Digital Fiber Amplifier Unit E3X-DA-S/MDA CSM_E3X-DA-S_MDA_DS_E_15_3 Advanced Fiber Amplifier Units * Features a Power Tuning function that optimizes light reception at the press of a button. * APC circuits to suppress LED aging degradation used with 4element LEDs. * 2-channel models achieve the thinnest* profile in the industry, at only 5 mm per channel. * 2-channel models also offer AND/OR control output. * The E3X-MDA0 with two channels supports an EtherCAT Sensor Communications Unit or CompoNet Sensor Communications Unit. * (Based on July 2012 OMRON investigation.) For the most recent information on models that have been certified for safety standards, refer to your OMRON website. Be sure to read Safety Precautions on page 15. Features Models available for a wide variety of applications at manufacturing sites Industry Leading Two Amplifiers Loaded in a Small Body . . . . 2-channel models Two amplifiers are loaded in a 10 mm-wide body. Space usability can be approximately doubled. In addition, approximately 40% of the energy can be saved. (compared to the value per channel of the former model) Checking LCD substrates seating and alignment 20mm 10mm 2-channel models E3X-MDA High-speed and High-resolution Analog Output Supports Wide Variety of Applications . . . .Advanced Analog Output Models Analog Control Output High-speed and High Resolution The voltage in the range of 1 to 5 V is output according to the incident level (digital display). Wide variety of applications is possible including positioning control or difference detection with multiple levels. Detection modes can be switched in accordance with applications. High-speed response of 80 s (super-high-speed mode) supports the positioning controls that require high-speed control. Sheet Displacement ON/OFF Analog 1 E3X-DA-S/MDA Ordering Information Fiber Amplifier Units Amplifier Units with Cables (2 m) [Refer to Dimensions on page 17.] Item Remote setting, counter, differential operation Area output, self-diagnosis, differential operation ATC (Threshold value automatic correction) Analog output models Model NPN output PNP output E3X-DA11SE-S 2M E3X-DA41SE-S 2M E3X-DA11-S 2M E3X-DA41-S 2M E3X-DAG11-S 2M E3X-DAG41-S 2M E3X-DAB11-S 2M E3X-DAB41-S 2M E3X-DAH11-S 2M E3X-DAH41-S 2M E3X-DA11RM-S 2M E3X-DA41RM-S 2M E3X-DA11TW-S 2M E3X-DA41TW-S 2M E3X-DA11AT-S 2M E3X-DA41AT-S 2M E3X-DA11AN-S 2M E3X-DA41AN-S 2M AND/OR output E3X-MDA11 2M Appearance Functions Single-function models Standard models Mark-detecting models (multiple color light sources) Advanced models --Green LED Blue LED Infrared LED External-input models Twin-output models ATC function models Analog output models Timer, Response speed change 2-channel models E3X-MDA41 2M Amplifier Units with Wire-saving Connectors [Refer to Dimensions on page 18.] Item Appearance Remote setting, counter, differential operation Area output, self-diagnosis, differential operation ATC (Threshold value automatic correction) NPN output E3X-DA6SE-S E3X-DA6-S * E3X-DAG6-S * E3X-DAB6-S * E3X-DAH6-S * E3X-DA6RM-S * E3X-DA6TW-S * E3X-DA6AT-S PNP output E3X-DA8SE-S E3X-DA8-S * E3X-DAG8-S * E3X-DAB8-S * E3X-DAH8-S * E3X-DA8RM-S * E3X-DA8TW-S * E3X-DA8AT-S AND/OR output E3X-MDA6 * E3X-MDA8 * Single-function models Standard models Mark-detecting models (multiple color light sources) Advanced models Model Functions --- Green LED Blue LED Infrared LED External-input models Twin-output models ATC function models Timer, Response speed change 2-channel models * These models allow you to use an E3X-DRT21-S VER.3 Sensor Communications Unit. When using the E3X-DRT21-S VER.3, use an E3X-CN02 Connector without a Cable for the Wire-saving Connector. Amplifier Units with Connectors for EtherCAT or CompoNet Sensor Communications Units [Refer to Dimensions on page 19.] Item Appearance Functions Applicable Sensor Communications Unit Model E3X-ECT 2-channel model E3X-MDA0 AND/OR output E3X-CRT Ratings and Specifications Control output/input Type Light source Single-function models Standard models Markdetecting models Advanced models E3X-DA@G-S 3X-DA@B-S E3X-DA@H-S Twin-output models External-input models ATC function models ON/OFF output Input Analog output Power tuning Timer --- --- Functions InterferDifferenence pretial detecvention tion counter ATC Red LED 1 ms 50 s to 4 ms Only main --- --- --- --- --- Green LED Blue LED Infrared LED 50 s to 4 ms Only main --- --- --- --- --- Only main (1 line) Red LED 50 s to 4 ms 80 s to 4 ms 130 s to 4 ms 80 s to 4 ms Analog output 2-channel models Response time Red LED 130 s to 4 ms Main + sub (2 lines) Only main Main + main (2 independent lines) ----- --- --(1 line) --- --- --- --- --- --- --- 2 E3X-DA-S/MDA Accessories (Order Separately) Amplifier Unit Connectors (Required for models for Wire-saving Connectors.) Note: Protector seals are provided as accessories. [Refer to Dimensions on page 19.] Item Cable length Appearance No. of conductors Model 3 E3X-CN11 4 E3X-CN21 1 E3X-CN12 2 E3X-CN22 Master Connector 2m Slave Connector Ordering Precaution for Amplifier Units with Wire-saving Connectors Amplifier Units and Connectors are sold separately. Refer to the following tables when placing an order. Fiber Amplifier Unit Model NPN output Single-function models E3X-DA6SE-S Standard models E3X-DA6-S E3X-DAG6-S Mark-detecting models (multiple color light E3X-DAB6-S sources) E3X-DAH6-S Advanced models 2-channel models Applicable Connector (Order Separately) Master Connector Slave Connector PNP output E3X-DA8SE-S E3X-DA8-S E3X-DAG8-S + E3X-CN11 E3X-CN12 E3X-CN21 E3X-CN22 E3X-DAB8-S E3X-DAH8-S E3X-DA6TW-S E3X-DA6RM-S E3X-DA6AT-S E3X-MDA6 E3X-DA8TW-S E3X-DA8RM-S E3X-DA8AT-S E3X-MDA8 When Using 5 Amplifier Units Fiber Amplifier Units (5 Units) + 1 Master Connector + 4 Slave Connectors Mobile Console [Refer to Dimensions on page 20.] Appearance Model Remarks E3X-MC11-SV2 (model number of set) Mobile Console with Head, Cable, and AC adapter provided as accessories E3X-MC11-C1-SV2 Mobile Console E3X-MC11-H1 Head E39-Z12-1 Cable (1.5 m) Note: Use the E3X-MC11-SV2 Mobile Console for the E3X-DA-S/MDA-series Fiber Amplifier Units. The E3X-MC11-SV2 is an upgraded version of the E3X-MC11-S that is fully interchangeable with the older model. Mounting Bracket [Refer to E39-L/E39-S/E39-R.] Appearance Model E39-L143 Quantity 1 End Plate [Refer to PFP-@.] Appearance Model PFP-M Quantity 1 3 E3X-DA-S/MDA Ratings and Specifications Refer to pages 17 to 20 for dimensions. Fiber Amplifier Units Single-function, Standard, and Mark-detecting Amplifier Units Item Type Single-function models Standard