54
Analog Input Modules GT1-AD
Analog Input ModuleCompatiblewith
MULTIPLEI/O TERMINAL
Inputblock incorporates connectorsthatcan be
easilymounted ordismounted.
8inputs
High resolution of1/6,000
High conversion speed of8ms/8 pointsor4ms/4
points.
Dimensionsofconnector model:
110 × 60 × 65 (W × H × D)
Dimensionsof terminalblock model:
80 × 80 × 65 (W × H × D)
DINtrack mounting.
Ordering Information
I/Oclassification I/OpointsTerminalPowersupply
voltage
I/Ospecification Model
Analog input8Molex connector24 VDC 4to 20 mA,0to 20 mA,
0
t
o
5
V
,
1
t
o
5
V
,
0
t
o
GT1-AD08MX
4Terminalblock
0
t
o
5
V
,
1
t
o
5
V
,
0
t
o
10 V,--10 to 10 VGT1-AD04
Note:Aconnectorcable,GCN1--004,isincluded with eachmodule.
Specifications
Input
ItemVoltageinputCurrentinput
Inputpoints8
Input type0to5V,1to5V,0to 10 V,--10 to 10 V0to 20 mA,4to 20 mA
Max.signal input±15 V±30 mA
Inputimpedance 1MWmin.Approx.250 W
Resolution 1/6,000 (FS)
Overall accuracy 25°C±0.3%FS±0.4%FS
O
v
e
r
a
l
l
a
c
c
u
r
a
c
y
--10°Cto55°C±0.6%FS±0.8%FS
Conversion speed8ms/8 points,4ms/4 points
Conversion outputdataBinarydata
--10-to 10-Vrange:F448 to 0BB8full scale
Othersignalranges:0000 to 1770 full scale
Insulation method Transistororphotocouplerinsulation between inputsand powerlines.
GT1-AD GT1-AD
55
Characteristics
I/Opowersupply voltage20.4to 26.4VDC (24 VDC +10%/--15%)
Currentconsumption I/Omoduleinterface Internalcircuitrypowersupply
C
u
r
r
e
n
t
c
o
n
s
u
m
p
t
i
o
n
50 mAmax.100 mAmax.
Noise immunity±1,500 V(p-p)with a pulsewidth of0.1to1ms
Vibration resistance 10 to 150 Hz,1.0-mm double amplitude or70 m/s2
Shock resistance 200 m/S2
Dielectric strength500 VAC
Mounting method 35-mm DINtrack mounting
Mounting strengthNo damage when 100 Npull load wasapplied in all directions(10 Nmin.inthe DINtrack
direction)
TerminalstrengthNo damage when 100 Npull load wasapplied
Ambient temperatureOperating:--10°Cto 55°C(withnoicing orcondensation)
Storage:--25°Cto 65°C(withnoicing orcondensation)
AmbienthumidityOperating:25%to 85%
Connector
TypeModelRemarks
Molex connectorIDC (UsePress-fit tool.)Housing GCN1--MX25--B*(25 piece bag from
OMRON)22 AWG
Solderless terminalHousing 50--57--9403
S
o
l
d
e
r
l
e
s
s
t
e
r
m
i
n
a
l
Chainterminal16--02--0069 24 to30AWG
C
h
a
i
n
t
e
r
m
i
n
a
l
16--02--0086 22 to24AWG
Looseterminal16--02--0096 24 to30AWG
Press-fit tool11--01--0209 (See Note.)
Note:ContactyourOMRONrepresentativesforthe aboveconnectors.
*Stocked byOMRON.
Nomenclature
Supply24 VDC +10%/--15%tothese
terminalsforthe operation of the
Module.
The green indicatorislitwhen internalcircuitrypowersupplyisprovided.
Analog inputconnectors0to7
Internalpower
supplyterminals
U.ERR indicator(module errorindicator)
ConnectorsforI/Omoduleinterface
Theseconnectorsareforanalog inputuse.
Eachinputconnectorhasthree pins(i.e., a pinfor
voltage input, COM,and currentinput fromleft to
right)
Connectstothe CommunicationsUnitsorotherI/OMod-
ules.
·Connect the CommunicationsModuletoconnector1.
·When connecting I/OModulestothe GT1-AD,
connector2 of the GT1-ADmustbe connected to
connector1 of the first I/OModule and connector2 of
the first I/OModulemustbe connected toconnector1
of the next I/OModule.Connectall the I/OModulesin
the sameway.
