400 VAC KT7XS2
240…250 VAC/DC KT7XS3
220…240 VAC/DC KT7XS4
120…127 VAC/DC KT7XS5
110…120 VAC/DC KT7XS6
60 VAC/DC KT7XS7
48 VAC/DC KT7XS8
30 VAC/DC KT7XS9
24 VAC/DC KT7XS0
Undervoltage Field installation
Catalog number
T7/T7M
415…440 VAC KT7XU1
380…400 VAC KT7XU2
240…250 VAC/DC KT7XU3
220…240 VAC/DC KT7XU4
120…127 VAC/DC KT7XU5
110…120 VAC/DC KT7XU6
60 VAC/DC KT7XU7
48 VAC/DC KT7XU8
30 VAC/DC KT7XU9
24 VAC/DC KT7XU0
Spring charging motor 1Field installation
Catalog number
T7M
380…415 VAC KT7MXM2
220…250 VAC/DC KT7MXM3
100…130 VAC/DC KT7MXM5
48…60 VAC/DC KT7MXM7
24…30 VAC/DC KT7MXM9
Auxiliary contacts Field installation
Catalog number
T7/T7M 2 Form C 400 VAC KT7XAS2
2 Form C 24 VDC KT7XAS2-AU
Trip signal
Field/factory
installation
Catalog number
T7M Contact for signalling electronic trip unit tripped 1KT7MTS
Accessories
Electrical
T7M
Ready to close auxiliaries (IEC) Field installation
Catalog number
T7M 24 VDC KT7MX-RTC24V
250 VAC/DC KT7MX-RTC250V
Signals the circuit breaker is ready to accept a close signal if the following ve conditions are met:
• Circuit breaker is open • Any opening coil de-energized • Opening solenoid armed
• Closing springs are charged • Any undervoltage coil energized
Spring charged contacts (IEC) Field installation
Catalog number
T7M Contact signalling springs charged 24 VDC KT7MX-SC24V
Contact signalling springs charged 250 VAC/DC
KT7MX-SC250V
Trip reset (IEC) Field installation
Catalog number
T7M
Trip reset command 24-30 VAC/DC KT7MX-TR9
Trip reset command 110-130 VAC/DC
KT7MX-TR5
Trip reset command 200-240 VAC/DC
KT7MX-TR4
Allows remote circuit breaker resetting following a trip of the overcurrent release
KT7MXC1
Tmax
MCCBs
Low Voltage Products & Systems 17.53
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
17
Accessories
Mechanical
T7M
KT7MXMC
KT7XPG
KT7MKL*
1 Comes standard with high prole terminal covers.
2 Fixed breakers only
3 Not Suitable for T7 toggle version
Terminal lugs
Frame Size Wire Size Catalog number
(3 pieces)
Catalog number
(4 pieces)
T7/T7M 1(4) 4/0-500 kxmil KT7X1200-3 1KT7X1200-4 1
Terminal covers - Low profile - kit includes two pieces-fixed breakers
Frame Size Catalog number
(3 pole)
Catalog number
(4 pole)
T7/T7M 2KT7XLTC-3 KT7XLTC-4
Terminal covers - High profile - kit includes two pieces
Frame Size Catalog number
(3 pole)
Catalog number
(4 pole)
T7/T7M KT7XHTC-3 KT7XHTC-4
Phase barriers - Low profile 100mm - 3.93 in
Frame Size Catalog number
4 pcs (3 pole)
Catalog number
6 pcs (4 pole)
T7/T7M KT7PBL-3 2KT7PBL-4
Phase barriers - High profile 200mm - 7.87 in
Frame Catalog number
4 pcs (3 pole)
Catalog number
6 pcs (4 pole)
T7/T7M KT7PBH-3 KT7PBH-4
Mechanical operation counter 3
Frame Field/factory installation
Catalog number
T7M Mechanical counter 3KT7MXMC
Transparent protection for buttons 3
Frame Field/factory installation
Catalog number
T7M Button Guard 3KT7MXPG
Padlock provision 3
Frame Field/factory installation
Catalog number
T7M Padlock-open 3KT7MXLDO
IP54 door protection 3
Frame Field Installation
Catalog number
T7M Protective cover 3KT7MXDC
Key locks
Frame SizerKey lock
open position
Field/factory installation
Catalog number
T7M
Key lock on breaker
open position
key lock # 20005 3
KT7MKL2
Key lock on breaker
open position
different keys 3
KT7MKL1
Mechanical interlock
Frame Catalog
part number
T7M/T7M
Cable T7 KT7XMLC
Mechanical interlock plate - drawout KT7XMLPW
Mechanical interlock plate - xed KT7XMLPF
Tmax
MCCBs
17.54 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
17
Sliding contact blocks
T7M - Drawout Moving part
breaker
Fixed part
cradle
Left Block
Spring charging motor
Spring charged contact
Ready to close contact
Early auxiliary contact
Contact for trip coil trip release
Trip reset
KT7XSCMP-L KT7XSCFP-L
Center Block
PR331
PR332
KT7XSCMP-C KT7XSCFP-C
Right Block
Auxiliary contacts
Shunt trip
Closing coil
Undervoltage release
KT7XSCMP-R KT7XSCFP-R
If at least one of the accessories in the table is installed on the breaker - respective pair of contact blocks must be installed on the
xed part (cradle) and the moving part (breaker)
Sliding Contacts
Position key lock
Locks drawout breaker in
racked-in/test-isoloated/racked-out Catalog number
Key #20005
Different keys
KT7XPL2
KT7XPL1
Position lock accessory
Added to position lock allows breaker
to be locked in racked out postion only Catalog number
Position lock accessory KT7XPLA
Draw-out kits
Frame Adaptor moving part Fixed Part
T7M 3 Pole with horizontal/vertical terminals KT7XWMK KT7WFHR
Accessories
Mechanical
T7M
PR330/D-M
Rating plugs (UL) Catalog number
T7/T7M
400A Rating plug KT7X0400RP
600A Rating plug KT7X0600RP
800A Rating plug KT7X0800RP
1000A Rating plug KT7X1000RP
1200A Rating plug KT7X1200RP
Modules for T7M PR332 trip units Catalog number
T7/T7M Voltage module 1
Communication module (Modbus RTU)
PR330/VT7MX1
PR330/D-M
External units Catalog number
T7/T7M
Battery power supply unit 2PR030/B
External Bluetooth communication module
Includes diagnostic software for
Modbus/Bluetooth networks
BT030
Test conguration unit PR010/T
Allows tripping of all electronic trip units for Tmax
(except PR33x) K7TUT
Current sensor for external neutral KT7NCT
Accessory connector Catalog number
For wiring to internal accessories KT7XAC
Tmax
MCCBs
Low Voltage Products & Systems 17.55
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
17
Technical data T7/T7M
Shunt tips, closing coil,
Undervoltage & spring charging motor
Standard shunt trip
Inrush Power Consumption T7/T7M
Voltage AC (VA) DC (W)
24 VAC/DC 300 300
30 VAC/DC 300 300
48 VAC/DC 300 300
60 VAC/DC 300 300
110…120 VAC/DC 300 300
120…127 VAC/DC 300 300
220…240 VAC/DC 300 300
240…240 VAC/DC 300 300
380…400 VAC 300
415…440 VAC 300
Opening time (ms) 20 20
Closing coil
Inrush Power Consumption T7M
Voltage AC (VA) DC (W)
24 VAC/DC 300 300
30 VAC/DC 300 300
48 VAC/DC 300 300
60 VAC/DC 300 300
110…120 VAC/DC 300 300
120…127 VAC/DC 300 300
220…240 VAC/DC 300 300
240…240 VAC/DC 300 300
380…400 VAC 300
415…440 VAC 300
Opening time (ms) 20 20
Undervoltage
Inrush Power Consumption T7/T7M
Voltage AC (VA) DC (W)
24 VAC/DC 3.5 3.5
30 VAC/DC 3.5 3.5
110…120 VAC/DC 3.5 3.5
120…127 VAC/DC 3.5 3.5
220…240 VAC 3.5 3.5
240…250 VAC/DC 3.5 3.5
380…400 VAC 3.5
415…440 VAC 3.5
Opening time (ms) 25 25
Spring charging motor
Power Consumption T7M
Voltage AC (VA) DC (W)
24….30 VAC/DC 100 100
48…60 VAC/DC 100 100
100…130 VAC/DC 100 100
220…250 VAC/DC 100 100
380…415 VAC 100
Opening voltage (% Un) 85-110 85-110
Charging time (s) 8-10 8-10
Tmax
MCCBs
17.56 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
17
T8
1600/2000/2500/3000A, 600VAC ∆
Electronic trip
General
The T8 is available in a 1600A, 2000A, 2500A, 3000A frame with a microprocessor
over current protective trip system.