models Model E3X-DA@SE-S E3X-DA@-S Mark-detecting models (multiple color light sources) Green LED Blue LED Infrared LED E3X-DAG@-S E3X-DAB@-S E3X-DAH@-S Infrared LED Green LED (525 nm) Blue LED (470 nm) (870nm) Light source (wavelength) Red LED (635 nm) Power supply voltage Power consumption 12 to 24 VDC 10%, ripple (p-p) 10% max. 960 mW max. (current consumption: 40 mA max. at power supply voltage of 24 VDC) Load power supply voltage: 26.4 VDC; NPN/PNP open collector; load current: 50 mA max.; residual voltage: 1 V max. No-voltage input --(contact/non-contact) Reverse polarity for power supply connection, output short-circuit Control output Remote control input Protection circuits Super-highspeed mode High-speed Remode sponse time Standard mode High-resolution mode Sensitivity setting Power tuning Timer function --- Operate: 48 s, reset: 50 s *1, *2 --- Operate/reset: 250 s Operate or reset: 1 ms --- Operate or reset: 4 ms Teaching or manual method --Light emission power and reception gain, digital control method Select from OFF-delay, ON-delay, or one-shot timer. --1 ms to 5 s (1 to 20 ms set in 1-ms increments, 20 to 200 ms set in 10-ms increments, 200 ms to 1 s set in 100-ms increments, and 1 to 5 s set in 1 s-increments) Automatic power High-speed control method for emission current control (APC) Zero-reset --Negative values can be displayed. (Threshold value is shifted.) Initial reset Settings can be returned to defaults as required. Mutual interferPossible for up to 10 Units *3 ence prevention Operation indicator Display Operation indicator (orange), Power Tuning indicator (orange) (orange) incident level + Digital display Select from incident level + threshold or other 6 patterns threshold Display orientation --Switching between normal/reversed display is possible. Ambient illumination Incandescent lamp: 10,000 lux max. Sunlight: 20,000 lux max. (Receiver side) Functions Ambient temperature range Ambient humidity range Insulation resistance Dielectric strength Vibration resistance Shock resistance Degree of protection Connection method Weight (packed state) Case Materials Cover Accessories Operating: Groups of 1 to 2 Amplifiers: -25C to 55C Groups of 3 to 10 Amplifiers: -25C to 50C Groups of 11 to 16 Amplifiers: -25C to 45C Storage: -30C to 70C (with no icing or condensation) Operating and storage: 35% to 85% (with no condensation) 20 M min. (at 500 VDC) 1,000 VAC at 50/60 Hz for 1 minute Destruction: 10 to 55 Hz with a 1.5-mm double amplitude for 2 hrs each in X, Y and Z directions Destruction: 500 m/s2, for 3 times each in X, Y and Z directions IEC 60529 IP50 (with Protective Cover attached) Pre-wired or amplifier unit connector Pre-wired model: Approx. 100 g, Amplifier unit connector model: Approx. 55 g Polybutylene terephthalate (PBT) Polycarbonate (PC) Instruction manual *1. Communications are disabled if the detection mode is selected during super-high-speed mode, and the communications functions for mutual interference prevention and the Mobile Console will not function. *2. PNP output is as follows: Operate: 53 s, reset: 55 s. *3. Mutual interference prevention can be used for only up to 6 Units if power tuning is enabled. 4 E3X-DA-S/MDA Advanced and 2-channel Amplifier Units Advanced models Type External input models Model Item Light source (wavelength) Power supply voltage Power consumption ON/OFF output Twin output models E3X-DA@RM-S E3X-DA@TW-S E3X-DA@AT-S Analog output models E3X-DA@AN-S Red LED (635 nm) 12 to 24 VDC 10%, ripple (p-p) 10% max. 1,080 mW max. (current consumption: 45 mA max. at power supply voltage of 24 VDC) Supplied from the connector through the Sensor Communications Unit Load power supply voltage: 26.4 VDC; NPN/PNP open collector; load current: 50 mA max.; residual voltage: 1 V max. Cont rol outp ut Analog output ATC function models 2-channel models Model for Sensor Standard Communications models Unit *1 E3X-MDA@ E3X-MDA0 (@: 11/41/6/8) --- Control output Voltage output: 1 to 5 VDC (Connection load 10 k min.) Temperature characteristics 0.3%F.S./C Response speed/repeat accuracy Super-high-speed mode: 80 s/1.5%F.S. High-speed mode: 250 s/1.5%F.S. Standard mode: 1 ms/1%F.S. High-resolution mode: 4 ms/0.75%F.S. --- No-voltage input (contact/ --transistor) *2 Protection circuits Reverse polarity for power supply connection, output short-circuit Operate: 48 s, Super-highOperate or reset: Operate or reset: 80 s *3 --reset: speed mode 130 s *3, *6 *3, *4, *5 50 s Resp Operate or reset: 450 s onse High-speed mode Operate or reset: 250 s time Standard mode Operate or reset: 1ms High-resolution Operate or reset: 4ms mode Sensitivity setting Teaching or manual method Power tuning Light emission power and reception gain, digital control method Switchable between single edge and double edge detection mode Single edge: Can be set to 250 s, Differential 500 s, 1 ms, 10 ms, or 100 ms. --detection Double edge: Can be set to 500 s, 1 ms, 2 ms, 20 ms, or 200 ms. Select from OFF-delay, ON-delay, or one-shot timer. Timer function 1 ms to 5 s (1 to 20 ms set in 1-ms increments, 20 to 200 ms set in 10-ms increments, 200 ms to 1 s set in 100-ms increments, and 1 to 5 s set in 1 s-increments) Func Automatic power High-speed control method for emission current tions control (APC) Zero-reset Negative values can be displayed. (Threshold value is shifted.) Initial reset Settings can be returned to defaults as required. Mutual interference Possible for up to 9 Units (18 Possible for up to 10 Units *7 prevention channels) *8 Switchable between up counter and Counter --down counter. Set count: 0 to 9,999,999 Remote control input *1.This model allows you to use an E3X-ECT EtherCAT Sensor Communications Unit or E3X-CRT CompoNet Sensor Communications Unit. *2.Input Specifications NPN PNP Contact input (relay or switch) ON: Shorted to 0 V (sourcing current: 1 mA max.). OFF: Open or shorted to Vcc. ON: Shorted to Vcc (sinking current: 3 mA max.). OFF: Open or shorted to 0 V. Non-contact input (transistor) ON: 1.5 V max. (sourcing current: 1 mA max.) OFF: Vcc - 1.5 V to Vcc (leakage current: 0.1 mA max.) ON: Vcc - 1.5 V to Vcc (sinking current: 3 mA max.) OFF: 1.5 V max. (leakage current: 0.1 mA max.) *3.Communications are disabled if the detection mode is selected during super-high-speed mode, and the communications functions for mutual interference prevention and the Mobile Console will not function. *4.PNP output is as follows: Operate: 53 s, reset: 55 s. *5.When counter is enabled: 80 s for operate and reset respectively. *6.When differential output is selected for the output setting, the second channel output is 200 s for operation and reset respectively. *7.Mutual interference prevention can be used for only up to 6 Units if power tuning is enabled. *8.Mutual interference prevention can be used for up to 5 Units (10 channels) if power tuning is enabled. 