·Besuretoconnect the end connectortoconnector2 of
the last I/OModule.
The red indicatorislitif the Modulemalfunctionsorno internal
circuitrypowersupplyisprovided.
PWRindicator(internalpowersupplyindicator)
TSindicator(statusindicatorofI/OModuleinterface)
Indicatesthe statusof the I/OModuleInterface.
Voltage inputCOMCurrentinput
+24VDC -24VDC
Specification
Setting
Switch
TSIndicator(StatusIndicatorofI/OModuleInterface)
Green indicatorlitThe Moduleisnormal.
Red indicatorlitThe I/OModuleinterface hasan error.
OFF No poweris supplied tothe Module or
the Moduleisbeing initialized.
T
1
-
A
D
0
8
M
X
GT1-AD GT1-AD
56
Green indicatorlitThe Moduleisnormal.
The indicatorislitgreen when internalcircuitrypowersupplyisprovided.
The indicatorisnotlitwhen internalcircuitrypowerisnotsupplied.
U.ERR indicator
Connector2forI/OModuleinterface (connectstoend node)
The indicatorislitred if the Modulemalfunctionsorno internal
circuitrypowersupplyisprovided.The indicatorisnotlitwhen the
Moduleisnormal.
PWRindicator
TSindicator
Indicatesthe communications statusof the I/OModuleInterface.
TSIndicator
(CommunicationsStatusIndicatorofI/OModuleInterface)
Red indicatorlitThe I/OModuleinterface hasan error.
NotlitNo poweris supplied tothe Module or
the Moduleisbeing initialized.
GT1-AD04
Cassette
Lightlypushthe upperpart, then pull out to disconnect.
Terminalblock
DINTrack connection hook
Specification setting switch
Located on left side of the
connecting section.
Connector1forI/OModuleinterface
(connectstoCommunicationsMod-
ule)
Operation
InternalCircuitConfiguration
Photocoupler
I/OModuleinterface
Inputcircuit
Eightcircuits
Internalcircuitry
powersupplyInternalcircuit
I/OModuleinterface
PhotocouplerI/OModuleinterface
Insulated DC-DC
converter
+24 VDC
--24 VDC
GT1-AD08MX
GT1-AD04
Photocoupler
I/OModuleinterface
Internalcircuitry
powersupplyInternalcircuit
I/OModuleinterface
PhotocouplerI/OModuleinterface
Insulated DC-DC
converter
+24 VDC
--24 VDC
Inputcircuit
Fourcircuits
GT1-AD GT1-AD
57
Dimensions
Note:All unitsareinmillimetersunless otherwiseindicated.
G
T
1
-
A
D
0
8
M
X
GT1-AD04
Installation
Wiring
BesuretoconnectMolex-made connectorsforanalog inputwiresand connect the wiresas shown below.
InternalCircuitryPowerSupplyVoltageInputCurrentInput
24 VDC
GT1-AD GT1-AD
58
Precautions
Refertothe DeviceNetOperation Manual(W267)before using the
Module.
Wiring
·To preventinductive noise,do notwire powerlinesor
high-tension linesalong with ornearthe cables.Other
noise-prevention techniques,such asusing shielding or
separateconduit/ducting,are also effective.
·Install the Module asfaraspossiblefromequipment that
generates strong high-frequency signals(such ashigh-fre-
quency welders)and equipment thatgenerates surges.Such
equipmentcan causethe Moduletomalfunction.
·Install surge absorbersornoisefilterson nearbyequipment that
generatesnoise,particularlyequipment thathasinductive
components such asmotors, transformers,solenoids,or
magnetic coils.
·When using a noisefilterinthe powersupply,check the voltage
and currentand install the noisefilteras close aspossibletothe
Module.
Cat. No. PP10FAX1A 6/00 Specifications subject to change without notice. Printed in U.S.A.
OMRONELECTRONICS, INC.
One EastCommerceDrive
Schaumburg, IL 60173
NOTE:DIMENSIONS SHOWN AREINMILLIMETERS.To convertmillimeterstoinches divideby 25.4.
1-800-55-OMRON
OMRON CANADA, INC.
885 MilnerAvenue
Scarborough,OntarioM1B5V8
416-286-6465
R
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Omron:
GT1-AD04 GT1-AD04CST GT1-AD08MX