Standards
The UL489/CSA 22.2 version of the T8 also carries an IEC-60947-2 rating.
Versions
To meet all application requirements the T8 is available in the following versions:
C = Adjustable LSI PR232/P-T8 Dip switch settings
D = Molded Case Switch
E = Adjustable LSIG PR331/P Dip switch settings
P = Adjustable LI PR332/P LCD Display
R = Adjustable LSI PR332/P LCD Display
S = Adjustable LSIG PR332/P LCD Display
Rc = Residual Current (IEC, 3 pole, under 3200A only)
Trip functions
These trip functions are available:
L = Long time
S = Short time
I = Instantaneous
G = Ground fault
Performance levels
Each version is also available at the following maximum fault interrupting level:
V = Very high
Number of poles
The T8 is available in three and four pole versions.
Dimensions 3P Fixed Version 15.0H x 16.8W x 11.2D
Weight 161 lbs (1600, 2000, 2500A)
236 lbs (3000A)
UL489/CSA C22.2 Interrupting
capacity (kA RMS)
Voltage V
240VAC 125
480VAC 125
600VAC 100
DC
IEC 60947-2 Interrupting
capacity (kA RMS)
Voltage V
230VAC 130
415VAC 130
440VAC 100
690VAC 80
DC
T8
Tmax
MCCBs
Low Voltage Products & Systems 17.57
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
17
T 8 V
Trip Unit Accessories: PR332/P ONLY
0 = None
B = Voltage measuring module; C = Modbus module
Trip Unit:
C = PR331/P-T8-LSI; D = Non-Automatic (MCS); E = PR331/P-LSIG;
P = PR332/P-LI; R = PR332/P-LSI; S = PR332/P-LSIG; H = PR332/P-LSIRc (IEC)
Rating Plug:
D = 1000; E = 1200; F = 1600; G = 2000; H = 2500; J = 3000, 3200; 0 = Non-Automatic (MCS)
Frame Amp Rating:
C3 = 1600 (3P UL only); D3 = 2000 (3P); E3 = 2500 (3P); F3 = 3000 UL/3200 IEC (3P)
C4 = 1600 (4P UL only); D4 = 2000 (4P); E4 = 2500 (4P); F4 = 3000 UL/3200 IEC (4P)
Version:
B = UL Fixed; Q = UL Fixed 100% Rated; F = IEC Fixed; 0 = Fixed Non-Automatic (MCS)
Breaking capacity:
V = Very High; L (IEC only. Call factory for IEC breaker pricing.)
Closing Coil:
0 = None
A = 24 VDC; B = 30 VAC/DC; C = 48 VAC/DC; D = 60 VAC/DC; E = 110..120 VAC/DC;
F = 120..127 VAC/DC; G = 220..240 AC/DC; H = 240..250 VAC/DC; J = 380..400 VAC; K = 440VAC
Contacts:
0 = None
A = 4 aux contacts; (supplied as standard for breakers with PR332 trip units)
B = 4 aux contacts digital (24V)
D = UV energ NO; E = UV energ NC;
F = A+D; G = A+E; H = B+D; J = B+E
Accessories
X = None; A = Mechanical counter; B = Bell Alarm
C = Bell Alarm w/remote reset, 24..30 VAC/DC
D = Bell Alarm w/remote reset 110..130 VAC/DC
E = Bell Alarm w/remote reset 220..240 VAC/DC
F = A+B; G = A+C; H = A+D; J = A+E
Undervoltage
0 = None
A = 24 VDC; B = 30 VAC/DC
C = 48 VAC/DC; D = 60 VAC/DC
E = 110..120 VAC/DC; F = 125..127 VAC/DC
G = 220..240 VAC/DC; H = 250 VAC/DC
J = 380..400 VAC; K = 440 VAC
Second shunt trip:
L = 24 VDC; M = 30 VAC/DC
N = 48 VAC/DC; P = 60 VAC/DC
Q = 110..120 VAC/DC; R = 125..127 VAC/DC
S = 220..240 VAC/DC; T = 250 VAC/DC
U = 380..400 VAC; V = 440..480 VAC
Spring charging motor:
0 = None
A = 24..30 VAC/DC; B = 48..60 VAC/DC;
C = 100..130 VAC/DC; D = 220..250 VAC/DC
Shunt trip
0 = None
A = 24 VDC; B = 30 VAC/DC; C = 48 VAC/DC;
D = 60 VAC/DC; E = 110..120 VAC/DC
F = 120..127 VAC/DC; G = 220..240 VAC/DC;
H = 240..250 VAC/DC; J = 380…400 VAC;
K = 440 VAC
Locking provisions:
X = None; A = Keylock
B = Button guard; C = Padlock provision; D = A+B; E = A+C
T = Heavy duty padlock;
9 = Extra heavy duty padlock
T8
Catalog number explanation
Tmax
MCCBs
17.58 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
17
2000A Frame, electronic trip unit (AC only) standard
horizontal terminals
Breaker IC at
480VAC kA Trip Unit 3 pole, 600V
Catalog number
T8V 125
PR232 LSI (Dip Switch) T8VBD3GC000000XX
PR331 LSIG (Dip Switch) T8VBD3GE000000XX
PR332 LI (LCD) T8VBD3GP00A000XX 1
PR332 LSI (LCD) T8VBD3GR00A000XX 1
PR332 LSIG (LCD) T8VBD3GS00A000XX 1
2500A Frame, electronic trip unit (AC only) standard
horizontal terminals
Breaker IC at
480VAC kA Trip Unit 3 pole, 600V
Catalog number
T8V 125
PR232 LSI (Dip Switch) T8VBE3HC000000XX
PR331 LSIG (Dip Switch) T8VBE3HE000000XX
PR332 LI (LCD) T8VBE3HP00A000XX 1
PR332 LSI (LCD) T8VBE3HR00A000XX 1
PR332 LSIG (LCD) T8VBE3HS00A000XX 1
3000A Frame, electronic trip unit (AC only) standard with
vertical terminals - Required
Breaker IC at 480VAC
kA Trip Unit 3 pole, 600V
Catalog number
T8V 125
PR232 LSI (Dip Switch) T8VBF3JC000000XX
PR331 LSIG (Dip Switch) T8VBF3JE000000XX
PR332 LI (LCD) T8VBF3JP00A000XX 1
PR332 LSI (LCD) T8VBF3JR00A000XX 1
PR332 LSIG (LCD) T8VBF3JS00A000XX 1
1600A Frame, electronic trip unit (AC only) standard
horizontal terminals
Breaker IC at 480VAC
kA Trip Unit 3 pole, 600V
Catalog number
T8V 125
PR232 LSI (Dip Switch) T8VBC3FC000000XX
PR331 LSIG (Dip Switch) T8VBC3FE000000XX
PR332 LI (LCD) T8VBC3FP00A000XX 1
PR332 LSI (LCD) T8VBC3FR00A000XX 1
PR332 LSIG (LCD) T8VBC3FS00A000XX 1
T8
1600/2000/2500/3000A 600V∆ - Three Pole
Electronic (AC Only)
1 Includes 4 open/closed auxillary contacts as standard
Tmax
MCCBs
Low Voltage Products & Systems 17.59
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
17
T8
1600/2000/2500/3000A 600V∆ - Three Pole
Electronic (AC Only) 100% Rated
2000A Frame, electronic trip unit (AC only) standard
horizontal terminals
Breaker IC at
480VAC kA Trip Unit 3 pole, 600V
Catalog number
T8V 125
PR232 LSI (Dip Switch) T8VQD3GC000000XX
PR331 LSIG (Dip Switch) T8VQD3GE000000XX
PR332 LI (LCD) T8VQD3GP00A000XX 1
PR332 LSI (LCD) T8VQD3GP00A000XX 1
PR332 LSIG (LCD) T8VQD3GR00A000XX 1
2500A Frame, electronic trip unit (AC only) standard with
vertical terminals - Required
Breaker IC at
480VAC kA Trip Unit 3 pole, 600V
Catalog number
T8V 125
PR232 LSI (Dip Switch) T8VQE3HC000000XX
PR331 LSIG (Dip Switch) T8VQE3HE000000XX
PR332 LI (LCD) T8VQE3HP00A000XX 1
PR332 LSI (LCD) T8VQE3HR00A000XX 1