5 E3X-DA-S/MDA Type Model Item Functions I/O setting Display Digital display Display orientation Ambient illumination (Receiver side) Ambient temperature range Ambient humidity range Insulation resistance Dielectric strength Advanced models Twin-output ATC function models models External input models E3X-DA@RM-S E3X-DA@TW-S E3X-DA@AT-S Analog output models E3X-DA@AN-S External input Output setting Output setting Analog output setting (Select (Select from (Select from setting (offset from teaching, channel 2 channel 2 output, voltage power tuning, zero output, area area output, selfreset, light OFF, or output, or selfdiagnosis output, or adjustable) counter reset.) diagnosis.) ATC error output) Operation Operation indicator Operation indicator for channel 1 indicator (orange), Power (orange), Operation indicator for (orange), Tuning indicator channel 2 (orange) Power Tuning (orange) indicator (orange) Select from incident level + Select from incident level + threshold or other 6 threshold or patterns other 7 patterns Switching between normal/reversed display is possible. Incandescent lamp: 10,000 lux max. Sunlight: 20,000 lux max. Operating: Groups of 1 to 2 Amplifiers: -25C to 55C Groups of 3 to 10 Amplifiers: -25C to 50C Groups of 11 to 16 Amplifiers: -25C to 45C *9 Storage: -30C to 70C (with no icing or condensation) 2-channel models Standard Model for Sensor models Communications Unit E3X-MDA@ E3X-MDA0 (@: 11/41/6/8) Output setting (Select from channel 2 output, AND, OR, leading edge sync, falling edge sync, or differential output) Operation indicator for channel 1 (orange), Operation indicator for channel 2 (orange) Select from incident level for channel 1 + incident level for channel 2 or other 7 patterns Operating and storage: 35% to 85% (with no condensation) 20 M min. (at 500 VDC) 1,000 VAC at 50/60 Hz for 1 minute Vibration resistance (Destruction) 10 to 55 Hz with a 1.5-mm double amplitude for 2 hrs each in X, Y and Z directions Shock resistance (Destruction) 500 m/s2, for 3 times each in X, Y and Z directions Degree of protection IEC 60529 IP50 (with Protective Cover attached) Connection method Pre-wired or amplifier unit connector Weight (packed state) Case Materials Cover Accessories Pre-wired model: Approx. 100 g, Amplifier unit connector model: Approx. 55 g Polybutylene terephthalate (PBT) Polycarbonate (PC) Instruction manual 10 to 150 Hz with a 0.7mm double amplitude for 80 min each in X, Y, and Z directions 200 m/s2 for 3 times each in X, Y, and Z directions Connector for Sensor Communications Unit Approx. 55 g *9. The following temperature ranges apply for operation when an E3X-ECT or E3X-CRT Sensor Communications Unit is used with the E3X-MDA0: Groups of 1 or 2 Amplifier Units: 0 to 55C, Groups of 3 to 10 Amplifier Units: 0 to 50C, Groups of 11 to 16 Amplifier Units: 0 to 45C, Groups of 17 to 30 Amplifier Units (with the E3X-ECT): 0 to 40C. Amplifier Unit Connectors Item Model Mobile Console E3X-CN11/21/22 E3X-CN12 Rated current 2.5 A Rated voltage 50 V Contact resistance 20 m max. (20 mVDC max., 100 mA max.) (The figure is for connection to the Fiber Amplifier Unit and the adjacent Connector. It does not include the conductor resistance of the cable.) No. of insertions Destruction: 50 times (The figure for the number of insertions is for connection to the Fiber Amplifier Unit and the adjacent Connector.) Mater Housing ials Contacts Weight (packed state) Polybutylene terephthalate (PBT) Item Model E3X-MC11-SV2 Applicable Fiber Amplifier Units E3X-DA-S E3X-MDA E3C-LDA E2C-EDA Power supply voltage Charged with AC adapter Connection method Connected via adapter Weight (packed state) Approx. 580 g (Console only: 120 g) Phosphor bronze/gold-plated nickel Approx. 55 g Approx. 25 g Refer to Instruction Manual provided with the Mobile Console for details. 6 E3X-DA-S/MDA Sensing Distance Single-function, Standard, Advanced, and 2-channel Amplifier Units Threaded Models (Unit: mm)) E3X-DA@-S Sensing method Sensing direction Size Right-angle Throughbeam M4 Straight M3 Right-angle M4 M6 Reflective M3 M4 Straight M6 E3X-MDA@ Model E32-T11N 2M E32-LT11N 2M E32-T11R 2M E32-LT11 2M E32-LT11R 2M E32-C31N 2M E32-C21N 2M E32-D21N 2M E32-C11N 2M E32-LD11N 2M E32-D21R 2M E32-C31 2M E32-C31M 1M E32-D211R 2M E32-D11R 2M E32-CC200 2M E32-LD11 2M E32-LD11R 2M 700 2,300 700 2,700 2,300 40 75 300 280 300 50 530 1,750 530 2,050 1,750 25 65 170 170 170 30 120 75 50 22 75 50 300 500 305 300 30 170 300 180 170 20 120 200 125 120 8 50 90 55 50 30 170 300 175 170 Standard mode Highspeed mode SuperHighhighresolution speed mode mode 140 450 460 1,500 140 450 540 1,750 460 1,500 7 24 20 50 50 170 50 160 50 170 8 30 Highresolution mode 350 1,150 350 1,350 1,150 16 45 120 110 120 20 230 750 230 890 750 10 30 80 70 80 14 Superhighspeed mode 140 460 140 540 460 7 20 50 50 50 8 50 30 22 22 120 210 125 120 14 80 140 85 80 8 50 90 55 50 Standard mode Highspeed mode 350 1,150 350 1,350 1,150 16 45 120 110 120 22 Cylindrical Models E3X-DA@-S Sensing method Size Sensing direction Throughbeam 1 dia. 1.5 dia. 3 dia. Reflective Top-view Side-view 1.5 dia. 1.5 dia. + 0.5 dia. Top-view 3 dia. 3 dia. + 0.8 dia. Model E32-T223R 2M E32-T22B 2M E32-T12R 2M E32-T14LR 2M E32-D22B 2M E32-D43M 1M E32-D22R 2M E32-D221B 2M E32-D32L 2M E32-D33 2M Highresolution mode 160 240 700 270 50 10 50 110 250 25 Standard mode E3X-MDA@ Highspeed mode 130 200 530 210 30 6 30 70 150 16 75 110 350 130 20 4 20 45 100 10 SuperHighhighresolution speed mode mode 30 110 45 150 140 450 50 170 8 30 2 6 8 30 20 70 45 150 4 16 Standard mode Highspeed mode 85 110 350 130 22 4 22 50 100 10 55 70 230 85 14 2.5 14 30 65 6 Superhighspeed mode 30 45 140 50 8 2 8 20 45 4 Flat Models E3X-DA@-S Sensing method Throughbeam Reflective Sensing direction Top-view Side-view Flat-view Top-view Side-view Flat-view Model E32-T15XR 2M E32-T15YR 2M E32-T15ZR 2M E32-D15XR 2M E32-D15YR 2M E32-D15ZR 2M Highresolution mode Standard mode E3X-MDA@ 350 230 Superhighspeed mode 140 50 170 130 85 50 120 50 170 120 80 50 26 12 40 29 19 12 Highspeed mode 700 530 350 270 210 130 300 170 70 40 SuperHighhighresolution speed mode mode 140 450 Standard mode Highspeed mode Note: The super-high-speed mode cannot be used with the E3X-MDA0. 