Thermal-Magnetic Circuit Breaker 2215-L.../G...
www.e-t-a.de
1633
1
1
Description
Typical applications
Technical data
Miniaturised single pole thermal-magnetic circuit breakers with trip-free
mechanism and toggle actuation (S-type TM CBE to EN 60934). Two
designs provide the option of either printed circuit board or threadneck
panel mounting. A separate shunt tap terminal and auxiliary contacts
are available. Fast acting, medium or long delay characteristics can be
specified for both models.
Suitable for use in distribution rails – see section Power Distribution
Systems.
Complies with CBE standard EN 60934 (IEC 60935).
Control equipment, communications systems, instrumentation.
Suitable for mounting on Euro cards.
2215-L1.. 2215-G1...
Voltage rating AC 250 V (50/60 Hz); DC 50 V
(UL: AC 250 V; DC 75 V)
Current rating range 0.05...10 A
(higher current ratings to special order)
Auxiliary circuit 1 A, AC 250 V / DC 28 V
Typical life 10,000 operations at 1 x IN
Ambient temperature -30...+60 °C (-22...+140 °F)
Insulation co-ordination rated impulse pollution
(IEC 60664 and 60664 A) withstand voltage degree
2.5 kV 2
reinforced insulation in operating area
Dielectric strength
IEC 60664 and 60664A) test voltage
operating area AC 3,000 V
main/aux. circuit AC 1,500 V
Insulation resistance > 100 MΩ (DC 500 V)
Interrupting capacity Icn 300 A
Interrupting capacity
(UL 1077) IN UN
0.05 A AC 250 V 200 A
0.1...6 A AC 250 V 1,000 A
8...10 A AC 250 V 2,000 A
0.05...10 A DC 50 V 1,000 A
Degree of protection operating area IP30
(IEC 60529/DIN 40050) terminal area IP00
Vibration
curve F1: 6 g (57-500 Hz), ± 0.46 mm (10-57 Hz)
curves M1, T1: 8 g (57-500 Hz), ± 0.61 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
Shock
curves F1, M1, T1: 30 g (11 ms), directions 1, 2, 3, 4, 5,
curve F1: 10 g (11 ms), direction 6
curves M1, T1: 15 g (11 ms), direction 6
to IEC 60068-2-27, test Ea
Corrosion 96 hours at 5 % salt mist
to IEC 60068-2-11, test Ka
Humidity 240 hours at 95 % RH
to IEC 60068-2-78, test Cab
Mass approx. 25 g
Type No.
2215 single pole thermal-magnetic circuit breaker
Mounting
L1 PCB mounting
Number of poles
1 1-pole protected
Mounting hardware
0 without accessories
Terminal design (main contacts)
L1 solder pins, without shunt terminal
Characteristic curve
F1 fast acting:1.01-1.4xIN; magn.2-4xIN DC (DC only)
M1 standard delay: therm. 1.01-1.4xIN;
magn. 4.5-10.5xIN DC; magn. 3.5-8xIN AC
Auxiliary contacts - terminal design
S0 without auxiliary contact
S12 with auxiliary contact (change over)
solder pins
Current ratings
0.05...10 A
2215 - L1 1 0 - L1 F1 - S12 - 0.5 A ordering example
Ordering information 2215-L1
Type No.
2215 single pole thermal-magnetic circuit breaker
Mounting
G1 threadneck panel mounting
Number of poles
1 1-pole protected
Mounting hardware
1 2 hex nuts 1/4“-40 UNS-2A, serrated washer,
location pin (-G1 only)
Terminal design (main contacts)
P1 blade terminals 6.3-0.8, without shunt terminal
Characteristic curve
F1 fast acting:1.01-1.4xIN; magn.2-4xIN DC (DC only)
M1 standard delay: therm. 1.01-1.4xIN;
magn. 4.5-10.5xIN DC; magn. 3.5-8xIN AC
T1 delayed: therm. 1.01-1.4xIN; DC
magn. 8-17xIN DC, 6-13xIN AC
Auxiliary contacts
S0 without auxiliary contact
S11 with auxiliary contact (change over)
blade terminals 6.3x0.8 (QC .250)
Current ratings
0.05...10 A
2215 - G1 1 1 - P1 F1 - S11 - 0.5 A ordering example
Ordering information 2215-G1
Approvals
Authority Standard Rated voltage Current ratings
UL UL 1077 AC 250 V
DC 75 V 0.05 A…10 A
0.05 A…10 A (20 A)
CSA C22.2 No.