PR332 LSIG (LCD) T8VQE3HS00A000XX 1
3000A Frame, electronic trip unit (AC only) standard with
vertical terminals - Required
Breaker IC at
480VAC kA Trip Unit 3 pole, 600V
Catalog number
T8V 125
PR232 LSI (Dip Switch) T8VQF3JC000000XX
PR331 LSIG (Dip Switch) T8VQF3JE000000XX
PR332 LI (LCD) T8VQF3JP00A000XX 1
PR332 LSI (LCD) T8VQF3JR00A000XX 1
PR332 LSIG (LCD) T8VQF3JS00A000XX 1
1600A Frame, electronic trip unit (AC only) standard
horizontal terminals
Breaker IC at
480VAC kA Trip Unit 3 pole, 600V
Catalog number
T8V 125
PR232 LSI (Dip Switch) T8VQC3FC000000XX
PR331 LSIG (Dip Switch) T8VQC3FE000000XX
PR332 LI (LCD) T8VQC3FP00A000XX 1
PR332 LSI (LCD) T8VQC3FR00A000XX 1
PR332 LSIG (LCD) T8VQC3FS00A000XX 1
1 Includes 4 open/closed auxillary contacts as standard
Tmax
MCCBs
17.60 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
17
T8
1600/2000/2500/3000A 600V∆— Four pole
Electronic (AC Only)
2000A Frame, electronic trip unit (AC only) standard
horizontal terminals
Breaker IC at
480VAC kA Trip Unit 4 pole, 600V
Catalog number
T8V 125
PR232 LSI (Dip Switch) T8VBD4GC000000XX
PR331 LSIG (Dip Switch) T8VBD4GE000000XX
PR332 LI (LCD) T8VBD4GP00A000XX 1
PR332 LSI (LCD) T8VBD4GR00A000XX 1
PR332 LSIG (LCD) T8VBD4GS00A000XX 1
2500A Frame, electronic trip unit (AC only) standard
horizontal terminals
Breaker IC at
480VAC kA Trip Unit 4 pole, 600V
Catalog number
T8V 125
PR232 LSI (Dip Switch) T8VBE4HC000000XX
PR331 LSIG (Dip Switch) T8VBE4HE000000XX
PR332 LI (LCD) T8VBE4HP00A000XX 1
PR332 LSI (LCD) T8VBE4HR00A000XX 1
PR332 LSIG (LCD) T8VBE4HS00A000XX 1
3000A Frame, electronic trip unit (AC only) standard with
vertical terminals - Required
Breaker IC at
480VAC kA Trip Unit 4 pole, 600V
Catalog number
T8V 125
PR232 LSI (Dip Switch) T8VBF4JC000000XX
PR331 LSIG (Dip Switch) T8VBF4JE000000XX
PR332 LI (LCD) T8VBF4JP00A000XX 1
PR332 LSI (LCD) T8VBF4JR00A000XX 1
PR332 LSIG (LCD) T8VBF4JS00A000XX 1
1600A Frame, electronic trip unit (AC only) standard
horizontal terminals
Breaker IC at
480VAC kA Trip Unit 4 pole, 600V
Catalog number
T8V 125
PR232 LSI (Dip Switch) T8VBC4FC000000XX
PR331 LSIG (Dip Switch) T8VBC4FE000000XX
PR332 LI (LCD) T8VBC4FP00A000XX 1
PR332 LSI (LCD) T8VBC4FR00A000XX 1
PR332 LSIG (LCD) T8VBC4FS00A000XX 1
1 Includes 4 open/closed auxillary contacts as standard
Tmax
MCCBs
Low Voltage Products & Systems 17.61
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
17
T8
1600/2000/2500/3000A 600V∆—Four pole
Electronic (AC Only) 100% Rated
2000A Frame, electronic trip unit (AC only) standard
horizontal terminals
Breaker IC at
480VAC kA Trip Unit 4 pole, 600V
Catalog number
T8V 125
PR232 LSI (Dip Switch) T8VQD4GC000000XX
PR331 LSIG (Dip Switch) T8VQD4GE000000XX
PR332 LI (LCD) T8VQD4GP00A000XX 1
PR332 LSI (LCD) T8VQC4GR00A000XX 1
PR332 LSIG (LCD) T8VQD4GS00A000XX 1
2500A Frame, electronic trip unit (AC only) standard vertical
terminals - Required
Breaker IC at
480VAC kA Trip Unit 4 pole, 600V
Catalog number
T8V 125
PR232 LSI (Dip Switch) T8VQE4HC000000XX
PR331 LSIG (Dip Switch) T8VQE4HE000000XX
PR332 LI (LCD) T8VQE4HP00A000XX 1
PR332 LSI (LCD) T8VQE4HR00A000XX 1
PR332 LSIG (LCD) T8VQE4HS00A000XX 1
3000A Frame, electronic trip unit (AC only) standard with
vertical terminals - Required
Breaker IC at
480VAC kA Trip Unit 4 pole, 600V
Catalog number
T8V 125
PR232 LSI (Dip Switch) T8VQF4JC000000XX
PR331 LSIG (Dip Switch) T8VQF4JE000000XX
PR332 LI (LCD) T8VQF4JP00A000XX 1
PR332 LSI (LCD) T8VQF4JR00A000XX 1
PR332 LSIG (LCD) T8VQF4JS00A000XX 1
1600A Frame, electronic trip unit (AC only) standard
horizontal terminals
Breaker IC at
480VAC kA Trip Unit 4 pole, 600V
Catalog number
T8V 125
PR232 LSI (Dip Switch) T8VQC4FC000000XX
PR331 LSIG (Dip Switch) T8VQC4FE000000XX
PR332 LI (LCD) T8VQC4FP00A000XX 1
PR332 LSI (LCD) T8VQC4FR00A000XX 1
PR332 LSIG (LCD) T8VQC4FS00A000XX 1
1 Includes 4 open/closed auxillary contacts as standard
Tmax
MCCBs
17.62 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
17
T8
2000/2500/3000A 600V∆
Molded Case Switch
2000A Frame, standard horizontal terminals
Breaker 3 pole, 600V
Catalog number
T8V-D T8V0D30D000000XX
2500A Frame, standard horizontal terminals
Breaker 3 pole, 600V
Catalog number
T8V-D T8V0E30D000000XX
3000A Frame, standard with vertical terminals - Required
Breaker 3 pole, 600V
Catalog number
T8V-D T8V0F30D000000XX
T8V-D
Rated Voltage
AC 600VAC
DC
Magnetic Overide 40000
Tmax
MCCBs
Low Voltage Products & Systems 17.63
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
17
UL Rating plugs Catalog number
T8
1000A Rating plug KT81000RP
1200A Rating plug KT81200RP
1600A Rating plug KT81600RP
2000A Rating plug KT82000RP
2500A Rating plug KT82500RP
3000A Rating plug KT83000RP
Current sensor for external neutral Field installation
Catalog number
T8 Current sensor for external neutral 1000A-3000A KT8NCT
Accessories for trip units Field/factory installation
Catalog number
T8
Communication module (Modbus (RTU) PR330/D-M 2
External wireless communication module BT030
Power supply unit PR030/B
Voltage module, 3 pole 3PR330/V-T83
Voltage module, 4 pole 3PR330/V-T84
Contact signaling undervoltage de-energized Field/factory installation
Catalog number
T8 NC UV signaling contact KE6UE01
NO UV signaling contact KE6UE10
Bell alarm with remote reset command Field/factory installation
Catalog number
T8
Remote setting of circuit breaker after opening by overcurrent release
220-240 VAC/DC DE6TBAR4
Remote setting of circuit breaker after opening by overcurrent release
110-130 VAC/DC DE6TBAR5
Remote setting of circuit breaker after opening by overcurrent release
24-30 VAC/DC DE6TBAR9
Bell alarm Field/factory installation
Catalog number
T8 Allows visual signaling (mechanical) and remote signaling (electrical)