7 E3X-DA-S/MDA Sleeve Models E3X-DA@-S Sensing method Sensing direction E32-T24R 2M E32-T24E 2M E32-T21-S1 2M E32-T33 1M E32-TC200BR 2M E32-D24R 2M E32-D24-S2 2M E32-D43M 1M E32-D331 2M E32-D33 2M E32-D32-S1 0.5M E32-D31-S1 0.5M E32-DC200F4R 2M E32-D22-S1 2M E32-D21-S3 2M E32-DC200BR 2M E32-D25-S3 2M Side-view Throughbeam Model Top-view Side-view Reflective Top-view Highresolution mode Standard mode E3X-MDA@ Highspeed mode 25 75 85 25 350 10 23 4 2 10 SuperHighhighresolution speed mode mode 10 35 30 100 34 120 10 35 140 450 4 15 7 26 2 6 0.8 3 4 16 60 160 180 53 700 26 40 10 5 25 50 130 150 44 530 15 26 6 3 16 21 13 9 3 14 50 30 20 8 30 85 55 36 15 56 300 85 170 55 120 36 50 15 170 56 18 45 57 18 230 6 15 2.5 1.3 6 Superhighspeed mode 10 30 34 10 140 4 7 2 0.8 4 9 6 3 22 14 8 36 24 15 120 36 80 24 50 15 Standard mode 27 70 85 28 350 10 23 4 2 10 Highspeed mode Small-spot, Reflective E3X-DA@-S Type spot diameter Center distance (mm) Variable spot 0.1 to 0.6 dia. 0.3 to 1.6 dia. 6 to 5 10 to 30 Parallel light 4 dia. 0 to 20 Integrated lens 0.1 dia. 0.1 dia. 5 0.5 dia. Small-spot 7 0.2 dia. 0.5 dia. 3 dia. 17 50 Model E32-C42 1M + E39-F3A E32-C42 1M + E39-F17 E32-C31 2M + E39-F3C E32-C31N 2M + E39-F3C E32-C42S 1M E32-C41 1M + E39-F3A-5 E32-C31 2M + E39-F3A-5 E32-C31N 2M + E39-F3A-5 E32-C41 1M + E39-F3B E32-C31 2M + E39-F3B E32-C31N 2M + E39-F3B E32-CC200 2M + E39-F18 E32-C11N 2M + E39-F18 E3X-MDA@ SuperSuperHighHighStandard Standard highhighresolution speed mode mode speed speed mode mode mode mode Spot diameter of 0.1 to 0.6 mm at 6 to 15 mm. Spot diameter of 0.1 to 0.6 mm at 6 to 15 mm. Spot diameter of 0.3 to 1.6 mm at 10 to 30 mm. Spot diameter of 0.3 to 1.6 mm at 10 to 30 mm. Highresolution mode Highspeed mode Spot diameter of 4 mm max. at 0 to 20 mm. Spot diameter of 4 mm max. at 0 to 20 mm. Spot diameter of 0.1 mm at 5 mm. Spot diameter of 0.1 mm at 7 mm. Spot diameter of 0.1 mm at 5 mm. Spot diameter of 0.1 mm at 7 mm. Spot diameter of 0.5 mm at 7 mm. Spot diameter of 0.5 mm at 7 mm. Spot diameter of 0.2 mm at 17 mm. Spot diameter of 0.2 mm at 17 mm. Spot diameter of 0.5 mm at 17 mm. Spot diameter of 0.5 mm at 17 mm. Spot diameter of 3 mm at 50 mm. Spot diameter of 3 mm at 50 mm. Note: The super-high-speed mode cannot be used with the E3X-MDA0. 8 E3X-DA-S/MDA High-power Beam E3X-DA@-S Type Through-beam Integrated lens Sensing direction Aperture angle Right-angle 15 10 Top-view Side-view Right-angle Top-view Side-view Top-view Side-view Throughbeam models with lenses Top-view Side-view Top-view Side-view Top-view Side-view Top-view 15 30 12 6 12 6 60 12 6 60 12 6 60 12 6 60 12 6 60 12 6 Model E32-LT11N 2M E32-T17L 10M E32-LT11 2M E32-LT11R 2M E32-T14 2M E32-T11N 2M + E39-F1 E32-T11N 2M + E39-F16 E32-T11R 2M + E39-F1 E32-T11R 2M + E39-F16 E32-T11R 2M + E39-F2 E32-T11 2M + E39-F1 E32-T11 2M + E39-F16 E32-T11 2M + E39-F2 E32-T51R 2M + E39-F1 E32-T51R 2M + E39-F16 E32-T51R 2M + E39-F2 E32-T81R-S 2M + E39-F1 E32-T81R-S 2M + E39-F16 E32-T81R-S 2M + E39-F2 E32-T61-S 2M + E39-F1 E32-T61-S 2M + E39-F16 E32-T61-S 2M + E39-F2 E32-T51 2M + E39-F1-33 E32-T51 2M + E39-F16 Highresolution mode Standard mode 2,300 1,750 20,000 *1 20,000 *1 2,700 2,050 2,300 1,750 4,000 *2 3,400 4,000 *2 3,700 4,000 *2 4,000 *2 4,000 *2 3,700 4,000 *2 4,000 *2 520 400 4,000 *2 3,600 4,000 *2 4,000 *2 820 660 3,900 2,900 4,000 *2 4,000 *2 500 380 4,000 *2 3,200 4,000 *2 4,000 *2 540 410 4,000 3,400 4,000 *2 4,000 *2 600 450 4,000 *2 4,000 *2 4,000 *2 4,000 *2 E3X-MDA@ Highspeed mode 1,150 10,000 1,350 1,150 2,250 2,400 4,000 *2 2,400 4,000 *2 250 2,300 4,000 *2 430 1,900 3,500 250 2,100 3,700 270 2,200 3,700 300 3,500 4,000 *2 SuperHighhighresolution speed mode mode 460 1,500 4,000 13,000 540 1,750 460 1,500 900 2,900 970 3,100 1,700 4,000 *2 970 3,100 1,700 4,000 *2 100 330 930 3,000 2,200 4,000 *2 160 530 780 2,500 1,400 4,000 *2 100 320 840 2,700 1,500 4,000 *2 100 350 900 3,000 1,500 4,000 *2 120 390 1,400 4,000 *2 2,500 4,000 *2 Standard mode 1,150 10,000 1,350 1,150 2,200 2,400 4,000 *2 2,400 4,000 *2 260 2,300 4,000 *2 430 1,900 3,500 250 2,100 3,700 270 2,200 3,700 300 3,500 4,000 *2 Highspeed mode 750 6,500 890 750 1,450 1,600 2,900 1,600 2,900 170 1,500 3,700 280 1,300 2,300 160 1,380 2,500 170 1,450 2,500 200 2,300 4,000 *2 Superhighspeed mode 460 4,000 540 460 900 970 1,700 970 1,700 100 930 2,200 160 780 1,400 100 840 1,500 100 900 1,500 120 1,400 2,500 Reflective Top-view 4 E32-D16 2M 40 to 1,000 40 to 700 40 to 450 40 to 240 40 to 600 40 to 490 40 to 300 40 to 240 Integrated lens *1. The fiber length is 10 m on each side, so the sensing distance is given as 20,000 mm. *2. The fiber length is 2 m on each side, so the sensing distance is given as 4,000 mm. Narrow View E3X-DA@-S Sensing method Sensing direction Aperture angle 1.5 Throughbeam Side-view 3.4 4 Model E32-A03 2M E32-A03-1 2M E32-A04 2M E32-T24SR 2M E32-T24S 2M E32-T22S 2M Highresolution mode Standard mode E3X-MDA@ Highspeed mode Superhighspeed mode Highresolution mode Standard mode Highspeed mode Superhighspeed mode 1,150 890 600 250 750 580 380 250 460 1,480 1,750 2,500 340 1,100 1,300 1,900 225 730 870 1,250 100 290 350 500 300 920 1,100 1,600 220 730 870 1,250 145 480 580 830 100 290 350 500 Detection without Background Interference E3X-DA@-S Sensing method Limitedreflective Sensing direction Model Highresolution mode E32-L16-N 2M E32-L24S 2M E32-L25L 2M Flat-view Side-view Standard mode E3X-MDA@ Highspeed mode 0 to 15 0 to 4 5.4 to 9 (center 7.2) Superhighspeed mode 0 to 12 Highresolution mode Standard mode Highspeed mode 0 to 15 0 to 4 5.4 to 9 (center 7.2) Superhighspeed mode 0 to 12 Transparent Object Detection (Retro-reflective) E3X-DA@-S Sensing method Retroreflective Feature Size Film detection M3 Square Threaded models - M6 Hex-shaped M6 Model E32-C31 2M + E39-F3R + E39-RP37 E32-R16 2M E32-R21 2M E32-LR11NP 2M + E39-RP1 Highresolution mode 250 Standard mode E3X-MDA@ Highspeed mode 150 100 Superhighspeed mode 45 Highresolution mode 150 150 to 1500 10 to 250 630 600 Standard mode Highspeed mode 100 Superhighspeed mode 65 45 330 275 150 to 1500 10 to 250 500 275 600 500 Note: The super-high-speed mode cannot be used with the E3X-MDA0. 