235
AC 250 V
DC 75 V 0.05 A…10 A
0.05 A…10 A (20 A)
Thermal-Magnetic Circuit Breaker 2215-L.../G...Thermal-Magnetic Circuit Breaker 2215-L.../G...
www.e-t-a.de 1633
2
1
blade terminals
DIN 46244-A6.3-0.8
(QC .250)
.236
LINE
21112 14 1
I0
52.5
62.5
threadneck
1/4"-40 UNS-2A
hex nut
serrated washer
lock washer
10°
10°
tightening torque max. 1 Nm
53.5
19
ø3
9
11.5
ø6.4+0.1
6.1
ø2.4+0.1
front panel cut-out
29
2.07
.098
1.14
11
.118
.748
.433
.453
.315
2.11
.354
.240
.094+.004
.252+.004
8
Dimensions 2215-L1..
Installation drawing
11.5
52
212
2.5
25°
14
I0
LINE
11 14 1
6
29
1.7
49
25.6
4
spacer
ø1.5
5
11
1x0.8
25°
.551
2.05
1.01.067
.098 .236
1.14
1.93
.157
.059
.197
1x.031
.433
.453
212
LINE
11 14 1
operating area
(reinforced insulation)
mounting area
(standard insulation)
1435
43
19
4
16
11
1.38 .551
.157 .118
.748
.157
.630
.433
56
1
3
4
2
Shock directions
Dimensions 2215-G1..
Internal connection diagram
0I 111
12 14
2
line
I >
This is a metric design and millimeter dimensions take precedence ( mm )
inch
Standard current ratings and typical internal resistance values
Current
ratings (A) Internal
resistance (Ω) Current
ratings (A) Internal
resistance (Ω)
0.05 440 1.5 0.55
0.1 108 2 0.34
0.2 29.9 2.5 0.21
0.3 14.2 3 0.15
0.4 7.9 4 0.084
0.5 5.0 5 0.057
0.6 3.5 6 0.043
0.8 1.8 8 ≤ 0.02
1 1.2 10 ≤ 0.02
Thermal-Magnetic Circuit Breaker 2215-L.../G...
www.e-t-a.de
1633
3
1
Thermal-Magnetic Circuit Breaker 2215-L.../G...
0.05...10 A: The time/current characteristic curve depends on the ambient temperature
prevailing. In order to eliminate nuisance tripping, please multiply the circuit
breaker current ratings by the derating factor shown below. See also section
Technical information.
Ambient °F
temp. °C
-22
-30 -4
-20 +14
-10 +32
0+73.4
+23 +86
+30 +104
+40 +122
+50 +140
+60
Derating factor 0.76 0.79 0.83 0.88 1 1.04 1.11 1.19 1.29
-T1 8…10 A AC/DC
1)
-T1 0.05…6 A AC/DC
1)
-M1 8…10 A AC/DC
1)
Trip time in seconds
… times rated current
12468102040
10000
1000
100
10
1
0.1
0.01
0.001
60 80 100
-M1 0.05…6 A AC/DC
1)
Trip time in seconds
12468102040
… times rated current
10000
1000
100
10
1
0.1
0.01
0.001
60 80 100
+60 °C
+140 °F +23 °C
+73.4 °F
-30 °C
-22 °F
Trip time in seconds
12468102040
… times rated current
10000
1000
100
10
1
0.1
0.01
0.001
60 80 100
12468102040
Trip time in seconds
… times rated current
10000
1000
100
10
1
0.1
0.01
0.001
60 80 100
-F1 0.05…6 A DC only -F1 8…10 A DC only
… times rated current
Trip time in seconds
12468102040
10000
1000
100
10
1
0.1
0.01
0.001
60 80 100
… times rated current
Trip time in seconds
12468102040
10000
1000
100
10
1
0.1
0.01
0.001
60 80100
1)
Magnetic tripping currents are increased by 30 % on DC supplies (curve M1 and T1).
Typical time/current characteristics
All dimensions without tolerances are for reference only. In the interest of improved design,
performance and cost effectiveness the right to make changes in these specifications
without notice is reserved.Product markings may not be exactly as the ordering codes.
Errors and omissions excepted.
www.e-t-a.de 1633
4
1