of circuit breaker opening by overcurrent release DE6TBA
Closing coil Field/factory installation
Catalog number
T8
440 VAC KE6C1
380…400VAC KE6C2
240…250 VAC/DC KE6C3
220…240 VAC/DC KE6C4
120…127 VAC/DC KE6C5
110…120 VAC/DC KE6C6
60 VAC/DC KE6C7
48 VAC/DC KE6C8
30 VAC/DC KE6C9
24 VDC KE6C0
Auxiliary contacts Field/factory installation
Catalog number
T8
4 open/closed PR232-T8/PR331 KT8A4
4 open/closed PR332 1KT8A4-PR332
4 open/closed 24V PR232-T8/PR331 KT8A4D
4 open/closed 24V PR332 KT8A4D-PR332
Spring charging motor Field/factory installation
Catalog number
T8
24…30 VAC/DC KE6M9
48…60 VAC/DC KE6M7
100…130 VAC/DC KE6M5
220…250 VAC/DC KE6M3
KE6C*
KT8A4
KE6M*
1 Included as standard on breakers ordered with PR332 trip unit
2 Discount schedule SAT (T0)
3 Factory install only.
T8
Accessories, electrical
Tmax
MCCBs
17.64 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
17
Shunt trip Field/factory installation
Catalog number
T8
440 VAC KE6S1
380…400 VAC KE6S2
240…250 VAC/DC KE6S3
220…240 VAC/DC KE6S4
120…127 VAC/DC KE6S5
110…120 VAC/DC KE6S6
60 VAC/DC KE6S7
48 VAC/DC KE6S8
30 VAC/DC KE6S9
24 VDC KE6S0
Second shunt trip 1Field/factory installation
Catalog number
T8
440 VAC KE6S1-2
380…400 VAC KE6S2-2
240…250 VAC/DC KE6S3-2
220…240 VAC/DC KE6S4-2
120…127 VAC/DC KE6S5-2
110…120 VAC/DC KE6S6-2
60 VAC/DC KE6S7-2
48 VAC/DC KE6S8-2
30 VAC/DC KE6S9-2
24 VDC KE6S0-2
Undervoltage Field/factory installation
Catalog number
T8
440 VAC KE6U1
380…400 VAC KE6U2
240…250 VAC KE6U3
220…240 VAC/DC KE6U4
120…127 VAC/DC KE6U5
110…120 VACV/DC KE6U6
60 VAC/DC KE6U7
48 VAC/DC KE6U8
30 VAC/DC KE6U9
24 VDC KE6U0
KE6S*
KE6U*
T8
Accessories, electrical
1 May be used in place undervoltage.
Tmax
MCCBs
Low Voltage Products & Systems 17.65
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
17
KE6PG
Key lock in open position Field/factory installation
Catalog number
T8
Key lock n. 20005 1KT8KL2
Key lock n. 20006 KT8KL3
Key lock n. 20007 KT8KL4
Key lock n. 20008 KT8KL5
Key lock different keys KT8KL1
Vertical terminals Field installation
Catalog number
T8 Rear Vertical Terminals (2) Set of six KT82500VR-6
Set of eight KT82500VR-8
Cable terminals Wire size Field installation
Catalog number
T8 Mechanical Lugs (set of 3) 1/0-750 kcmil (4) K8TL
1/0-750 kcmil (6) K8TM
Padlocking button cover Field/factory installation
Catalog number
T8
3-4mm locks (padlocks not supplied) KE6PD1
HD padlock device KE6PDHD1
Extra HD padlock device KE6PDHD2
Button guard Field/factory installation
Catalog number
T8 Protective cover for opening and
closing pushbuttons KE6PG
Mechanical operation counter Field/factory installation
Catalog number
T8 Indicates the number of mechanical operations KE6MC
IP54 door protection Field installation
Catalog number
T8 Protective cover KE6DC
Phase barriers-top terminals only Field installation
Catalog number
T8
Low 100mm 2 pcs (3P) KT8PBL-3
Low 100mm 3 pcs (4P) KT8PBL-4
High 200mm 2 pcs (3P) KT8PBH-3
High 200mm 4 pcs (4P) KT8PBH-4
T8
Accessories, mechanical
1 Key lock number when factory installed is 20005.
Tmax
MCCBs
17.66 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
17
Absorbed power on inrush
Shunt trip, Second shunt trip, closing coil
Voltage AC DC
24 VDC 200
30 VAC/DC 200 200
48 VAC/DC 200 200
60 VAC/DC 200 200
110…120 VAC/DC 200 200
120…127 VAC/DC 200 200
220…240 VAC/DC 200 200
380…400 VAC 200
440 VAC 200
Opening time shunt trip - Second shunt trip (ms) 60 60
Closing time closing coil (ms) 80 80
Spring charging motor
Shunt trip, Second shunt trip, closing coil
Rated Voltage AC DC
24…30 24…30
48…60 48…60
100…130 100…130
220…250 220…250
Operating voltage (%Un) 85-110 85…110
Power consumption on inrush 500 VA 500 W
Inrush time (s) 0.2 0.2
Charging time (s) 4-5 4-5
T8
Technical data
Tmax
MCCBs
Low Voltage Products & Systems 17.67
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
Introduction
Thanks to its experience with Tmax UL,
ABB is proposing a complete range of
products in accordance to UL489B, a
new standard, whose requirements cover
molded case circuit breakers and molded
case switches rated up to 1000V DC, in-
tended for use with photovoltaic systems.
A complete range of MCCB and MCS is
available up to 1000A for use at 1000V
DC, complete with jumpers for connection
of poles in series.
Standards
UL489B
Dimensions
All PV breakers are the same size as their
standard UL/IEC counterparts.
Weights
T1 - 3.2 lbs.
T4 - 6.18 lbs.
T5 - 8.55 lbs.
T6 - 20.9 lbs.
T7 - 24.25 lbs.
Accessories
Standard Tmax accessories are able to work
with all UL 489B units.
Jumpers come standard with all breakers in
either all poles in series or 2+1 or 2+2.
Breakers without lug kits come with termi-
nals to connect to Busbar poles in series for
installation options.
Tmax
UL489B Photovoltaic circuit breakers
Tmax
UL489B Photovoltaic circuit breakers
Tmax
MCCBs
17.68 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
General information
Catalog number explanation
Catalog number explanation
___ ___ ___ ___ ___ ___ ___ ___
Frame size
Photovoltaic designation
Number of poles
Blank = 3 pole
Connection
L = With lugs
W = Bus connection
Jumpers
A = Jumpers with all poles in series
B = Jumpers with 2+2 or 2+1 conguration
Amperage
Device
D = Molded case switch
T = Thermal-mag circuit breaker
P
T
Tmax
MCCBs
Low Voltage Products & Systems 17.69
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
Tmax UL489B
Molded case circuit breakers and switches
T4 - 200A Frame TMA, Thermal magnetic adjustable
IC at 1000VDC Rating Lugs Poles in Series Catalog
number
3kA 40A Ye s 2+1 T4PB040TL
3 T4PA040TL
3kA 50A Ye s 2+1 T4PB050TL
3 T4PA050TL
3kA 80A Ye s 2+1 T4PB080TL
3 T4PA080TL
3kA 100A Yes 2+1 T4PB100TL
3 T4PA100TL
3kA 125A Yes 2+1 T4PB125TL
3 T4PA125TL
3kA 150A Yes 2+1 T4PB150TL
3 T4PA150TL
3kA 200A Yes 2+1 T4PB200TL
3 T4PA200TL
T5 - 400A Frame TMA, Thermal magnetic adjustable
IC at 1000VDC Rating Lugs Poles in Series Catalog
number
5kA 400A Yes 2+1 T5PB400TL
3 T5PA400TL
5kA 400A No 2+1 T5PB400TW
3 T5PA400TW
T6 - 800A Frame TMA, Thermal magnetic adjustable
IC at 1000VDC Rating Lugs Poles in Series Catalog
number
10kA 600A Yes 2+2 T6PB600TL-4
4 T6PA600TL-4
10kA 800A No 2+2 T6PB800TW-4
4 T6PA800TW-4
T1-D 100A Molded case switch
Rating Lugs Poles in Series Catalog
number
100A Yes 2+2 T1PB100DL-4
4 T1PA100DL-4
T4-D 200A Molded case switch
Rating Lugs Poles in Series Catalog
number
200A Yes 2+1 T4PB200DL
3 T4PA200DL
T5-D 400A Molded case switch
Rating Lugs Poles in Series Catalog
number
400A Yes 2+1 T5PB400DL
3 T5PA400DL
400A No 2+1 T5PB400DW
3 T5PA400DW
T6-D 800A Frame molded case switch
Rating Lugs Poles in Series Catalog
number
600A Yes 2+2 T6PB600DL-4
4 T6PA600DL-4
800A No 2+2 T6PB800DW-4
4 T6PA800DW-4
T7-D 1000A Molded case switch
Rating Lugs Poles in Series Catalog
number
1000A Yes 2+2
T7MPB1000DL-4
4
T7MPA1000DL-4
NOTE: All poles in series is for use in grounded systems.
2+1 or 2+2 congurations are for ungrounded systems.