9 E3X-DA-S/MDA Transparent Object Detection (Limited-reflective) E3X-DA@-S Sensing method Sensing direction Feature Limitedreflective Small size Standard Glass substrate alignment, 70 C Standard/ long-distance Side view form Glass substrate mapping, 70 C Model Highresolution mode E32- L24S 2M E32-L16-N 2M Standard mode E3X-MDA@ Highspeed mode 0 to 4 0 to 15 Superhighspeed mode Highresolution mode Standard mode Highspeed mode 0 to 4 0 to 15 0 to 12 Superhighspeed mode 0 to 12 Flat-view E32-A08 2M 10 to 20 - 10 to 20 - E32-A12 2M 12 to 30 - 12 to 30 - Side-view E32-L25L 2M 5.4 to 9 (center 7.2) Top-view E32-A09 2M 15 to 38 5.4 to 9 (center 7.2) - - 15 to 38 Chemical-resistant, Oil-resistant E3X-DA@-S Sensing method Sensing direction Type Oil-resistant Throughbeam Chemical/ oil-resistant Model Right-angle E32-T11NF 2M E32-T12F 2M Top-view E32-T11F 2M Side-view E32-T14F 2M Highresolution mode 4,000 * 4,000 * 2,500 500 Chemical/oil-resistant Top-view E32-T51F 2M 1,800 at 150 C Chemical/oil-resistant E32-D12F 2M 160 Top-view Reflective Chemical-resistant cable E32-D11U 2M 300 * The fiber length is 2 m on each side, so the sensing distance is given as 4,000 mm. Standard mode E3X-MDA@ Highspeed mode SuperHighhighresolution speed mode mode 1,100 3,600 800 2,600 520 1,600 100 320 4,000 * 3,000 2,000 400 2,800 2,000 1,300 250 1,400 900 350 95 170 65 120 30 50 2,800 2,000 1,300 250 1,800 1,300 850 160 Superhighspeed mode 1,100 800 520 100 1,190 920 600 350 95 170 70 125 45 80 30 50 Standard mode Highspeed mode Bending-resistant E3X-DA@-S Sensing method Size 1.5 dia. M3 M4 Square 1.5 dia. M3 3 dia. M4 M6 Square Throughbeam Reflective Model E32-T22B 2M E32-T21 2M E32-T11 2M E32-T25XB 2M E32-D22B 2M E32-D21 2M E32-D221B 2M E32-D21B 2M E32-D11 2M E32-D25XB 2M Highresolution mode Standard mode E3X-MDA@ Highspeed mode Superhighspeed mode Highresolution mode Standard mode Highspeed mode Superhighspeed mode 240 200 110 45 150 110 70 45 900 180 680 150 450 85 180 35 580 125 450 95 300 60 180 35 50 30 20 8 30 22 14 8 110 70 45 20 70 50 30 20 300 85 170 50 120 30 50 15 170 50 125 35 80 23 50 15 E3X-MDA@ SuperHighHighStandard highresolution speed mode speed mode mode mode 110 360 280 180 200 650 500 330 70 230 180 120 120 390 300 200 40 130 95 60 72 230 165 110 27 90 63 40 10 to 20 - 20 to 30 - Superhighspeed mode 110 200 70 120 40 72 27 - - Heat-resistant E3X-DA@-S Sensing method Throughbeam Reflective Heat-resistant temperature 100 C 150 C 200 C 350 C 100 C 150 C 200 C 300 C 350 C 400 C Model E32-T51R 2M E32-T51 2M E32-T81R-S 2M E32-T61-S 2M E32-D51R 2M E32-D51 2M E32-D81R-S 2M E32-A08H2 2M E32-A09H2 2M E32-D611-S 2M E32-D61-S 2M E32-D73-S 2M Highresolution mode Standard mode Highspeed mode 560 1,000 360 600 240 400 150 425 760 280 450 135 230 90 10 to 20 20 to 30 280 500 180 300 95 160 60 150 90 60 27 90 63 40 27 100 60 40 18 60 40 25 18 Note: The super-high-speed mode cannot be used with the E3X-MDA0. 10 E3X-DA-S/MDA Area Beam E3X-DA@-S Sensing method Type Throughbeam Area Reflective Array Sensing width 11 mm 30 mm 11 mm Model E32-T16PR 2M E32-T16JR 2M E32-T16WR 2M E32-D36P1 2M Highresolution mode 1,100 980 1,700 250 Standard mode E3X-MDA@ Highspeed mode 840 750 1,300 150 560 480 850 100 SuperHighhighresolution speed mode mode 220 730 190 600 340 1,100 45 150 Standard mode Highspeed mode 560 480 860 100 370 320 570 65 Superhighspeed mode 220 190 340 45 Liquid-level Detection Sensing method Tube diameter 3.2/6.4/9.5 dia. Tube-mounting 8 to 10 dia. Feature Model Stable residual E32-A01 5M quantity detection Mounting at E32-L25T 2M multi levels No restrictions Large tubes E32-D36T 2M - - E32-D82F1 4M Liquid contact (heat-resistant up to 200 C) E3X-DA@-S E3X-MDA@ SuperHighHighhighStandard resolution speed speed mode mode mode mode Applicable tube: Transparent tube with a diameter of 3.2, 6.4, or 9.5 mm, Recommended wall thickness: 1 mm Applicable tube: Transparent tube with a diameter of 8 to 10 mm, Recommended wall thickness: 1 mm Applicable tube: Transparent tube (no restriction on diameter) Superhighspeed mode Applicable tube: Transparent tube with a diameter of 3.2, 6.4, or 9.5 mm, Recommended wall thickness: 1 mm Applicable tube: Transparent tube with a diameter of 8 to 10 mm, Recommended wall thickness: 1 mm Applicable tube: Transparent tube (no restriction on diameter) Liquid-contact Type Liquid-contact Type Highresolution mode Standard mode Highspeed mode Vacuum-resistant E3X-DA@-S Sensing method Throughbeam Heat-resistant temperature Model E32-T51V 1M E32-T51V 1M + E39-F1V E32-T84SV 1M 120 C 200 C Highresolution mode 260 1,350 630 Standard mode E3X-MDA@ Highspeed mode 200 1,000 480 130 680 320 SuperHighhighresolution speed mode mode 50 170 260 850 130 410 Standard mode Highspeed mode 130 650 310 85 430 200 Superhighspeed mode 50 260 130 FPD, Semiconductors, and Solar Cells E3X-DA@-S Sensing method Application Glass presence detection Limitedreflective Glass substrate alignment 70 C 300 C 70 C Glass substrate mapping Throughbeam Operating temperature Wafer mapping 300 C 70 C Model E32-L16-N 2M E32-A08 2M E32-A08H2 2M E32-A12 2M E32-A09 2M E32-A09H2 2M E32-A03 2M E32-A03-1 2M E32-A04 2M E32-T24SR 2M E32-T24S 2M Highresolution mode E3X-MDA@ 0 to 15 Superhighspeed mode 0 to 12 10 to 20 12 to 30 15 to 38 20 to 30 Standard mode Highspeed mode 0 to 15 Superhighspeed mode 0 to 12 - 10 to 20 - - - - 12 to 30 15 to 38 20 to 30 - - - Highresolution mode Standard mode Highspeed mode 1,150 890 600 250 750 580 380 250 460 1,480 1,750 340 1,100 1,300 225 730 870 100 290 350 300 920 1,100 220 730 870 145 480 580 100 290 350 Note: The super-high-speed mode cannot be used with the E3X-MDA0. 11 E3X-DA-S/MDA Mark-detecting Amplifier Units (Different Colors of Light Sources) Threaded Models E3X-DAG@-S/DAB@-S Sensing method Sensing direction Size Throughbeam Right-angle Straight M4 M3 Reflective Straight M6 Model E32-T11N 2M E32-T11R 2M E32-C31 2M E32-D11R 2M E32-CC200 2M Highresolution mode Standard mode Highspeed mode E3X-DAH@-S Superhighspeed mode Highresolution mode Standard mode Highspeed mode Superhighspeed mode 65 50 35 30 280 190 130 55 7.5 17 32 6 14 25 4 10 16 3.5 8 16 50 120 200 37 90 150 25 60 100 8.5 21 35 Cylindrical Models E3X-DAG@-S/DAB@-S Sensing method Throughbeam Reflective Sensing direction Size Top-view Side-view Top-view 3 dia. 3 dia. Model E32-T12R 2M E32-T14LR 2M E32-D32L 2M Highresolution mode Standard mode 65 25 15 50 20 12 Highspeed mode 35 22 8 E3X-DAH@-S SuperHighhighresolution speed mode mode 30 280 12 100 7.5 100 Standard mode 190 75 75 Highspeed mode 130 80 50 Superhighspeed mode 55 21 17 Flat Models E3X-DAG@-S/DAB@-S Sensing method Sensing direction Top-view Side-view Flat-view Top-view Side-view Flat-view Throughbeam Reflective Model E32-T15XR 2M E32-T15YR 2M E32-T15ZR 2M E32-D15XR 2M E32-D15YR 2M E32-D15ZR 2M Highresolution mode Standard mode Highspeed mode E3X-DAH@-S SuperHighhighresolution speed mode mode 30 280 65 50 35 25 20 22 12 17 14 10 8 4.2 3.3 2.2 2.1 190 130 Superhighspeed mode 55 100 75 80 21 120 90 60 21 28 20 13 5 Standard mode Highspeed mode Sleeve Models E3X-DAG@-S/DAB@-S Sensing method Sensing direction Throughbeam Reflective Model Highresolution mode Standard mode Highspeed mode E3X-DAH@-S Superhighspeed mode Highresolution mode Standard mode Highspeed mode Superhighspeed mode Top-view E32-TC200BR 2M 65 50 35 30 280 190 130 55 Top-view E32-DC200BR 2M 17 14 10 8 120 90 60 21 High-power Beam E3X-DAG@-S/DAB@-S Type Sensing direction Aperture angle Through-beam Integrated lens Side-view 30 Model E32-T14 2M Highresolution mode 320 Standard mode 260 Highspeed mode 220 E3X-DAH@-S Superhighspeed mode 160 Highresolution mode 1800 Standard mode 1200 Highspeed mode 820 Superhighspeed mode 360 12 E3X-DA-S/MDA Output Circuit Diagrams NPN Output Operation mode Model E3X-DA11-S E3X-DA6-S E3X-DAG11-S E3X-DAG6-S E3X-DAB11-S E3X-DAB6-S E3X-DAH11-S E3X-DAH6-S E3X-DA11SE-S E3X-DA6SE-S Light-ON Operation selector Timing charts Incident light No incident light Operation ON indicator OFF (orange) ON Output transistor OFF Load Operate (relay) Reset Output circuit LIGHT ON (L-ON) Power tuning indicator (orange) (Between brown and black leads) Dark-ON Incident light No incident light Operation ON indicator OFF (orange) ON Output OFF transistor Operate Load Reset (relay) Operation indicator (orange) Display Brown Black Load Control output Photoelectric Sensor main circuit 12 to 24 VDC Blue DARK ON (D-ON) (Between brown and black leads) Light-ON E3X-DA11TW-S E3X-DA6TW-S E3X-MDA11 E3X-MDA6 E3X-DA11AT-S E3X-DA6AT-S CH1/ Incident light CH2 No incident light Operation ON indicator OFF (orange) ON Output transistor OFF Operate Load Reset (relay) LIGHT ON (L-ON) Display Operation indicator (orange) ch 1 Brown Load Black Control output 1 Photoelectric Sensor main circuit (Between brown and black leads) Dark-ON Operation indicator (orange) ch 2 CH1/ Incident light CH2 No incident light Operation ON indicator OFF (orange) ON Output transistor OFF Operate Load (relay) Reset Load Orange Control output 2 12 to 24 VDC Blue DARK ON (D-ON) (Between brown and black leads) Light-ON Incident light No incident light Operation ON indicator OFF (orange) ON Output OFF transistor Operate Load (relay) Reset LIGHT ON (L-ON) Power tuning indicator (orange) (Between brown and black leads) E3X-DA11RM-S E3X-DA6RM-S Dark-ON Operation indicator (orange) Display Incident light No incident light Operation ON indicator OFF (orange) ON Output OFF transistor Operate Load Reset (relay) Brown Load Black Control output Photoelectric Sensor main circuit Orange DARK ON (D-ON) External input 12 to 24 VDC Blue (Between brown and black leads) Incident light Light-ON No incident light Operation ON indicator OFF (orange) ON Output OFF transistor Load Operate (relay) Reset LIGHT ON (L-ON) (Between brown and black leads) E3X-DA11AN-S Display Power tuning indicator (orange) Incident light Dark-ON No incident light Operation ON indicator OFF (orange) Operation indicator (orange) Brown Load Black Control output Analog Orange output models Photoelectric Sensor main circuit Load 10kmin Blue DARK ON (D-ON) ON Output OFF transistor Load Operate (relay) Reset 12 to 24 VDC (Between brown and black leads) Note: 1. The ON/OFF regions when areas settings are used with the E3XDA@TW-S are as follows: LIGHT ON: ON when the incident level is between the thresholds for channels 1 and 2. DARK ON: OFF when the incident level is between the thresholds for channels 1 and 2. 2. Timing Charts for Timer Function Settings (T: Set Time) ON delay OFF delay Incident light No incident light L-ON D-ON Incident light ON OFF Incident light No incident light T ON OFF One-shot L-ON T D-ON T ON OFF ON OFF No incident light L-ON T D-ON T ON OFF T 3. Control Output (AND, OR, Sync) and Timing Chart for Timer Settings (T: Set Time) ON OFF ON CH2 OFF OUT ON (AND) OFF OUT ON (OR) OFF OUT ON (sync) OFF CH1 ON OFF ON CH2 OFF ON delay ON (AND) OFF OFF delay ON (AND) OFF One-shot ON (AND) OFF CH1 T T T T ON OFF 13 E3X-DA-S/MDA PNP Output Model Operation mode Timing chart Operation selector Output circuit Incident light E3X-DA41-S E3X-DA8-S E3X-DAG41-S E3X-DAG8-S E3X-DAB41-S E3X-DAB8-S E3X-DAH41-S E3X-DAH8-S E3X-DA41SE-S E3X-DA8SE-S Light-ON No incident light Operation ON indicator OFF (orange) ON Output transistor Load (relay) LIGHT ON (L-ON) Operation indicator (orange) Display OFF Power tuning indicator (orange) Operate Reset (Between blue and black leads) Incident light Dark-ON No incident light Operation ON indicator OFF (orange) ON Output transistor OFF Load Operate (relay) Reset Photoelectric Sensor main circuit DARK ON (D-ON) Brown Control output Black 12 to 24 VDC Load Blue (Between blue and black leads) Light-ON E3X-DA41TW-S E3X-DA8TW-S E3X-MDA41 E3X-MDA8 E3X-DA41AT-S E3X-DA8AT-S Incident light CH1/ CH2 No incident light Operation ON indicator OFF (orange) ON Output transistor Load (relay) OFF LIGHT ON (L-ON) Operation indicator (orange) ch 1 Display Operate Reset Photoelectric Sensor main circuit (Between blue and black leads) Incident light Dark-ON Operation indicator (orange) ch 2 CH1/ CH2 No incident light Operation ON indicator OFF (orange) ON Output transistor Load (relay) Brown Control output 1 Black 12 to 24 VDC Control output 2 Orange Load Load DARK ON (D-ON) Blue OFF Operate Reset (Between blue and black leads) Incident light Light-ON No incident light Operation ON indicator OFF (orange) ON Output transistor OFF Load Operate (relay) Reset E3X-DA41RM-S E3X-DA8RM-S LIGHT ON (L-ON) Display Power tuning indicator (orange) (Between blue and black leads) Incident light Dark-ON No incident light Operation ON indicator OFF (orange) Output transistor Load (relay) ON Operation indicator (orange) Photoelectric Sensor main circuit Brown Orange Black Blue External input Control output 12 to 24 VDC Load DARK ON (D-ON) OFF Operate Reset (Between blue and black leads) Incident light Light-ON No incident light Operation ON indicator OFF (orange) ON Output transistor Load (relay) LIGHT ON (L-ON) OFF Power tuning indicator (orange) Operate Reset (Between blue and black leads) E3X-DA41AN-S Incident light Dark-ON No incident light Operation ON indicator OFF (orange) ON Output transistor Load (relay) Display Operation indicator (orange) Photoelectric Sensor main circuit Brown Analog Orange output models 12 to Control 24 VDC output Black Blue Load Load 10kmin DARK ON (D-ON) OFF Operate Reset (Between blue and black leads) Note: The ON/OFF regions when areas settings are used with the E3X-DA@TW-S are as follows: LIGHT ON: ON when the incident level is between the thresholds for channels 1 and 2. DARK ON: OFF when the incident level is between the thresholds for channels 1 and 2. 