Tmax
MCCBs
17.70 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
Tmax UL489B
Jumper kit accessories
T1-D
Description Rating Poles in Series Catalog
number
JUMPER KIT T1PV 100A 4P 2+2PS LUG UL 100A 2+2 KT1PB100-L
JUMPER KIT T1PV 100A 4P 4PS LUG UL 4 KT1PA100-L
T4-D
Description Rating Poles in Series Catalog
number
JUMPER KIT T4PV 100A 3P 2+1PS LUG UL 100A 2+1 KT4PB100-L
JUMPER KIT T4PV 100A 3P 3PS LUG UL 3 KT4PA100-L
JUMPER KIT T4PV 200A 3P 2+1PS LUG UL 200A 2+1 KT4PB200-L
JUMPER KIT T4PV 200A 3P 3PS LUG UL 3 KT4PA200-L
T5-D
Description Rating Poles in Series Catalog
number
JUMPER KIT T5PV 400A 3P 2+1PS LUG UL
400A
2+1 KT5PB400-L
JUMPER KIT T5PV 400A 3P 3PS LUG UL 3 KT5PA400-L
JUMPER KIT T5PV 400A 3P 2+1PS BUS UL 2+1 KT5PB400-W
JUMPER KIT T5PV 400A 3P 3PS BUS UL 3 KT5PA400-W
T6-D
Description Rating Poles in Series Catalog
number
JUMPER KIT T6PV 600A 4P 2+2PS LUG UL 600A 2+2 KT6PB600-L
JUMPER KIT T6PV 600A 4P 4PS LUG UL 4 KT6PA600-L
JUMPER KIT T6PV 800A 4P 2+2PS BUS UL 800A 2+2 KT6PB800-W
JUMPER KIT T6PV 800A 4P 4PS BUS UL 4 KT6PA800-W
T7-D
Description Rating Poles in Series Catalog
number
JUMPER KIT T7PV 1000A 4P 2+2PS LUG UL 1000A 2+2 KT7PB1000-L
JUMPER KIT T7PV 1000A 4P 4PS LUG UL 4 KT7PA1000-L
NOTE: See pages 17.71-17.83 for additional electrical/mechanical accessories
Tmax
MCCBs
Low Voltage Products & Systems 17.71
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
Accessories
Electrical
T1 - T7
KT3S4
1 For factory installation add sufx given to end of circuit breaker catalog number per accessory format.
2 Must be ordered separately for eld installation.
T1 with KT3S4
T7 X1 Shunt trip - UVR
Shunt trips -(Standard) 1
For remote opening of circuit breaker. Guaranteed operation for a voltage of between 75-110%
of the rated power supply voltage. T1-T6 mounts in the left hand cavity cannot be used with UVR on 2-3P
breakers
Factory Installation 1Field Installation
Frame Size Voltage Catalog number sufx Catalog number
T1-T3
480 - 500VAC S1 KT3S1
220-250VAC/DC S2 KT3S2
380 - 440VAC S3 KT3S3
110 - 125VAC/DC S4 KT3S4
48 - 60VAC/DC S7 KT3S7
24 - 30VAC/DC S8 KT3S8
12VDC S9 KT3S9
Ts3
480VAC/250VDC S1 KTS3S1
240 VAC S2 KTS3S2
120VAC/125VDC S4 KTS3S4
48VDC S7 KTS3S7
24VAC/VDC S8 KTS3S8
12VDC S9 KTS3S9
T4, T5, T6
3
480-500VAC S1 KT5S1
220/250VAC/DC S2 KT5S2
380-440VAC S3 KT5S3
110-125VAC/DC S4 KT5S4
48-60VAC/DC S7 KT5S7
24VAC/DC S8 KT5S8
12VDC S9 KT5S9
T7
415-440VAC S1 KT7XS1
380-400VAC S2 KT7XS2
240-250VAC/DC S3 KT7XS3
220-240VAC/DC S4 KT7XS4
120-127VAC/DC S5 KT7XS5
110-120VAC/DC S6 KT7XS6
60VAC/DC S7 KT7XS7
48VAC/DC S8 KT7XS8
30VAC/DC S9 KT7XS9
24VAC/DC S0 KT7XS0
Shunt trip connector (REQUIRED for Ts3) 2Field Kit
Ts3
Fixed Mount 2Included when shunt
trip factory installed KTS3C-SU
Draw-out 2Included when shunt
trip factory installed KTS3C-SUP
Shunt trips (Permanent Supply) 1
For remote opening of circuit breaker. Guaranteed operation for a voltage of between 75-110% of the rated
power supply voltage. These shunt trips have much lower power consumption.
Factory Installation 1Field Installation
Frame Size Voltage Catalog number sufx Catalog number
Ts3 24VDC SA KTS3SA
120VAC SB KTS3SB
T4, T5, T6 324-30VDC SA KT5SA
110/120/VAC SB KT5SB
Shunt trip connector (REQUIRED for Ts3) 2Field Kit
Ts3
Fixed Mount 2Included when shunt
trip factory installed KTS3C-SU
Draw-out 2Included when shunt
trip factory installed KTS3C-SUP
Tmax
MCCBs
17.72 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
Accessories
Electrical
T1 - T7
T7 X1 Shunt trip - UVR
KT3U2
Undervoltage release - UVR
Will trip circuit breaker when connected voltage drops to 35-70% of the undervoltage release
voltage rating. Will allow circuit breaker to close when voltage is approximately 85% of the
rated voltage. T1-T6 mounts in the left hand cavity cannot be used with shunt trip on 2-3P breakers
Factory Installation 1Field Installation
Frame Size Voltage Catalog number
sufx Catalog number
T1-T3
480 - 500VAC U1 KT3U1
220-250VAC/DC U2 KT3U2
380 - 440VAC U3 KT3U3
110 - 125VAC/DC U4 KT3U4
60VAC/DC U5 KT3U5
48VAC/DC U7 KT3U7
24 - 30VAC/DC U8 KT3U8
Ts3
480VAC U1 KTS3U1
240VAC U2 KTS3U2
24VAC U3 KTS3U3
120VAC U4 KTS3U4
250VDC U5 KTS3U5
125VDC U6 KTS3U6
48VDC U7 KTS3U7
24VDC U8 KTS3U8
T4, T5, T6
480-500VAC U1 KT5U1
220/250VAC/DC U2 KT5U2
380-440VAC U3 KT5U3
110-125VAC/DC U4 KT5U4
60VAC/DC U5 KT5U5
48VAC/DC U7 KT5U7
24VAC/DC U8 KT5U8
T7
415-440VAC U1 KT7XU1
380-400VAC U2 KT7XU2
240-250VAC/DC U3 KT7XU3
220-240VAC/DC U4 KT7XU4
120-127VAC/DC U5 KT7XU5
110-120VAC/DC U6 KT7XU6
60VAC/DC U7 KT7XU7
48VAC/DC U8 KT7XU8
30VAC/DC U9 KT7XU9
24VAC/DC U0 KT7XU0
Undervoltage trip connector (REQUIRED for Ts3) 2Field Kit
Ts3
Fixed Mount 2
Included when
under voltage factory
installed
KTS3C-SU
Plug-In/Draw-out 2
Included when under
voltage factory
installed
KTS3C-SUP
1 For factory installation add sufx given to end of circuit breaker catalog number per accessory format.
2 Must be ordered separately for eld installation.
Tmax
MCCBs
Low Voltage Products & Systems 17.73
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
Accessories
Electrical
T1 - T7
KTS3AS
T1 with K3TAS
Auxiliary contacts - AUX 1
Auxiliary contacts are for indication of the circuit breaker open-closed. Bell alarm contacts (BA) can be
used to indicate circuit breaker tripped.
Frame Size
Factory Installation
1Field Installation
Catalog number
sufx Catalog number
T1-T3 2
1 Form C + 1BA AKT3AS
3 Form C + 1BA A3 KT3AS3
3 Form C + 1BA 24VDC A3AU KT3AS3-AU
T2 T2 PR221DS 1 Form C + 1BA AKT2AS-E
Ts3 2 Form C AKTS3AS
1 Form C+ 1 BA BA KTS3BA
T4, T5, T6 4
1 Form C + 1BA 250VAC/VDC AKT5AS
2 Form C 400VAC/250VDC A2 KT5AS2-B
3 Form C + 1BA 250VAC/VDC A3 KT5AS3
3 Form C + 1BA 24VDC A3AU KT5AS3-AU
T7
1 Form C + 1BA 400VAC/250VDC A KT7AS
2 Form C 400VAC/250VDC A2 KT7XAS2
1 Form C + 1BA 24VDC AAU KT7AS-AU
2 Form C 24VDC A2AU KT7XAS2-AU
3 Form C + 1BA 400VAC/250VDC A3 KT7AS3
3 Form C + 1BA 24VDC A3AU KT7AS3-AU
Auxiliary contact connector (REQUIRED for Ts3) 3Field Kit
Ts3 Fixed Mount 3Included KTS3C-AB
Plug-In /Drawout 3Included KTS3C-ABP
1 For factory installation add sufx to end of breaker part number per accessory format .
2 Not compatible for T2 with PR221DS trip unit.
3 Must be ordered separately for eld installation.
Tmax
MCCBs
17.74 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
Accessories
Motor operators
T1 - T7
KT3M1
KTS3M2
KT5M2
Electrical operators
Allows remote opening and closing of circuit breaker
Frame size Voltage Catalog
number
Solenoid operator
T1-T3 48 - 60VDC KT3M1
110 - 250VAC/DC KT3M2
Direct action motor operator
Ts3
240VAC/250VDC KTS3M2
120VAC/125VDC KTS3M4
48VDC KTS3M7
24VDC KTS3M8
Motor operator connector (REQUIRED for Ts3) 1
Ts3 Fixed Mount 1KTS3C-M
Plug-In / Draw-out 1KTS3C-MP
Stored energy motor operator
T4, T5
220-250VAC/DC KT5M2
110--125-VAC/DC KT5M4
48-60VDC KT5M7
24VDC KT5M8
Contact for remote/manual operation (stored energy operator)
T4, T5, T6 - KT5MA
Stored energy motor operator
T6
220-250VAC/DC KT6M2
110--125-VAC/DC KT6M4
48-60VDC KT6M7
24VDC KT6M8
380VAC KT6M3
1 Must be ordered separately for eld installation.
Tmax
MCCBs
Low Voltage Products & Systems 17.75
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
Accessories
Trip units
T4 - T7
1 Always supplied with PR332/P trip unit.
3 Factory installed only.
Frame Size Rating plug Catalog
number
Rating plugs (UL)
T7
400A Rating plug KT7X0400RP
600A Rating plug KT7X0600RP
800 Rating plug KT7X0800RP
1000A Rating plug KT7X1000RP
1200 Rating plug KT7X1200RP
Modules for T7 PR332 trip units
T7 Voltage module 2PR330/VT7
Communication module (Modbus RTU) PR330/D-M
External units
Test and conguration unit 3PR010/T
Trip coil test-all Tmax electronic trip unit except PR33* K7TUT
External Bluetooth communication module 1
Includes diagnostic software for Modbus / Bluetooth networks BT030
Battery power supply unit 1PR030/B
Not suitable for UL applications.
T7 - Allows remote opening when used with PR330/D-M and shunt trip
T7M - Allows remote opening and closing when used with PR330//D-M. shunt trip and closing coil
Actuator module (IEC)
T7 Actuator module 2PR330/R-T7
Neutral current transformers (required for 4 wire ground fault systems)
T4
100A KT4NCT-100
150A KT4NCT-150
250A KT4NCT-250
T5 300A KT5NCT-300
400A KT5NCT-400
T6 600A KT6NCT-600
800A KT6NCT-800
Current sensor for external neutral
T7 400 - 1200A KT7NCT
Tmax
MCCBs
17.76 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
Technical data
Shunt trips, Undervoltages
T1 - T7
Standard shunt trip
Voltage
Inrush Power Consumption
T1,T2,T3 Ts3 T4,T5,T6 T7
AC (VA) DC (W) AC (VA) DC (W) AC (VA) DC (W) AC (VA) DC (W)
12 VDC - 50 - 120 - 150 - -
24 VAC/DC - - 100 100 or 4 1- - 300 300
24…30 VAC/DC 50 50 - - 150 150 - -
30 VAC/DC - - - - - - 300 300
48 VAC/DC - - - 120 - - 300 300
48…60 VAC/DC 60 60 - - 150 150 - -
60 VAC/DC - - - - - - 300 300
100…120 VAC/DC - - 100 or 4 1- - - 300 300
120…127 VAC/DC - - - - - - 300 300
110…127 VAC 110…125 VDC 50 50 - 120 150 150 - -
220…240 VAC/DC - - - - - - 300 300
220…240 VAC 220…250 VDC 50 50 100 120 150 150 - -
240…250 VAC/DC - - - - - - 300 300
380…400 VAC - - - - - - 300 -
380…440 VAC 55 - - - 150 - - -
415…440 VAC - - - - - - 300 -
480 VAC - - 100 - - - - -
480…525 VAC 55 - - - 150 - - -
Opening Time (ms) 15 15 ≤15 ≤15 15 15 20 20
Permanent supply shunt trip
Voltage T4,T5,T6
AC (VA) DC (W)
24 VAC/DC 4 4
100…120 VAC 4 -
Undervoltage
Voltage
Power consumption during permanent operation
T1,T2,T3 Ts3 T4, T5, T6 T7
AC (VA) DC (W) AC (VA) DC (W) AC (VA) DC (W) AC (VA) DC (W)
24 VAC/DC - - 63 - - 3.5 3.5
24…30 VAC/DC 1.5 1.5 - - 63 - -
30 VAC/DC - - - - - - 3.5 3.5
48 VAC/DC 116363 - -
60 VAV/DC 1 1 - - 63 - -
110…120 VAC/DC - - 6- - - 3.5 3.5
120…127 VAC/DC - - - - - - 3.5 3.5
110…127 VAC 110…125 VDC 2 2 - - 63 - -
220…240 VAC/DC - - - - - - 3.5 3.5
220…240 VAC 220…250 VDC 2.5 2.5 - 3 63 - -
220…250 VAC - - 6-----
240…250 VAC/DC - - - - - - 3.5 3.5
380…400 VAC - - - - - - 3.5 -
380…440 VAC 3 - - - 6- - -
415 - 440 VAC - - - - - - 3.5 -
480…525 VAC 4 - - - 6- - -
480 VAC - - 6-----
Opening Time (ms) 15 15 ≤18 ≤18 ≤25 ≤25 ≤25 ≤25
1 Shunt trip permanent supply
Tmax
MCCBs
Low Voltage Products & Systems 17.77
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
Technical data
Electrical operators
T1 - T6
Electrical operator, T1-T3
Rated Voltage AC DC
- 48…60
110...250 110...250
Operating Voltage 85…110% Un
Inrush power absorption during operation 1800 (VA) 1000 (W)
Power on stand by < 100 (mW)
Time opening (s) < 0.1
closing (s) < 0.1
Minimum control impulse time on
opening and closing (ms) >100
This unit is permanently supplied on stand by, a control is applied by means of
external contact in a low power circuit.
Contact characteristics:
Voltage AC/DC=24V
Current 50 mA
Electrical operator, Ts3
Rated Voltage AC DC
- 24
- 48…60
120 125
240 250
440 -
Operating Voltage 85…110 % Un
Inrush power absorption 500 (VA) 500 (W)
Service power absorption 350 (VA) 350 (W)