14 E3X-DA-S/MDA Nomenclature Fiber Amplifier Units E3X-DA@-S E3X-DA@RM-S E3X-DA@AN-S Main Display (Red) Incident level, function, etc. Sub-Display (Green) Threshold, function settings, etc. E3X-DA@TW-S E3X-DA@AT-S E3X-MDA@ Operation Keys Function setting operations UP Lock lever Locks the fiber unit. DOWN Main Display (Red) Incident level, function, etc. Lock lever Locks the fiber unit. MODE Operation Indicator (orange) ON when output is ON. OFF when output is OFF. Power Tuning Indicator ON: Power tuning is set. Operation Selector Use to switch between Light ON and Dark ON modes. Mode Selector Use to select SET or RUN mode. Operation indicator for channel 1 (orange) ON when output is ON. OFF when output is OFF. Sub-Display (Green) Threshold, function settings, etc. Operation Keys Function setting operations UP DOWN MODE Channel Selector Use to switch between channels Operation indicator for 1 and 2. channel 2 (orange) Mode Selector ON when output is ON. Use to select SET or RUN mode. OFF when output is OFF. Safety Precautions Refer to Warranty and Limitations of Liability. WARNING This product is not designed or rated for ensuring safety of persons either directly or indirectly. Do not use it for such purposes. Precautions for Correct Use Do not use the product in atmospheres or environments that exceed product ratings. Fiber Amplifier Unit Removing Connectors 1. Slide the slave Amplifier Unit(s) for which the Connector is to be removed away from the rest of the group. 2. After the Amplifier Unit(s) has been separated, press down on the lever on the Connector and remove it. (Do not attempt to remove Connectors without separating them from other Amplifier Units first.) Press down Lever Designing Operation after Turning Power ON The Sensor is ready to detect 200 ms after the power supply is turned ON. If the Sensor and load are connected to separate power supplies, be sure to turn ON the Sensor first. Mounting Connecting and Disconnecting Wire-saving Connectors Remove Adding and Removing Fiber Amplifier Units Adding Fiber Amplifier Units 1. Mount the Amplifier Units one at a time onto the DIN track. Mounting Connectors 1. Insert the Master or Slave Connector into the Amplifier Unit until it clicks into place. 2. Slide the Amplifier Units together, line up the clips, and press the Amplifier Units together until they click into place. Insert 2. Attach the protector seals (provided as accessories) to the sides of master and slave connectors that are not connected. Seal Seal Note: Attach the seals to the sides with grooves. Click into place Removing Fiber Amplifier Units Slide Amplifier Units away from each other, and remove from the DIN track one at a time. (Do not attempt to remove Amplifier Units from the DIN track without separating them first.) Note: 1. The specifications for ambient temperature will vary according to the number of Amplifier Units used together. For details, refer to Ratings and Specifications. 2. Always turn OFF the power supply before joining or separating Amplifier Units. 15 E3X-DA-S/MDA Mounting the End Plate (PFP-M) Fiber Units That Cannot Be Free-Cut (with Sleeves) An End Plate should be used if there is a possibility of the Amplifier Unit moving, e.g., due to vibration. If a Mobile Console is going to be mounted, connect the End Plate in the direction shown in the following diagram. 9 mm 13 mm 2. Disconnecting Fiber Units Remove the protective cover and raise the lock lever to pull out the fiber units. End Plate Mounting the Mobile Console Head Leave a gap of at least 20 mm between the nearest Amplifier Unit and the Mobile Console head. Protective cover 20 mm Locked Fiber Unit Connection The E3X Amplifier Unit has a lock button for easy connection of the Fiber Unit. Connect or disconnect the fiber units using the following procedures: 1. Connection Open the protective cover, insert the fiber units according to the fiber unit insertion marks on the side of the Amplifier Unit, and lower the lock lever. Unlocked Note: 1. To maintain the fiber unit properties, confirm that the lock is released before removing the fiber units. 2. Be sure to lock or unlock the lock button within an ambient temperature range between -10C and 40C. Adjusting Mutual Interference Protection Function There may be some instability in the digital display values due to light from other sensors. If this occurs, decrease the sensitivity (i.e., decrease the power or increase the threshold) to perform stable detection. EEPROM Writing Error Lock button Protective cover Locked Unlocked Insertion position If the data is not written to the EEPROM correctly due to a power failure or static-electric noise, initialize the settings with the keys on the Amplifier Unit. ERR/EEP will flash on the display when a writing error has occurred. Optical Communications Fiber unit insertion mark Several Amplifier Units can be slid together and used in groups. Do not, however, slide the Amplifier Units or attempt to remove any of the Amplifier Units during operation. Fiber unit 9 mm Note: If one of the fibers from the Fiber Unit is labeled as the Emitter fiber, such as with a Coaxial Sensor, insert that fiber into the Emitter section. Refer to Dimensions for the Fiber Unit to see if there is an Emitter fiber label. Fiber Units with E39-F9 Attachment Others Protective Cover Always keep the protective cover in place when using the Amplifier Unit. Mobile Console Use the E3X-MC11-SV2 Mobile Console for the E3X-DA-S-series Amplifier Units. Fiber Unit 9 mm 13 mm 16 E3X-DA-S/MDA (Unit: mm) Dimensions Tolerance class IT16 applies to dimensions in this data sheet unless otherwise specified. Fiber Amplifier Units Amplifier Units with Cables E3X-DA11-S E3X-DA41-S E3X-DAG11-S 15.6 E3X-DAG41-S 10 E3X-DAB11-S E3X-DAB41-S Operation indicator E3X-DAH11-S E3X-DAH41-S 4.3 E3X-DA11RM-S E3X-MDA@ only E3X-DA41RM-S 101.45 E3X-DA11TW-S ch2 E3X-DA41TW-S E3X-DA11SE-S 4.5 32 E3X-DA41SE-S 7 (16.5) E3X-DA11AT-S 4.5 E3X-DA41AT-S 5.65 3.4 E3X-DA11AN-S ch1 18.7 E3X-DA@-STwo, 2.4 dia. E3X-DA41AN-S E3X-MDA@Four, 2.4 dia. E3X-MDA11 E3X-DA@-S E3X-MDA41 (E3X-MDA@) Area of digital indication Round ( ): Power tuning indicator Oblong ( ): Operation indicator for channel 2 35.25 6.3 Main display Sub-display DIN track mounting 141.1 180 Vinyl-insulated round cable Standard length: 2 m* 12.5 Hole for optical communications (36.2) Multiple connection diagram (21.3) 70 L Center of DIN track End Plate (sold separately) PFP-M DIN track (sold separately) PFP-@N 10 Fiber Attachment mounted (E39-F9) * Cable Specifications 10 10 The number of expansion L (mm) 1 10 2 20 3 30 4 40 5 50 6 60 E3X-DA11-S -DA41-S -DAG11-S -DAG41-S -DAB11-S -DAB41-S -DAH11-S -DAH41-S 4-dia., 3-conductor (Conductor cross section: 0.2 mm2, insulator diameter: 1.1 mm) E3X-DA11TW-S -DA41TW-S -DA11RM-S -DA41RM-S 4-dia., 4-conductor (Conductor cross section: 0.2 mm2, insulator diameter, 1.1 mm) 7 70 8 80 E3X-MDA11 -MDA41 4-dia., 2-conductor (Conductor cross section: 0.2 mm2, insulator diameter: 1.1 mm) 9 90 10 100 4.3 With Mounting Bracket Attached 141.1 E3X-MDA@ only 180 101.45 ch2 Vinyl-insulated round cable Standard length: 2 m* 4.5 32 7 (16.5) 4.5 12.5 5.65 3.4 ch1 10.3 E3X-DA@-STwo, 2.4 dia. E3X-MDA@Four, 2.4 dia. Two, 3.2 dia. holes 18.7 Hole for optical communications 4.3 (9.4) 16 70 E3X-DA@-S (E3X-MDA@) Mounting Bracket (E39-L143) SUS304 stainless steel 3.4 Mounting Holes 4.4 Two, M3 16 28.1 16 Note: When using E39-L143 Mounting Brackets, there will be small gaps between the Fiber Amplifier Units if they are mounted side by side. Fiber Attachment mounted (E39-F9) 17 E3X-DA-S/MDA Amplifier Units with Wire-saving Connectors E3X-DA6-S E3X-DA8-S E3X-DAG6-S 15.6 E3X-DAG8-S 10 E3X-DAB6-S E3X-DAB8-S Operation indicator E3X-DAH6-S E3X-DAH8-S 4.3 E3X-DA6RM-S E3X-MDA@ only E3X-DA8RM-S 101.45 E3X-DA6TW-S ch2 E3X-DA8TW-S 4.5 E3X-DA6SE-S 32 E3X-DA8SE-S 7 (16.5) E3X-DA6AT-S 4.5 E3X-DA8AT-S 5.65 3.4 E3X-MDA6 ch1 18.7 E3X-DA@-STwo, 2.4 dia. E3X-MDA8 E3X-MDA@Four, 2.4 dia. Area of digital indication Round ( ): Power tuning indicator Oblong ( ): Operation indicator for channel 2 35.25 6.3 Main display Sub-display DIN track mounting 141.1 180 A dia. * 12.95 Hole for optical communications (36.2) E3X-DA@-S (E3X-MDA@) Multiple connection diagram (21.3) 70 L Center of DIN track End Plate (sold separately) PFP-M DIN track (sold separately) PFP-@N 10 Fiber Attachment mounted (E39-F9) * Cable Diameters E3X-CN22 (2 conductors) E3X-CN21 (4 conductors) E3X-CN11 (3 conductors) 4.0-mm dia. E3X-CN12 (1 conductor) 2.6-mm dia. L (mm) 1 10 2 20 3 30 4 40 5 50 6 60 7 70 8 80 10 4.3 10 The number of expansion 9 90 10 100 With Mounting Bracket Attached 141.1 E3X-MDA@ only 180 101.45 ch2 4.5 A dia. * 32 7 (16.5) 4.5 12.95 5.65 3.4 ch1 10.3 E3X-DA@-STwo, 2.4 dia. E3X-MDA@Four, 2.4 dia. Two, 3.2 dia. holes 18.7 Hole for optical communications 4.3 (9.4) 16 70 E3X-DA@-S (E3X-MDA@) Mounting Bracket (E39-L143) SUS304 stainless steel 3.4 4.4 Mounting Holes Two, M3 28.1 16 16 Fiber Attachment mounted (E39-F9) Note: When using E39-L143 Mounting Brackets, there will be small gaps between the Fiber Amplifier Units if they are mounted side by side. 18 E3X-DA-S/MDA Amplifier Unit with Connector for Sensor Communications Unit E3X-MDA0 32.8 29.8 15.1 12.15 11.7 11.75 3.25 4.3 70 8.1 10 4.5 Four, 2.4 dia. 32 7 4.5 5.65 3.4 28.1 18.7 16 34.8 44.3 Two, 3.2 dia. 3.4 28.1 4.4 16 Amplifier Unit Connectors Master Connectors E3X-CN11 E3X-CN21 2,000 +500 Edge of amplifier (7) * * E3X-CN11: 4 dia. cable / 3 conductors / Standard length: 2 m (Conductor cross section: 0.2 mm2 (AWG24), Insulator diameter: 1.1 mm) E3X-CN21: 4 dia. cable / 4 conductors / Standard length: 2 m (Conductor cross section: 0.2 mm2 (AWG24), Insulator diameter: 1.1 mm) Slave Connectors E3X-CN12 E3X-CN22 2,000 +500 Edge of amplifier (7) * * E3X-CN12: 2.6 dia. cable / 1 conductor / Standard length: 2 m (Conductor cross section: 0.2 mm2 (AWG24), Insulator diameter: 1.1 mm) E3X-CN22: 4 dia. cable / 2 conductors / Standard length: 2 m (Conductor cross section: 0.2 mm2 (AWG24), Insulator diameter: 1.1 mm) 19 E3X-DA-S/MDA Mobile Console E3X-MC11-SV2 Mobile Console AC adapter jack Mobile Console Head Communications jack 26 Menu indicators 22 Optical communications connection indicator Communications jack 52.8 10 20 Channel indicator (38.2) 13.1 16.3 28.8 31.8 13.2 Sensor operation indicator 1.2 5.1 12.3 Main display 17.3 24.3 Channel buttons 27.7 30.3 Sub-display 9.9 136 UP key Optical communications position RIGHT key M5 ball plunger LEFT key 31.2 36.7 51.3 5.6 ESC/PWR key DOWN key 57 ENT key Operation keys Battery indicators 12 26 50 Refer to E32 Series for details on Fiber Units. 20 Terms and Conditions Agreement Read and understand this catalog. Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Warranties. (a) Exclusive Warranty. Omron's exclusive warranty is that the Products will be free from defects in materials and workmanship for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron disclaims all other warranties, express or implied. (b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron's sole obligation hereunder shall be, at Omron's election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other claims or expenses regarding the Products unless Omron's analysis confirms that the Products were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above warranty. See http://www.omron.com/global/ or contact your Omron representative for published information. Limitation on Liability; Etc. OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY. Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted. Suitability of Use. Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the combination of the Product in the Buyer's application or use of the Product. At Buyer's request, Omron will provide applicable third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with respect to Buyer's application, product or system. Buyer shall take application responsibility in all cases. NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. Programmable Products. Omron Companies shall not be responsible for the user's programming of a programmable Product, or any consequence thereof. Performance Data. Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of Omron's test conditions, and the user must correlate it to actual application requirements. Actual performance is subject to the Omron's Warranty and Limitations of Liability. Change in Specifications. Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change part numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be assigned to fix or establish key specifications for your application. Please consult with your Omron's representative at any time to confirm actual specifications of purchased Product. Errors and Omissions. Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical or proofreading errors or omissions. 2015.9 In the interest of product improvement, specifications are subject to change without notice. OMRON Corporation Industrial Automation Company http://www.ia.omron.com/ (c)Copyright OMRON Corporation 2015 All Right Reserved.