Time constant (ms) 18
Duration opening (s) 0.1
closing (s) 0.1
Minimum duration of the opening and closing
command impulse (ms) ≥150
Electrical operator, T4-T5
Voltage AC DC
- 24
- 48…60
110…125 110…125
220-250 220-250
380 -
Operating Voltage 85…110%
Inrush power consumption ≤ 300VA ≤ 300W
In service power consumption ≤150VA ≤150W
Duration
opening (s) 1.5
closing (s) < 0.1
resetting (s) 3
Minimum duration of the opening and closing
command impulse (ms) ≥100
Electrical operator, T6
Voltage AC DC
- 24
- 48…60
110-125 110-125
220-250 220-250
380 -
Operating Voltage 85…110%
Inrush power consumption ≤ 400VA ≤ 400W
In service power consumption ≤150VA ≤150W
Duration
opening (s) 3
closing (s) < 0.1
resetting (s) 5
Minimum duration of the opening and closing
command impulse (ms) ≥100
Tmax
MCCBs
17.78 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
Accessories
Mechanical
T1 - T7
1 Comes standard with high prole terminal covers.
2 Uses front extended spreaded terminals... refer to technical catalog.
3 Not suitable for use on T5 600A.
Standard cable terminal
Frame Wire Size Catalog number
(set of 3)
Catalog number
(set of 4)
T1 14 AWG-1/0 Integral Integral
T2 14 AWG-1/0 KT2100-3 KT2100-4
T3 14 AWG - 1/0 KT3100-3 KT3100-4
4 AWG - 300 kcmil KT3225-3 KT3225-4
Ts3
14-2 K3TA K3TA-4
14-1/0 K4TB K4TB-4
2-4/0 K4TC K4TC-4
4-300 kcmil K4TD K4TD-4
T4 14 AWG-1/0 KT4100-3 KT4100-4
6 AWG-350 kcmil KT4250-3 KT4250-4
T5 3250 kcmil-500 kcmil KT5300-3 KT5300-4
T5 13 (2) 3/0-250 kcmil KT5400-3 KT5400-4
T5 2(2) 3/0-500 kcmil KT5600-3
T6 (2) 250-500 kcmil K6TH K6TH-4
T6 1(3) 2/0-400 kcmil K6TJ K6TJ-4
T7 1(4) 4/0-500 kcmil KT7X1200-3 KT7X1200-4
Standard cable lug kits with power control taps
Frame Wire Size Catalog number
(set of 3)
Catalog number
(set of 4)
T3 14 AWG - 1/0 KT3100-3C KT3100-4C
4 AWG - 300 kcmil KT3225-3C KT3225-4C
Ts3
14 AWG-1/0 K4TBC K4TBC-4
2 AWG-4/0 K4TCC K4TCC-4
4 AWG-300 kcmil K4TDC K4TDC-4
T4 14 AWG-1/0 KT4100-3C KT4100-4C
6 AWG-350 kcmil KT4250-3C KT4250-4C
T5 3250 kcmil-500 kcmil KT5300-3C KT5300-4C
T5 13 (2) 3/0-250 kcmil KT5400-3C KT5400-4C
T6 (2) 250-500 kcmil K6THC K6THC-4
T6 1(3) 2/0-400 kcmil K6TJC K6TJC-4
Terminal covers for fixed breakers - Low prole-kit
includes two pieces
Frame Catalog number
(3 pole)
Catalog number
(4 pole)
T1 KT1LTC-3 KT1LTC-4
T2 KT2LTC-3 KT2LTC-4
T3 KT3LTC-3 KT3LTC-4
Ts3 KTS3LTC-3 KTS3LTC-4
T4 KT4LTC-3 KT4LTC-4
T5 KT5LTC-3 KT5LTC-4
T6 KT6LTC-3 KT6LTC-4
T7 KT7XLTC-3 KT7XLTC-4
Terminal covers for fixed breakers - High prole-kit
includes two pieces
Frame Catalog number
(3 pole )
Catalog number
(4 pole)
T1 KT1HTC-3 KT1HTC-4
T2 KT2HTC-3 KT2HTC-4
T3 KT3HTC-3 KT3HTC-4
Ts3 KTS3HTC-3 KTS3HTC-4
T4 KT4HTC-3 KT4HTC-4
T5 KT5HTC-3 KT5HTC-4
T6 KT6HTC-3 KT6HTC-4
T7 KT7XHTC-3 KT7XHTC-4
KT3100-3
KT1HTC-3
KT4LTC-3
Tmax
MCCBs
Low Voltage Products & Systems 17.79
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
Accessories
Mechanical
T1 - T7
KT2EF-3
KT2R-3
KT4EF-_
Phase barriers - Low prole 100mm-3.93 in
Frame 4 pcs (3p) 6 pcs (4p)
T1-T3 KT3PBL-3 KT3PBL-4
T4-T5 KT5PBL-3 KT5PBL-4
T6 KT6PBL-3 KT6PBL-4
T7 KT7PBL-3 KT7PBL-4
Phase barriers - High prole 200mm-7.87 in
Frame 4 pcs (3p) 6 pcs (4p)
T1-T3 KT3PBH-3 KT3PBH-4
T4-T5 KT5PBH-3 KT5PBH-4
T7 KT7PBH-3 KT7PBH-4
Saddle terminals for Copper Cables - IEC
Frame Catalog number
( Set of 3 )
Catalog number
(Set of 4)
T2 KT2100S-3 KT2100S-4
T3 KT3225S-3 KT3225S-4
Ts3 K4TES K4TES-4
T4 KT4250S-3 KT4250S-4
T5 KT5300S-3 KT5300S-4
Extended front terminals
Frame Catalog number
(set of 3)
Catalog number
(set of 4)
T1 KT1EF-3 KT1EF-4
T2 KT2EF-3 KT2EF-4
T3 KT3EF-3 KT3EF-4
Ts3 KTS3EF-3 KTS3EF-4
T4 KT4EF-3 KT4EF-4
T5 KT5EF-3 KT5EF-4
Rear terminals 1
Frame Catalog number
(set of 3)
Catalog number
(set of 4)
T2 KT2R-3 KT2R-4
T3 KT3R-3 KT3R-4
T4 KT4R-3 KT4R-4
T5 KT5R-3 KT5R-4
T6 KT6R-3 KT6R-4
T7 KT7R-3 KT7R-4
1 Includes low prole terminal cover.
2 Includes high prole terminal cover.
Distribution cable lug kit 2
Frame Wire Size Catalog number
(set of 3)
Catalog number
(set of 4)
T3 (6) #14-6 KT3TN KT3TN-4
Ts3 (6) #14-6 KTS3TN KTS3TN-4
T4 (6) #14-6 KT4TN KT4TN-4
T5 (6 )#14-1/0 KT5TGD KT5TGD-4
Tmax
MCCBs
17.80 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
Accessories
Mechanical
T1 - T7
OHB65J6
KT5RH
OHB125J10
Padlock locking device
Frame Style Locking Position Breaker
Mounting Catalog number
T1,T2,T3 PLL OPEN/CLOSED Fixed KT3LD
OPEN KT3LDO
Ts3 FLD OPEN Fixed, Plug-In KTS3FLD
Draw-0ut KTS3FLDW
T4-T5 FLD OPEN Fixed, Plug-In KT5FLD
Draw-out KT5FLDW
T6 FLD OPEN Fixed, Plug-In KT6FLD
Draw-out KT6FLDW
T7 PLL OPEN Fixed, Drawout KT7LDO
Keylocks-rotary handle mechanism
Frame Style Locking Position Keys Catalog number
T1,T2,T3 RHL OPEN/CLOSED Different KT3RHL3
Ts3 - OPEN Different KTS3KLFD
T4-T5 KLF-D OPEN Different KT5KLFD
T6 KLF-D OPEN Different KT6KLFD
T7 KLF-D OPEN Different KT7KLFD
Direct mount rotary operator handle
Frame Breaker
Mounting Catalog number
T1, T2, T3 Fixed, Plug-In KT3RH
Ts3 Fixed, Plug-In KTS3RH
Ts3 Draw-out KTS3RHW
T4-T5 Fixed, Plug-In KT5RH
T4-T5 Draw-0ut KT5RHW
T6 Fixed, Draw-out KT6RH
T6 Draw-out KT6RHW
T7 Fixed, Draw-out KT7RH
Variable depth handle operators
Frame NEMA rating Mechanism
catalog number Shaft catalog number Handle catalog
number
T1—T3
1,3R,12 OHB65J6
OHY65J6
4, 4X KT3VD-M OXP6X430 (16.9”) 1OHB80L6
OHY80L6
1 KT3VD-S (11.8”) KT3VD-H
Ts3
1,3R,12 OXP10X148 (5.8") 1OHB95J10
OHY95J10
4,4X KTS3VD-M OXP10X225 (8.9") OHB95L10
OHY95L10
OXP10X500 (19.7")
1 KTS3VD-S (20") KTS3VD-H
T4-T5
1,3R,12 OXP10X148 (5.8") OHB95J10
OHY95J10
4,4X KT5VD-M OXP10X225 (8.9") OHB95L10
OHY95L10
OXP10X500 (19.7")
1 KT5VD-S (19.7") KT5VD-H
T6
1,3R,12 OXP10X148 (5.8") OHB125J10
OHY125J10
4,4X KT6VD-M OXP10X225 (8.9") OHB125L10
OXP10X500 (19.7")
1 KT5VD-S (19.7) KT6VD-H
T7
1,3R,12 OXP10X148 (5.8") OHB175J10
OHY175J10
4, 4X KT7VD-M OXP10X225 (8.9") OHB175L10
OXP10X500 (19.7")
1 KT7VD-S (19.7") KT7VD-H
1 Discount schedule H6.
Tmax
MCCBs
Low Voltage Products & Systems 17.81
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
KT4PMK (on back of
breaker)
KT4PFVR
KT2PFF + KT2PMK (on back of breaker) +
breaker
Accessories
Mechanical
T1 - T7
Plug-in kits 1
Frame Catalog number
Adapter moving part
Catalog number
xed part
T2 - 3 pole with front terminals KT2PMK KT2PFF
T3 - 3 pole with front terminals KT3PMK KT3PFF
T2-T3 Fixed parts accept the same cable and rear terminal kits as the circuit breakers
Ts3 3 pole with front terminals KTS3PMK KTS3PFF
Ts3 3 pole with rear terminals KTS3PFR
T4 3 pole with extended front terminal KT4PFEF
T4 3 pole with rear horizontal terminals KT4PMK KT4PFHR
T4 3 pole with rear vertical terminals KT4PFVR
T5, 400A
T5 400A 3 pole with extended front terminal KT5PFEF
T5 400A 3 pole with rear horizontal terminal KT5PMK KT5PFHR
T5 400A 3 pole with rear vertical terminal KT5PFVR
T5, 600A
T5 600A 3 pole with extended front terminal KT56PFEF
T5 600A 3 pole with rear horizontal terminal KT56PMK KT56PFHR
T5 600A 3 pole with rear vertical terminal KT56PFVR
1 Plug connectors (T2-T3), Adaptors (T4-T5), required when adding accessories to plug-in breakers.
Plug connectors, T1-T3
Required when adding accessories to plug-in breakers
Plug Connector Catalog
number
Shunt trip or UVR KT3PC-3
1 form C plus 1 BA KT3PC-6
3 form C plus 1 BA KT3PC-12
Adaptors, T4-T6
Required when adding accessories to plug-in or drawout breakers
Adaptors Catalog
number
1 form C plus 1 BA KT5ADP-6
Shunt trip/UVR KT5ADP-5
Stored energy operator KT5ADP-10
Stored energy operator plus shunt trip/UVR KT5ADP-10
3 form C plus 1BA KT5ADP-12
Testing extension, T4 - T6
Extension Catalog
number
5 pin for blank tests w/service release KT5EXT-5
6 pin for blank tests w/aux contacts (1+1)
service and residual current releases KE5EXT-6
10 pin for blank tests w/motor operator and
early contacts KT5EXT-10
12 pin for blank tests w/aux contacts (3+1) KT5EXT-12
Tmax
MCCBs
17.82 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
1 Adaptors (T4-T6), Sliding contact blocks (T7) required when adding accessories to draw-out breakers.
2 Comes standard with horizontal terminals eld convertible to vertical
3 IEC
KT4WMK (on back of
breaker)
KT5WFVR
Accessories
T1 - T7
Draw-out kits 1
Item Catalog number
Adaptor moving part
Catalog Number
Fixed part
Ts3 3 pole with front terminals KTS3WMK KTS3WFF 3
Ts3 3 pole with rear terminals KTS3WFR 3
T4 3 pole with extended front terminal
KT4WMK
KT4WFEF
T4 3 pole with rear horizontal terminals KT4WFHR
T4 3 pole with rear vertical terminals KT4WFVR
T5 3 pole with extended front terminal KT5WFEF
T5 3 pole with rear horizontal terminal KT5WMK KT5WFHR
T5 3 pole with rear vertical terminal KT5WFVR
T5 3 pole with extended front terminal, 600A KT56WFEF
T5 3 pole with rear horizontal terminal, 600A KT56WMK KT56WFHR
T5 3 pole with rear vertical terminal, 600A KT56WFVR
T6 3 pole with extended front terminal KT6WFEF 3
T6 3 pole with rear horizontal terminal KT6WMK KT6WFHR 3
T6 3 pole with rear vertical terminal KT6WFVR
T7 3 pole with horizontal/vertical terminals KT7XWMK KT7WFHR 2
Adaptors — T4-T6
Required when adding accessories to plug-in or drawout breakers
Adaptors Catalog
number
1 form C plus 1 BA KT5ADP-6
Shunt trip/UVR KT5ADP-5
Stored energy operator KT5ADP-10
Stored energy operator plus shunt trip/UVR KT5ADP-10
3 form C plus 1BA KT5ADP-12
Sliding contact blocks — T7-Draw-out
Item Moving Part
Breaker
Fixed Part
Cradle
Left Block
KT7XSCMP-L KT7SCFP-L
Spring charging motor
Spring charged contact
Ready to close contact
Early auxiliary contact
Contact for trip coil release trip
Trip rest
Center Block
PR331 KT7XSCMP-C KT7XSCFP-C
PR332
Right Block
Auxiliary contacts
KT7XSCMP-R KT7XSCFP-R
Shunt trip
Closing Coil
Undervoltage release
If at least one of the accessories in table is installed on the breaker - respective pair of contact
blocks must be installed on the xed part (cradle) and the moving part. (breaker)
Position key lock — T7 - T7M-X1
Item Catalog
number
Key #20005 KT7XPL2
Different key KT7XPL1
Locks drawout breaker in racked-in / test isolation / racked-out position.
Position key lock accessory — T7 - T7M-X1
Item Catalog
number
Key lock accessory KT7XPLA
Accessory added to position key lock allows breaker to be locked in racked-out position only.
Tmax
MCCBs
Low Voltage Products & Systems 17.83
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
Accessories
T1 - T7
KT3MIF2
DIN rail adapters
Item Catalog Number
T1/T2 (mounts on 35 mm DIN rail 15mm high) KT2DIN
T3 (mounts on 35mm DIN rail 15mm high) KT3DIN
Ts3 (mounts on 75 mm DIN rail) KTS3DIN
Mechanical interlocks
T1-T3 Catalog Number
Sliding bar interlock-front mounted (2 Breakers) KT3MIF2
Sliding bar interlock-front mounted (3 Breakers) KT3MIF3
T3
Rear Interlock-horizontal KT3MI-H
Rear Interlock-vertical KT3MI-V
TS3
Horizontal KTS3MI-H
Vertical KTS3MI-V
T4-T5 1
Interlock frame
Mechanical Interlock frame-horizontal KT5MIR-HB
Mechanical Interlock frame-vertical KT5MIR-VB
Plate type
A T4 (F-P-W) T4 (F-P-W) KT5MIR-PA
B T4 (F-P-W) T5 400 (F-P-W) OR T5 600 (F) KT5MIR-PB
C T4 (F-P-W) T5 600 (P-W) KT5MIR-PC
D T5 (F-P-W) T5 400 (F-P-W) OR 630 (F) KT5MIR-PD
E T4 (F-P-W) T5 600 (P-W) KT5MIR-PE
F T4 (F-P-W) T5 600 (P-W) KT5MIR-PF
T6
Horizontal KT6MI-H
Vertical KT6MI-V
T7 2
Cable T7-X1 KT7XMLC
Mech. interlock plate-xed KT7XMLPF
Mech. interlock plate-draw-out KT7XMLPW
1 T4-T5 Complete assembly consists of one interlock frame and one plate.
2 To interlock two circuit breakers, you have to order a cable kit and two plates.
Flange cable mechanisms
Item Catalog Number
Handles
T1 - T3 NEMA 1, 3R, 12 OHF1C12T
NEMA 4, 4X OHF1C4T
Ts3 - T5 NEMA 1, 3R, 12 OHF1C12
NEMA 4, 4X OHF1C4
Mechanisms
T1 - T2 MKCT2
T3 MKCT3
T4 - Ts3 MKCT4
T5 MKCT5
Cables
36” OXC1L36
48” OXC1L48
60” OXC1L60
72” OXC1L72
84” OXC1L84
96” OXC1L96
108” OXC1L108
Tmax
MCCBs
17.84 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
Approximate dimensions
T1 & T2
T1 — 3 pole
T2 — 2 & 3 pole
T1 — Single pole
90
30 30
181
130
65
76.2
78
83
70
¯ 9.38
103
17
45 53.25
106.5
XX
Y
Y
>3 < 2
Tmax
MCCBs
Low Voltage Products & Systems 17.85
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
Approximate dimensions
T3
T3 — 2 & 3 pole
Door cut-out for Tmax without faceplate
Tmax
MCCBs
17.86 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
Approximate dimensions
Ts3
Tmax
MCCBs
Low Voltage Products & Systems 17.87
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
Approximate dimensions
T4
Fixed circuit breaker
Flange for
compartment door
Drilling templates of the compartment door
Drilling templates for support sheet
For front terminals For rear terminals
3 POLES 4 POLES
Caption
1 Overall dimensions with
cabled accessories mounted
(SOR-C, UVR-C,
RC221-222)
2 Overall dimensions with
cabled auxiliary contacts
mounted
(only 3Q 1SY)
3-4 POLES 3-4 POLES
With ange Without ange
Tmax
MCCBs
17.88 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
Approximate dimensions
T5
Fixed circuit breaker
Flange for
compartment door
Drilling templates of the compartment door
Drilling templates for support sheet
For front terminals For rear terminals
3 POLES 4 POLES
3 POLES 4 POLES
Fixing on sheet
Caption
1 Overall dimensions with
cabled accessories mounted
(SOR-C, UVR-C,
RC221-222)
2 Overall dimensions with
cabled auxiliary contacts
mounted
(only 3Q 1SY)
With ange (3-4 POLES) Without ange (3-4 POLES)
Tmax
MCCBs
Low Voltage Products & Systems 17.89
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
Approximate dimensions
T6
Tmax
MCCBs
17.90 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
Approximate dimensions
T7
Tmax
MCCBs
Low Voltage Products & Systems 17.91
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
Approximate dimensions
T7M
Fixed, 3 Pole, front terminals
Tmax
MCCBs
17.92 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
Approximate dimensions
T8, Fixed, 3 pole, front terminals
1600A, 2000A, 2500A
Tmax
MCCBs
Low Voltage Products & Systems 17.93
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
Approximate dimensions
T8, Fixed, Vertical rear terminals
80% rated 3000A; 100% rated 2500A, 3000A
Tmax
MCCBs
17.94 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
Approximate dimensions
T8, Fixed, Optional vertical rear terminals (KT82500VR-x)
1600A/2000A/2500A
Tmax
MCCBs
Low Voltage Products & Systems 17.95
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
Approximate dimensions
T1 - T3
Variable depth mechanism with OHB handle
Tmax
MCCBs
17.96 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
Approximate dimensions
Ts3
Variable depth mechanism with OHB handle
Tmax
MCCBs
Low Voltage Products & Systems 17.97
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
Approximate dimensions
T4 - T5
Variable depth mechanism with OHB handle
Tmax
MCCBs
17.98 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
Approximate dimensions
T6
Variable depth mechanism
Tmax
MCCBs
Low Voltage Products & Systems 17.99
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
17
Approximate dimensions
T7
Variable depth mechanism
Tmax
MCCBs
17.100 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
17
Notes